Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
specs FIR2020-0039
State of Washington Sprinkler License # Designer: Kenneth H. Robinson RO-BI-NP-*272C2, Level 3 Robinson-Elmslie 29330124th Ave N.E. State of Washington Sprinkler Plumbing Inc Arlington, WA 98223 Designer, Certificate of 360-403-7462 Competancy #7659-0106-CE L-3 Builder: Echelbarger Properties Property address: 714 13th Way, Edmonds (Jenkins lot 3) Total quantity of sprinkler heads: 25 Fire sprinkler system notes: * Fire sprinkler system design per NFPA 13d (standard for houses and duplexes). * Fire sprinkler system to be pressure tested and flow tested. * Sprinkler piping and fittings to be C.P.V.C. "Flameguard" by Speers Mfg. * Installation of C.P.V.C. pipe and fittings to be done by manufacturer certified installers. * Underground water service to be combination fire and domestic. * Sprinkler heads to be Globe Sprinkler Co. "Inch" concealed pendant with escutcheons per listing. SIN # GL4906 and Globe sidewll SIN # GL3241. * Lines in attic to be protected from freezing with tent insulation (by others). * Sprinkler system to supply water connection for toilets, providing "flow through" in lieu of backflow prevention. Dead end branch lines shall be kept to no more than 20' in length- * Design spacing is 16' x 16' (256 square feet). * Design Density is minimum .05 gpm/square foot * Design area is for 2 head simultaneous flow. * Minimum flow requirements are: (1) head flow =13 gpm @7.0 psi (flat or sloped ceilings) (2) head flow =13 gpm (ea) @ 7.0 psi (flat or sloped ceilings) RECEIVED MAR 13 2020 BUILDING F71 F. ao ao-oa3q JOB: ECHELBARGER PROPERTIES ADDRESS: 714 13TH WAY, EDMONDS (LOT 3) DESIGNER: KENNETH H. ROBINSON-ELMSLIE CALCULATIONS FOR 26 GPM FLOW (2 HEADS) IND. LOSS NET TOTAL A. WATER PRESSURE IN STREET 80.00 B: SELECT PIPE SIZE: 1" C: DEDUCT METER & SETTER LOSS (1 ") 12.00 68.00 DEDUCT BACKFLOW DEVICE LOSS (NONE) 0.00 68.00 D: DEDUCT HEAD LOSS FOR ELEVATION HEIGHT 20 X .434 LBS/FT 8.68 59.32 E. DEDUCT PRESSURE LOSS FROM MAIN TO SRINKLER 1-1/4" WATER SERVICE ITEM QUANTITY EQUIV FT. TOTAL FT. PIPE: 280 1 280 ELLS: 8 2 16 R-TEES 7 3 21 B-TEES 3 2 6 TOTAL: 323 TOTAL EQUIVALENT FT. X .04 PSI/FT = 12.92 46.40 F: DEDUCT PRESSURE LOSSES FOR 1-1/2" PIPING FROM CONTROL VALVE TO MOST REMOTE SPRINKLER ITEM QUANTITY EQUIV FT. TOTAL FT. PIPE: 0 1 0 ELLS: 0 7 0 R-TEES 0 1 0 B-TEES 0 8 0 TOTAL: 0 TOTAL EQUIVALENT FT. X .0178 PSI/FT = 0 46.40 F: DEDUCT PRESSURE LOSSES FOR 1-1/4" PIPING FROM CONTROL VALVE TO MOST REMOTE SPRINKLER ITEM QUANTITY EQUIV FT. TOTAL FT. PIPE: 35 1 35 ELLS: 6 6 36 R-TEES 3 1 3 B-TEES 4 6 24 TOTAL: 98 TOTAL EQUIVALENT FT. X .0343 PSI/FT = 3.3614 43.04 F: DEDUCT PRESSURE LOSSES FOR 1" PIPING FROM CONTROL VALVE TO MOST REMOTE SPRINKLER ITEM QUANTITY EQUIV FT. TOTAL FT. PIPE: 30 1 30 ELLS: 3 5 15 R-TEES 5 1 5 B-TEES 2 5 10 TOTAL: 60 TOTAL EQUIVALENT FT. X .1067 PSI/FT = 6.40 36.64 w w w w w w w w w w ■ WAENINGTON STATt ■ F: DEDUCT PRESSURE LOSSES FOR 3/4" PIPING ■ CERTIFICATE OF COMFETE■ICy ■ FROM CONTROL VALVE TO MOST REMOTE SPRINKLER ■ FIRE PROTECTION SPRINKLER SYSTEMS ' ITEM QUANTITY EQUIV FT. TOTAL FT. ■ ; Kenneth Fl. PIP 7 Robinson-Elmslfe ■ ELLS: 2 4 8 a 7659-0106-CE Level 3 ' R-TEES 0 1 0 " Robinson Plumbing,Inc. B-TEES 0 3 R BINP" 72C2 TOTAL: 15 OHO o' ' �G TOTAL EQUIVALENT FT. X .0296 PSI/FT = 0.44 36.19 pire $Ist — rd. 12�/31/20 11 w� w w w w w w w w w w w w w w r r w �, w■ REMAINING PRESSURE FOR SPRINKLER OPERATION 36.19 CALCULATIONS PER NFPA 13D A.10.4.3 (A) (2013 ED.) .... FIRE SPRINKLER CORPORATION "THE INCH" RESIDENTIAL AUTOMATIC SPRINKLERS MODEL GL4906 ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT DESCRIPTION AND OPERATION The Globe Model GL4906 Residential One Inch Adjustable Concealed Pendent Sprinkler has a flat plate profile that utilizes 3mm frangible glass ampule as the thermosensitive element. Itfeatures economy, aesthetics and the lowest allowable water flowwith a nominal 1"of adjustment for easier installation. The combination of the 3mm frangible glass ampule and specially designed deflector make the Model GL4906 the ultimate in life safety and fire control. It has met the strict requirements of Underwriters Laboratories Inc. as described in UL Standard,1626, for Residential Sprinklers for Fire Protection Service, and should be used accordingly. This sprinkler should also be installed in accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the approving authorities having jurisdiction. All that is seen at the ceiling is the 3 5/16" diameter flat ceiling plate color finished to match the specifier's exact requirements. The ceiling plate is soldered to the sprinkler's special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the residential pendent spray sprinkler. Atthe prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass bulb to shatter. This results in water discharge which is distributed in an approved pattern. TECHNICAL DATA * See reverse side for Approvals and Specifications. • Temperature Rating: 155"F (68°C) • Water Working Pressure Rating: 175 psi (12 Bars) • Factory tested hydrostatically to 500 psi (34 Bars) • Maximum lowtemperature glass bulb rating: -670F (-55°C) • Frame -'bronze • Deflector - brass • Screw - brass • Bulb seat - copper • Spring - nickel alloy • Seal - teflon • Bulb - glass with alcohol based solution, 3mm size • Cover Plate - brass • Upper Escutcheon Assembly -steel RESIDENTIAL FLAT PLATE CONCEALED PENDENT • SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING 4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658 SEPTEMBER 2011 A-10 9894346-4583 • FAX989-846-9231 BULLETIN GL4906, REV. #1 RESIDENTIAL AUTOMATIC SPRINKLERS MODEL GL4906 ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT SPECIFICATIONS AND APPROVALS SIN NOMINAL "IC' ITHREADSIZE LENGTH FINISHES 16rF (SrC) SPRINKLER WITH cULus MODEL FACTOR 13rF SrC PLATE Bright Chrome White Painted GL4906 4.9 (68 metric) 1/2" NPT 3" (7.6 cm) Bright Brass* X X Satin Chrome* Other Painted Finishes* NOTE: METRIC CONVERSIONS ARE APPROXIMATE. -FINISHES AVAILABLE ON SPECIAL ORDER. FOR PAINTED PLATES OTHER THAN WHITE, CONTACT GLOBE FOR ORDERING SPECIFICATIONS. INSTALLATION DATA FOR FLAT AND SLOPED CEILINGS" ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT MODEL MAXIMUM AREA OF COVERAGE MINIMUM WATER DISCHARGE S PRESSURES NEEDED PER SPRINKLER" GL49M 12' x 12' 13 G.P.M. - 7 P.S.I. 14' x 14' 13 G.P.M. - 7 P.S.I. 16' x IV 13 G.P.M. - 7 P.S.I. 18' is 18' 17 G.P.M. - 12 P.S.I. 20' x 29 20 G.P.M. - 16.7 P.S.I. NOTE: MINIMUM W SPRINKLER SPACING. `WHEN THESE SPRIN10.ER5 ARE USED IN NFPA 13 SYSTEMS, A 0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED. "REFER TO PAGE 2 OF THE GLOBE RESIDENTIAL SPRINKLER INSTALLATION GUIDE FOR NFPA 13D and 13R REQUIREMENTS. ORDERING INFORMATION CROSS SECTION SPECIFY 2 3/4' M& MIN. - - HOLE M SING —2 3/8' 01A. 1kL2•- I I ssElx�x , U912crnR DROP PIN SL VPW 91e1N 2 3/4' MAX 1 7/8' MIN. CELM Cave+. PLATE FLAT PLATE CONCEALEDPENDENT GL&33E FIRE SPRINKLER CORPORATKOAI SEPTEMBER2011 • Quantity • Model Number • Style • Orifice - Temperature • Finishes desired • Quantity - Concealed Wrenches - P/N 332765 • Quantity - Protective Caps - P/N 332868 COVER PLATE SIZE WHITE 136OF PART # CHROME 136OF PART # 3 5116' 332892 332891 GLOBE° PRODUCT WARRANTY Globe agrees to repair or replace any of its own manu- factured products found to be defective in material or workmanship for a period of one year from date of ship- ment_ For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846.4583 FAX989-846-9231 1-800-248-0278 www.globesprinkler.com PRINTED U.S.A. BULLETIN GL4906, REV. #1 GLOBE RESIDENTIAL SPRINKLER GUIDE NFPA 13 REQUIREMENTS: When sprinklers are used in NFPA 13 Systems, A 0.1 Design Density minumum shall be utilized. NFPA 130 REQUIREMENTS: For each of the following situations, the number of sprinklers in the design area shall be all of the sprinklers within a compartment, up to a maximum of two sprinklers, that require the greatest hydraulic demand: (1). A flat smooth, horizontal ceiling with no beams up to a maximum of 24 ft. above the floor. (2). A smooth flat, sloped ceiling with no beams up to a maximum slope of 8 in 12. The highest portion of the ceiling shall not be more than 24 ft. above the floor. The highest sprinkler in the sloped portion of the ceiling shall be above all openings from that compartment containing the sloped ceiling into any communicating spaces. (3). A sloped ceiling with beams up to 14 in. deep with pendent sprinklers under the beams. The compartment containing the sloped, beam ceiling shall be a maximum of 600 Win area_ The slope of the ceiling shall be between 2 in 12 and 8 in 12. The highest portion of the ceiling shall not be more than 24 ft. above the floor. The highest sprinkler in the sloped portion of the ceiling shall be above all openings from the compartment containing the sloped ceiling into any communicating spaces. (4). A sloped ceiling with beams of any depth with sidewall or pendent sprinklers in each pocket formed by the beams. The compartment containing the sloped, beamed ceiling shall be a maximum of 600 ftx in area. The slope of the ceiling shall be between 2 in 12 and 8 in 12. The highest portion of the ceiling shall not be more than 24 ft above the floor. For situations not meeting one of the conditions above, residential sprinklers listed for use in specific ceiling configurations shall be permitted to be used in accordance with their listings. For situations not meeting one of the conditions above, the number of sprinklers in the design area shall be determined in consultation with the authority having jurisdiction as appropriate forthe conditions. Sprinklers shall be installed in accordance with their listing where a type of ceiling configuration is referenced in the listing. NFPA 13R REQUIREMENTS: Horizontal Ceiling criteria may be used for sloped ceiling configurations up to 8: 12 pitch when accept- able to the Local Authority having Jurisdiction. The following pages contain illustrations for customers reference. If conflicting data is found, NFPA 13,13D, or 13R requirements take presedence. SEPTEMBER 2011 Page 2 BULLETIN R.S.I.G., REV. #15 wAkw Oman ummm �a r� FIRE SPRINKLER CORPORATION RESIDENTIAL AUTOMATIC SPRINKLERS MODEL GL4231 HORIZONTAL SIDEWALL RECESSED HORIZONTAL SIDEWALL DESCRIPTION AND OPERATION The Globe Model GL4231 Residential Horizontal Sidewall Sprinklers have a durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. They feature econ- omy, aesthetics and low flow. The combination of the 3mm frangible glass ampule and specially designed deflector make the Model GL4231 Sprinklers the ultimate in life safety and fire control. These Globe Horizontal Sidewall and Recessed Horizontal Sidewall Residential Sprinklers have met the strict requirements of Underwriters Laboratories Inc. as described in the UL Standard for Residential Sprinklers for Fire Protection Service, UL 1626, and should be used accordingly. These sprin- klers should also be installed in accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the ap- proving authorities having jurisdiction. The heart of Globe's Model GL4231 sprinklers proven actuating assembly is a hermetically sealed frangible glass ampule that con- tains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which isdistributed in an approved pattern. The sprinkler and escutcheon are not factory assembled. Assembly is done in the field. TECHNICAL DATA See reverse side for Approvals and Specifications. Temperature Rating - 1550F (680C), 175OF (79°C) Water Working Pressure Rating - 175 psi (12 Bars) Factory tested hydrostatically to 500 psi (34 Bars) Maximum low temperature glass bulb rating is -670F (-55°C) Frame - bronze Deflector - brass Screw - brass Lodgement Wire - stainless steel Bulb seat - copper Spring - nickel alloy Seal - teflon Bulb - glass with alcohol based solution, 3mm size Escutcheon Assembly - steel RESIDENTIAL HORIZONTAL SIDEWALL RESIDENTIAL RECESSED HORIZONTAL SIDEWALL SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CEILING CLASSIFICATION BULB COLOR TEMPERATURES TEMPERATURE ORDINARY 155"F 68"C RED 100*F 381C INTERMEDIATE 175°F 790C YELLOW 150"F 66°C DEC 2016 GFS-330 (Formerly A-4) RESIGIENTIAL AUTOMATIC SPRINKLERS MODEL GL4231 HORIZONTAL SIDEWALL RECESSED HORIZONTAL SIDEWALL SPECIFICATIONS AND APPROVALS SIN MODEL NOMINAL "K" FACTOR THREAD SIZE LENGTH FINISHES cULus CE NYC - DOB MEA 101-92-E Factory Bronze GL4231 4.2 ( 60 metric) 1/2"NPT 2 1/2" Chrome X X (15mm) (6.4cm) White Polyester2 Black Polyester'.2 NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. 'AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER. INSTALLATION DATA FOR FLAT AND SLOPED CEILINGS** SIN MODEL STYLE TEMPERATURE MAX. AREA OF COVERAGE Feet (Meters) •*MIN. PRES- SURE (a./. (bars) *MIN. FLOW G.P.M. (Umin.) DEFLECTOR TO CEILING DISTANCE Inches (mm) MIN. DISTANCE BETWEEN SPRINKLERS Feet (Meters) (68°C) 68-C 175°F (79°C) 12 (3.7) x 12 (3.7) 9.6 (.66) 13 (49) 14 (4.3) x 14 (4.3) 12.8 (.88) 15 (57) HORIZONTAL SIDEWALL 4(101.6) 16 (4.9) x 16 (4.9) 14.5 (1.00) 16 (61) GL4231 RECESSED X X to 8(2.4) HORIZONTAL SIDEWALL 6(152.4) 16 (4.9) x 18 (5.5) 20.5 (1.41) 19 (72) 16 (4.9) x 20 (6.1) 30.0 (2.07) 23 (87) NOTE: METRIC CONVERSIONS ARE APPROXIMATE. *WHEN THESE SPRINKLERS ARE USED IN NFPA 13 SYSTEMS, A 0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED REFER TO PAGE 2 OF GLOBE'S RESIDENTIAL SPRINKLER INSTALLATION GUIDE (BULLETIN R.S.I.G.) FOR NFPA 13D AND 13R REQUIREMENTS. 'FOR COVERAGE AREA DIMENSIONS LESS THAN OR BETWEEN THOSE INDICATED, USE THE MINIMUM REQUIRED FLOW FOR THE NEXT HIGHEST COVERAGE AREA FOR WHICH HYDRAULIC DESIGN CRITERIA ARE STATED THE LENGTH x WIDTH REFERS TO THE BACKWALL WHERE THE SPRINKLER IS LOCATED (WIDTH) x HORIZONTAL THROW OF THE SPRINKLER (LENGTH). CROSS SECTION all RETOWER 2 15/16DIA. 1 29/32• DIA.I 2• MIN. DIA "OIE IN CHUNG I 1" x 1/2" REDUCER 1/B" MIN 5/8" MAX -1/2" A. 7/8" MAX - 3/9" ADJ. ORDERING INFORMATION SPECIFY • Quantity • Model Number • Style ,• MM • Orifice • Temperature • Finishes desired 6•MIJIX. • Quantity - Wrenches - P/N 325390 ,1 • Quantity - Recessed Wrenches - P/N 327102 • Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed) 1" MIN, 1 3/4" MAX 1/2" OR 3/4" ADJUSTMENT RECESSED HORIZONTAL SIDEWALL GL . SE FIRE SPRINKLER CORPORATION GLOBE@ PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 FAX 989-846-9231 1-800-248-0278 www.globesprinkler.com DEC 2016 PRINTED U.S.A. GFS-330 (Formerly A-4) P.O. Box 3365 South E! Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afoon.org 515 DOUBLE OFFSET CYN.C. HANGER SIZE - 3/4" and 1" pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanize([. LlsTnvGs - Sm EX 4231 PATENT - No. 6,702,236 FUNCTION - Hanger/restrainer on CPVC pipe. INSTALLATION - Per NASA 13. l3R and 13D on side of beam. FASTENERS - UL Listed per NFPA 13. in WOOD: #904 screw - no pre -drill. in STEEL: 1/4" or A 4 Tek Screw. FEATURES "Double 1 1/2" offset. • Center line matches AFCON#514. • 3/4" and l" pipe size have common center -line. • Offbet edge eliminates abrasion. • Required AFCON#904 screw has 3/8" bex head - included. ORDERING - Part # and pipe size. 1 /04 Toqc)o INCORPORATED CORONA CA • 714 M-5599 t t 32A FIG. 22 HANGER FOR C. P. V. C. PLASTIC PIPE SINGLE FASTENER STRAP TYPE Size Range - 3/4" thru 2" C.P.V.C. pipe. Material - Carbon Steel with galvanized finish G-90 govt. spec. Function - Figure 22 is intended to perform as a hanger to support only C.P.V.C. piping used in automatic fire sprinkler systems. The product acts as a hanger when tab is upward and the fastener screw is in the horizontal position. Figure 22 can be installed on the top of a beam, but in this situation acts as a guide to the piping which is supported by the beam itself. Figure 22 is not intended to support C.P.V.C. pipe from under a flat horizontal surface, such as a ceiling. For this type of installation use the Tolco Figure 21 Double Fastener Strap Hanger For C.P.V.C. Piping. Figure 22, when inverted, with the hanger tab downward, does not act as a hanger, but can function as a restrainer to prevent the upward movement of the sprinkler head during activation. Approvals - Underwriters' Laboratories listed to support fire sprinkler piping. Meets and exceeds the requirements of N.F.P.A. 13, 13R, and 13D. Features - Figure 22 incorporates features which protect the pipe and ease installation. The flared edge design" protects C.P.V.C. pipe from any rough surface. Figure 22 is easily attached to the building structure using the special hex head self threading screw" furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been known to result from installations using impact type tools. No pre drilling of a pilot hole in wood is required. Order By -Figure number. and C.P.V.C. pipe size. Patent Pending " - Minimum fastener size acceptable, &12 x 1-1/4" hardened hex mead self threading screw. A -- — — - - MAX. HANGER FASTENER APPROX. C.P.V-C. SPACING HEX HEAD WEIGHT PIPE SIZE A B C (FT.) SIZE LENGTH PER 100 — ... ....-- 3/4 2 - 7/16 1 5/16 1 - 3/16 _ 5-1/2 .t.. t 5/16 1-1/4 9 tn� `. :. , L Y� r� 4 �y� c�t- � R�ur� y / 4 �w N�n��wii'i.�j�y �y�o•,�,:�� :,. ..�V.Y t�i.r�'�^�r'a':.:i✓Y_y,.� ^'Zjit'..'1;" ^�tX�ft+ lYr�i��4e'4..���e ..�iii"_� ♦. .�2�E'.sit, _ i'sL�.:!S:<.:�.P,!SIK1�1.:�:.y��:l`.<. 1 '1(�)t:.^r.•.•;:.wTj�+'�:-�L!•� 1 - l/4 3 - 1/16 1-5/8 1 - 3/16 6-1/2 i5/16 1 1/4 11 2 3 3/4 2-1/8 1 - 3/16 8 5/16 1 1/4 15 Fig. 29 - Double Offset Hanger & Restrainer for CPVC Plastic Pipe Size Range -- Available in 3/4" and 1" pipe sizes Material -- Pre -Galvanized Steel Function — Intended to perform as a hanger and restrainer for CPVC, plastic fire sprinkler pipe. Provides double offset 1 W x 1 Y2" from mounting surface. This design will ease installation by eliminating the need for wood block extension and allow retro-fit attachment of hanger to sprinkler pipe. Features — • Thumb tab provides protection to restrain pipe in rough job site conditions. Tab is not required to be bent for listed installation. • Offset edge eliminates abrasion. • Attaches easily to wood structure with two special #10 x 1 hex head self -threading screws furnished with product. • Can be used as a single offset hanger by aligning "dimples" with top of mounting surface and utilizing two fasteners in two of the three holes provided. Approvals — Underwriters' Laboratories Listed in the USA (UL) and Canada (cUL) as a hanger and restrainer to support fire sprinkler systems. Meets and exceeds requirements of NFPA 13, 13R and 13D. Finish — Pre -Galvanized Order By — Figure number and pipe size. PATENT PENDING Install using a rechargeable electric drill idted with a 5/16" socket attachment with the special hex head self -tapping screws provided. Install screws until they bottom out. Pipe can be "snapped" Into hanger before or after installation of the screws to the mounting surface. "Thumb tab" may be bent up to provide additional protection to the pipe, but is rut required for performance of the hanger / restrainer function. 9@Va LWO L----------j OFFICEAIANUFAC URING FACWTV " 1375 SAMPSON AVF " CORONA CA 92W9 • PH: 951-737.5599 - FAX 951.737.0330 CUSTOMER SERVICE • 000.796.5M Wwwrolco.com ■ Ire �c0 INCORPORATED 3213 C' .';rk OA • M4: 737-5599 FIG. 23 HANGER FOR C.P:V:C. PLASTIC PIPE DOUBLE FASTENER STRAP TYPE Size Range - 3/4" thru 2" C.P.V.C. pipe. Material - Carbon Steel with galvanized finish G-90 govt. spec. Function - The Fig- 23 and Fig. 24 are intended to perform as a hanger / restrainer to support only C.P.V.C. piping used in automatic fire sprinkler systems. Fig. 23 and Fig. 24 can be installed on the top or on the bottom of a beam. The Fig. 23 can also be installed on the side of a beam. The Fig. 23 and Fig. 24 can also function as a restrainer to prevent the upward movement of the sprinkler head during activation. Approvals - Underwriters' Laboratories listed to support fire sprinkler piping. Meets and exceeds the requirements of N.F.P.A. 13, 13R, and 13D. A B I C C.P.V_C. � PIPE SIZE FIG. 23 FIG. 24 FIG. 23 FIG: 24 ;FIG. 23 FIG. 3/4 _ 3-1/8 2 - 5/16 1- 9/16 1- 5/32 ` 1- 3/16 1-3 1-1/4 4- 3/16 3 ; 2- 3/32 1-14 1- FIG. 24 HANGER FOR C.P.V.C. PLASTIC PIPE DOUBLE FASTENER STRAP TYPE - SIDE MOUNT Features - The Fig. 23 and Fig. 24 incorporate features which protect the pipe and ease installation. The flared edge design" protects the C.P.V-C. pipe from any rough surface. The Fig. 23 and Fig. 24 are easily attached to the building structure using the two hex head self threading screws — furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been known to result from installations using impact type tools. No pre drilling of a pilot hole in wood is required. Order By - Figure number and C.P.V-C. pipe size. ° Patents Pending - Minimum fastener size acceptable, +#12 x 1-1/4" hardened hex head self threading screw. MAX. HANGER FASTENER APPROX. SPACING HEX HEAD WEIGHT (FT.) SIZE LENGTH PER 100 5-1/2 1 5A6 1 1-1/4 ' i 9 6-1/2 1 5/16 1 1-1/4 1 11 E HEMS D "I 4-7/8 3-11/16 2-7/16 1- 34 1- 3/16 1- 3/161 8 ' 5/16 1-1/4 I_. 15 Fig. 28M - Offset Hanger and Restrainer for CPVC Plastic Pipe and IPS :Pipe Size Range — 3/4" thru 1-:1/4" pipe Material — Carbon Steel; Electra -Galvanized Function — Designed to be used as a hanger. _and restrainer for CPVC piping where the "stand-off' design will ease installation by eliminating the need fear wood blocking Features - - Flared edge design protects CPVC pipe from any rough or abrasive surfaces • Unique snap -on design holds pipe firmly in place and allows retrofit type of installation • The "Stand -Off design eliminates the need for wood block extension • Can be installed on horizontal or vertical piping regardless of mounting surface orientation • Attaches easily to wood structure with two hex head self -threading screws furnished with product • Installs easily using rechargeable electrical driver with 5/16" extension socket eliminating impact tool damage to pipe • Attaches easily: to.steel, minimum 18 gauge with (2) 1/4" x 1" tek type self drilling tapping screws • cULus Listed as a hanger and a restrainer for fire sprinkler piping Approvals = Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fas- teners screws_ Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28M satisfies the UL vertical restraint requirements where needed. Order By — Figure number and pipe size PATENT PENDING "7 - --------- 4 � I. - - : .- RESTRAINT Fig. 28M 1 A I j 1 r 7 1 I 1 I Dimensions • Weights Max. Spacing Pipe required per Appprox Size A B C NFPA 13 for WiJ100 CPVC pksdc pipe 314 2 3/16 3-1/2 5'-6" 9 1 2-1/6 3116 3-1/2 6'-0" 12 1-1/4 2-5/16 3/16 3-1/2 6'-6" 13 C@08 LWO RESTRAINT W_ 0FHCE7MAIIUFACMNG FACIM • 1375 SAMPSON AVE • CORONA. CA 92979 • PH: 951.737.M • FAX' 951.737.U330 CUSTOMER SERVICE • 8D9.78&5266 ■ Friction Loss (PSI per Linear Foot) and Velocity (Feet per second) (Haxer41111ams C Factor - 150) Nominal Pipe Us: 3/4Inch 1 inch I inches 1Y2 inches 2 inches 2Ma inches 3 inches Avg.1.D. Onches) (484) (1.109) (1.400) (1.602) (2.003) (2.423) (2.951) Friction Friction Friction Friction Friction Friction Friction . GPM Loss Velocity loss Velocity Loss Velocity lass Velocity Loss Velocity lass Velocity Loss Velocity 1 .0008 .5 .0003 .3 .0001 .2 .0000 .1 .0000 .1 .0000 .0 .0000 .0 2 .0028 1.0 .0009 .6 _0003 A .0002 .3 .0001 .2 .0000 .1 .0000 .0 3 .0059 1.5 .0020 .9 .0006 .6 .0003 .4 .0001 .3 .0000 .2 ODDD .1 4 .0101 2.0 .0033 1.3 .0011 .6 .0006 .6 .0002 .4 :0001 .2 .0000 .1 5 .0152 2.6 .0051 1.6 .0016 1.0 .0008 .7 OD03 .5 .0001 .3 .0000 .2 6 .0214 31 .0071 1.9 .0023 1.2 .0012 .9 .0D04 .6 .0002 .4 .0001 .2 7 .0284 3-6 .0094 2.3 .0030 1.4 .0016 1.1 .0005 .7 .0002 .4 .0001 .3 6 .0364 4.1 .0121 2.6 .0039 1.6 .0020 1.2 .0007 .8 .0003 .5 .0001 .3 9 .0452 4.7 .0150 2.9 .0048 1.8 .0025 1.4 .OD08 .9 .0003 .6 .0001 .4 10 .0550 5.2 .0182 3.3 .0059 2.0 .0030 1.5 .0010 1.0 .0004 .6 .0002 .4 11 .0656 5.7 .0217 3.6 .0070 2.2 .0036 1.7 .0012 1.1 .DO05 .7 0002 .5 12 .0770 6.2 .0255 3.9 .0082 2.5 .0043 1.9 .0014 1.2 .0006 .8 .0002 .5 13 .0893 6.7 .0296 4.3 .0095 2.7 .0049 2.0 .0017 1.3 .0007 .9 .0003 .6 14 .1024 7.3 .0340 4.6 .0109 2.9 .0057 2.2 .0019 1.4 .0008 .9 .0003 .6 15 .1164 7.8 .0386 4.9 .0124 3.1 .0064 2.3 .0022 1.5 .0009 1.0 .0003 .7 16 AM 8.3 .0435 5.3 .0140 3.3 .0072 2.5 .0024 1.6 .0010 1.1 .0004 .7 17 .1467 8.8 .0486 5.6 .0156 3.5 .0081 2.7 .0027 1.7 .0011 1.1 .0004 .7 18 .1631 9.4 .0541 5.9 .0174 3.7 .0090 2.8 .0030 1.8 .0012 1.2 .0005 .8 19 .1802 9.9 .0597 6.3 .0192 3.9 .0100 3.0 .0034 1.9 .0013 1.3 .0005 .8 20 .1982 10.4 .0657 6.6 .0211 4.1 .0110 3.1 .0037 2.0 .0015 1.3 .0006 .9 21 .2169 10.9 .0719 6.9 .0231 4.3 .0120 3.3 .OD40 2.1 .0016 1.4 .0006 .9 22 .2364 11.5 .0783 7.3 .0252 4.5 .0131 3.5 DD44 2.2 .0017 1.5 .0007 1.0 23 .2567 12.0 .0851 7.6 .0273 4.7 .0142 3.6 .0048 2.3 .0019 1.6 .0007 1.0 24 .2777 12.5 .0920 7.9 .0296 5.0 .0153 3.8 .0052 2.4 .0020 1.6 .0008 1.1 25 .2995 13.0 .0993 8.3 .0319 5.2 .0166 3.9 .0056 2.5 .0022 1.7 .0008 1.1 26 .3220 13.5 .1067 8.6 .0343 5.4 .0178 4.1 .0060 2.6 .0024 1.8 .0009 1.2 27 .3453 14.1 .1144 8.9 .0368 5.6 .0191 4.2 .0064 2.7 .0025 1.8 .0010 1.2 28 .3693 14.6 .1224 9.3 .0394 5.8 .0204 4.4 .0069 2.8 .0027 1.9 .0010 1.3 29 .3941 15.1 .1306 9.6 .0420 6.0 .0218 4.6 .0073 2.9 .0029 2.0 .0011 1.3 30 .4196 15.6 .1391 9.9 .0447 6.2 .0232 4.7 .0078 3.0 .0031 2.0 .0012 1.4 31 .4468 16.2 .1478 10.2 .0476 6.4 .0246 4.9 .0083 3.1 _0033 2.1 .0013 1.4 32 .4728 16.7 .1567 10.6 .0504 6.6 .0261 5.0 .0088 3.2 .0035 2.2 .0013 1.5 33 .5005 17.2 .1659 10.9 .0533 6.8 .0277 5.2 .0093 3.3 _0037 2.2 .0014 1.5 34 .5289 17.7 .1753 11.2 .0564 7.0 o292 5.4 .0098 3.4 .0039 2.3 .0015 1.5 35 .5580 18.2 .1850 11.6 .0595 7.2 .0308. 5.5 .0104 3.5 .0041 2.4 .0016 1.6 36 .5879 18.8 .1949 11.9 .0626 7.5 .0325 5.7 .0109 3.6 .0043 2.5 .0017 1.6 37 .6185 19.3 .2050 12.2 .0659 7.7 .0342 5.8 .0115 3.7 .0046 2.5 .0017 1.7 38 .6498 19.8 .2154 12.6 .0692 7.9 .0359 6.0 .0121 3.8 .0048 2.6 .0018 1.7 39 .6817 20.3 .2260 12.9 .0726 8.1 .0377 6.2 .0127 3.9 .0050 2.7 .0019 1.8 40 .7144 20.9 .2368 13.2 .0761 8.3 .0395 6.3 1.0133 4.0 1 .0053 2.7 .0020 1.8 41 .2479 13.6 .0797 8.5 .0413 6.5 .0139 4.1 .0055 2.8 .0021 1.9 42 .2592 13.9 .0833 8.7 .0432 6.6 .0146 4.2 .0058 2.9 .0022 1.9 43 2707 14.2 .0870 8.9 .0451 6.8 .0152 4.3 .0060 2.9 .0023 2.0 44 .2824 14.6 .0908 9.1 .0471 7.0 .0159 4.4 .0063 3.0 .0024 2.0 45 .2944 14.9 .0947 9.3 .0491 7.1 .0165 4.5 .0065 3.1 .0025 2.1 46 .3087 15.2 .0986 9.5 '0511 7.3 .0172 4.6 .0068 3.2 .0026 2.1 47 .3191 15.6 .1026 9.7 .0532 7.4 .0179 4.7 .0071 3.2 .0027 2.2 48 :3318 15.9 .1067 10.0 .0553 7.6 .0186 4.8 .0074 3.3 .0028 2.2 49 .3447 16.2 .1108 10.2 .0575 7.7 .0194 4.9 .0077 3.4 .0029 2.2 50 .3576 16.6 .1150 10.4 .0597 7.9 .0201 5.0 .0080 3.4 .0030 2.3 52 .3847 17.2 .1237 10.8 .0642 8.2 .0216 5.2 .0086 3.6 .0033 2.4 54 .4126 17.9 .1326 11.2 .0688 8.5 .0232 5.4 .0092 3.7 .0035 2.5 56 .4413 18.6 .1419 11.6 .0736 8.9 .0248 5.7 .0098 3.8 .0038 2.6 58 .4709 19.2 .1514 12.0 .0785 9.2 .0265 5.9 .0105 4.0 .0040 2.7 50 .5013 19.9 .1612 12.5 .0836 9.5 .0282 6.1 .0111 4.1 .0043 2.8 62 .5327 20.5 .1713 12.9 .0888 9.8 .0299 6.3 .0118 4.3 .0045 2.9 64 .5649 21.2 .1816 13.3 .0942 10.1 .0317 6.5 .0126 4.4 .0048 3.0 66 .5900 21.9 .1923 13.7 .0997 10.5 .0336 6.7 .0133 4.5 .0051 3.0 68 .6320 22.5 .2032 14.1 .1054 10.8 .0355 6.9 .0141 4.7 .0054 3.1 70 .6668 23.2 .2144 14.5 .1112 11.1 .0375 7.1 .0148 4.8 .0057 32 72 .7025 23.9 .2258 15.0 .1171 11.4 .0395 7.3 .0156 5.0 .0060 3.3 74 .7390 24.5 .2376 15.4 .1232 11.7 .0415 7.5 .0164 5.1 .0063 3.4 76 .7764 25.2 .2496 15.8 .1295 12.0 .0436 7.7 .0173 5.2 .0066 3.5 78 .8146 25.9 .2619 16.2 .1358 12.4 .0458 7.9 .0181 5.4 .0069 3.6 80 .8536 26.5 .2744 16.6 .1424 12.7 .0480 8.1 .0190 5.5 .0073 3.7 Engineering Data Pipe and Fitting Specifications Spears® FlameGuard® CPVC Sprinkler Pipe is produced in SDR 13.5 dimensions, as specified in ASTM F 442. Engineering data on Material Properties and Expansion & Contraction are provided in this manual for (A) Spears® FlameGuard® or Victaulic FireLock® and (B) Harvel BlazeMaster® CPVC Fire Sprinkler Pipe. Consult other manufacturers for applicable variations Spears® FlameGuard® CPVC Sprinkler Fittings are produced in Schedule 40 and Schedule 80 dimensions for sizes 3/4" through 1-114", and in Schedule 80 for sizes 1-1/2" through 3", in accordance with ASTM F 437, ASTM F 438, and ASTM F 439 as applicable. These products are UL Listed FM/Approved for a rated working pressure of 175 psi (1200kPa)at 150* F (65° C) for sprinkler service and LPCB listed for a rated working pressure of 175 psi (1200kPa) at 120° F (49° C). CPVC Fire Sprinkler Pipe Dimensions SDR 13.5 (Ref. ASTM F442) Weight Ibs/ft (kg/m) Size Average Average Nominal riches OD inches (mm) ID inches 3/4 1.050 0.874 0.168 (DN20) (26,7) (22,5) (0,2) 1 1.315 1.101 0.262 (DN25) (33,4) (28,2) (0,4) 1-1/4 1.660 1.394 0.418 (DN32) (42,2) (35,6) (0,6) 1-1/2 1.900 1.598 0.548 (DN40) (48,3) (40,7) (0,7) 2 2.375 2.003 0.859 (DN50) (60,3) (50,9) (1,2) 2-1/2 2.875 2.423 1.257 (DN65) (73,0) (61,5) (1,2) 3 3.500 2.950 1.867 (DN80) (88,9) (75,0) (1,2) Hydraulic Design Hydraulic calculations for the sizing of systems incorporating Spears® FlameGuard® CPVC Fire Sprinkler Products must be calculated using a Hazen -Williams C value of 150. Pipe friction loss calculations must be made according to NFPA Standard 13. The following table shows the allowance for friction loss for fittings, expressed as equivalent length of pipe. For additional information regarding friction loss, contact Spears®. FG-3-1010 0 2010 Speae Manufacturing Company Page 37 Allowance for Friction Less In Man Equivalent Feet (meters) of Pipe 3/40 26,7 mm 1" 33,7 mm 1-1/4° 42,4 mm 1-1/2" 48,3 mm 20 60,3 mm 2-1/2" 73,0 mm 3" 88,9 mm Tee Run 1(0,3) 1(0,3) 1(0,3) 1(0,3) 1(0,3) 2(0,6) 2(0,6) Tee Branch 3(0,9) 5(1,5) 6(1,8) 8(2,4) 10(3,1) 12(3,7) 15(4,6) 90° Elbow 4(1,2) 5(1,5) 6(1,8) 7(2,1) 9 (2,7) 12 (3,7) 13(4,0) 45° Elbow 1(0,3) 1(0,3) 2(0,6) 2(0,6) 2(0,6) 3(0,9) 4(1,2) Coupling 1(0,3) 1(0,3) 1(0,3) 1(0,3) 1(0,3) 2(0,6) 2(0,6) Hangers & Supports Since CPVC Fire Sprinkler pipe is rigid, it requires fewer supports than flexible, plastic systems. Spears® recommends use of hangers that are designed and listed for supporting the CPVC Fire Sprinkler pipe. However, some hangers designed for steel pipe may be used if their suitability is clearly established. These hangers must have a minimum 1/24nch, load -bearing surface, and they must be selected to accommodate the specific pipe size. In addition, they cannot contain rough or sharp edges that contactthe pipe, and they must not bind the pipe from axial movement. Vertical runs must be supported so that the weight of the run is not on a fitting or a joint. Horizontal runs must be braced so that the stress loads (caused by bending or snaking pipe) will not be placed on a fitting or a joint. Support spacing is shown in the following table. See °Snaking/Deflection of Pipe" in this manual for information regarding bending or snaking CPVC Fire Sprinkler Pipe, Pipe Size Nominal inches Maximum Support Spacing feet (meters) Wt. Water Filled Pipe Ibs/ft (kg/m) 3/4 (DN20) 5-1/2 (1,7) 0.427 (0,6) 1 (DN25) 6(1,8) 0.674 (0,9) 1-1/4 (DN32) 6-112 (2,0) 1.078 (1,5) 1-1/2 (DN40) 7(2,1) 1.412 (1,9) 2 (DN50) 8(2,4) 2.223 (3,0) 2-1/2 (DN65) 9(2,7) 3.254 (61,5) 3 (DN80) 10(3,0) 4.831(75,0) Page 38 © 2010 Spears" Manufacturing Company FG-3-1010 NFPA 13D permits "support methods comparable to those required by local plumbing codes.° The above hanger/support requirements must also be followed on NFPA 13D systems. CAUTION: DO NOT use hanger items such as plumber's tape or 'nail -on" devices. Pipe hanger must comply with NFPA 13,13D and 13R. When a sprinkler head activates, a significant reactive force can be exerted on the pipe. With a pendent head, this reactive force can cause the pipe to lift vertically if it is not secured properly, especially if the sprinkler drop is from small diameter pipe. The pipe must be braced against the vertical lift -up with the closest hanger. Refer to the following illustration and Table A & B. Hat 9uppmt amwsuppo►t SracelSuppod i�i Finished Ceft Uhe Table A - Maximum Support Spaclog Distance End Une Sprlokler Head Drop Elbow Pipe Size Nominal inches Line Pressure <100 psi. (<689kPa) Line Pressure >100 psi (>689kPa) 3/4 (DN20) 9 inches (228,6 mm) 6 inches (168,3 mm) 1(DN25) 12 inches (304,8 mm) 9 inches (228,6 mm) 1-1/4 (DN32) 16 inches (406,4 mm) 12 inches (304,8 mm) 1-1/2 - 3 (DN40 - DN80) 24 inches (610,0 mm) 12 inches (304,8 mm) Note: Support spacing can be increased by approximately 50% for lower pressures. Table B - Maximum Support Spacing Distance Inllne SprinMu Head Drop Tee Pipe Size Line Pressure Line Pressure Nominal inches <100 psi (<689kPa) >100 psi (>689kPa) 3/4 (DN20) 4 feet (1,22 meters) 3 feet* (0,91 meters) 1(DN25) 5 feet.(1,52 meters) 4 feet* (1,22 meters) 1-1/4 (DN32) 6 feet (1,83 meters) 5 feet* (1,52 meters) 1-1/2 - 3 (DN40 - DN80) 7 feet (2,13 meters) 7 feet (2,13 meters) Note: *Support spacing can be increased by one foot for lower pressures. FG-3-1010 0 2010 Spears"' Manufacturing Company Page 39