Mr. Lentz,
I have reviewed the resubmittal Taco Time and only one item remains that has still not been addressed:
2. Previous item 5 not addressed: A 1-hour exterior wall is required at the south side opening
(between the columns) of the covered drive-through due to the close proximity to the property line (IBC
602 & 704.8). A 30 parapet with on-combustible face on the roof side is required for this exterior wall
unless an exception can be used. Provide details and cross-reference where they apply to clearly show
code compliance. This was included in the preapplication comments dated 1/17/07 and discussed at the
meeting. Architectural and Structural plans must be revised.
The plans show detail 7/A5 at the opening between the columns of the drive thru canopy, but this needs
to be shown on the plans as 1-hour exterior wall with a parapet (unless a parapet exception is used). The
opening created by the columns and beam is not permitted due to the fire separation distance. Floor
plans, structural plans, elevation views and sections must also be revised to show this clearly. Please
resubmit to Marie Harrison, Senior Permit Coordinator.
If you have questions please contact me.
Sincerely,
Ann Bullis, CBO
Building Official