Loading...
Fire Comments Mallory Paint Plan Review DATE: 06/02/2020 PERMIT #:BLD2020-0482 JOB NAME/ADDRESS:MALLORY PAINT-M & N REALTY LLC 7711 244th St SW CONTACTS:JOSHUA HARRISON JOSHUA.HARRISON@MALLORYPAINT.COM FIRE COMMENTS: 1) Building does not have a Fire Alarm or Sprinkler System. As per Edmonds City Code 19.25.035, A. Automatic Fire Sprinklers. In addition to the requirements of Section 903.2, an approved automatic fire sprinkler system shall be installed and maintained throughout all buildings, structures, floors, and suites described in this section. If conflicts exist between the IFC and this section, this section shall prevail. All sprinklers shall be installed per the applicable NFPA and South County Fire’s (SCF) fire sprinkler standard. For the purposes of ECDC 19.25.035, spaces separated by fire walls, fire barriers, fire partitions and fire-resistance-rated horizontal assemblies noted in Chapter 7 IBC shall not be considered to be separate buildings. Partial area automatic sprinkler systems are prohibited except where approved by the fire code official. #4. When required by the International Existing Building Code (IEBC) for existing buildings and structures undergoing additions, alteration, repairs, or changes of occupancy. The classification of work level shall be determined by the building andfire code official. 2) Because of the extent of the tenant improvement, Fire is requiring a monitored building Fire Alarm be installed in accordance with NFPA 72. A fire sprinkler system will not be required at this time. 3) Separate permit required for Fire Alarm. 4) Fire Final inspection required for business license and occupancy. Fire extinguishers, exit signs, fire lane markings and emergency lighting at final inspections. Thank you,   Karl Fitterer CFI, FPE Assistant Fire Marshal Fire Prevention Services 121 5th Ave N Edmonds, WA 98020 O: (425)771-0213 VM: (425)551-1980 kfitterer@southsnofire.org