STF20070014 App letter dated 7-2-07.pdf'grace May 14, 2007 To the City of Ednonds Building Department Hand Delivered Subject: Alternate design review request 1 Old Milltown / heavy timber columns To whom it may concern We are requesting that the city review and allow the use of 8x8 Glu Lanacolunuas for the primary structural elements to be used as indicated on the Structural Plans for the project. We are malting this request to use the referenced heavy timber columns as allowed in many municipalities around the country where preservation of historic buildings is paramount. -For instance the Seattle IBC interpretation 1602.5 is as follows: Type VA building may include exposed heavy -timber construction for colurrrns, beams, girders, arches, trusses, floors and roof decks except for fire resistive construction required by section 707 and chapters 5 and 10. This suggested interpretation is supported in a variety of sections as noted below as it relates to the fire resistivity of the proposed element. The structural efficacy of the column is established separately as part of the now approved structural design. Tables 503 and 601 clearly establish the code equivalency beth,,,ecn our proposed Heavy Timber usage at the colunuis only and the levels of protection attained for a type 5A building. This is deduced from the obvious indication that. all of the heavy timber building heights and areas are in excess of those allowed in the type 5A building across all occupancy group types. This interpretation is supported in the excerpted section from the IBC conunentary Vol 1 on the 2003 IBC... section 602.4 States in the cozaunentary: o "The interior elements are required, to be unprotected because of the massive element sizes and the requirements that there not be any concealed spaces, such as soffits, plenums or suspended ceilings. (Where our proposed colunurs enter such a space, they are entering into a rated assembly, the penetration of which shall be properly fire -caulked, should a suspended ceiling be placed as part of the tenant wank, the wood column will 1927 Post Alley Seattle, WA 98701 206957-9800 f 206-682-3159 Www..gracearcliltectsplic.coilI be appropriately wrapped with 1 hour protective construction above the ceiling.) o ...an examination of table 503 indicates that the allowable height and areas for type IV construction is greater than that permitted for buildings to type IIb construction. This distinction is based on testing that demonstrated that HT structural members perform better structurally under fire conditions than comparable unprotected steel members because of charring, which insulates the wood mass. (We maintain that this is also the case for the relationship to Type VA structural members as stated earlier and we are proposing that similar conclusion applies.) Section 602.4.1 requiring an miniiilum. 8" dimension for Columns carrying floor and roof loads as being compliant with the requirements of HT construction that will meet the equivalent fire protection requirements. The Commentary goes on to establish the relationship between the Nominal and actual dimensional requirement of the HT structural laminated column. We are well in excess of these minium requirements as the specific requirement is for a 6x8" nominal column when supporting floor, roof and ceiling loads. This equates to a 5-118" x 6-114" dimensional column and we are providing glu-lam columns in 8-114" x 8- 114" in actual dimension. Where these items are part of a required exit corridor, they will be protected as required by type VA construction requirements. fearuline, I hope that these additional elaborations will assist you iii making your ruling with eonfrdenee that this is a well established and viable alternative design methodology and one that will not only keep our building safe, but will euhanee the historic character of the remodeled building for many generations to come. Thanks for your consideration. 4435 ARCI�IERC s RALPH W. At I EN I.PSTATE OF WASHINGTON Ralph W. Allen Principal 1927 Post Alley Seattle, WA 98109 p 201-957-9800 f 206-.682-3159 www. gracearchi tectspllc.Coln IW7 TYPES OF CONSTRUCTION nal in width, set on edge close together and laid as required for floors. Other types of decking shall be permitted to be used if providing equivalent fire resistance and structural properties. 602.4.6 Partitions. Partitions shall Uo of solid wood con- struction formed by not less than two layers of 1 -inch (25 nun) matched boards orlarninated construction 4 inches (102 min) thick, or of 1 -hour fire -resistance -rated construction. 602.4.7 Exterior structural members. Where a horizontal separation of 20 feet (6096 ITmi) or more is prodded, wood columns and arches conforming to heavy timber sizes shall be permitted to be used externally. 602.5 Type V. Type V construction is that type of construction in which the structural elements, exterior walls and interior walls are of any materials permitted by this code. Interpretation I602.5: ypeVA buildings may include ex- posed heavy-firnber const •actio r umns 1 )eaBis, gird- ers, arches. trusses floors and roof decks except for fire-regigiye construcdon-l=uired 7 and Chap- teus 5 and 10. SECTION 603 COMBUSTIBLE MATERIAL IN TYPE I AND II CONSTRUCTION 603.1 AIlowable materials. Combustible materials shall be permitted in buildings of Type Ior II construction in thefollow- ing applications and in accordance with Sections 603.1.1 through 603.1.3: 1. Fire -retardant -treated wood shall be permitted in: 1.1. Nonbearing partitions where the required fire -re- sistance rating is 2 hours: or less. 1.2. Nonbearin; exterior walls where no fire rating is required. 1.3. Roof construction as permitted in Table 601, Note c, Item 3. 2. Ther n-ial and acoustical insulation, other than foam plas- tics, having a flame spread index of not more than 25.. Exceptions: 1. Insulation placed between two layers of noncombustible materials without an inter- vening airspace shall be. allowed to have a flame spread index of not more than 100. 2. Insulation installed between a finished floor and solid decking without inteivening air- space shall be allowed to have a flame spread index of not more than 200. 3. Foam plastics in accordance with Chapter 26. 4. Roof coverings that have an A, B or C classification. 5. interior floor finish and interior finish, trim and mill- work such as doors, door frames, window sashes and frames. 6. Where not installed over 15 feet (4572 mm) above grade, show windows, nailing or furring strips, wooden 104 bulkheads below show windows, their frames, aprons and shod' cases. 7. Finished flooring applied directly to the floor slab or to wood sleepers that are firestopped in accordance with Section 717.2.7. S. Partitions dividing portions of stores, offices or similar places occupied by one tenant only and which do not establish a corridor serving an occupant load of 30 or more shall be permittecl to be constructed of fire -retardant -treated wood, 1 -hour fire -resistance - rated construction or of wood panels or similar light conscLuction up to 6 feet (1829 mm) in height. 9. Platforms as permitted in Section 410. 40 10. Combustible exterior wall coverings, balconies, bay or oriel windows, or similar appendages in accor- dance with Chapter 14. 11. Blocking such as for handrails, millwork, cabinets, and window and door frames. 12. Light -transmitting plastics as permitted by Chapter 26. 13. Mastics and caulking materials applied to provide flexi- ble seals between components of exterior wall construc- tion. 14. Exterior plastic veneer installed in accordance with Section 2605.2. 15. Nailing or furring strips as permitted by Section 803.4. 16. Heavy timber as permitted by Note c, Item 2, to Table 601 and Sections 602.4.7 and 1406.3. 17. Aggregates, component materials and admixtures as permitted by Section 703.2.2. 19. Sprayed cementitious and mineral fiber fire -resistance - rated materials installed to comply with Section 1704.11. 19. Materials used to protect penetrations in fire -resistance - rated assemblies in accordance with Section 712. 20. Materials used to protect joints in fire -resistance -rated assemblies in accordance with Section 713. 21. Materials allowed in the concealed spaces of buildings of Type I-ana II construction in accordance with Sec- tion 717.5. 22. Materials exposed within plenums complying with' Section 602 of the International Mechanical Code. 23. Stairways withill in 'dual dwe i - t i G d s 'waw s vi b a sit o tenai s a ma ofire-iiptatdauL at di n or av - e stia 'on. tI r ha Group c u cies. t 1 stairways shall llotsvemas - a required m!,-,lns.Qf egress,. 603.1.1 Ducts. The use of nonmetallic ducts shall be permit- ted when installed in accordance with the limitations of the International Mechanical Code. 603.1 .2 Piping. The use of combustible piping materials shall be permitted when installed in accordance with the limitations of the International Mechanical Code and the Ullifnrnr Plr.rrnbiirg Code. 603.1.3 EIectrical. The use of electrical wiring methods with combustible insulation, tubing, raceways and related components shall be permitted when installed in accordance with the limitations of the IGE Seattle Electrical Code. 2403 SEATTLE BUILDING CODE GENERAL BUILDING HEIGHTS AND AREAS TABLE 503 ALLOWABLE HEIGHT AND BUILDING AREAS y - Height limitations shown as stories and feet above grade plane. Area limitations as determined by the definition of "Area, building," per fl - TYPE OF CONSTRUCTION i TYPE 1 TYPE 11 TYPE 111 TYPE IV TY EV B ATB5 A B HTGROUP ffAL Hat(5} 160 65 55 55 65 50. 40 - A 1 S UL UL 5 UL 3 15500 2 8,SD0 3 14,040 2 8,500 3 }5,400 2 11,500 1 5,500 A-2 A S UL I1 UL 3 15,500 2 9,500 3 14,DOD 2 9,500 3 15,00(' 2 11500 I 6,000 A UL 2 1 A-3 UL UL 3 15 500 2 9,500 3 14,000 2 9,504 3 15,400 11,500 6,OOD A-4 S U� CFL 1€ UL 3 15,500 2 9,500 g €4,004 2 9,500 3 15,000 � 11500 I 6,000 A S UL UL UL UL UL UL UL ' UL UL UL � UL UL A 5 A UL UL UL UL UL UL A [UILL.. 11 UL 5 37,500 23600 '' 5 28,50D 4 19,000 5 36,000 ; IS,000 3 9,000 ' 5 UL 3 26,504 2 14,540 3 23.500 ? 14,506 3 25,5(0 € ]3,500 1 9,5011 L- S A UL 4 2 3 2 4 2 1 F-1 S UL UL ]l UL 25,000 15,500 19,000 12.040 33,500 14,400 5,500 F-2 A S UL 11 UL 5 37,500 3 23,000 4 28,540 3 18,OOD 5 50,500 3 21,000 2 13,000 A UL 1 I NP H-1 S A l 21.000 1 16,500 I 11,000 ] 7,000 I 9,500 I 7,000 10,504 7,500 NP H-2 S A UL 21,000 3 1650011,000 2 1 7,000 2 9500 1 71000 2 10,500 1 7,500 ] 3,000 H-3 A UL 5 I 60,000 4 26.500 2 1400( 4 17,500 2 13,004 4 25500 2 10,000 l 5,006 II- 4 S UL. UL UL 37500 17 500 28,500 3 17,50D 5 31,000 3 15,000 2 6,504 1.1-5 UL UL 37,500 3 23,000 3 28.503 3 ]9,000 3 36,006 3 lSOUO ? 4,000 1-1 A S UL UL 9 55,(00 } 19,00{5 fff 3 10,000 4 11,500 3 10.000 4 18,000 3 ]0,500 2 4,540 A , 1 NP I l NP }4 I--7 1 5 UL UL UL 2- 15,004 1 11,400 12,000 �P 12,OQ0 9,500 VP A 2 2 1 ]3 5 UL UL 4 UL 2 15,009 I 10,000 2 10,504 - 1 ` 7.544 12,000 7,500 S,OOD 1 4A A g UL UL 5 6,0,540 3 26,500 13,000 23500 13000 25,500 I 18,500 I 9,000 S UL 11 UL 4 21500 4 . 12.50( 4 18,500 4 12,500 4 - 20,500 3 14,400 1 9,000 A S UL UTI., it UL 4 24,000 4 16,000 4 24,006 4 16,000 4 � 20,500 34 12,(140 2 7,000 A UL 4 4 4 4 34 2 R_2n S UL UL 11 2} g 4 16,000 24,000 16,OOD 20500 12,000 7,000 A 4 4 4 4 4 3L R-3-` S A UL UL 11 UL UL UL UL UL UL UL UL R 4 S UL ULUI. 11 2q OOD 4 16,000 4 24.000 4 16,(00 4 20500 3 12,(00 2 7,000 A 3 4 3 I S-1 S CIL UL i I 45.000 26,000 17,500 26 004 17.500 25,500 14,000 9,000 S-2� `A A S UL UL l l 79,OOD 5 39,006 4 26,000 4 I 39,D00 4 26,000 5 35,506 4 2t,a64 2 13,5(0 Uc S UL 5 35,500 4 19,000 2 3,500 3 14,004 2 $500 4 18,000 2 9,400 l 5,500 A UL For SI; I foot 30=4.8 min, I'square foot = 0.0929 m'. UL =Unlimited, NIP =-Not penuitted. a, As app[icable it, Section 101.2. open .lri,l b. Por P P u0, structures see Section 406.3. c. For private garages, see Section 406.1. 97 2003 SEATTLE BUILDING CODE TYPES OF CONSTRUCTION TABLE 601 FIRE -RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (hours) TYPE I TYPE H TYPE III TYPE. IV TYKE V d $ BUILDING ELEMENT A B Ad B Ad l3 BT Structural frame' Including colulmis, girders, trusses 3b 2s 1 0 1 0 HT 1 0 I3earing walls 2 2 i 0 > xteriorr 3 2 1 0 Interior 3b 2" 1 0 1 0 1LHT 1 0 Nonbearing walls and partitions L Exterior See Table 602 Nonbearing walls and partitions 0 0 0 0 0 0 See Section 602.4.6 0 0 Interiors Floor construction 2 2 1 0 1 0 HT 1 0 Including supporting beams and joists Roof construction I,/,c I` I= 0` 0 HT 1` 0 Including supporting beams ant] joists For SI: 1 foot = 304.8 mm. a. The structural frame shall be considered to be the columns and the girders, beams, trusses and spandrels having direct connections to the columns and bracing members designed to carry gravity loads. The members of floor or roof panels+'hick have no connection to the columns shall be considered secondary members and not a part of the structural frame. infer ret. ion 1601: Bririnoi emhesth, rov'deve cals7hilit'shallh consjdered Part of the sialcalralframewhetlerartnthevca y a_Mvity1 s b. Roof supports: Fire -resistance ratin-es of structural frame and bearing galls are permitted to.be reduced by 1 hour where supporting a roof only. c. L F-xcepl in Factory -Industrial (F -I), Hazardous (H), U'lereantile (NI) and Moderate -Hazard Storage (S-1) occupancies, fire protection of structural members shall not be required, including protection of roof framing and decking where every part of the roof construction is 20 feetor more above any floor inunediately below. Fire -retardant -treated wood members shall be allowed to be used for such unprotected members. 2. In all occupancies, heavy timber shall be allowed where a I -hour or less fire -resistance rating is required. 3. In Type I and II construction, fine -retardant -treated wood shall be allowed in buildings including girders and trusses as part of the roof construction when t€te building is: I. Two stories or less in height; ii. Type II construction over nvo stories; or. iii. Type 1 construction over owo stories and the vertical distance from the upper floor to tile roof is 20 feet or more. d. An approved automatic sprinkler system in accordance with Section 903.3.1.1 shall be allowed to be substituted for I -hour lire -resistance -rated construction, pro- vided such system is not otherwise required by other provisions of the code or used for art allowable area increase in accordance with Section 506.3 or an allowable height increase in accordance with Section 504.2. The 1 -hour substitution for the fire resistance of exterior trolls shall not be permitted. Ris WIr-611160D bbill not be __ in building—.e.r.,,...,.r.l:,,o hn.CPrlinn 1(€18.2e%('� np d�L4I. _ _ e. Not less than the fire -resistance rating required by other sections of this code. f. Not less than the fire -resistance rating based on fire separation distance (see Table 602). 105 CHAPTER 6 SECTION 601 GENERAL 601.1 Scope. The provisions of this chapter shall control the classification of buildings as to type of construction. SECTION 602 CONSTRUCTION CLASSIFICATION 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire -resistance rating not less than that specified in Table 601 and exterior walls shall have a fire -resistance rating not less than that specified in Table 602. 6021.1 Minimum requirements. A building or portion thereof shall not be required to conform to the details of a type of construction higher than that type, which meets the minimum requirements based on occupancy even though .certain features of such a building actually conform to a higher type of construction. 602.x. `Types land II. Type I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials. 602.3 Type III. Type III construction is that type of construc- tion in which the exterior walls are of noncombustible materi- als and the interior building elements are of ally material permitted by this code. Fire -retardant -treated wood framing complying with Section 2303.2 shall be permitted within exte- rior wall assemblies of a 2 -hour rating or less. Intexln-etation1602.3: Type IIIA buildings irnav include ex- posed heavy timber construction for columns- beams. >7ird- _ rs, arches, tr es s floors and f decks except o1` fire resistive constructirni re4liii-ed by Section 707 and C'haptel:s 5 and 1 Cl 602.4 Type Il'. Type IV construction (Heavy Timber, HT) is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of solid or laminated wood without concealed spaces. The details of 7),pe IV construction shall comply with the provi- sions of this section. Fire -retardant -treated wood framing com- plying with Section 2303.2 shall be perniitted within exterior wall assemblies with a 2 -hour rating or less. 602.4.1 Columns. Wood columns shall be sawn or glued laminated and shall not be less than 8 inches (203 nun), nominal, in any dimension where supporting floor loads and not less than 6 inches (152 mm) nominal in width and not less than 8 inches'(203 mm) nominal in depth where sup- porting roof and ceiling loads only. Colunms. shall be con- tinuous or superimposed and connected in in approved manner. 4 2003 SEATTLE BUILDING CODE . . 602.4.2 Floor framing. Wood beams and girders shall be of sawn or glued -laminated timber and shall be not less than 6 inches (152 mm) nominal in width and not less than 10 inches (254 rain) nominal in depth. Framed sawn or glued -laminated timber arches, which spring from thefloor line and support floor loads, shall be not less than S inches (203 linin) nominal in any dimension. Framed timber trusses supporting floor loads shall have members of not less than 8 inches (203 mm) nominal in any dimension. 602.4.3 Roof frau-drag. Wood -frame or glued -laminated arches for roof construction, which spring from the. floor line or from grade and do not support floor loads, shall have members not less than 6 inches (152 mm) nominal in width and have less than 8 inches (203 niln) nominal in depth for the lower half of the height and not less than 6 inches (152 ram) nominal in depth for the upper half. Framed or glucd- laminated arches for roof construction that spring from the top of walls or wall abutinents, fraEned timber trusses and other roof framing, which do not support floor loads, shall have members not less than 4 inches (102 mm) nominal in width and not less than 6 inches (152 man) nominal in depth. Spaced members shall be permitted to be composed of two or more pieces not less than 3 inches (76 nun) nominal in thickness where blocked solidly throughout their interven- ing spaces or where spaces are tightly closed by a continu- ous wood cover plate of not less than 2 inches (51 nun) nominal in thickness secured to the underside of the mernt- bers. Splice plates shall be not less than 3 inches (76 nun) nominal in thickness. Where protected by approved auto- matic sprinklers under the roof deck, framing members shall be not less than 3 inches (76 mm) nominal in width. 602.4.4 Floors. Floors shall be without concealed spaces. Wood floors Shall be of sawn or glued -laminated planks, splined or tongue -and -groove, of not Iess than 3 inches (76 nim) nominal. in thickness covered with 1 -inch (25 nun) nominal dimension tong€ie-and-groove flooring, laid cross- wise or diagonally, or 0.5 -inch (12.7 min) particleboard or planks not less than 4 inches (102 nnnn) nominal in width set on edge close together and well spiked and covered with 1 -inch (25 num) nominal dimension flooring or 151,E -inch (12 inm) wood structural panel or 0.5 -inch (12.7 man) particleboard. The lumber shall be laid so that no continu-. ous line of joints will occur except at points of support. Floors shall not extend closer than 0.5 inch (12.7 urn) to walls. Such 0.5 -inch (12.7 nim) space shall be covered by a molding fastened to the wall and so arranged that it will not obstruct the swelling or shrinkage movements of the floor. Corbeling of masonry walls under the floor shall be permit- ted to be used in place of molding: 602.4.5 Roofs. Roofs shall be without concealed spaces and wood roof decks shall be sawn or glued laminated, splined or ton'gue-and-groove plank, not less than 2 inches (51 nnili) thick, 111$ -inch -thick (32 ram) wood structural: panel (exte- rior gIue), or of planks not less than 3 i nclics (76 mm) nonni- 103 li -fypES OF CONSTRUCTION assemblies. For example, the required rating for struc- tural frame members in Type IA construction is 3 hours, for Type IB is 2 hours, for Type IIA is 1 hour and for Type 1113 is 0 hours. The required fire -resistance ratings of structural elements range from zero for Type IIB con- struction to 3 hours for most of the elements of Type IA construction. Often, the fire -resistance ratings required by Tables 601 and 602 for structural elements are achieved by "fireproofing" structural members. Fire- proofing is typically the process of creating a fire -resis- tance -rated assembly that incorporates the structural member by encapsulating it, either by boxing it in or by spraying on a coating to achieve the required fire -resis- tance ratings. It should be noted that when a protective covering is used to provide the fire -resistance rating, it must be a noncombustible material, except as indicated in Section 603.1, Item 18 and in Section 703.2.2. Fire -retardant -treated wood (FRTW), although combus- tible, is permitted in limited uses in buildings of Type I and II construction (see Section 603 and Table 601, Note C). While FRTW is permitted in certain applica- tions in buildings of Type I and ll construction, it is not assumed to be fire -resistance rated, and generally does not afford any higher fire -resistance rating than un- treated wood material. 602.3 Type III. Type III constriction is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of any material permitted by this code. lire -retardant -treated wood framing complying with Section 2303.2 shall be permitted within exterior wall. assem- blies of a 2 -lour rating or less. .• Buildings of Type III construction are made with both com- bustible and noncombustible materials. The exterior walls are required to be noncombustible with load-bearing exte- rior walls required to have a minimum 2 -hour fire -resis- tance rating. Exterior nonload-bearing walls are not required by Table 601 to have a fire -resistance rating, but must comply with the provisions of Table 602. The •interior elements (i.e., floors, roofs and walls) are permitted to be of combustible materials. An example of a typical building of Type Ill construction is a structure having its. exterior walls constructed of concrete, masonry or. other approved noncombustible materials, but with a wood -frame floor and roof construction (see Figure 602.3 for an example of Type 111 construction). Type III construction is further di- vided into two subclassifications: Types IIIA and I1113, An example of a building of Type IIIA construction is one in which the interior load-bearing walls, floors, roofs [those members that are less than 20 feet (6096 mm) to the low- est member] and all structural members are protected to provide a minimum 1 -hour fire -resistance rating. The structural members of a building of Type IIIB construction are not required to have a fire -resistance rating with the exception of the exterior load-bearing wails. Although FRTW sloes not meet the specifications of the code as a noncombustible material, it is permitted as a substitute for noncombustible materials in exterior wall assemblies of Type III construction, While the exte- rior walls are permitted to be either nonload bearing or 602.3 — 602.4 load bearing, the required fire -resistance rating of the exterior wall must be no greater than 2 hours where FRTW is used. FRTW is required to comply with the pro- visions in Section 2303.2. GYPSUM WALLEOARO W000 RAFTERS FURRED PdNLi.ING AND TRIM d (� CON CRE F BLOCK %I� t �crasura Sr�aueaARo BRICK - t�: •I WOOD JUST AND FLOOR Figure 602.3 EXAMPLE OF TYPE III CONSTRUCTION 602.4 Tt ,pe IV. Type IV construction (Heavy Timber, HT) is that type of construction in which the exterior walls are of noncombustible materials and the interior buildin.-.elements are of solid or laminated wood without concealed spaces. The de- tails of Type IV construction shall comply with the provisions of this section, Fire -retardant -treated wood framing complyin.- with Section 2303.2 shall be permitted within exterior wall as- semblies with a 2 -hour rating or less. •:•This section provides the general regulations for Type IV HT construction, HT construction requires the exte- rior walls to be constructed of noncombustible materi- als. The interior elements are required to be constructed of solid or laminated wood without anyconcealed spaces. All, of'the combustible structural elements are permitted to be unprotected because of the massive el- ement sizes and the requirement that there not be any concealed spaces, Such assoffits, plenums or sus- pended ceilings. Sections 602.4.1 through 602.4.7 pro- vide specific requirements for the connection of structural members and minimum dimensions. An ex-; amination of Table 503 indicates that the allowable height and area for Type !V construction is greater than that permitted for buildings of Type IIB construction. This distinction is based on testing that demonstrated that HT structural members perform better structurally under fire conditions than comparable unprotected steel structural members because of charring, which insu- lates the wood mass. As with Type III construction, FRTW is permitted as a substitute for noncombustible materials in exterior wall assemblies of Type IV construction. While the exterior walls are permitted to be either nonload bearing or load bearing, they must have a fire -resistance rating of no greater than 2 hours where FRTW is used in the exterior wall, FRTW is required to comply with the provisions of 2003 INTERNATIONAL BUILDING CODE° COMMENTARY 6-3 . 602.4.1 — 602.4.3 TYPES OF CONSTRUCTION ::'-ITYPES Section 2303.2. It should be noted that the sizes of specified timber members are nominal. Actual sizes for sawn timbers will generally be'12 inch (12.7 mm) to 314 inch (19.1 mm) less than nominal in both width and thickness as required by the U.S. Department of Commerce Standard PS 20 -99. - Due to requirements for additional finishing (sanding), glued laminated sizes will be less, as shown in Figure 602.4. Nominall (inches) 3 1 4 f 6 S 10 12 i ( 14 16 1 Actual (inches) 12114 31/, 51/8 6314 8314 1031q 12'14 14'14 For 51: 1 inch = 25.4 mm. Figure 602.4 NOMINAL VERSUS ACTUAL DIMENSIONS FOR GLUED -LAMINATED MEMBERS .1 Columns. Wood columns shall be sawn or glued lami- nated and shall not be less than 8 inches (203 mm), nominal, in any dimension where supporting floor loads and not less than 6 inches (152 nein) nominal in width and not less than 8 inches (203 min) nominal in depth where, supporting roof and ceiling loads only. Columns shall be continuous or superimposed and .connected in an approved manner:_ _00 .• Minimum construction requirements and dimensions for timber columns aro provided in this section. Columns are required to be a minimum of 8 inches (203 mm) nominal in any dimension if they support floor loads, or a minimum of 6 by 8 inches (152 by 203 mm) nominal if they support a roof and ceiling. Timber columns are re- quired to be continuous or superimposed, positioned on or over each other, through floors for the entire height of the building. The design engineer or architect must pro- vide details of all column connections. As with all struc- tural members, each column must also be adequately fastened to other structural members in order to with- stand the loads that will be placed upon the column. Some typical examples include reinforced concrete or metal caps, steel or iron column caps and timber splice plates [see Figures 602.4.1 (1) and 602.4.1(2)]. 602.4.2 Floor framing. Wood beams and girders shall be of sawn or glued -laminated timber and shall be. not Iess than 6 inches (152 iron) nominal in width and not less than 10 inches r mm) nominal in depth. Framed sawn or glued -laminated `ar arches, which spring from the floor line and suppoit.floor loads, shall be not less than 8 inches (203 n1m) nonduat is any dimension. Framed timber trusses supporting floor loads shall have members of not less than 8. inches (203 mm) nominal in any dimension. *4• Minimum construction requirements and dimensions for floor framing are provided in this section. Girders aro the principal horizontal structural members that support columns or beams. Beams are the structural members that support a floor or roof. Both girders and beams are required to be a minimum 6 inches (152 mm) wide and 10 inches (254 mm) deep. Both framed timber trusses supporting floor loads and framed sawn or glued lami. nated timber arches that spring from the floor line and support floor loads are required to be at least 8 inches (203 mm) in any dimension. 602.4.3 Roof framing. Wood -frame or glued -laminated arches for roof construction, which spring from the floor line or from ;rade and do not support floor loads, shall have members not less than 6 inches (152 mm) nominal in width and have less titan 8 inches (203 mm) nominal in depth for the lower halt of the height and not less than 6 inches (152 nun) nominal in depth for the upper half. Framed or glued -laminated arches for roof cott- suriction that spring from the top of walls or wall abutments, framed timber trusses and other roof framing, which do not sup- port floor loads, shall have members not less than 4 inches (102 mm) nominal in width and notless,than 6 inches (152 nim) nom- inal in depth. Spaced members shall be permitted to be com- posed of two or more pieces not less than 3 inches (76 nun) nominal in thickness where blocked solidly throughout their in- tervening spaces or where spaces are tightly closed by a continu- atts wood cover plate of not less than 2 inches (51 mm) nominal in thickness secured to the underside of the members. Splice plates shall be not less than 3 inches (76 mm) nominal in thick- ness. Where protected by approved automatic sprinklers under the roof deck, framing members shall be not Iess than 3 inches (76 mm) nominal in width. +;• Minimum construction requirements and dimensions for arches and other types of roof framing are provided in this section. Other types of roof framing included in this section.are heavy timbertrusses with spaced members. When the members of a heavy timber truss are split and placed on either side of a main member, such as a web connecting a chord, each component of the web must be 3 inches (76 mm) or more in nominal thickness. The space between the two web members must be pro- tected with a 2 -inch -thick (51 mm) cover plate [see Fig- ure 602.4.3(1)], or solidly filled with blocking [see Figure 602.4.3(2)]. The size of the roof framing members is de- pendent on the configuration used and is regulated by this section. If a building of Type IV construction is equipped with approved automatic sprinklers under the roof deck, the minimum size of the roof framing members is reduced to 3 inches (76 mm). Roof framing members of a smaller size will have a lower resistance to fire than the 6 -inch by 8 -inch (152 mm by 203 mm) or 4 -inch by 6-inch.002 mm by 152 mm) members required by this section. The tradeoff allowing smaller roof framing members when the building is equipped with an automatic sprinkler sys- tem is consistent with the concept of maintaining "equiv- alent risk" for the building.