Response to Fire Consultant Comments.pdfContractor's Registration FOXFIP1127M8
18MAR2016
RE: BLD2015-1562
Project Address: 21006 72nd Avenue W
Project: Edmonds Memory Care fire sprinkler
Response to Fire Marshall review comments dated 23DEC2016
FOX FIRE PREVENTION, INC.
PO BOX 594
PORT ORCHARD, WA 98366
360.871.1985
206.623.2993
FAX 360.871.2262
info@ fox faroprovention.00m
MAR 22, 2016
CRY OF EDMMIUS
F1. For building more than two stories in height including basements, or having more than 16
dwelling units does allow for 13R systems per IBC 903.2.8. If we are reading this in error, please
give us a call to discuss the code in question.
F2.A. Additional Earthquake bracing calculations provided for 2.5" and 4" longitudinal and 2.5"
lateral. See plan sheet 2.
F2.13. Earthquake Sway brace figure numbers added to details. See plan sheet 2 and Material
Data Sheets.
F2.C. Spacing requirements are as noted by Earthquake bracing symbols on plans. Lateral
Earthquake bracing calculations provide the brace with the greatest demand all bracing is similar
in installation configuration. Longitudinal Earthquake bracing is calculated at maximum lengths
per NFPA but in most cases will be placed at closer intervals as noted by Earthquake bracing
symbols on plans.
F3. See Response F1.
F4.A. See Response F1.
F4.13.1. Added note to Riser Detail. See plan sheet 4.
F4.13.2. Added note to Riser Detail. See plan sheet 4. Also see Material Data Sheets.
F5. Added note to Site Plan. See plan sheet 1.
F6. Confirmed, Flex Head Industries does not manufacture flexible hose fittings over 6'. See
Material Data Sheets.
F7. Confirmed, added note to General Notes. See plan sheet 1.
F8. Added hanger detail. See plan sheet 3.
F9. Noted fire rated assemblies. See Section A, plan sheet 1 and Material Data Sheets.
Contractor's Registration FOXFIP1127M8
O, FIRE PREVENTION,
PO BOX 594
PORTORCHARD, WA 983611
360.871.1985
,i�7
FAX 36 .871.2262
jjjk@jc xJop revention.co
F10. Noted see General Notes plan sheet 1.
F11. Most hangers will be less than 6" so may not be used. Added hanger restraint detail and
noted in General Notes if needed. See plan sheet 1.
F12. Maximum hanger spacing in the general notes is for the CPVC pipe hangers installed
throughout the 2 d and 3`d floors. Added notes to hanger details. See plan sheets 1, 3 and 4.
F13. Signs will be attached to system risers before final inspection. Information for signs on plan
sheet 1. Added note to Riser Detail. See plan sheet 4.
Adam Cole
Design Division
Fox Fire Prevention, Inc.
PO Box 594, Port Orchard WA 98366
360.871.1985 ph. 360.871.2262 fax
www.foxfireprevention.com