Loading...
Trike Stop 22309-76th Ave W Fire Connection Underground.rtf From: Westfall, John Sent: Wednesday, September 20, 2006 9:52 AM To: Smith, Mike Subject: Trike Stop 22309-76th Ave W Fire Connection / Underground I witnessed hydrotest for 1.5" CPVC underground approved at 200 psi for 2 hours. Engineering Div offered that 18" minimum cover was adequate and this supply was below that level. Cascade Alarm flushed the line twice through a temporary PVC installation to the storm system in the street. I asked for a single-strand copper wire to use as a trace for underground utility detection. John