Loading...
Engineers Field ReportFOSSATTI PAWLAK l� STRUCTURAL ENGINEERS ® MEMORANDUM DATE: April 30, 2019 FIRM: City of Edmonds ❑ MEETING RECORD ATTENTION: Building Inspector PHONE NO: 425-771-0220 EMAIL: milton.thompson@edmondswa.gov eric.carter@edmondswa.gov RE: 907 Dayton St — Kitchen Floor Joist Framing ❑ PHONE LOG -CALL ❑ SITE VISIT RE: 907 Dayton St — Kitchen Floor Joist Framing FROM: Ty Bartley, P.E. PHONE NO: 206-456-3071 EMAIL: TBartlev@Fossatti.com Fossatti Pawlak conducted a site visit at your request to 907 Dayton St, Edmonds, WA on Sunday April 28, 2019. The purpose of the site visit was to investigate the I" floor framing at the kitchen. The kitchen floor is constructed of 2x10 floor joists at 16" on center, spanning approximately 15'-0". A 4x12 beam was placed approximately 1'-0" off the midspan point of the joists. The 412 bears at the south retaining wall and the intermediate retaining wall, and cantilevers approximately 7'-0" past the intermediate retaining. The 4x while not necessary, was most likely placed during initial construction as a header for the opening in the storage space and run long to pick up the floor joists supporting the kitchen island. Observation of the 4x shows that only the joist at the tip of the cantilever is bearing on the 4x, and all other joists on the cantilever portion of the 4x have a gap between the joists and the top of the beam. Fossatti Pawlak observed that all floor framing of the house was 2x10 joists at 16"oc, spanning approximately 15'-0" in the east to west direction. The 2x10 joists are supported by bearing walls or beams depending on the location in the house. The house is constructed as a series of three offset 15'- 0" wide boxes with the framing repeating throughout. The 2x10 joists are adequate to carry the existing dead load of 15psf and live load of 40psf. If you have any questions, please call. FOSSATTI PAWLAK STRUCTURAL ENGINEERS WAS P11 cur) ■�� Dn�G 23024 Ffc��RA L Ty Bartley, P.E., Associate `SIGNAL E� 4/30/2019 1735 Westlake Ave N I Suite 2051 Seattle WA 98109 1 P I 206.456.3071 1 F 1 206.456.3076 1 W I www.fossatti.com FOSSATTI PAWLAK STRUCTURAL ENGINEERS 11 Kitchen Floor Framing Cantilevered Beam —Joist Not Bearing End of Cantilevered Beam -Joist Bearing 1735 Westlake Ave N I Suite 2051 Seattle WA 981091 P 1206.456.30711 F 1206.456.30761 W I www.fossatti.com