OTTO ROSENAU & ASSOCIATES INC. sec
g 20�e
Geotechnical Engineering, Construction Inspection & Materials Testing
E1-�PMEN� ,r
PROPRIETARY ANCHOR ADHESIVE INSPECTION REPORT C��N�R
Job Number: 18-0269
Project: Margo Day Residence
Address: 219 Skyline Drive, Edmonds
Inspector: Travis Linn
Report Number: 365450
Permit Number: (In progress)
Client: Morris Originals, LLC
Address: 3111 New Markey Street, Suite 105, Bellingham
Date: 4/18/2018
Description/Location: ORA representative on site to inspect installation of epoxy all thread for foundation pad on west side of
property.
Intended Use: Steel column / foundation connection Building Code & Year: 2015 IBC
❑ Reinforcing Steel
® All Thread
Bar/Dowel Size & Quantity:
Anchor Size & Quantity: 1/4", (24)
Type of Steel (ASTM): ❑ A-36 ❑ F-1554 ® A-307
Grade: ❑ 36 ® 50 ❑ 75 ❑ Other:
Rebar Manufacturer:
Rebar Grade: ❑ 40 ❑ 60 ❑ Other:
Type of Bar: ❑ A-615 ❑ A-706 ❑ A-775 ❑ Other:
Special Ductile Quality (SDQ): ❑ Yes ❑ No
Anchor Length: 181,
Hole Depth: 9"
Required Embedment: 9"
Hole Diameter: 7/8"
Concrete Thickness: 24" (2), 12" (2)
Concrete Strength: 2500+
Hole Orientation: ® Vertical Down ❑ Vertical Up ❑ Horizontal
Base Material: ® Normal Weight Concrete ❑ Light Weight Concrete ❑ CMU
❑ Brick ❑ Composite Deck
Hole Cleaning: ® Compressed Air
❑ Hand Pump ❑ Other:
Compressed Air PSI: 100+
Brushed: ® Yes ❑ No Hole Condition: ❑ Dry ® Damp ❑ Water Saturated ❑ Submerged
Drill Bit (ANSI B212.15): ® Yes ❑ No Approved Diamond Cored Hole: ❑ Yes ® No
Adhesive Type: SET XP
Expiration Date: 5/5/2019
ICC ESR #: 2508
Weather: Clear
Ambient Temperature: 43°F
Substrate Temperature: 417
Comments
First (12) holes used SET XP, as stated above, on southwest pads. Last (12) holes used CIAGEL 7000-C, expiration date 8/14/2019,
ESR #437, for holes on northwest side.
Reference Standard(s) Used: Conforms X Does Not Conform _
Copies to:
X Client X Engineer Others
Owner Contractor Technical Responsibility:
Architect X Building Dept. Isaac Ru , Project Manager
This report applies only to the items tested or reported and is the exclusive property of Otto Rosenau & Associates, Inc. Reproduction of this report,
except in full, without written permission from our firm is strictly prohibited.
Page 1 of 1
6747 M.L. King Way S., Seattle, Washington 98118 - Phone (206) 725-4600 or 1-888-OTTO-4-US - Fax (206) 723-2221
Form No.: ADM/N-86-02 (Rev. 05113)
OTTO ROSENAU & ASSOCIATES, INC.
Geotechnical Engineering, Construction Inspection & Materials Testing
CONSTRUCTION INSPECTION REPORT RECEIVED
Report Number: 367913
MAY 2 9 2018
Project: Margo Day Residence Permit Number: (In progress)
Address: 219 Skyline Drive, Edmonds Job Number: 18-0269 DEVELOPMENT SERVICES
Client: Morris Originals. LLC
Steel Decking
Structural Steel Fabrication
Structural Steel Erection
Inspector
and Date
Chris Smith
4/11/2018
Copies to
Client Address:
Inspections Performed
Other (specify):
Soil bearing X
Remarks
3111 New Market 5treet`F,%A ldl r=, beumgnam
Other (specify):
Contractor requested a site visit to inspect soil bear capacity. ORA representative soil probed 4 spread
footings and one continuous footing at the south west corner of the property.
A representative number of probe tests were taken throughout the referenced vicinity; based on
penetration of 2" to 3" with sustainable resistance to advance into surface it is our recommendation that
the top 1" to 2" of soil be removed before placement of concrete to reach competent soils that can
support 1500 psf.
Does Not Conform
X Client X Engineer Others / � _C2�
Owner Contractor Technical Responsibility: l�
Architect X Building Dept. Isaac Ruoff, Project Manager
This report applies only to the items tested or reported and is the exclusive property of Otto Rosenau & Associates, Inc. Reproduction of this report,
except in full, without written permission from our firm is strictly prohibited.
Page 1 of 1
6747 M.L. King Way S., Seattle, Washington 98118 - Phone (206) 725-4600 or 1-888-OTTO-4-US - Fax (206) 723-2221
Form No.: ADMIN-63-05 (Rev 10/10)
c
OTTO ROSENAU & ASSOCIATES, INC.
SPECIAL INSPECTION & MATERIALS TESTING
OPEN ISSUE LOG
Project: Margo Day Residence Permit:
Job No.: 18-0269
Date Updated: 4/23/2018
Item Inspection
No. Date
Report I
Inspector(s)
No.
Remarks
Action Required
(e.g. re -inspection, engineer follow up, etc.)
Date
Resolved
1
4/11/2018
367913
Chris Smith
A representative number of probe tests were taken
throughout the referenced vicinity; based on penetration of 2"
to 3" with sustainable resistance to advance into surface it is
our recommendation that the top 1" to 2" of soil be removed
before placement of concrete to reach competent soils that
can support 1500 psf.
Reinspection
RECEIVE,)
MAY 2 9 2018
0EVEWPIVENT SERVICES
Copies to: COUNTER
X Client X Engineer
Owner Contractor Technical Responsibility:
Architect X Building Dept. Isaac Ruoff, Project Manager
This report applies only to the items tested or reported and is the exclusive property of Otto Rosenau & Associates, Inc. Reproduction of this report, except in full, without written permission from our firm
is strictly prohibited.
Page 1 _ of
6747 M.L. King Way S., Seattle, Washington 98118 — Phone (206) 725-4600 or 1-888-OTTO-4-US — Fax (206) 723-2221