PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: May 1, 2008
TO: SPT Mechanical
e-mail: tom@STPmechanical
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check # 2008-0321
Project: Stevens Hospital Cafeteria plumbing
th
Project Address: 21601 76 Ave W
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please resubmit to Thresa Umbaugh, Permit Coordinator.
1.Architectural plans (stamped and signed by State licensed architect and drawn to scale) must be
submitted as part of this permit application showing the following:
a.Provide overall general floor plan of this floor of building showing reference location
of the proposed espresso stand.
b.Provide building type of construction, fire separation locations and ratings, listed and
tested fire stopping assemblies for walls and floor-ceilings for each type of
penetration.
c.Provide partial enlarged floor plan of the cafeteria showing the proposed espresso
stand area, including uses of space, walls, fixtures, furnishings, kitchen fixture
schedule, etc. Clearly show that exiting will not be obstructed.
2.On the plumbing isometric note the type of piping and also slope. Note backflow protection
devices for proposed kitchen equipment on the plans.
3.The Plumbing Fixture Count schedule submitted with the application notes the sink trap as 1¼.
The minimum trap size is 1½ please note on the isometric drawing.
4.Provide approval letter from State Department of Health for this project.