Loading...
Sunset 100 LP Condos 2.DOC EDMONDS FIRE DEPARTMENT MEMORANDUM Date: January 12, 2009 To: File From: Mike Smith Fire Marshal 425-775-7720 Subject: Sunset 100 LP 6 Unit Condo 121 Sunset Ave The Fire Department has the following comments: 1) Please show the sprinkler riser room on the drawings. They are labeled on the sprinkler plans but not on the building plans. I would also suggest you relocate the location of the room to the eastern exterior wall for reasons that I have discussed with your sprinkler contractor Ken Robinson. 2) Portable fire extinguishers are required in the building with a maximum travel distance of 75 feet (noted from entry door to the condos). At least two will be required in the S-2 garage. Minimum size is 2A10:BC. 3) A Fire Department Lock Box will be required for emergency access by our department. An authorization to purchase can be obtained from my office prior to occupancy. 4) Bulding addresses are required and must be visible from the street. Minimum number size is 4 inches tall with a 1 inch stroke on a contrasting backround.