Taki Tiki 518 Main St
Jeannine:
I inspected this morning at the request of GC Lance 425.218.0010. Lance said he would work through the
weekend to finish outstanding items.
Outstanding items found:
1) No fire suppression permit or plans on-site.
2) Suppression system requires acceptance test (SCHEDULED MONDAY 7/31 @ 1145 RT HOOD 206
726-0940)
-Fan under hood ON/swamp cooler OFF/gas fuel & electric power under hood OFF
3) Mount 4A:60B:C portable fire extinguisher next to kitchen pass-through.
4) Post occupant load - 97 (count chairs).
5) Documentation for flame resistant acceptance from EFD (IFC 805.2).
6) Candle holders are not approved must be removed.
-IFC 308.3.2 (4) holder not designed to return to upright position when tilted to 45 degrees from
vertical.
-IFC 308.3.2.(5) flame not enclosed from side and will ignite a tissue paper placed on top for 10
seconds.
7) Two penetrations in ceiling from previous gas ceiling heater requires patches. Parapets confirmed on
east and west walls-patches not required to be rated. Lance informed of this.
Decorative palm fronds tested in accordance with NFPA 701 field test
(10 second flame application:2 second flame extinguishment upon removal)-ACCEPTED
Decorative thatching treated with National Fireproofing FS I-DS by Mr. Colgan tested same-ACCEPTED
John