Response to Fire Consultant Comments.pdfContractor's Registration FOXFIP1127M8 18MAR2016 RE: BLD2015-1562 Project Address: 21006 72nd Avenue W Project: Edmonds Memory Care fire sprinkler Response to Fire Marshall review comments dated 23DEC2016 FOX FIRE PREVENTION, INC. PO BOX 594 PORT ORCHARD, WA 98366 360.871.1985 206.623.2993 FAX 360.871.2262 info@ fox faroprovention.00m MAR 22, 2016 CRY OF EDMMIUS F1. For building more than two stories in height including basements, or having more than 16 dwelling units does allow for 13R systems per IBC 903.2.8. If we are reading this in error, please give us a call to discuss the code in question. F2.A. Additional Earthquake bracing calculations provided for 2.5" and 4" longitudinal and 2.5" lateral. See plan sheet 2. F2.13. Earthquake Sway brace figure numbers added to details. See plan sheet 2 and Material Data Sheets. F2.C. Spacing requirements are as noted by Earthquake bracing symbols on plans. Lateral Earthquake bracing calculations provide the brace with the greatest demand all bracing is similar in installation configuration. Longitudinal Earthquake bracing is calculated at maximum lengths per NFPA but in most cases will be placed at closer intervals as noted by Earthquake bracing symbols on plans. F3. See Response F1. F4.A. See Response F1. F4.13.1. Added note to Riser Detail. See plan sheet 4. F4.13.2. Added note to Riser Detail. See plan sheet 4. Also see Material Data Sheets. F5. Added note to Site Plan. See plan sheet 1. F6. Confirmed, Flex Head Industries does not manufacture flexible hose fittings over 6'. See Material Data Sheets. F7. Confirmed, added note to General Notes. See plan sheet 1. F8. Added hanger detail. See plan sheet 3. F9. Noted fire rated assemblies. See Section A, plan sheet 1 and Material Data Sheets. Contractor's Registration FOXFIP1127M8 O, FIRE PREVENTION, PO BOX 594 PORTORCHARD, WA 983611 360.871.1985 ,i�7 FAX 36 .871.2262 jjjk@jc xJop revention.co F10. Noted see General Notes plan sheet 1. F11. Most hangers will be less than 6" so may not be used. Added hanger restraint detail and noted in General Notes if needed. See plan sheet 1. F12. Maximum hanger spacing in the general notes is for the CPVC pipe hangers installed throughout the 2 d and 3`d floors. Added notes to hanger details. See plan sheets 1, 3 and 4. F13. Signs will be attached to system risers before final inspection. Information for signs on plan sheet 1. Added note to Riser Detail. See plan sheet 4. Adam Cole Design Division Fox Fire Prevention, Inc. PO Box 594, Port Orchard WA 98366 360.871.1985 ph. 360.871.2262 fax www.foxfireprevention.com