SKMBT_C45008051416570.pdfMay 14, 2008
TO: Warren LaFon
FROM: Steve Fisher, City of Edmonds Public Works, 425-771-0235
RE: Plan review for proposed trash enclosure
#2008-0287 Jantz Building, 547 Dayton St.
The location of the proposed trash enclosure at the northwest comer of the property is
appropriate, due to its relation to the existing alleyway. The approximate finished inside
size is shown as 10' wide by 8' deep, which is the absolute minimum required. The
concrete slab shall be at grade with the finished alley.
Some details need to be addressed. First the entire gated area needs to show 10' clear
when the gates are in the open position. Gate supports need to be placed so this is
accomplished. This also allows the gate sections to swing open to the minimum
requirement of just past 90 degrees. In this case the ability to swing to a full 180 degrees
is desirable.
Appropriate hardware, such as drop pins/pavement sleeves are required for proper
positioning of gates when open and closed. Securing devices need to be indicated on the
enclosure detail required under the general design standards, along with indication of gate
swing's fullest extension.
Please show an elevation, showing finished inside dimensions, including minimum height
of 8' (since this area is entirely within the building), exclusive of lighting, sprinklers, etc.