0216_001(Medical Gas Services 918 S Horton St, Suite 917 )L0 z0z't—C 5- T Seattle, WA 98134 medgasservices.io (425) 894 5918 Medical Gas Line Verification Report Date: September 23, 2020 Job Number: 2675 Contractor: Ritter Plumbing and Mechanical Date(s) and Time(s) of Testing: September 23, 2020-1200hrs Facility: Bridge Animal Referral Center 8401 Main St Edmonds, WA 98026 Scope of Work: Installation of five new medical oxygen outlets. Our firm certifies that the verifiers) named in the report are properly trained and certified to perform the activities required. All test and measurement equipment is properly calibrated and maintained. As a representative of Medical Gas Services, LLC the verifier(s) named in this report have conducted testing and verification of Medical Gas piping systems and related equipment to certify the following on the above date. General Findings: A. Medical Gases are in compliance with NFPA 99(2012ed): Level 3, Dental "NOT FOR ANESTHESIA" B. No crossed lines were found in the medical oxygen in the tested areas on the day of testing. C. Medical oxygen meets minimum concentrations. D. Medical oxygen is below normal pressure. E. Purge Gas: Lot#W2458221GC01 (Airgas) F. City of Edmonds: Permit # BLD2020-0537 G. Attachments: Worksheet Note: Existing Equipment and Systems NFPA 99(2012ed) #53.1.4 - An existing Level 3 system that is not in strict compliance with the provisions of this standard shall be permitted to be continued in use as long as the authority havingjurisdiction has determined that such use does not constitute a distinct hazard to life. 2675-9.23.20-VR Pg.1 of 2 (Mtdical Gas Services 8 S Horton St. Suite 917 Seattle. WA 98134 medgasservices.io (425) 894 5918 II. Medical Gases A. Oxygen: 1. Static line pressure: psig. 2. Oxygen concentration at outlet: >99.0% 3. Dynamic outlet free flow at outlet: >3.5 scfm Ill. Particulate Line Test: PASS IV. Odor: PASS V. Outlet: A. Outlet Style: DISS X. Brazier: Chris Fitzgerald A. Brazier Number: FITZGCM988PZ B. Plumbing Contractor: Ritter Plumbing and Mechanical XI. Witness: Mark Westbrook - Ritter Plumbing and Mechanical XII. Comments: A. Oxygen pressure was low on the day of testing. XIII. Recommendations: A. Set oxygen delivery pressure between 50-55psi per nfpa 99. Tested By: David Pomeranz - ASSE 6030 Verifier . )A9taa4j2- 2675-9.23.20-VR Pg. 2 of 2 CMtdical Gas Services 8 S Horton St, Suite 917 Seattle. WA 98134 medgasservices.io (425) 894 5918 Medical Gas Outlet / Inlets Evaluation Worksheet Facility: Bainbridge Animal Referral Center Job #: 2675 I Date: 9.23.20 Area Tested: Care Facility I Verifier: DP Outlets & Inlets - ® New p Existinq •utlet / Inlets Quick Connect: 1M. MOM 2675-9.2.20 Page 1 of 1