Response to Mech plumb Comments 1.pdfEngineered Environments 4�- April 20, 2015 DUMAIS 0 ROMANS, INC CONSULTING MECI 1ANICAL ENGINEERS Guy Dumais, P.E. C 401 Central Street SE Olympia, WA 98501-1708 Attn: Jeff Yates Re: Cedar View Memory Care EM Jeff Romans, P.E. HVAC Engineering Piping,jwtems Construction AdminivIration Liffe Cycle Cost Analpis Pool/Spa Alechimical Systems M General Review 1. The gas piping is shown and sized on Sheets M2.1 — M2.5. 2. The storm water system for the area drains is shown and sized on Sheets M2.1 - M2.4. Sheet M1.1 (now referenced as M2.1) 3(a) The north arrow has been corrected. 3(b) Sizes are noted for the rainwater leader piping serving the area drains. Sheet M2.1 (now referenced as M2.2) 4. The General Notes have been completed. 5. The Plan Notes have been deleted. 6(a) The north arrow has been corrected. 6(b) The Mechanical Legend has been added to Sheet M2.1. 6(c) Sizes are noted for the rainwater leader piping serving the area drains. Sheet M2.2 (now referenced as M2.3) 7(a) The north arrow has been corrected. 7(b) The Mechanical legend has been added to Sheet M2.1. 7(c) Detail is not necessary — reference has been deleted. 7(d) The area drains are sized. 7(e) Area Drain AD -1 is now listed in the Plumbing Fixture Schedule located on Sheet M4.2. North 210 University Road — Suite 100 Spokane Valley, Washington 99206 Phone (509) 893-9646 Fax (509) 893-9648 4/21/2015 Dumais • Romans, Inc. Page 2 7(f) Sizes are noted for the rainwater leader piping serving the area drains. 7(g) The reference is revised to 4/M2.8. 7(h) The shower is specified on Sheet M4.2. 7(i) The tub is specified on Sheet M4.2. 70) The designations have been corrected. Food service equipment is specified on Sheet M2.5 and plumbing fixtures are specified on Sheet M4.2. Sheet M2.3 (now referenced as M2.4) 8. The General Notes have been completed. 9. The Plan Notes have been deleted. 10(a) The north arrow has been corrected. 10(b) The Mechanical Legend has been added to Sheet M2.1. 10(c) Detail is not necessary — reference has been deleted. 10(d) The area drains are sized. 10(e) Area Drain AD -1 is now listed in the Plumbing Fixture Schedule located on Sheet M4.1. 10(f) The'/4 scale designation has been corrected. 10(g) The Y4 scale designation has been corrected. 10(h) The'/4 scale designation has been corrected. 10(i) The shower is specified on Sheet M4.2. 100) The pipe sizing has been corrected. 10(k) The designations have been corrected. Food service equipment is specified on Sheet M2.5 and plumbing fixtures are specified on Sheet M4.2. Sheet M2.4 (now referenced as M2.5) 11(a) The pipe sizing has been corrected and completed. 11(b) The floor drain has been added. 11(c) The drawing title has been corrected. Sheet M2.5 (now referenced as M2.6) 13. The Mechanical Legend has been added to Sheet M2.1. 14. The piping has been corrected to feed First Floor fixtures — Detail revised to #3. Sheet M2.6 (now referenced as M2.7) 15. The Mechanical Legend has been added to Sheet M2.1. 16. The vent route has been revised and corrected — See Sheet M2.2. Sheet M3.1 17(a) Grille designations have been completed. 17(b) Diffuser designations have been completed. 17(c) Diffuser information has been completed. 17(d) response required by others. Sheet M3.2 18(a) The cfm is now noted. 18(b) The cfm is now noted. North 113 Conklin Road Veradale, Washington 99037 Phone (509) 893-9646 Fax (509) 893-9648 4/21/2015 Dumais - Romans, Inc. Page 3 18(c) Grille designations have been completed. 18(d) Exhaust duct is now shown connected to range hood and extended through roof. 19. The plan note designation has been deleted. Sheet M3.3 20(a) Outside air ducts are now shown and sized. 20(b) Outside air ducts are now shown and sized. 20(c) The note has been deleted. 20(d) The smoke damper callouts have been corrected. 20(e) The cfm is now noted. 20(f) Grille designations have been completed. 20(g) Exhaust duct is now shown connected to range hood and extended through roof. 20(h) Range hood is exhausted through roof. 20(i) The thermostat is now shown. 200) Response is required by others. Sheet M3.4 21. Intake Hood IH -4 is now shown. 610 =81191M 22(a) Makeup air unit supply and exhaust ducts are routed to Type 1 hood. 22(b) Makeup air unit supply and exhaust ducts are routed to Type 1 hood. 22(c) The exhaust and supply ducts are now shown and sized. 23. Outside air duct from Intake Hood IH -4 is now shown serving F-10. Sheet M3.6 24(a) The sections have been completed and corrected. 24(b) The sections have been completed and corrected. 24(c) The sections have been completed and corrected. 24(d) The sections have been completed and corrected. 24(e) The duct sizes are now shown. 10*5 R KIN 25(a) Grille designations have been completed. 25(b) Grille designations have been completed. 25(c) The sections have been corrected and updated. 25(d) Plans and sections are now coordinated. 25(e) Plans and sections are now coordinated. 25(f) Plans and sections are now coordinated. 25(g) Plans and sections are now coordinated. Sheet M5.1 26. Corrected to 4/M5.1. 27. Code reference is corrected. 28(a) Note is deleted. North 113 Conklin Road Veradale, Washington 99037 Phone (509) 893-9646 Fax (509) 893-9648 4/21/2015 Dumais - Romans, Inc. Page 4 28(b) Corrected to 4/M5.1. Public Works Sheet M2.5 — Double check valve assembly has been deleted. Refer to civil drawings for reduced pressure backflow preventer. Grease Interceptor Sizing Calculation 80 meals per peak hour 6 gpm flow (dishwasher) + 1 gpm flow (disposal) = 7 gpm flow Retention time = 2.5 hours Storage Factor = 1 80 * 7 * 2.5 * 1 = 1,400 gallons Therefore, use 1,500 gallon interceptor. Fire Marshal Fire protection design / permit features: 2. Kitchen cooking suppression system and fuel gas shutoff are referenced on Detail 2, Sheet M4.2. 2. The grease interceptor has been sized in anticipation of a garbage disposal being utilized in the building. 9. The fixtures listed are discharging into the grease interceptor — refer to Sheets M2.1 and M2.5. 10. The fixtures listed do not discharge into the grease interceptor — refer to Sheets M2.1 and M2.5. 14. See Sheet M2.5 for location of exterior hose bib. 9. Refer to attached pdf titled Shower P-4. 14. Refer to Details 1, 2 and 3, Sheet M4.2. 16. Sheet M3.4 has been corrected. 30. Refer to Kitchen Equipment Connection Schedule, Sheet M2.5. 33. Refer to Sheet M3.5 for Type II hood at dishwasher. North 113 Conklin Road Veradale, Washington 99037 Phone (509) 893-9646 Fax (509) 893-9648 4/21/2015 Dumais • Romans, Inc. Page 5 Please feel free to call if you have questions. Sincerely, North 113 Conklin Road Veradale, Washington 99037 Phone (509) 893-9646 Fax (509) 893-9648