JAIIA CAFE SUBMITTALLOW VOLTAGE SYSTEMS BY
ro omm
PROTECTION & COMMUNICATIONS INC.
Fire Alarm System -
Product Data & Battery Calculations -
for
EDMONDS
WATERFRONT
10032 EDMONDS WAY
SUITE 100
EDMONDS WA 98020
Protection & Communications, Inc.
220 RAILROAD AVE
EDMONDS WA 98020
Phone: 425.774.9099
Fax: 425.774.6317
Sales Account Engineer -LYLE WELLS
Project #PRO-C-4345
(E)POTTER
The Symbol of Protection
Features
• 24VDC units have field selectable candela options of 15, 30, 60,
75 & 110
• Super -Slide® Bracket - Ease of Supervision Testing
• Checkmate® - Instant Voltage Verification
• Synchronize strobe and/or horn with AVSM Control Module
• Prewire entire system, install mounting bracket, then install
signals
• Documented lower installation and operating costs
• Switch selection for high or low dBA
• Switch for chime, whoop, mechanical and 2400Hz tone
• Tamperproof re-entrant style grill
• Switch for continuous or temporal 3 tone (not available on
whoop tone)
• Silence audible while visual appliance will remain flashing (for
use in accepted jurisdictions)
• Faceplate available in red or off-white
Description
The S-24/HS-24 Series is a low profile strobe and horn/
strobe combination that offers dependable audible and visual
alarms and the absolute lowest current available. The S-24
& HS-24 Series 24VDC offers tamperproof field selectable
candela options of 15, 30, 60, 75, and 110 candela. The
Strobe and Horn/Strobe offers a continuous or sync temporal
three in 240011z and mechanical tone, a chime and whoop
tone. All tones are easy for the professional to change in the
field by the use of switches. The S-24 & HS-24 Series has a
minimal operating current and has a minimum flash rate of
1Hz regardless of input voltage.
This Series is shipped with a standard 4" metal mounting
plate which incorporates the popular Super -Slide® feature
that allows the installer to easily test for supervision. The
product also features a locking mechanism which secures the
product to the bracket without any screws showing.
The S-24/HS-24 also features the patented Checkmate® -
Instant Voltage Verification feature which allows the installer
to check the voltage drop draw and match it to the blueprint.
The S-24 & HS-24 Series appliances are ANSI/UL 464 and
ANSI/UL 1971, listed for use with fire protective systems
and are warranted for three years from date of purchase.
S-24 & H S-24
Selectable Candela Strobe & Horn/Strobes
/j y , I1111J�_
i
U�
LISTED
S3247
Technical Specifications
Single or Double gang, 4"
Mounting Options
square box, and AVBB surface
mount back box
Terminals
Screw -Clamp Type
Wire Gauge
18 — 12 AWG
Operating Temp
32°F — 120°F (0° — 49°C)
Height — 5"
Dimensions
Width — 4.5"
Depth — 2.5"
Shipping Weight
1.05 lbs
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830054-REV C 6/17 PAGE 1 OF 4
(E)POTTER
The Symbol of Protection
TONE
SWITCH POSITION
3
4
5
Mechanical Temporal 3
ON
ON
ON
Mechanical Continuous
OFF
ON
ON
2400 Hz Temporal 3
ON
OFF
ON
2400 Hz Continuous
OFF
OFF
ON
Chime Temporal 3
ON
ON
OFF
Chime Continuous
OFF
ON
OFF
Whoop
ON
OFF
OFF
Whoop
OFF
I OFF
OFF
NOTE:
• Switch Positions IThe and 2 in the OFF position to select
isolated horn and strobe power inputs
• Switch Position 6 ON = HIGH dBA
• Switch Position 6 OFF = LOW dBA
rnnrlcln Cnlcr4inn
Super Slide® Mounting Bracket
Allows the installer to pre -wire the system, test for system
supervision, remove the signal head until occupancy, switch
out signals without changing mounting brackets and has
locking edge connector for snap -in -place installation.
S-24 & H S-24
Selectable Candela Strobe & Horn/Strobes
Switch Locations
LMEMO 00
NNEE M M
MEMO 0
'Manin
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830054-REV C 6/17 PAGE 2 OF 4
(E)POTTER
® The Symbol of Protection
S-24 24 VDC Selectable Candela, Low
Profile Evacuation Strobe
S-24 & H S-24
Selectable Candela Strobe & Horn/Strobes
Model
Nominal
Candela (ANSI/UL
Part Number
Number
Voltage
1971)
S-24WR
4890010
24 VDC
15, 30, 60, 75, 110
S-24WW
4890011
24 VDC
15, 30, 60, 75, 110
HS-24 24 VDC Selectable Candela,
Low Profile Evacuation Strobe
Candela (ANSI/
Reverberant dBA at 10
In Anechoic Room at
Model Number
Part Number
Nominal Voltage
UL 1971)
ft, per ANSI/UL 464
loft
HS-24WR
4890030
24 VDC
15, 30, 60, 75, 110
62-82
100
HS-24WW
4890031
24 VDC
15, 30, 60, 75, 110
62-82
100
S-24 & HS 24 Strobe Current Ratings
24 VDC (16 - 33 Volts)
Candela
24 VDC
UL Max
15 cd
30 mA
42 mA
30 cd
35 mA
58 mA
60 cd
66 mA
97 mA
75 cd
80 mA
116 mA
110 cd
103 mA
161 mA
S-24 & HS-24 Horn Ratings
Model Designations:
W = Wall mount
R = Red Faceplate W=White Faceplate
All units are available in plain (no lettering)
Plain units are non -returnable.
"ALERT" bezel available for order.
"AGENT" bezel available for order.
Horn Mode
Horn Decibel Levels
Horn Current Ratings
Minimum SPL at 10 ft, per
ANSI/UL 464 (HIGH)
Minimum SPL at 10 ft,
per ANSI/UL 464 (LOW)
Regulated 24 VDC Max
Operating @ High Setting (mA)
Temp 3 (2400 Hz)
78 dBA
71 * dBA
28 mA
Temp 3 (Mechanical)
76 dBA
70* dBA
25 mA
Temp 3 (Chime)
70* dBA
66* dBA
15 mA
Continuous (2400 Hz)
81 dBA
74* dBA
28 mA
Continuous (Mechanical)
80 dBA
72* dBA
25 mA
Continuous (Chime)
70* dBA
66* dBA
15 mA
Whoop
82 dBA
69* dBA
56 mA
NOTES.
• For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave
Rectified]) power see installation manual.
• Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products.
• The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While
the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level
required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA
setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode).
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830054-REV C 6/17 PAGE 3 OF 4
(E)POTTER
The Symbol of Protection
S-24 & HS-24 Series Wiring Diagram
UL Listed
Control
Signal
Panel
S+ S+ S- H+ H-
Supervised 0 0
Signal Circuit
n
S-24 & HS-24
Selectable Candela Strobe & Horn/Strobes
UL Listed
Control
Signal
Panel
S- H+ H-
Supervised
0 a
Signal Circuit
END LINE
RESISTOR
Signal I I Signal
END OF LINE
RESISTOR
END OF LINE
RESISTOR
Notes:
All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits.
However, use of the Potter AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn, and/or mute the horn.
• FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM
CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND
MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC TECHNICAL SUPPORT AT 1-866-956-1211
Architect & Engineering Specifications
The audible and/or visible signal shall be Potter S-24 strobe and Potter HS-24 horn/strobe Series or approved equal and shall be
listed by Underwriters Laboratories, Inc. per ANSI/UL 1971 and/or ANSI/UL 464. The notification appliance shall also be listed with
Factory Mutual Listing Service (FM) and the California State Fire Marshal (CSFM).
The notification appliance (combination audible/visible) shall produce a peak sound output of 100dBA or greater at 24VDC as
measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the
visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or
temporal tone output with the temporal signal having the ability to be synchronized.
Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at
the fire alarm control panel.
The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1 Hz or up to 21-lz regardless of power
input voltage. The strobe appliance shall have an operating current of 42mA or less at 24VDC for the 15Cd strobe circuit.
The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting
bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double
workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current or full
wave rectified power for 24VDC models.
The appliance shall be capable of testing supervision without disconnecting wires, verify voltage without removing unit and be
capable of mounting to a surface back box.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830054-REV C 6/17 PAGE 4 OF 4
SMARTWIRE
GL/O
T E C H N O L O G V�
CABLE SPECIFICATIONS
DESCRIPTION 14 AWG 2 Conductor twisted Bare Copper, Non -Shielded Plenum Fire Alarm, FPLP (UL)
CONDUCTOR 14 (Solid Bare Copper)
INSULATION Low -Smoke PVC .010"
COLOR CODE Black/Red
LAY LENGTH 3.75" LHL (3.2 TPF)
SHIELD N/A
DRAIN WIRE N/A
JACKET Low -Smoke PVC .018" -
JACKET COLOR Red Jacket
MARKING FIRE/LIFE SAFETY CONTROL CABLE INIT. / IND. DEVICE / ZONE A B C D E 0 1 2 3 4 5 6 7 8 9
14 AWG FPLP (UL) ROHS MADE IN THE USA
OVERALL DIAMETER 206" Nom
CABLE WEIGHT 36 Lbs/Mft.
CAPACITANCE 26 pF/Ft. Nom.
IMPEDANCE 72 Ohms
DC RESISTANCE 2.57 Ohms/Mft @ 20 deg. C
TEMPERATURE RATING 0 C to 75 C / 300 Volt
INDUSTRY STANDARDS
FLAME RATING Approved For Plenum Use Without Conduit Per NFPA 262 Flame Test
AGENCY APPROVALS NEC Article 800; FPLP (UL), RoHS Compliant, Made in the USA
®MADE IN
AMERI
All specifications referenced are nominal measurements unless otherwise noted.