Fire Comments Mallory Paint
Plan Review
DATE: 06/02/2020
PERMIT #:BLD2020-0482
JOB NAME/ADDRESS:MALLORY PAINT-M & N REALTY LLC 7711 244th St SW
CONTACTS:JOSHUA HARRISON
JOSHUA.HARRISON@MALLORYPAINT.COM
FIRE COMMENTS:
1) Building does not have a Fire Alarm or Sprinkler System.
As per Edmonds City Code 19.25.035, A. Automatic Fire Sprinklers. In addition to
the requirements of Section 903.2, an approved automatic fire sprinkler system
shall be installed and maintained throughout all buildings, structures, floors, and
suites described in this section. If conflicts exist between the IFC and this section,
this section shall prevail. All sprinklers shall be installed per the applicable NFPA
and South County Fire’s (SCF) fire sprinkler standard. For the purposes of ECDC 19.25.035, spaces separated by fire walls, fire barriers, fire partitions and fire-resistance-rated horizontal
assemblies noted in Chapter 7 IBC shall not be considered
to be separate buildings. Partial area automatic sprinkler systems are prohibited
except where approved by the fire code official.
#4. When required by the International Existing Building Code (IEBC) for existing
buildings and structures undergoing additions, alteration, repairs, or changes of
occupancy. The classification of work level shall be determined by the building andfire code official.
2) Because of the extent of the tenant improvement, Fire is requiring a monitored building Fire Alarm be installed in accordance with NFPA 72. A fire sprinkler
system will not be required at this time.
3) Separate permit required for Fire Alarm.
4) Fire Final inspection required for business license and occupancy. Fire
extinguishers, exit signs, fire lane markings and emergency lighting at final
inspections.
Thank you,
Karl Fitterer CFI, FPE
Assistant Fire Marshal
Fire Prevention Services
121 5th Ave N Edmonds, WA 98020
O: (425)771-0213 VM: (425)551-1980
kfitterer@southsnofire.org