Shoring, Special insp.pdf. & ASSOCIATES, INC. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING CONSTRUCTION TESTING & INSPECTION FORENSIC INVESTIGATION July 18, 2016 Mr. Douglas Spee (E -Mail) EDMONDS 2020 LLC 307 Bell Street Edmonds, WA 98020 RE: FINAL LETTER Edmonds Post Office 130 2"d Avenue North Edmonds, WA Krazan No. 096-14139 .JUL " 1 2016 ENWERING DIVISION In accordance with your request and authorization, we have performed periodic special testing and inspection services for the above referenced project. The special inspections for this project were: • Soil Compaction Testing • PT Prestressed Concrete • Reinforced Concrete — CIP • Proprietary Anchor Installation • Shotcrete • Soil Nail Grout • Wood Seismic Resistance System To the best of our knowledge, the above referenced items have been found to be in general accordance with the approved plans and specifications, at locations represented within Krazan reports only. If you have any questions, or if we can be of further assistance, please do not hesitate to contact our office at (425) 485-5519." INC. Jeff P,ici fi �' M,'Aftlikkest Division JSM/Ikm CC: HALLER ARCHITECTURE (E-MAIL) DC1 ENGINEERS (E-MAIL) CITY OF EDMONDS 4303 198t1 Street SW, Lynnwood, Washington 98036 • (425) 485-5519 • FAX (425) 485-6837 With Offices Serving the Western United States 1'( & ASSOCIATES, INC. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING CONSTRUCTION TESTING & INSPECTION • FORENSIC INVESTIGATION November 18, 2014 Mr. Douglas Spee (E -Mail) EDMONDS 2020 LLC 307 Bell Street Edmonds, WA 98020 RE: CONSTRUCTION TESTING AND INSPECTION Edmonds Post Office 1302 d Avenue North Edmonds, WA Dear Mr. Spee, KA No. 096-14139 In accordance with your request and authorization, our firm performed construction testing and inspection for the above -referenced project. The sampling and testing was performed by our inspectors and reports are included. If you have any questions, or if we can be of further assistance, please do not hesitate to contact our office. Respectfully submitted, KRAZAN & ASSOCIATES, INC. Jeff Mercer Project Manager Pacific Northwest Division JM/Ikm CC 14ALLFRARCHITECTURE (E-MAIL) DCT ENGINEERS (E-MATL) CITY OF EDMONDS 4303 198" Street SW, Lynnwood, Washington 98036 • (425) 485-5519 - FAX (425) 485-6837 With Offices Serving the Western United States 09614139 DFR doc FIELD ^^ & A s s o c i a t e s, I n c. REPORT NO.: 14139DFR111414-CC - Geotechnical Engineering • Environmental Engineering Construction Testing and Inspection DATE: 11/14/2014 CONTRACTOR: DeWitt PROJECT #: 09614139 PERMIT #: 20140 PROJECT: Edmonds Post Office INSPECTOR: Christopher Congdon LOCATION: 130 - 2nd Ave N. JURISDICTION: Edmonds KA P.M.: Mercer WEATHER: Clear TEMP: 40 Arrived on site per request lbar reinforced concrete placement inspection for continuous footings approximately @ A.5-1-1/ l , 1-5/11, A-11/5, & 2.3-5/A. Reinforcing conforms to plans, verified re -steel size, grade, lap, clearance, and coverage. Re -steel ree of damage, oil, dirt, and excessive rust, and was adequately tied, chaired and supported to prevent displacement during ~oncrete placement. Monitored load tickets, batch weights, and water allowance. hscl-ved contractor place approximately 135 yd of Concrete Nor' West mix #01550. One set of five 4x8 cylinders was ade for compressive strength testing. Breaks scheduled for one on 11-21, three on 12-12, and one hold cylinder. See ,under report #14139CR1 1 1414 -CC for break results, to to allowed space only one truck was able to be backed up to concrete pump at a time. Pump needed to be moved during ncrete placement, as outriggers would have blocked road. Reviewed By: ASTM Test #: Equipment/Asset Number(s): To the best of my knowledge, the above WAS performed in accordance with the approved plans, specifications and regulatory requirements. S u peri ntendent/Represe ntative: Technician: Offices Serving the Western United States Lynnwood (425) 485-5519 • Poulsbo (360) 598-2126 • Puyallup (253) 939-2500 Daily Field Report Revision 8 Effective. 02(1312013 The, i'bK iau pmvi&d on thierelk'.e,p'_lel tortbr. exrinsive use orlhe mbenl. Tbis m— —Y aol be mpmduudm any fomrut. wilk nnt lb—Mtee part ar the client and Knm,&Assoaretes TbW n7urrt imdirates aur inv�r 9orc nhux'vxrirm andleslmR cu"�tlts bxs{rm sitn rrondiviuns and annhnctm[ ..Mliex.. Thhlallonnalbeiseubjeet to lrvixw prim tn� xl snhrnht®I. Fay siKning laAs repor[, aur inspector dncv amt arvmpt resgrnsibi)i[y for veii0.ity mrre:ulis. the saure iufOrmxlimn bes becu pruviQed by others an rite. N1_'KOF raZan & ASSOCIATES, INC. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING CONSTRUCTION TESTING & INSPECTION FORENSIC INVESTIGATION November 18, 2014 Mr. Douglas Spee (E -Mail) EDMONDS 2020 LLC 207 Bell Street Edmonds, WA 98020 RE: COMPRESSIVE STRENGTH TEST RESULTS Edmonds Post Office 130 2nd Avenue North Edmonds, Washington Dear Mr. Spee, KA No. 096-14139 Enclosed are copies of the compressive strength test results for the above referenced project. If you have any questions, or if we can be of further assistance, please do not hesitate to contact our office. Respectfully submitted, KRAZAN & ASSOCIATES, INC. Jeff Mercer Project Manager Pacific Northwest Division JM/Im CXHALLER ARCHITECTURE (E-MAIL) DCI ENGINEERS (E-MAIL) CITY OF EDMONDS 4303 198" Street SW, Lynnwood, Washington 98036 • (425) 485-5519 • FAX (425) 485-6837 With Offices Serving the Western United States 09614139 BRK,doe �a z wr MASONRY GROUT &Associate suInc . REPORT#: 14139MGR101514-JLG Geotechnical Engineering . Environmental Engineering Constructions Testing and Inspection Date: 10/15/2014 Contractor: DeWitt Project #: 09614139 Permit #: Project: Edmonds Post Office Inspector: Jerry L. Gelder Location: 120 2nd Ave N Edmonda Jurisdiction: City of Edmonds KA P.M.: Weather: Mostly Cloudy Temp: 55 ° Placement Area: Soil nail grout. West wall from approximately 20' north to 50' north. 2nd Row of nails. Remarks: Grout mixed mechanically onsite. Placed by pump. 1500psi at 3 days. Asset -Equipment Numbers: 111spec[or: perry ueloer J-aboratory Reviewed By: Laboratory Data Design Strength: Set Tested 3000 Ca) 28 days ASTM C39 Time Mid Pt. Type Out of Section Maximum Comp. Cyl. Test Width Height Plumb Area Load Strength Code Date Age (in) (in) M) (sq. in) (Ibs) (psi) 49590-1 10/18/14 3 2.0/1.97 2.00 0 3.94 28110 7130 49590-2 11/12/14 28 2.0/2.0 1.98 0 4.00 1 41120 10280 49590-3 11/12/14 28 2.0/1.99 2.00 0 3.98 1 402407 10110 Field Test Methods ASTM C143 ASTM C138 ASTM C1064 ASTM C173 ASTM C31 Other ASTM C231 C. Mercer Date Specimens Redd.: 10/16/2014 J-aboratory Test Methods Test Set Tested Break ASTM C39 Time # By Type ASTM C109 1 RG 1 ASTM C617 1 RG 1 ASTMI C1019 _ 1 1 RG 1 Other _est R Lints Conforming RemarksA 1A.,0—r Results Reviewed By C. Mercer Date Reviewed 11/14/2014 Codes for Break Types: 1t.. 2 3 4 5 S Offices Serving The Western United States Lynnwood (425) 485-5519 • Poulsbo (360) 598-2126 • Puyallup (253) 939-2500 Fonn 04103 Revision 8 Effmiiv° 01-11.13 Tho infonnnlion provided on this rep dfi p,¢p..d fw lho ¢xeluaiv¢ nse oftheeliem, —1—Y not ha rep od,-d in my farm wilh.d the 6K! n pznn . r n nfthe di¢nl wnd K—, & As—inter. Thi.—W indiwlrs napecmr'so rvutian and lrsling mnpa hwd.-ik..dilionw xnd canPrn¢(ar aetivilies Thin infnmelion is.snbjcct to review prior to l}nal.aubmittnl.. Fay signing this rcporl, our inapc¢lor doer nal acreptn:apnnsibilily for vnfidity of rcvultr 1'he wmYe inCnmtalian hes hcen prnvidcd by others an xile,. .Y &Associates,Inc. Geotechnical Engineering . Environmental Engineering Construction Testing and Inspection DATE: 10/15/2014 PROJECT#: 09614139 PROJECT: Edmonds Post Office LOCATION: 120 2nd Ave N Edmonds KRAZAN P.M.: CORE BREAK REPORT NO.: 14139CBR101514-JLG CORE CODE: 49587 POUR DATE: 10/15/2014 CONTRACTOR: DeWitt PERMIT #: INSPECTOR: Jerry L. Gelder JURISDICTION: Ci!y of Edmonds WEATHER: Mostly Cloudy TEMP 55 ° Laboratory Data Sample No. Max A, Size 1 0.375 2 - -0.375 3 0.375 4 0.375 ASTM C-39 Capped Design Strength: 4,22L@ 28 das 2.75 2.75 2.75 2.75 ASTM C-42 X Ratio of Max A 0.136 ASTM C-174 Code Reported Batch Data Field Data %Air (ASTM C-231) Temp. (ASTM C-1064) 65 ° Supplier: Salmon Bay L/D Slump (ASTM C-143) 2 1/4 Sampling (ASTM C-172) Plant Number: 3 Making (ASTM C-31) Unit Wt. (ASTM C-138) Batch Time: 2:14 2.01 -2 Sample Time: 3:45 28 1 Field Notes Truck #: 77 Ticket#: Y675995 2.00 Soil Nail Shotcrete. South wall Line 3 to 5 Elevation 34.5' to 28.8'. 2000psi at 3 days. Design Wts. Actual Wts. 2.75 Mix No. S4756000 11/12/2014 Cem. (Ibs) NO INFO I'll 2.75 F. Ash (Ibs) i I GIVEN P.M. Review: Agg. 1 (Ibs) A Sand (Ibs) Water (lbs) Air Ent. (oz) Admix. (oz) Water Added on Job (gal) Initial Curing Temps: (High) (Low) Amb. Air Temp.: Site Mix: Field Test Results Conforming Inspector: Jerry Gelder Laboratory Data Sample No. Max A, Size 1 0.375 2 - -0.375 3 0.375 4 0.375 ASTM C-39 Capped Design Strength: 4,22L@ 28 das 2.75 2.75 2.75 2.75 ASTM C-42 X Ratio of Max A 0.136 ASTM C-174 Code Test Date Age Length Diameter L/D -1 10/18/2014 3 5.53 2.75 2.01 -2 11/12/2014 28 1 5.50 2.75 2.00 -3 11/12/2014 28 5.55 2.75 2.02 -4 11/12/2014 28 5.45 I'll 2.75 1.98 P.M. Review: I.-,. t A Lab Data Reviewed By: C. Mercer 0.136 0.136 0.136 Date Specimens Redd: 10/16/2014 Diam. Uncapped Length Direction of Load 5.40 Pe 5.37 Pe 5.42 Pe 5.31 Pe ASTM C-617 X ASTM C-1140 ASTM C-1604 Area Load PSI C. F. 5.94 30340 5110 1.0 5.94 44940 7570 1.0 5.94 44240 7450 1.0 5.94 44700 7530 1.0 Date Reviewed: -1 q Date Reviewed: 11/14/2014 Corr. PSI Break Tested By 5110 1 RG 7570 3 RG 7450 3 RG 7530 3 RG Lab Test Results Conforming Offices Serving The Western United States Lynnwood (425) 485-5519 • Poulsbo (360) 598-2126 • Puyallup (253) 939-2500 Core Break RepotlRryMlstoo 3 611aiA�Wa 01-12.13 TM Information v. srn 1lwa'WPM 4 maP-d f. 04 *ft*,'mnP a or"owop kad -r W be OPl .rl..d 1r..Y Npnati%wM% -q ewn. arnluunn pw'mlpp,nxM d Fria dl -Ma t Kw n 8 A.4.k4nYim 1%nry nappal' IPMIznYa tbuv' n vMay+Y.n+�.w'�+w.wF 1pymhnG tldwNMm'I;amed on.ke Ga".b+F%d'W+m wanl aa�ba aaw,rk'rgFaw, 'fihia Cnft iabaAMaag Nwa hJnrp9r�Yavama YM&w a%w firref ayµ ..arvkdEtM aY We�n�N em6u re,�yPrp"uw'r Vrvepasma mmw antl44txmpt resprwyn¥.ihny+fa wa%rddwJNCamduW6M 'PMa Yams InNPmwnk. h" to Wrvrii.*d tq.0-pay. did, ,g�K- r . &Associates, Inc. Geotechnical Engineering - Environmental Engineering Construction Testing and Inspection Date: 10/17/2014 Project M 09614139 Project: Edmonds Post Office Location: 130 2nd Ave. N KA P.M.: JSM MASONRY GROUT REPORT #: 14139MGR101714-GE Contractor: Spee West Permit #: Bld 20140 Inspector: Gerald Eooink Jurisdiction: Edmonds Weather: Overcast Field data GROUT Supplier 1plant No. Site Mix Grout Air Max/Min Slump Temp. Temn. Temp. Time Truck# Ticket # % Air (in.) (F) (F) (F) Section Area (sq. In) Maximum Load (llbs) 65o 60 Grout Box Used Break Type T T, 49616-1 10/24/14 Number of units used to form specimens 2.0/1.95 2.0 0 Placement Area: For soil nails on the north facing wall, Remarks: Lefarge type 1-11 portland cement. pment Numbers: Inspector: Gerald Reviewed By: Temp: 60 ° Field Test Methods ASTM C143 ASTM C138 17 ASTM C1064 ASTM C173 17 ASTM C31 Other ASTM C231 I Laboratory Data Design Strength: 3000 @ 28 days Date Specimens Redd.: 10/22/14 aborato,ry L Cyl. Code Test Date Age Mid Pt. Width (in) Height (in) Out of Plumb (%) Section Area (sq. In) Maximum Load (llbs) Comp. Strength (psi) Test Set Time # Tested By Break Type T T, 49616-1 10/24/14 7 2.0/1.95 2.0 0 3.90 18870 4840 1 RG 1 49616-2 11/14/14 28 2.0/1.94 1.99 0 3.88 27960 7210 -- 1 RG 1 49616-3 11/14/14 28 2.0/1.93 2.0 0 3.86 27100 7020 -- 1 RG 1 Methods ASTM C39 ASTM C109 ASTM C617 ASTM C1019 Other Test Results Conforming Remarks — Results Reviewed By C. Mercer Date Reviewed 11 /14/2014 Codes for Break Types: fx� � ° / u � ` 1 2 3 4 5 6 Offices Serving The Western United States Lynnwood (425) 485-5519 - Poulsbo (360) 598-2126 - Puyallup (253) 939-2500 Form 04103 Revision H ERbctive 01-11-13 The in0semalion provided an this report ii,prepared f r the evelasive ass of'Ihc client, end may not ba rcpmducsd in any runnel Oh -1 the wrinen permissVon arthe imm and K—.& Assoaialra. Thio eep d indicxtss onr inspector's abssrvatian and testing resuhs boxed on sit., esmdilim:s acrd wmmctw selivities This informntian is :nxbject to reviser pri�sr Ia Onal anbmittnl. Hy si@Hing This report, aur inspatar dnKa Hat nwepi resp�nvsibi{iry f r vnlidiry of resntts, The samo intamsa(ion has horn pmvided by athera on siG:. Ql(mzw-i&Associates, Inc. Geotechnical Engineering a Environmental Engineering Construction Testing and Inspection DATE: 10/20/2014 PROJECT#: 09614139 PROJECT: Edmonds Post Office LOCATION: 130 -2nd Ave N.. Edmonds KRAZAN P.M.: J.Mercer CORE BREAK REPORT NO.: 14139CBR102014-KB Field Data CORE CODE: 49613 % Air (ASTM C-231) Temp. (ASTM C-1064) 70 -deg POUR DATE: 10/20/2014 CONTRACTOR: Spee West PERMIT #: Batch Time: 11:06a INSPECTOR: Kevin Boekholt JURISDICTION: City of Edmonds WEATHER: Overcast TEMP 65 ° Field Data Reported Batch Data % Air (ASTM C-231) Temp. (ASTM C-1064) 70 -deg Supplier: Salmon Bay Slump (ASTM C-143) 2 -inches Sampling (ASTM C-172) X Plant Number: Shilshole Making (ASTM C-31) X Unit Wt. (ASTM C-138) Batch Time: 11:06a Sample Time: 12:30 Field Notes Truck #: 7513o iAt 12:30pm a 12"x12"x6" sample panel was created during the application of the shotcretd for the 8 nails of the 2nd row of the West wall. Sample was left onsite and will be picked up Ticket #: Y676164 tomorrow and delivered to our lab for appropriate compression testing. Only 10 of the 27 Desl n Wts. Actual Wt& allowable gallons of water was added to the mix. See Report 09614139DFRIO2014KB for Mix No S4756000 additional information. Cem. (Ibs) 705 F. Ash (Ibs) Agg. 1 (Ibs) 910 Sand (Ibs) 2120 Water (Ibs) 304 Air Ent. (oz) Admix. (oz) Water Added on Job (gal) 10 Initial Curing Temps; 70 ° (High) (Low) Amb. Air Temp.: 65 ° Site Mix: Field Test Results Conforming Inspector: Kevin Boekholt Laboratory Data Design Strength: 4.000 Q 28 days Date Specimens Recd: 10/21/2014 Sample No. Max AverageDiameter Ratio of Max N2. To Diam, Len th Direction of Load 0.375Size 0.136 5.28 2 0.375 2.75 0.136 .42 Perpendicular 75.37 3 0.375 2.75 0.136 Perpendicular 4 0.375 2.75 0.136 5.31 Perpendicular ASTM C-39 ASTM C-42 X ASTM C-174 ASTM C-617 X ASTM C-1140 Capped ASTM C-1604 Cyl. Code Test Date Age Length Diameter LID Area Load PSI C.F. Corr. PSI Break Tested B -1 10/27/2014 7 5.41 2.75 1.97 5.94 33720 5680 1.0 5680 1gR RG -2 11/17/2014 28 5.55 2.75 2.02 5.94 38530 6490 1.0 6490 3RG -3 11/17/2014 28 5.50 2.75 2.00 5.94 37720 6350 1.0 6350 3RG -4 11/17/2014 28 5.43 2.75 1.98 5.94 38140 6420 1.0 6420 1G P.M. Review: Date Reviewed: Lab Test Results Lab Data Reviewed By: C. Mercer Date Reviewed: 11/18/2014 Conforming Offices Serving The Western United States Lynnwood (425) 485-5519 a Poulsbo (360) 598-2126 • Puyallup (253) 939-2500 Core Break Report Revision +a B.dYmtddva 01-12-13 The ini—a m pa.°,fdd.11dn d41N w"M fm p' nq!d tau,,a arsUu mina Of V* oWTL and may wAtm.'axat'u+s %K*d in any fa *t+A4ft )- 014 K..n 8 d0aao,z W*t Thi.i"nt Anka. wx 4napW— acne, Um"W"kUt+ t h. t ..d an ab Kaa%dMSINYa ano crr"Yra*3OA ap;YJYGJga. 1'YfVa iRIAtlMIM1ehklWli da aYpjtlky.WroNaN p(bY by Yu qa �Yy dly Nflak4Yj,Il"dM Nro'pnwl.Ole Y¢bWYlg4N:N GM Pa a44t'atxaWYstl panc*anat�+uXy 10l waWiPlCy °YcaMuka. AIYaaama fM'IYIY+m'!11(FPYI kMNe I'OANM Wq^+'b�a+d mp MF1YYW1a.VM%Wha. " -= & ASSOCIATES, INC. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING CONSTRUCTION TESTING & INSPECTION FORENSIC INVESTIGATION October 15, 2015 Mr. Douglas Spee (E -Mail) EDMONDS 2020 LLC 207 Bell Street Edmonds, WA 98020 RE: COMPRESSIVE STRENGTH TEST RESULTS Edmonds Post Office 130 2" Avenue North Edmonds, Washington Dear Mr. Spee, KA No. 096-14139 �{qui 2015„ Enclosed are copies of the compressive strength test results for the above referenced project. If you have any questions, or if we can be of further assistance, please do not hesitate to contact our office. TES, Jeff Mercer Project lwl :5a Pacific ort es ivision RWIM C'C' HALLER ARCHITECTURE (E-MAIL DCI ENGINEERS (E-MAIL) CITY OF EDMONOS 4303 198” Street SW, Lynnwood, Washington 98036 • (425) 485-5519 • FAX (425) 485-6837 Willi Offices Serving the Western United States 09614139 BRK.doc _ � CONCRETE &Associates, Inc. REPORT NO.: 14139CR081715-WB Geotechnical Engineering - Environmental Engineering Construction Testing and Inspection DATE: 8/17/2015 CONTRACTOR: Edmonds 2020 PROJECT #: 09614139 PERMIT #: BLD20140074 PROJECT: Edmonds Post Office INSPECTOR: William Bui LOCATION: 130 2nd Ave N JURISDICTION: Edmonds KA P.M.: Jeff Mercer WEATHER: Sunny TEMP: 6F,— Field Field Data Concrete: I Other: Supplier: CN W Plant No. Site Mix: Slump Mix Air Unit Time Truck # Ticket # % Air Inch Temp (F) Tem F Weight. 111:15aml C143 68053 1 5.5 1 7.5 75' 69 ° Location: Placement Area L3 (C.5 -E.5/ 1) Closure post tension and stern Remarks: Please Refer To Field Repot, Number: 9614139DFRO8172015-WB Inspector:E William Bui Reported Batch DATA � Cement Type Design Actual Mix No. 07600136 Corn Lbs 650 649 F. Ash Ibs, C. Agg Lbs 1650 1645 C. Agg• Lbs C. Agg. Lbs Sand lbs 1510 1504 water20891 18391 Adrd'Wure Adrnlu uro Admixture Air Ent, '... (oz /cwI................... Water Added On Job Site (Gals.) 10g1 � Field Test ASTM Method C143 C138 C1064 C173 C31 Other Laboratory Data Design Strength: 6000 @ 56 days Date Specimens Recd: 1 8/1812015 Cyl, Test Field Wt, Max 'Brk Test. Method Comp. SetENG Code Date Cure Age Dim. Area # Load Strength #TYp ASTM C39 52456-1 8/24/15 7 4x8 12.56 -- 62050 4940 12 ASTM C109 52456-2 9/14/15 28 4x8 12.56 -- 76050 6060 13 ASTM C617 52456-3 10/12/15 56 4x8 12.56 -- 83480 6650 1 1 NG 2 ASTM C1231 52456-4 10/12/15 56 4x8 12.56 -- 84160 6700 1 NG 3 ASTM C1019 52456-510/12/15 56 4x8 12.56 -- 83720 6670 1 L NG 2 OTHER Test Results Remarks: Results Reviewed By,] Conformin Gate; , ,( 9 Codes for Break Types: �" "� �' f N" , r3 1 21 4 5 Offices Serving The Western United States Concrete Report Revision 11 Effective 02-11-13 Lynnwood (425) 485-5519 - Poulsbo (360) 598-2126 - Puyallup (253) 939-2500 The Mormallon p°vaee an Mh wr�wp(w WwS+rmxAA Yal nx wwc�aaw4a uaw ar tkw WYpM,. MrtM pmY}batiap+adhKeU'ihervr Pr+wt�t W°�a ewwitllPoanrvµ Nrelmakury cn tna arp+Aemd NSawtlmnB Nwa¢minO+eP. 7CnVboaCtid bnd'em.a+wNwpp;;Rx.'n aiawncwallryrawzMtdeWrW?. F%awR,a. besatl °n eXeeorMltlone end Pn:,44oaMcr. wefidxNAati AfMn.4 fii W+M54'Y&,a'wn..pry�pw:E Ma apuiM+wi yH,gM Ad7Vraal.'eld8.w¢oAtlul. ByYeaVWm'ga"+'tl. Mutbwy"4cbu yY�gA!r,NArtcer'Emap'wkvkhdp lar a;4tlG1%Mf�Nd ovrvanuA% 9'IMw m,ry'wn imV"4mwY,Mm kiwro �pnAn p, y+MtlMak Mq a#Amrw W/I wM1m. OF miet�~ & ASSOCIATES, INC. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING CONSTRUCTION TESTING & INSPECTION FORENSIC INVESTIGATION September 20, 2014 Mr. Douglas Spee (E -Mail) EDMONDS 2020 LLC 207 Bell Street Edmonds, WA 98020 RE: COMPRESSIVE STRENGTH TEST RESULTS Edmonds Post Office 1302 d Avenue North Edmonds, Washington Dear Mr. Spee, KA No. 096-14139 l; NCANEE N WON Enclosed are copies of the compressive strength test results for the above referenced project. If you have any questions, or if we can be of further assistance, please do not hesitate to contact our office. le Mer Project er Pacif o wrest Division JM/Im C.C. HALLER ARCHITECTURE (E-MAIL) DCI ENGINEERS (E-MAIL) CITY OF EDMONDS 4303 19811 Street SW, Lynnwood, Washington 98036 • (425) 485-5519 • FAX (425) 485-6837 With Offices Serving the Western United States 09614139 BRK.doc MASONRY GROUT & A s s o c i a t e s, i n c. REPORT M 14139MGRO91514-GE Geotechnical Engineering - Environmental Engineering Construction Testing and Inspection Date: 9/15/2014 Contractor: Spee West Project #: 09614139 Permit #: Bid 20140 Project: Edmonds Post Office Inspector: Gerald Eggink Location: 130 2nd Ave. N Jurisdiction: Edmonds KA P.M.: JSM Weather: Clear Tamn- Fin Placement Area: Sample taken during placement at AR2. 3 day, 1800 psi requirement and 28 day, 3000 psi requirement. 5 bags of Lehigh type 1 -II portland cement was mixed with about 20 gallons of water. pment Numbers: maPUGLU . %3erala S291nK Reviewed By: Field Test Methods ASTM C143 ASTM C138 ASTM C1064 ASTM C173 ASTMi C31 Other ASTM C231 Laboratory Data Design Strength: 3000 0- 28 days ................... Date Specimens Rec'd.: 9/17/2014 Laboratory Pt. Out of Section Maximum' Comp. Test Methods Cyl. Test th Height Te(i Plumb Area Load Strength Test Set Tested Break ASTM C39 Code Date A) (in) (%) (sq. in) (Ibs) (psi) Time # By Type ASTM C109 49330-1 9/18/14 2.0 2.01 0 4.0 1 20130 5030 -- 1 1 RG 1 ,ASTM C617 49330-2 10/13/14 1 28 f ASTM C1019 49330-3 10/13/14 28 , �... Test Results Remarks Results Reviewed By C. Mercer Date Reviewed 9/20/2014 Codes for Break Types:W YYY111LLL ..� �.a, 1 2 3 4 5 6 Offices Serving The Western United States Lynnwood (425) 485-5519 - Poulsbo (360) 598-2126 - Puyallup (253) 939-2500 Foam 04103 Revision 8 Effw ive 01-11.13 TheW nonp ided-.hi. mpw ie p,.,.d ror the errc0 uV' I rtllwo<G•rvm 41—yno1WroKW,-AI.yiwa,ar110-d 0. x.fto 4amion orlhednl ndX..,,mua,h 1u.e. 'r'h,l, po Mk,,.,.rrlaapxeW,-inwnxrwos W NRWq. a ai JU hued oo Bile c-difi and eanhaclor.e Wi. Thu uMfW..N. re eu4.1 10 x0prim 1. rM MrOnavW By'�Aak'4pm.YiFb'w,1, epu YrrwpWiCµN de�vs nd e¢epl rcep,n ihdikry'dNa'xnOFtlump mtl'rxrv.�'IGY. The esme,eTC�rmrufwwl pWa EK.ntl,jMtrvwxdwp qry 0°WaN fNa Am'u�. f �r . R,&SC)CI I'1;5, INC. GFo rIiCIINICA I. ENG INC ERIN G a ENV IRO;' XIEN I AI HXGINEFRING CONS I -RUC rION I LSTiNG & INSPEC I ION - ['01115SW INVI?51ICrAnON Sw'�tWm'-.:r 1$.201 Mr. Douglas Stec (E -Mail) t'm-lo�t)s 2020 t,t,c 307 Bdl Street Edmonds, WA 98020 RE: CO\STRUCTION `I'll;S'FISG A --,'I) I\7SPY1(" HOI Edmonds Post Office 130 2" Avenue North Edmonds, NV KA No. 096-14139 Dear NO Spec.. In accordance with your request and authori'ration, our first put need connuMmi testing and inspection for the We referenced Qua The sainWhq and takhg waS perQWrne(1 by our inspectors and reports are included. If )uu have any questions, or if we can be or assistance, I)IC8SC do not hC'SiLlIC to contaC,I our oHlec. .P 1�etpec'GE.nVI ,ilf;"t�alt u I [M% % Jeff Mercer Project MitQ b Pacific��t�k��n�„t Division hUhn D('1 EN(11V1;1 RS U NI 111 i Crr1' Of!MhJ lWDS 4303 19WI Street SMA Igunwood, Washfugton 98036 o (425) 485-5519 a FAX (425) 485-6837 yI`itlr C3 ices .Yerving th 0 Wevern United ,.Walas RE ID I<X'�.., Z�111 1, & A s s o REPOFRF NO.� 14139 D FRO91 514 -GF- ... . .......... rout placed Or sail WN aWng Tu eag IfAng rewfing wall. In samMe "m taken f'rom A.R2 wid lefl. m siw,, for Ck LIP.. Gi•Wt Truxed on Mm mAT 5 Wags ol Lchigh type IQ[ PodMnd ownent and about 710 jW11mis M'%vtLtku-, mw has a 1500 pi reT%mem aPer 3 days and 3000 pi MOMMON aRu 28 d",s mwe IRmnathn, jAuasu rcfbr to Ejow nVon M l U39MCiR,09I5HG1.,, Rmhmd By 1I o the best of my knowIedge, N..: j I cps i�'rficnUAssoi� perforTned an amoQwwe WT the OPPmvcd Want apmOmiNns and rmway reymmnK Tedundan ORKes Semhn the Western LIMA States L,vmvvcq)d I 5 H 19 - NOW (NAU 5981126 - Nqydhp (21Y 939 2500 H. .- K Irlc4ai,, .,I � li, � , :" , I P ! , " " , , " i"' , , , I , 11111 , 1 11, : I , "', 10 n1ih Atl,, " , ' , , , , ,1 11 .n ' '" '­""'� ""l, �" P, I �'i' '' 1, , i, , �' ?I', I 11�1 ', .... ... ... 4" '' , ", , , , W, '�i �' " � ""J "&' , A i ik : 1", 1 , , , I I , 'I, , , , , " , , f , , , , , , , I " , , I , ' , , f 0 � " , " , , , " IJ , , , , I I I , 11 " I I Kraza-ri & ASSOCIATES, INC. GEOTECHNICAL ENGINEERING - ENVIRONMENTAL ENGINEERING CONSTRUCTION TESTING & INSPECTION FORENSIC INVESTIGATION August 31, 2015 Mr. Douglas Spee (E -Mail) EDMONDS 2020 LLC 207 Bell Street Edmonds, WA 98020 RE: COMPRESSIVE STRENGTH TEST RESULTS Edmonds Post Office 1302 d Avenue North Edmonds, Washington Dear Mr. Spee, KA No. 096-14139 ISE ) SI 2(1' 1(urk Enclosed are copies of the compressive strength test results for the above referenced project. If you have any questions, or if we can be of further assistance, please do not hesitate to contact our office. Respectfully submitted, KRAZAN & ASSOCIATES, INC. Jeff Mercer Project Manager Pacific Northwest Division ANIM C'C' HALLER ARCHITECTURE (E-MAIL) DCI ENGINEERS (E-MAIL) CITY OF EDMONDS 4303 198" Street SW, Lynnwood, Washington 98036 - (425) 485-5519 - FAX (425) 485-6837 Willi Offices Serving tl:e Western United Stales 09614139 BRK,doc azanUAssociates. Inc. Geotechnical Engineering • Environmental Engineering Construction Testing and Inspection DATE: 8/17/2015 PROJECT* 09614139 PROJECT: Edmonds Post Office LOCATION: 130 2nd Ave N KA P.M.: Jeff Mercer Field Data Concrete: Other: CONCRETE REPORT NO.: 14139CRO81715-WB CONTRACTOR: Edmonds 2020 PERMIT #: BLD20140074 INSPECTOR: William Bui JURISDICTION: Edmonds WEATHER: Sunny Supplier: CNW Plant No. Site Mix: Slump Mix Air Unit Time Truck # Ticket # % Air Inch Temp (F) Temp (F) Weight 11: 15 am C143 j 68053 5.5_L 7.5 1 75 ° 1 69 ° Location: Placement Area L3 (C.5 -E.5/ 1) Closure post tension and stern wa Remarks: Please Refer To Field Repol. Number: 9614139DFR08172015-WB Inspector -I William Bui TEMP: 69 ° Reported Batch DATA Cement Type Design Actual Mix No, 0760006 Cem. Lbs.. 650 649 !i F. Ash lbs, C. Agg. Lbs 1650 1645 C, Agg. Los _... C.. Agg. 4.bs, Sand Obs 1510 1504 Water 208al 18391 Addm2xltn e Admixiure Axdmhxlu o Air Ent. ( oz / CW1 Water Added On Job Site (Gals.) 1081 Field Test ASTM Method C143 C138 C1064P C173 C31 Other Laboratory Data Design Strength: 6000 an 56 days j Date Specimens Recd: 811812015 Cyl. Test Field Wt, Max Comp. Set Tested Brk Test Method Code Date Cure Age Dim. Area # Load Strength # By Typ ASTM C39 52456-1 8/24/15 7 4x8 12.56 -- 62050 4940 1 NG 2 ASTM C109 52456-2 9/14/15 28 4x8 1 ASTM C617 52456-3110/12/15 56 4x8 1 ASTM C1231 52456-4110/12/151 56 4x8 1 ASTM C1019 52456-510/12/15 56 4x8 1 OTHER Test Results Remarks: Results Reviewed By: I Date: T] Codes for Break Types: 1 2 3 4 5 -.6.. Offices Serving The Western United States Concrete Report Revision 11 Effective 02-11-13 Lynnwood (425) 485-5519 • Poulsbo (360) 598-2126 • Puyallup (253) 939-2500 The Ink—non pre.aed on this aogm%pdwpW'mdtofrheene&'wdr'0-01h­140, ----Y r x 4W In eny 00 OW 091—n&&Kodnft'Thk �,haM'CWF'WotnoM.fry�AOS'eo`uNFb1''tlnxpii W°A dka��rewns trn,ed on sna eonEMlorro eay,�m�wWrx,er»Wawm. Tnre,vr,nnn�nWew�mnaroav�w�dW�,t�rnnWWr,xwn eyeinmrninw,ewe.aureWtipaemW,tieweW�»�WwWaawu�yro<Ws�rvyWda'Wwene. tr�uWae»dnr nprWrnncwraWrhwrrvpenuuy.wwnene.