Response to Pre-Treatment.pdfCedar View Memory Care
7{0O672odAvenue W, Edmonds, WA48026
(7208J1UmStSW, Edmonds, VVA9OO26)
City 0fEdmonds
����
Response Letter toPlan Review Comments����������/��
����
r/�"
Attn: Les |{rCSte[
Plan Check: B[D20l5-0032 e,~y.���-�����~
Wastewater Treatment Plant Pretreatment Department
Please accept this resubmittal for the project located at 21006 72nd Avenue W and known
asCedar View Memory Care Community.
The following isaresponse tothe Planning Review Comments.
The City of Edmonds Pretreatment Ordinances states that any wholesale shredding of food
wastes into any fixture that discharges into a GI is prohibited.
W/rhowzoddrezScdo0nequirz/nentsl*providcxyor0o0edi,,pmaer/nthe kiic/en,
Z. Pretreatment requires either removing the garbage disposer from the kitchen eliminating the
added sediment loading to the interceptor or increasing the interceptor size.
"�eo6/plumbing aokn/odonsƒorNbeThi", is/oco&yd/nthe /espnnso
RJ Development
40lCentral StSE—Olympia, VVA98S01
(360)528-3343—
3. If the disposer is kept in the plans, more frequent pump outs may be required to keep the fat,
oils, greases and sediment levels captured in the GI within the city's acceptable limits.
This will bac' coorditi ted between the city and the client at- time of operations. They
are owore of the sitoatioo.
4. Pretreatment sets the pump out frequency for all grease collection equipment and routinely
examines FOG and sediment liquid levels.
This hos been noted,
5. Attached to the email is a grease interceptor (GI) sizing worksheet to be completed. Do not fill
out the GT portion.
Alto hed is the G1 sizing workshee3t,
6. When determined, please provide a detailed cut sheet showing the approved GI for this location.
This is something thol the controct;or will provide shop drowings for approval,
7. To better define fixture terminations, please provide an expanded kitchen plan such as
sheet# FS.01 with color coded lines illustrating fixtures connected to the grease drain and
fixtures connected to the sanitary drain.
";C -"e revis€: ea .yhra(t iy't.Z.!i, M2. F, hri2.7, stir! M2,8for krlrarrrt,)irig fine, ot-id drains.
8. Which sinks are intended for the meat prep sink and vegetable prep sink?
5`ez sheet B. 01 herr 12. his is the prep orea for both fneot and vegetables. The sink
will yo into one floor drain below the unit,
9. The following fixtures must be connected to the GI:
® Mop sink.
R1 Development
401 Central St SE — Olympia, WA 98501
(360-528-3343) — www.rideveloprnentservices.com
® 3 comp sink.
® Dishwashers and prewash sink.
® Meat prep sink.
® Floor drains in the scullery/food prep area.
® Disposer if kept.
Ser_ sheet M2.1 and i42-5 fo ;lin fixtures listed thot will clischorgE: into the 61,
10. The following must not be connected to the GI:
® Hand sink.
® Vegetable prep sink.
See sheet. t02-1 and 142,5 fc)r the fixtures listed that no not discharge into the Gi.
11. The GI should have:
® 6" PVC lines, baffle tees, and drop legs.
® Proper venting allowing free air exchange between both chambers.
® Brackets supporting all downlegs in GI. It is very important to secure the down legs
to the vault walls; it may prevent costly repairs in the future. It is recommended to use
stainless steel unistrut bar and 6" clamps to secure pipe.
® Manhole lids specific for traffic.
® Graded away from the manholes to prevent runoff from entering the GI.
® Man hole covers above each downleg for inspection and maintenance.
Sege sheet CO -0 for ootes added to the plon, The contactor will submit shop drawings
for the G1 design approvol.
12. For the 3 -comp sink - follow The Health Department standards for isolating the sanitize sink from
the GI.
All current plumbing ore c ll showing H(-,,alth 0eporiment standards for crll sr nitize
sinks,
RJ Development
401 Central St SE - Olympia, WA 98501
(360-528-3343) - www.Cdevelogmentservices.com
13. Please have the GI installer notify me prior to the setting of the GI. I prefer to be present during
the setting of the vessel to eliminate potential problems. Additionally, a water test will need to
be conducted, before any backfill, to verify the integrity of the tank. The tank is filled with fresh
water one compartment at a time; no leaks should be visible through the baffle wall or outside
the GI.
W/e will heave the contractor contoc tt ytpufor instcallotion sequencing and to c oorclinote
schedules.
14. An exterior hose bib should be installed as near as possible to the GI location to facilitate the
pumping, cleaning, and priming of the GI.
See rc: Wh.