RESPONSE TO BLDG COMMENTS 2.pdfSCANNED
2017 SCAW_.)
Edmonds, WA Comments Response.
Item 11a:
Added detail 6 on sheet G-02. Shows adding 3" wide chamfered edge to landing to prevent wheelchair
tip and to prevent a trip hazard. IAW ICC A117.1-2009, Sect 303.
Item 11c:
Changed wheelchair sign to Restroom sign identifying permanent room. IAW A117.1-2009, Sect 703.
Item 13b:
Changed wheelchair sign to Restroom sign identifying permanent room. IAW A117.1-2009, Sect 703.
Item 15:
Deleted U419 requirement for office walls. Modification of existing fire partition wall to extend up to
deck. required per IBC 2015 Sect 402.4.2.1. We are building another wall top of existing. U419
construction data shown on sheet A-2, pulled from 'On-line Certification Directory'.
Item 17:
See Item 21
Item 20:
Mechanical HVAC recalculated to show separation between Office and Lobby areas.
Item 21:
Revised WSEC Compliance forms to indicate 'Space by Space' method identifying individual rooms with
light fixture count and wattage per room.