Special Inspection reports.pdfOTTO ROSENAU & ASSOCIATES. INC.
SPECIAL INSPECTION & MATERIALS TESTING
OPEN ISSUE LOG
Project: Margo Day Residence Permit: Job No.: 18-0269 Date Updated: 4/23/2018
Item
No.
Inspection
Date
Report
No.
Inspector(s)
Remarks
Action Required
(e.g. re -inspection, engineer follow up, etc.)
Date
Resolved
A representative number of probe tests were taken
throughout the referenced vicinity; based on penetration of 2"
1
4/11/2018
367913
Chris Smith
to 3" with sustainable resistance to advance into surface it is
our recommendation that the top 1" to 2" of soil be removed
Reinspection
before placement of concrete to reach competent soils that
can support 1500 psf.
MAY 2 9 2018
Copies to:
DEVELOPMENT SERVICES
COUNTER
X Client X Engineer �.---�
Owner Contractor Technical Responsibility:
Architect X Building Dept. Isaac Ruoff; Project Manager
This report applies only to the items tested or reported and is the exclusive property of Otto Rosenau & Associates, Inc. Reproduction of this report, except in full, without written permission from our firm
is strictly prohibited.
Page 1 of 1
6747 M.L. King Way S., Seattle, Washington 98118 — Phone (206) 725-4600 or 1-888-OTTO-4-US — Fax (206) 723-2221
OTTO ROSENAU & ASSOCIATES, INC.
Geotechnical Engineering, Construction Inspection & Materials Testing
CONSTRUCTION INSPECTION REPORT RECEIVED
Report Number: 367913
Project: Margo Day Residence Permit Number: (In progress) MAY g 2018
Address: 219 Skyline Drive, Edmonds Job Number: 18-0269 DEVELOPMENT SERVICES
nni l.-
Client: Morris Originals, LLC client Address: 31 l I New marKet atreet�-xxte n¢A, tseiungnam
_ Inspections Performed
Steel Decking Other (specify): Other (specify):
Structural Steel Fabrication Soil bearing X
Structural Steel Erection
Inspector
and Date
Chris Smith
4/11/2018
Copies to:
Remarks
Contractor requested a site visit to inspect soil bear capacity. ORA representative soil probed 4 spread
footings and one continuous footing at the south west corner of the property.
A representative number of probe tests were taken throughout the referenced vicinity; based on
penetration of 2" to 3" with sustainable resistance to advance into surface it is our recommendation that
the top 1" to 2" of soil be removed before placement of concrete to reach competent soils that can
support 1500 psf.
Does Not Conform
X Client X Engineer Others t�
Owner Contractor Technical Responsibility: —f �,y�s'f ( �� a
Architect X Building Dept. y Isaac Ruoff, Project Manager
This report applies only to the items tested or reported and is the exclusive property of Otto Rosenau & Associates, Inc. Reproduction of this report,
except in full, without written permission from our firm is strictly prohibited.
Page 1 of 1
6747 M.L. King Way S., Seattle, Washington 98118 - Phone (206) 725-4600 or 1-888-OTTO-4-US - Fax (206) 723-2221
Form No.: ADMIN-63-05 (Rev 10/10)
eCElve'ry
OTTO ROSENAU & ASSOCIATES, INC. y J0
Geotechnical Engineering, Construction Inspection & Materials Testing Mayyl
PROPRIETARY ANCHOR ADHESIVE INSPECTION REPORT
Job Number: 18-0323 Report Number: 293036 Permit Number: 18100514RK
Project: Primm Retrofit Client: Cascadia Seismic, Inc.
Address: 6211 150th Place SW, Edmond Address: 1322 238th Place SW, Bothell
Inspector: Paul Kanikkeberg Date: 4/30/2018
Description/Location: 5/8" diameter anchor bolts epoxied into existing stem walls in garage, laundry room, and music room.
Inspected to approved plans and details.
Intended Use: Holdowns Building Code & Year: SBC 2015
❑ Reinforcing Steel
® All Thread
Bar/Dowel Size & Quantity: Anchor Size & Quantity: 5/8" (12)
Rebar Manufacturer: Type of Steel (ASTM): ® A-36 ❑ A-325 ❑ A-449
Rebar Grade: ❑ 40 ❑ 60 ❑ Other: ❑ Other:
Type of Bar: ❑ A-615 ❑ A-706 ❑ A-775 ❑ Other:
Special Ductile Quality (SDQ): ❑ Yes ❑ No
Anchor Length: 12"
Hole Depth: 8"
Required Embedment: 8"
Hole Diameter: 3/4"
Concrete Thickness: 6"
Concrete Strength: Existing
Hole Orientation: ® Vertical Down ❑ Vertical Up ❑ Horizontal
Base Material: ® Normal Weight Concrete ❑ Light Weight Concrete ❑ CMU ❑ Brick ❑ Composite Deck
Hole Cleaning: ® Compressed Air
❑ Hand Pump ❑ Other:
Compressed Air PSI: 100
Brushed: ® Yes ❑ No
Hole Condition: ® Dry ❑ Damp ❑ Water Saturated ❑ Submerged
Drill Bit (ANSI B212.15): ® Yes ❑ No
Approved Diamond Cored Hole: ❑ Yes ® No
Adhesive Type: Simpson SET XP
Expiration Date: 12/18/2019
ICC ESR #: 2508
Weather: Cloudy, indoors
Ambient Temperature: 50°F, 60°F
Substrate Temperature: 50°F, 60°F
Comments
Reference Standard(s) Used:
Conforms X Does Not Conform
Copies to:
Client X Engineer Others }f� �(/�/2�� �ry✓c Owner X Contractor Technical Responsibility: �"'" .
Architect X Building Dept. Isaac Ruoff, Project Manager
This report applies only to the items tested or reported and is the exclusive property of Otto Rosenau & Associates, Inc. Reproduction of this report,
except in full, without written permission from our firm is strictly prohibited.
Page 1 of 1
6747 M.L. King Way S., Seattle, Washington 98118 — Phone (206) 725-4600 or 1-888-OTTO-4-US — Fax (206) 723-2221
Form No.: ADMIN-86-02 (Rev. 05113)
ECElveo
OTTO ROSENAU & ASSOCIATES, INC. R
Geotechnical Engineering, Construction Inspection & Materials Testing ai 2g 2018
pEVE�-� ��UNTER
PROPRIETARY ANCHOR ADHESIVE INSPECTION REPORT
Job Number: 18-0269
Project: Margo Day Residence
Address: 219 Skyline Drive, Edmonds
Inspector: Travis Linn
Report Number: 365450
Permit Number: (In progress)
Client: Morris Originals, LLC
Address: 3111 New Markey Street, Suite 105, Bellingham
Date: 4/18/2018
Description/Location: ORA representative on site to inspect installation of epoxy all thread for foundation pad on west side of
property.
Intended Use: Steel column / foundation connection Building Code & Year: 2015 IBC
❑ Reinforcing Steel
® All Thread
Bar/Dowel Size & Quantity: Anchor Size & Quantity: %", (24)
Rebar Manufacturer: Type of Steel (ASTM): ❑ A-36 ❑ F-1554 ® A-307
Rebar Grade: ❑ 40 ❑ 60 ❑ Other: Grade: ❑ 36 ® 50 ❑ 75 ❑ Other:
Type of Bar: ❑ A-615 ❑ A-706 ❑ A-775 ❑ Other:
Special Ductile Quality (SDQ): ❑ Yes ❑ No
Anchor Length: 18"
Hole Depth: 9"
Required Embedment: 9"
Hole Diameter: 7/8"
Concrete Thickness: 24" (2), 12" (2)
Concrete Strength: 2500+
Hole Orientation: ® Vertical Down ❑ Vertical Up ❑ Horizontal
Base Material: ® Normal Weight Concrete ❑ Light Weight Concrete ❑ CMU ❑ Brick ❑ Composite Deck
Hole Cleaning: ® Compressed Air
❑ Hand Pump ❑ Other:
Compressed Air PSI: 100+
Brushed: ® Yes ❑ No
Hole Condition: ❑ Dry ® Damp ❑ Water Saturated ❑ Submerged
Drill Bit (ANSI B212.15): ® Yes ❑ No
Approved Diamond Cored Hole: ❑ Yes ® No
Adhesive Type: SET XP
Expiration Date: 5/5/2019
ICC ESR #: 2508
Weather: Clear
Ambient Temperature: 43°F
Substrate Temperature: 41 °F
Comments
First (12) holes used SET XP, as stated above, on southwest pads. Last (12) holes used CIAGEL 7000-C, expiration date 8/14/2019,
ESR #437, for holes on northwest side.
Reference Standard(s) Used: Conforms _ X Does Not Conform
Copies to:
X Client X Engineer Others
Owner Contractor Technical Responsibility:
Architect X Building Dept. Isaac Mqn, Project Manager
This report applies only to the items tested or reported and is the exclusive property of Otto Rosenau & Associates, Inc. Reproduction of this report,
except in full, without written permission from our firm is strictly prohibited.
Page 1 of 1
6747 M.L. King Way S., Seattle, Washington 98118 - Phone (206) 725-4600 or 1-888-OTTO-4-US - Fax (206) 723-2221
Form No.: ADM/N-86-02 (Rev. 05113)
OTTO ROSENAU & ASSOCIATES, INC.
Geotechnical Engineering, Construction Inspection & Materials Testing
CONSTRUCTION INSPECTION REPORT
Report Number: 367509
Project: Sunrise of Lynnwood Permit Number: BLD2015-1512
Address: 21500 72"d Avenue West, Edmonds Job Number: 17-0585
VIECEIVEE)
MAY 2g 2018 _.
66_ NOR
Client: Sunrise of Lynnwood Client Address: 2i500 72-, Ave vv, Edmonas
_ Inspections Performed
Steel Decking Other (specify): Other (specify):
Structural Steel Fabrication
Structural Steel Erection
Inspector
and Date
Remarks
Brian Robertson On site as requested by Jay Garthwaite Managing Director for TeamK12 to perform paint thickness
5/04/2018 testing at various locations in the newly painted section of the building. Mil thickness was taken
using PosiTector® Inspection Kit ORA #5579 D 260508. Locations and testing match the supplied
map and testing directions.
Locations and Results
1. Location 1.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 78 mils.
2. Location 1.
Mid Wall Wood Baseboard 74 mils.
3. Location 2.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 101 mils.
4. Location 2.
Mid Wall Wood Baseboard 84 mils.
5. Location 3.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 62 mils.
6. Location 3,
Mid Wall Wood Baseboard 72 mils.
7. Location 4.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 86 mils.
8. Location 4.
Mid Wall Wood Baseboard 78 mils.
9. Location 4. Mid Wall Casework 58 mils.
10. Location 5.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 80 mils.
11. Location 5.
Mid Wall Wood Baseboard 115 mils.
12. Location 6.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 58 mils.
13. Location 6.
Mid Wall Wood Baseboard 55 mils.
14. Location 6.
Mid Wall Wood Crown -Structure 56 mils.
15. Location 7.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 72 mils.
16. Location 7.
Mid Wall Wood Baseboard 71 mils.
17. Location 7. Mid Wall Casework 57 mils.
18. Location 8.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 59 mils.
19. Location 8.
Mid Wall Wood Baseboard 57 mils.
20. Location 9.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 66 mils.
21. Location 9.
Mid Wall Wood Baseboard 59 mils.
22. Location 10.
Mid Wall Gypsum Wall Board 60" Above Finished Floor 75 mils.
23. Location 10.
Mid Wall Wood Baseboard 61 mils.
Copies to:
4alte'
X Client X Engineer Others _
X Owner X Contractor
Technical Responsibility:
Architect X Building Dept.
i sen, Project Manager
This report applies only to the items tested or reported and is the exclusive property of Otto Rosenau & Associates, Inc. Reproduction of this report,
except in full, without written permission from our firm is strictly prohibited.
Page 1 of 3
6747 M.L. King Way S., Seattle, Washington 98118 - Phone (206) 7254600 or 1-888-OTTO-4-US - Fax (206) 723-2221
Form No.: ADMIN-63-05 (Rev 10/10)
OTTO ROSENAU & ASSOCIATES, INC.
Geotechnical Engineering, Construction Inspection & Materials Testing
Job Name: Sunset of Lynnwood
Job No.: 17-0585
Report No.: 367509
MAC 2� 2U19
24. Location 10. Mid Wall Wood Crown -Structure 81 mils.
25. Location 11. Mid Wall Gypsum Wall Board 60" Above Finished Floor 39 mils.
26. Location 11. Mid Wall Wood Baseboard 57 mils.
Location 12. Mid Wall Gypsum Wall Board 60" Above Finished Floor 57 mils
No specified thickness was given.
: W.* "
t•y .
-1.
COUNTER
I
} � 1
!1► .` y [ y
t �.eyyl 1- t3
l
hA:3
L to , 3i��\1� `
Page 2 of 3
OTTO ROSENAU & ASSOCIATES, INC.
Geotechnical Engineering, Construction Inspection & Materials Test!
Job Name: Sunset of Lynnwood
Job No.: 17-0585
Report No.: 367509
FjF'CE1'VF-[)
MAY 29 201%
-IV- -
.
COUN'MR
1
Mid Wall. Two samples. GWB at 60 inches AFF. Wood Base,
2
Mid Wall. Two samples. GWB at 60 inches AFF. Wood Base.
3
Mid Wall. Two samples. GWB at 60 inches AFF. Wood Base.
4
Mid Wall. Three samples. GWB at 60 inches AFF. Wood Base. Plus Casework
5
Mid Wall. Two samples, GWB at 60 inches AFF. Wood Base.
6
Mid Wall. Three samples. GWB at 60 inches AFF. Wood Base. Plus Wood Crown Structure
7
Mid Wall. Three samples. GWB at 60 inches AFF. Wood Base. Plus Casework
8
Mid Wall. Two samples. GWB at 60 inches AFF. Wood Base.
9
Mid Wali. Two samples. GWB at 60 inches AFF. Wood Base,
10
Mid Wall, Three samples. GWB at 60 inches AFF. Wood Base. Plus Wood Crown Structure
11
Mid Wall. Two samples. GWB at 60 inches AFF. Wood Base.
12
Mid Wall. Three samples. GWB at 60 inches AFF. Wood Base, Plus Wood Crown Structure
13
Mid Wall. Three samples. GWB at 60 inches AFF. Wood Base. Plus Wood Crown Structure
Conforms
Page 3 of