FIR2020-0102+Fire_Sprinkler_Equipment_Specification_Sheets+11.24.2020_12.59.54_PMJa 0
Rel ble
Specifically Listed for use in
Multipurpose Systems that
serve both domestic water
and fire protection.
Sprinkler Type
Residential Flat Concealed Sprinkler listed for
a minimum design density of .05 gpm/ft2 with
"potable water".
• Model RFC30 LL
• Model RFC43 LL
• Model RFC49 LL
Features
1. National Sanitation Foundation (NSF) Cer-
tified to NSF/ANSI Standard 61 Annex G
(Less than 0.25% Lead content).
2. Very low water flow requirements.
3. Cover plate attachment (Plain or Perforated)
with 1/2" (13mm) total adjustment
4. Thread-on/off or Push-on/off cover attach-
ment option.
5. Smooth Aesthetic ceiling profile.
6. Available in white, brass, chrome and black
plated or custom painted finishes.
Patent Pending
Listing & Approvals
1. Listed by Underwriters Laboratories, and certified by
UL for Canada (cULus)
2. NSF Cerified to NSF/ANSI Standard 61 Annex G
Product Description
Model RFC30 LL, RFC43 LL and RFC49 LL Concealed
Residential Sprinklers are fast response residential fusible
solder link automatic sprinklers. Residential sprinklers dif-
fer from standard sprinklers primarily in their response time
and water distribution patterns. Model RFC30 LL, RFC43
LL and RFC49 LL sprinklers discharge water in a hemi-
spherical pattern below the sprinkler deflector. Residen-
tial distribution patterns are higher and generally contain
Bulletin 032 Rev. C
Model RFC30 LL (SIN RA3211)
Model RFC43 LL (SIN RA3212)
Model RFC49 LL (SIN RA3216)
Residential Flat Concealed
Sprinklers
Plain Cover Plate
Perforated Cover Plate
a finer droplet size than standard sprinkler patterns. The
combination of speed of operation and high discharge pat-
tern required for residential sprinklers has demonstrated,
in fire testing, an ability for controlling residential fires, and
thereby providing significant evacuation time for occu-
pants. The RFC30 LL, RFC43 LL and RFC49 LL Sprinklers
provide the best form of fire protection by combining an at-
tractive appearance and (13mm) of cover adjustment
for ease of installation. The small diameter cover plate is
easily and positively attached and blends into the ceiling,
concealing the most dependable fire protection available,
an automatic sprinkler system. The RFC30 LL, RFC43 LL
and RFC49 LL are UL Listed and NSF Certified Residen-
tial Sprinklers to be installed in the residential "potable"
water applications of any occupancy in accordance with
NFPA 13, 13R, & 13D and meets all applicable low lead
standards, .25% or less. The cover plate adjustability of
the RFC30 LL, RFC43 LL and RFC49 LL can reduce the
need for precise cutting of drop nipples. The threaded
cover plate assembly can be adjusted without tools to fit
accurately against the ceiling. The fire protection system
need not be shut down to adjust or remove the cover plate
assembly.
CJ
0
W
N
0
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application and Installation
For use in fire sprinkler systems that also supply potable water to a
plumbing fixture or fixtures.
The RFC30 LL, RFC43 LL and RFC49 LL, for residential installa-
tions, use a 165°F (74°C) fusible solder link in a tuning fork style sprin-
kler frame with a drop -down deflector. This assembly is recessed
into the ceiling and concealed by a flat cover plate. The cover plate
is attached to the skirt, using 135°F (57°C) ordinary temperature clas-
sification solder. When the ceiling temperature rises, the solder hold-
ing the cover plate releases the cover allowing the deflector to drop
into position and exposing the sprinkler inside to ceiling temperature.
The subsequent operation of the solder link opens the waterway and
causes the deflector to drop into position to distribute the discharging
water in a hemispherical pattern below the sprinkler deflector. Any
adjustment of thread engagement between the cover plate and cup
will assure that the drop -down deflector is properly located below the
ceiling. The residential distribution pattern contains a finer droplet
size than a standard sprinkler, and the pattern produces significantly
higher well wetting. After a 21/8" inch diameter hole is cut in the ceiling,
the sprinkler is to be installed with the Model FC Wrench.
Installation Data:
When installing a sprinkler, the wrench is first positioned into the
sprinkler/cup assembly and around the hexagonal body of the sprin-
kler frame. The wrench must bottom out against the cup in order to
ensure proper, safe installation. The sprinkler is then tightened into
the pipe fitting. When inserting or removing the wrench from the
sprinkler/cup assembly, care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PARTOF THE
SPRINKLER/CUP ASSEMBLY. MODEL RFC30 LL, RFC43 LLAND
RFC49 LL CONCEALED SPRINKLERS MUST BE INSTALLED
ONLY WITH 135OF RATED COVERS.
Note: A leak tight'/2' NPT (R1/2) sprinkler joint can be obtained
with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers
over maximum recommended torque. It may cause leakage or im-
pairment of the sprinklers.
Cover assemblies provide up to'b" (13mm) of adjustment. Turn
the cover clockwise until the flange is in contact with the ceiling. For
the push-on/thread-off option, the cover assembly is pushed onto the
cup and final adjustment is made by turning the cover clockwise un-
til the skirt flange makes full contact with the ceiling. Cover removal
Model (SIN)
Thread Size
Inch (mm)
Nominal
Orifice
Inch (mm)
Sprinkler
Temp ating
CCP Assembly
Temp. Rating
Max.
Ambient Tem •
K
Factor
Max.
Pressure
psi (bar)
rF
PC
/F
rc
/F
PC
RFC 30 LL (RA3211)
1/2" (15)
21/64 (8,2)
165
74
135
57
100
38
3.0 (43.2)
175 (12)
RFC 43 LL (RA3212)
1/2" (15)
3/E (10)
165
74
135
57
100
38
4.3(62)
175 (12)
RFC 49 LL (RA3216)
1/2" (15)
'/s (11)
165
74
135
57
100
38
4.9 (70.6)
175 (12)
Note: 1 bar = 100 Kpa
RFC 30 LL
Max. Coverage
Ordinary Temp. Rating
Top of Deflector
Minimum
area
Max. Spacing
165wF/74!'C
to Ceiling
Installation
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
(mm)
Type
Ft (m)
GPM Vmin
PSI(bar)Inch
Concealed
12 x 12 (3,6 x 3,6)
12(3,6)
9(34,1)
9.0 (0,62)
Smooth Ceilings'/2 to 1 (13 to 25.4)
Beamed Ceilings per NFPA 13D, 13R or
8(2,4)
14 x 14 (4,3 x 4,3)
14(4,3)
10 (37,8)
11.0 (0,76)
13 installed in beams'/2 to 1 (13 to 25.4)
For Ceiling types refer to NFPA 13, 13R or 13D
RFC 43 LL
Max. Coverage
Ordinary Temp. Rating
Top of Deflector
Minimum
area
Max. Spacing
165r""' 4r'C
to Ceiling
Installation
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
(mm)
Type
Ft (m)
GPM Vmin
PSI(bar)Inch
12 x 12 (3,6 x 3,6)
12(3,6)
12(4,5)
7.8 (0,54)
Smooth Ceilings'/2 to 1 (13 to 25.4)
14 x 14 (4,3 x 4,3)
14(4,3)
13 (49)
9.1 (0,63)
16 x 16 (4,9 x 4,9)
16(4,9)
13 (49)
9.1 (0,63)
Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams'/2 to 1 (13 to 25.4)
Concealed
8(2,4)
18 x 18 (5,5 x 5,5)
18(5,5)
18 (68)
17.5 (1,21)
20 x 20 (6,1 x 6,1)
20(6,1)
21 (79)
23.8 (1,64)
For Ceiling types refer to NFPA 13, 13R or 13D
RFC 49 LL
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
165�'F/74r'C
Top of Deflector
to Ceiling
(mm)
Installation
Type
Minimum
Spacing
Ft (m)
Flow
GPM Vmin
Pressure
PSI(bar)Inch
12 x 12 (3,6 x 3,6)
12(3,6)
13 (49)
7.0 (0,48)
Smooth Ceilings'/2 to 1 (13 to 25.4)
Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams'/2 to 1 (13 to 25.4)
Concealed
8(2,4)
14 x 14 (4,3 x 4,3)
14(4,3)
13 (49)
7.0 (0,48)
16 x 16 (4,9 x 4,9)
16(4,9)
13 (49)
7.0 (0,48)
18 x 18 5,5 x 5,5
18(5,5)
17 64,3
12.0 0,83
20x20(6,1 x6,1)
20(6,1)
20(75,73)
16.7(1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
2.
requires turning in the counter -clockwise direction. In ceilings that
have a plenum space above the sprinkler, the plenum space
may have neutral or negative pressurization but must not be
positively pressurized. Inspect all sprinklers after installation to
ensure that the gap between the cover plate and ceiling and the
4 slots in the cup are all open and free from any air flow impedi-
ment
Maintenance
Model RFC3O LL, RFC43 LL and RFC49 LL Concealed
Sprinklers should be inspected quarterly and the sprin-
kler system maintained in accordance with NFPA25. Do
not clean sprinklers with soap and water, ammonia or any
other cleaning fluids. Remove dust by using a soft brush
or gentle vacuuming. Remove any sprinkler cover plate as-
sembly which has been painted (other than factory applied)
or damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until
used to minimize the potential for damage to sprinklers that
would cause improper operation or non -operation.
Model RFC3O LL, RFC43 LL and RFC49 LL
Residential Concealed Sprinkler Specification
Sprinklers shall be clJLus Listed and NSF-61 Annex G
certified low flow residential concealed sprinklers with drop -
down deflector and adjustable flat cover plate engineered
for a minimum design density of O.O5gpm/ft2. Sprinkler
frame and deflector shall be of bronze frame construction
having a'h" NPT thread.
Thermal element shall consist of an approved black -
painted beryllium -nickel fusible solder link with symmetric
lever mechanism, maintaining a Teflon -coated Belleville
spring washer and machined brass cap water seal assem-
bly containing no plastic parts. Sprinkler K-factors shall be
a nominal 3.0 (43.2), 4.3 (62) and 4.9 (70.6), having a 3/8"
Specify:
1. Sprinkler Model
2. Cover Plate Finish
3. Thread -On or
Push -On Feature
1 '" x 112" REDUCING
TEE OR ELBOW
6655
2 6' [58.42mm] DIA -
CUP
CEILING
2" [12.70mm] MAX.
COVER ADJUSTMENT
CCP COVER PLATE
ASSEMBLY
[ . mm]
HOLE IN CEILING
2" [50.8mm] MAX.
FACE OF FITTING
TO FACE OF CEILING
DIMENSION
-' - [4.96mm]
3��"" [84.21mm] DIA.
PLATE: 112" I`72.7mm7 ADJUSTMENT
006F601A
and 7/16" orifice respectively. Temperature rating shall be
Ordinary 165°F (74°C); cover plate temperature rating to
be 135°F (57C). Cover plate assembly shall consist of a
brass cover plate and copper alloy retainer flange allow-
ing a'/2" cover plate adjustment. Any secure engagement
between the cover plate and the cup will assure that the
drop -down deflector is properly located below the ceiling.
A plastic protective cap shall be provided and factory in-
stalled inside the sprinkler cup to protect the drop -down
sprinkler deflector from damage, which could occur during
construction before the cover plate is installed. Standard
cover finish: [Chrome] [White] [Specialty — specify]. Resi-
dential concealed sprinklers shall be Reliable Model RFC30
LL, SIN RA3211 (Bulletin 032), RFC43 LL, SIN RA3212 (Bul-
letin 032) or Model RFC49 LL, SIN RA3216 (Bulletin 032).
Ordering Information Cover Plate Finishes0)
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi -gloss, unless specified
otherwise.
z> For the perforated style cover -
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
3.
Uponof
Uponor AquaPEX° White
Submittal Information
Revision C: Oct. 7, 2009
Project Information
Job Name:
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer's Representative: Approved Bv:
Technical Data
Material: Crosslinked polyethylene PEX-a Engel Method; PEX 5006
Standard Grade Hydrostatic 200°F (93°C) at 80 psi
Ratings (PPI): 180OF (82°C) at 100 psi
73.4°F (23°C) at 160 psi
1/2", 3/4", and 1" AquaPEX White only: 120OF (49°C) at 130 psi
Linear Expansion Rate: 1.10"/10°F (120C)/100'
Product Information and Application Use
Uponor AquaPEX White is tubing used for hot and cold domestic potable water distribution, residential
fire safety and radiant heating systems containing no ferrous corrodible components or where ferrous
components are isolated from the tubina.
✓ Description Part Number I.D. (A)
O.D. (B)
1/4" Uponor AquaPEX White, 100-ft. coil
F1040250
0.241"
0.375"
3/8" Uponor AquaPEX White, 400-ft. coil
F1090375
0.350"
0.500"
3/8" Uponor AquaPEX White, 1,000-ft. coil
F1120375
0.350"
0.500"
1/2" Uponor AquaPEX White, 100-ft. coil*
F1040500
0.475"
0.625"
1/2" Uponor AquaPEX White, 300-ft. coil*
F1060500
0.475"
0.625"
1/2" Uponor AquaPEX White, 1,000-ft. coil*
F1120500
0.475"
0.625"
5/8" Uponor AquaPEX White, 300-ft. coil
F1060625
0.574"
0.750"
5/8" Uponor AquaPEX White, 1000-ft. coil
F1120625
0.574"
0.750"
3/4" Uponor AquaPEX White, 100-ft. coil*
F1040750
0.671"
0.875"
3/4" Uponor AquaPEX White, 300-ft. coil*
F1060750
0.671"
0.875"
3/4" Uponor AquaPEX White, 500-ft. coil*
F1100750
0.671"
0.875"
1" Uponor AquaPEX White, 100-ft. coil*
F1041000
0.862"
1.125"
1" Uponor AquaPEX White, 300-ft. coil*
F1061000
0.862"
1.125"
1" Uponor AquaPEX White, 500-ft. coil*
F1101000
0.862"
1.125"
11/4" Uponor AquaPEX White, 100-ft. coil
F1061250
1.054"
1.375"
11/4" Uponor AquaPEX White, 300-ft. coil
F1021250
1.054"
1.375"
11/2" Uponor AquaPEX White, 100-ft. coil
F1061500
1.244"
1.625"
11/2" Uponor AquaPEX White, 300-ft. coil
F1021500
1.244"
1.625"
2" Uponor AquaPEX White, 100-ft. coil
F1062000
1.629"
2.125"
2" Uponor AquaPEX White, 200-ft. coil
F1052000
1.629"
2.125"
2" Uponor AquaPEX White, 300-ft. coil
F1022000
1.629"
2.125"
3" Uponor AquaPEX White, 100-ft. coil
F1063000
2.400"
3.125"
3" Uponor AquaPEX White, 350-ft. coil
F1023000
2.400"
3.125"
Installation
Weight
4.0 lbs.
20.0 lbs.
44.0 lbs.
6.0 lbs.
18.0 lbs.
54.0 lbs.
28.0 lbs.
86.0 lbs.
10.0 lbs.
34.0 lbs.
54.0 lbs.
20.0 lbs.
56.0 lbs.
93.0 lbs.
34.0 lbs.
106.0 lbs.
44.0 lbs.
133.0 lbs.
68.2 lbs.
136.4 lbs.
204.6 lbs.
128.0 lbs.
442.0 lbs.
Approved fittings are ProPEXs' fittings' for sizes W through 2" AquaPEX. Use WIPEXTM fittings for 3" AquaPEX. Refer to the AquaPEX
Professional Plumbing Installation Handbook, AquaSAFETM Fire Safety Installation Guide or the Uponor Radiant Installation Handbook for details.
Standards Codes Listings
CSA B137.5; ASTM F876; ASTM IPC; UPC; *1/2% 3/4", 1" UL 1821; *ULC/ORD - C 199 P; IAPMO; CSA; HUD; WARNOCK HERSEY; NSF;
F877; ASTM F1960; ASTM-E84; NSPC; NPC ITS; UL; ICC; ANSI/NSF 14- and 61-certified; CAN/ULC S102.2; U.S.: 3/4" diameter and
ASTM-E119/UL 263 of Canada smaller; Canada: 1" diameter and smaller
Related Applications
PEX-a Plumbing Systems
AquaSAFE Fire Safety Systems
Contact Information
Uponor, Inc.
5925 148th Street West
Apple Valley, MN 55124 USA
Phone: (800) 321-4739
Fax: (952) 891-2008
www.uponor-usa.com
Uponor Ltd.
2000 Argentia Rd., Plaza 1, Ste. 200
Mississauga, ON L5N 1W1 CANADA
Phone: (888) 994-7726
Fax: (800) 638-9517
www.uponor.ca
IProPEX` is a registered trademark of Uponor, Inc. ProPEX"is a trademark of Uponor Ltd.
ProPEX° Ring
Submittal Information
Revision A: March 17, 2009
Project Information
Job Name:
Uponof
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer's Representative: Approved By:
Technical Data -
Material: PEX-a (Engel Method)
Density
926 to 940 kg/m3
Degree of Crosslinking: 70% to 89%
Product Information and Application Use
Manufactured from PEX-a material, Uponor ProPEX° Rings are required to
make a proper ProPEX connection.' Red print on the rings indicates hot
lines. The 1/2" and 3/4" ProPEX rings with stop includes a leading edge
chamfer and stop edge.
✓ Description
❑ ProPEX Ring, 3/8"
ProPEX Ring with Stop, 1/2" (red print)
ProPEX Ring with Stop, 1/2"
ProPEX Ring, 5/8"
ProPEX Ring with Stop, 3/4"
ProPEX Ring, 1"
ProPEX Ring, 11/4"
PProPEX Ring, 11/2"
ProPEX Ring, 2"
Installation
i
Part Number
Length
i.d.
o.d.
Weight
Q4690302
0.54"
0.49"
0.74"
0.005lbs.
Q4690511
0.63"
0.63"
0.87"
0.006lbs.
Q4690512
0.63"
0.63"
0.87"
0.006lbs.
Q4680625
0.79"
0.75"
1.00"
0.008lbs.
Q4690756
0.87"
0.88"
1.13"
0.012lbs.
Q4681000
1.10"
1.13"
1.42"
0.020lbs.
Q4681250
1.35"
1.38"
1.66"
0.030lbs.
Q4681500
1.61"
1.63"
1.91"
0.040lbs.
Q4682000
1.97"
2.14"
2.61"
0.133lbs.
Square cut the Uponor ProPEX tubing. Remove excess material. Slide the ProPEX Ring over the end of the tubing (maximum 1/1 ' over -hang).
When using the 1/2" ProPEX Ring with stop edge, slide the ring on (i.e., chamfered edge first) until the end of the tubing contacts the stop
edge. Expand tubing and ring. Rotate tool a quarter turn after each expansion to prevent the formation of grooves. Remove the expansion
tool and fully seat the tubing and ring against the shoulder of the fitting. You should make ProPEX connections at temperatures above
50F /-15°C. For more information, refer to the AquaPEX° Professional Plumbing Installation Handbook, AQUASAFE° Fire Safety Installation
Guide or the Uponor Radiant Installation Handbook.
Standards
ASTM F1960
Codes
IPC; UPC; NSPC; NPC of Canada
Listings
UL 1821 (1/2", 3/4" and 1"); ULC/ORD - C 199 P (1/2", 3/4" and 1"); HUD MR 1269; ICC ESR 1099; ANSI/NSF 14- and 61-certified
Related Applications Contact Information
PEX-a Plumbing Systems Uponor, Inc. Uponor Ltd.
Radiant Heating and Cooling Systems 5925 148th Street West 2000 Argentia Rd., Plaza 1, Ste. 200
AQUASAFE Fire Safety Systems Apple Valley, MN 55124 USA Mississauga, ON L5N 1Wl CANADA
Phone: (800) 321-4739 Phone: (888) 994-7726
Fax: (952) 891-2008 Fax: (800) 638-9517
www.uponor-usa.com www.uponor.ca
'ProPEX° is a registered trademark of Uponor, Inc. ProPEX is a trademark of Uponor Ltd.
ProPEX° Engineered
Submittal Information
Revision D: June 8, 2012
Project Information
Job Name:
Polymer (EP) Tee
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer's Reoresentative: ADoroved Bv:
Technical Data
Material: UDEL° Polysulfone, 20% Glass -reinforced (1/2" to 1")
Acudel° Modified Polyphenylsulfone (11/4" to 11/2")
Radel° Polyphenylsulfone (2")
Maximum Temperature
(no pressure): 320°F (160°C)
Maximum Working
Temperature/Pressure: 210OF (99°C) at 150 psi (1,034 kPa)
Product Information and Application Use
The ProPEX° Engineered Polymer (EP) Tee makes diverting connections for
Uponor crosslinked polyethylene (PEX-a) tubing for use in hot and cold
domestic potable water systems, residential fire sprinkler systems and
hydronic radiant heating and cooling systems. Each end of the tee is
manufactured with an Uponor ProPEX fitting for connections to Uponor
AquaPEX8 or Wirsbo hePEXTM tubing.'
Note: Branch size is listed last in the part descriptions.
uponof
Description
Part Number
A
B
Weight
❑ ProPEX EP Tee, MY' PEX x 1/2" PEX x 1/2" PEX
Q4755050
2.50"
1.53"
0.02 lbs.
❑ ProPEX EP Tee, 3/4" PEX x 3/4" PEX x 3/4" PEX
Q4757575
3.30"
1.94"
0.05 lbs.
❑ ProPEX EP Tee, 1" PEX x 1" PEX x 1" PEX
Q4751010
4.10"
2.47"
0.07 lbs.
❑ ProPEX EP Tee, 11/4" PEX x 11/4" PEX x 11/4" PEX
Q4751313
4.80"
3.22"
0.15 lbs.
❑ ProPEX EP Tee, 11/2" PEX x 11/2" PEX x 11/2" PEX
Q4751515
5.80"
3.82"
0.25 lbs.
❑ ProPEX EP Tee, 2" PEX x 2" PEX x 2" PEX
Q4752000
7.45"
4.79"
0.38 lbs.
Installation
Use the appropriate ProPEX Ring for PEX-a tubing. Refer to the Uponor AquaPEX° Professional Plumbing Installation Guide, AquaSAFET"
Residential Fire Sprinkler Installation Guide or Uponor Radiant Installation Handbook for additional information.
Standards
CAN/CSA B137.5; ASTM F877; ASTM F1960
Codes
IPC; UPC; NSPC; NPC of Canada
Listings
IAPMO 3558; ANSI/NSF 14- and 61-certified; HUD MR 1269; ICC ESR 1099; UL 1821; U1_C/0RD-C199P
Related Applications Contact Information
PEX-a Plumbing Systems Uponor, Inc. Uponor Ltd.
Hydronic Radiant Heating and Cooling Systems 5925 148th Street West 2000 Argentia Road, Plaza 1, Suite 200
Snow Melting Systems Apple Valley, MN 55124 USA Mississauga, ON L5N 1W1 CANADA
Turf Conditioning Systems Phone: (800) 321-4739 Phone: (888) 994-7726
Permafrost Prevention Systems Fax: (952) 891-2008 Fax: (800) 638-9517
AquaSAFE Fire Safety Systems www.uponorpro.com www.uponorpro.com
1ProPEX® is a registered trademark of Uponor, Inc. ProPEXTM is a trademark of Uponor Ltd.
ProPEX° Engineered Polymer (EP) Reducing Tee
Submittal Information
uponor
Revision E: June 8, 2012
Project Information
Job Name:
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer's Representative: Approved By:
Technical Data
Material: UDEL° Polysulfone, 20% Glass -reinforced (1/2 to 1")
Acudel° Modified Polyphenylsulfone (11/4" to 11/2") p�
Radel° R Polyphenylsulfone (2")
Maximum Temperature (no pressure): 320°F (160°C)
Max. Working Temperature/Pressure: 210OF (99°C) at 150 psi (1,034 kPa)
Product Information and Application Use
The ProPEX° Engineered Polymer (EP) Reducing Tee makes diverting connections for Uponor
crosslinked polyethylene (PEX-a) tubing for use in hot and cold domestic potable water
systems, residential fire sprinkler systems and hydronic radiant heating and cooling systems.
Each end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor
AquaPEX° or Wirsbo hePEXTM tubing.' Note: Branch size is listed last in the part descriptions.
✓
Description
Part Number
Length (A)
Height (B)
Weight
❑
ProPEX EP Reducing Tee, 1/2" PEX x 1/2" PEX x 3/a" PEX
Q4755575
2.86"
1.76"
0.03 lbs.
❑
ProPEX EP Reducing Tee, 3/4" PEX x 1/2" PEX x 1/2" PEX
Q4757555
3.10"
1.70"
0.04 lbs.
❑
ProPEX EP Reducing Tee, 3/4" PEX x 1/2" PEX x 3/a" PEX
Q4757557
3.10"
1.94"
0.04 lbs.
❑
ProPEX EP Reducing Tee, 3/a" PEX x 3/4" PEX x 5/8" PEX
Q4757563
3.30"
1.85"
0.05 lbs.
❑
ProPEX EP Reducing Tee, 3/4" PEX x 3/a" PEX x 1/2" PEX
Q4757550
3.30"
1.70"
0.04 lbs.
❑
ProPEX EP Reducing Tee, 3/4" PEX x 3/a" PEX x 1" PEX
Q4757710
3.64"
2.32"
0.08 lbs.
❑
ProPEX EP Reducing Tee, 1" PEX x 3/4" PEX x 3/a" PEX
Q4751775
3.90"
2.24"
0.08 lbs.
❑
ProPEX EP Reducing Tee, 1" PEX x 3/4" PEX x 1" PEX
Q4751751
3.90"
2.47"
0.08 lbs.
❑
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x 1/2" PEX
Q4751150
4.10"
2.00"
0.08 lbs.
❑
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x 3/4" PEX
Q4751175
4.10"
2.24"
0.09 lbs.
❑
ProPEX EP Reducing Tee, 11/4 PEX x 1" PEX x 3/4" PEX
Q4751317
4.60"
2.73"
0.11 lbs.
❑
ProPEX EP Reducing Tee, 11/4" PEX x 1" PEX x 1" PEX
Q4751311
4.60"
2.97"
0.12 lbs.
❑
ProPEX EP Reducing Tee, 11/4 PEX x 11/4" PEX x 3/4" PEX
Q4751337
4.80"
2.73"
0.13 lbs.
❑
ProPEX EP Reducing Tee, 11/4 PEX x 11/4" PEX x 1" PEX
Q4751331
4.80"
2.97"
0.14 lbs.
❑
ProPEX EP Reducing Tee, 11/2 PEX x 1" PEX x 3/4" PEX
Q4751517
5.25"
3.06"
0.17 lbs.
❑
ProPEX EP Reducing Tee, 11/2 PEX x 1" PEX x 1" PEX
Q4751511
5.25"
3.30"
0.18 lbs.
❑
ProPEX EP Reducing Tee, 11/2 PEX x 11/a" PEX x 3/4" PEX
Q4751537
5.50"
2.65"
0.18 lbs.
❑
ProPEX EP Reducing Tee, 11/2 PEX x 11/4 PEX x 1" PEX
Q4751531
5.50"
2.85"
0.19 lbs.
❑
ProPEX EP Reducing Tee, 11/2 PEX x 11/4 PEX x 11/4" PEX
Q4751533
5.50"
3.15"
0.21 lbs.
❑
ProPEX EP Reducing Tee, 11/2 PEX x 11/2 PEX x 3/4" PEX
Q4751557
5.80"
3.06"
0.20 lbs.
❑
ProPEX EP Reducing Tee, 11/2 PEX x 11/2 PEX x 1" PEX
Q4751551
5.75"
3.30"
0.21 lbs.
❑
ProPEX EP Reducing Tee, 11/2 PEX x 11/2 PEX x 11/4" PEX
Q4751553
5.80"
3.56"
0.22 lbs.
❑
ProPEX EP Reducing Tee, 2" PEX x 11/2" PEX x 3/4" PEX
Q4752575
6.62"
3.30"
0.30 lbs.
❑
ProPEX EP Reducing Tee, 2" PEX x 11/2" PEX x 1" PEX
Q4752051
6.50"
3.40"
0.30 lbs.
❑
ProPEX EP Reducing Tee, 2" PEX x 11/2" PEX x 11/4" PEX
Q4752053
6.62"
3.80"
0.34 lbs.
❑
ProPEX EP Reducing Tee, 2" PEX x 11/2" PEX x 11/2" PEX
Q4752055
6.62"
4.10"
0.35 lbs.
❑
ProPEX EP Reducing Tee, 2" PEX x 2" PEX x 3/4" PEX
Q4752275
6.93"
3.30"
0.34 lbs.
❑
ProPEX EP Reducing Tee, 2" PEX x 2" PEX x 1" PEX
Q4752210
6.93"
3.40"
0.36 lbs.
❑
ProPEX EP Reducing Tee, 2" PEX x 2" PEX x 11/4" PEX
Q4752213
6.62"
3.80"
0.37 lbs.
❑
ProPEX EP Reducing Tee, 2" PEX x 2" PEX x 11/2" PEX
Q4752215
7.13"
4.10"
0.44 lbs.
Installation
Use the appropriate ProPEX Ring for PEX-a tubing. Refer to the Uponor AquaPEX° Professional Plumbing Installation Guide, AquaSAFETI
Residential Fire Sprinkler Installation Guide or Uponor Radiant Installation Handbook for additional information.
Standards Codes Listings
CAN/CSA B137.5; ASTM F877; IPC; UPC; NSPC; NPC of Canada NSF U.P. CODE; ANSI/NSF 14- and 61-certified; HUD MR 1269;
ASTM F1960
ICC ESR 1099;
UL 1821 and ULC/0RD-C199P (except Q4757563)
Related Applications
Contact Information
PEX-a Plumbing Systems
Uponor, Inc.
Uponor Ltd.
Hydronic Radiant Heating and Cooling Systems
5925 148th Street West
2000 Argentia Rd., Plaza 1, Ste. 200
Snow and Ice Melting Systems
Apple Valley, MN 55124 USA
Mississauga, ON L5N 1W1 CANADA
Turf Conditioning Systems
Phone: (800) 321-4739
Phone: (888) 994-7726
Permafrost Protection Systems
Fax: (952) 891-2008
Fax: (800) 638-9517
AquaSAFE Fire Safety Systems
www.uponorpro.com
www.uponorpro.com
1ProPEX° is a registered trademark of Uponor, Inc. ProPEXTM is a trademark of Uponor Ltd.
ProPEX° Engineered
Submittal Information
Revision D: June 8, 2012
Project Information
Job Name:
Polymer (EP) Elbow
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer's Representative: ADDroved Bv:
Technical Data
Material:
Maximum Temperature
(no pressure):
Maximum Working
Temperature/Pressure:
UDEL° Polysulfone, 20% Glass -reinforced (1/2 to 1")
Acudel° Modified Polyp henylsulfone (11/4" to 11/2")
Radel° R Polyp henylsulfone (2")
320°F(160°C)
210OF (99°C) at 150 psi (1,034 kPa)
Product Information and Application Use
The ProPEX® Engineered Polymer (EP) Elbow makes 90-degree connections for
Uponor crosslinked polyethylene (PEX-a) tubing for use in hot and cold domestic
potable water systems, residential fire safety and hydronic radiant heating and
cooling systems. Each end of the elbow is manufactured with an Uponor ProPEX
fitting for connections to Uponor AquaPEX° or Wirsbo hePEX'" tubing.'
uponof
Description
Part
A
B
Weight
Number
❑ ProPEX EP Elbow,'/2" PEX x'/2" PEX
Q4760500
1.30"
1.30"
0.02 lbs.
❑ ProPEX EP Elbow, 3/4" PEX x 3/4" PEX
Q4760750
1.60"
1.60"
0.03 lbs.
❑ ProPEX EP Elbow, 1" PEX x 1" PEX
Q4761000
2.10"
2.10"
0.07 lbs.
❑ ProPEX EP Elbow, 11/4" PEX x 11/4" PEX
Q4761250
2.45"
2.45"
0.11 lbs.
❑ ProPEX EP Elbow, 11/2" PEX x 11/2" PEX
Q4761500
2.77"
2.77"
0.18 lbs.
❑ ProPEX EP Elbow, 2" PEX x 2" PEX
Q4762000
3.76"
3.76"
0.30 lbs.
Installation
Use the appropriate ProPEX Ring for PEX-a tubing.
Refer to the Uponor AquaPEX° Professional
Plumbing Installation Guide, AquaSAFE'"
Residential Fire Sprinkler Installation Guide or Uponor Radiant Installation Handbook for additional
information.
Standards
CAN/CSA B137.5; ASTM F877; ASTM F1960
Codes
IPC; UPC; NSPC; NPC of Canada
Listings
IAPMO 3558; ANSI/NSF 14- and 61-certified; HUD MR 1269; ICC ESR 1099; UL 1821; ULC/0RD-C199P
Related Applications Contact Information
PEX-a Plumbing Systems Uponor, Inc. Uponor Ltd.
Hydronic Radiant Heating and Cooling Systems 5925 148th Street West 2000 Argentia Road, Plaza 1, Suite 200
Snow Melting Systems Apple Valley, MN 55124 USA Mississauga, ON L5N 1W1 CANADA
Turf Conditioning Systems Phone: (800) 321-4739 Phone: (888) 994-7726
Permafrost Prevention Systems Fax: (952) 891-2008 Fax: (800) 638-9517
AquaSAFE Fire Safety Systems www.uponorpro.com www.uponorpro.com
1ProPEV is a registered trademark of Uponor, Inc. ProPEXTM is a trademark of Uponor Ltd.
ProPEX° Fire Sprinkler Adapter
Submittal Information
Revision B: March 17, 2009
Project Information
Job Name:
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer's Representative: Approved By:
Technical Data
Material: 300 Series Stainless Steel
Product Information and Application Use
Use the ProPEX° Fire Sprinkler Adapter in conjunction with the
appropriate sprinkler to provide a multi -purpose residential fire
sprinkler system'. For residential applications, the system is
installed with the cold -potable portion of the Uponor plumbing
system. Make connections with Uponor ProPEX fittings. These
fittings are designed for use only with 3/4" or 1" AquaPEX°
White tubing in the Uponor AQUASAFE° Looped System.
uponof
✓ Description Part A B C D E Weight
Number
ProPEX Fire Sprinkler Adapter, 3/4" PEX x 1/2" FNPT Q7517550 0.75" 1.88" 2.50" 1.82" 1.41" 0.268 lbs.
ProPEX Fire Sprinkler Adapter, 1" PEX x 1/2" FNPT Q7511050 0.75" 1.88" 2.50" 2.06" 1.54" 0.408 lbs.
Installation
Use appropriate ProPEX Ring for connecting the tubing. Refer to the AquaPEX Installation Handbook or the Uponor AQUASAFE°
Installation Guide for additional information.
Standards
CAN/CSA B137.5; ASTM F877; ASTM F 1960
Codes
IPC; UPC; NSPC; IRC; IMC; NPC of Canada
Listings
ANSI/NSF 14- and 61-certified; U.P. Code; ICC ESR 1099; HUD MR 1269; UL 1821; ULC/ORD - C 199 P
Related Applications
PEX-a Plumbing Systems
AQUASAFE Fire Safety Systems
Contact Information
Uponor, Inc.
5925 1481h Street West
Apple Valley, MN 55124 USA
Phone: (800) 321-4739
Fax: (952) 891-2008
www.uponor-usa.com
Uponor Ltd.
2000 Argentia Rd., Plaza 1, Ste. 200
Mississauga, ON L5N 1W1 CANADA
Phone: (888) 994-7726
Fax: (800) 638-9517
www.uponor.ca
'ProPEX° is a registered trademark of Uponor, Inc. ProPEXTM is a trademark of Uponor Ltd.
The Design Criteria for Sloped & Sloped Beamed Ceilings in NFPA 13D
One and Two Family Dwellings & Manufactured Homes Has Changed.
In L U2 L L2
A�G
D
LISTED AREA OF COVERAGE
CORRESPONDS TO CEILING SLOP
L = THE MAXIMUM LISTED SPRINKLER
SPACING, LENGTH (10'-0'MAXIMUM)
("'MINIMUM .
L2 = ONE HALF THE MAXIMUM LISTED
SPRINKLER SPACING (5'4'MAXIMUR
(1'4'MINIMUM
W = THE MAXIMUM LISTED SPRINKLER
SPACING.VADTH (10'-0 .
A =0'4'MAXIMUM.
8 •RANGE:912 (9A1ee18M2 (50.21
C=8'-0"MINIMUM.
G
81,VL
A
mucoe
A Tentative Interim Amendment (TIA
No.1028R) to NFPA 13D for 2010 has been
issued by the NFPA Standards Council.
Testing supported by The Fire Protection
Research Foundation indicates that
residential sprinklers listed for applications
with smooth, flat ceilings can meet the stated
purpose in NFPA 13D standards when
installed on a sloped or sloped and beamed
ceiling.
Sloped and Sloped/Beamed Ceilings, under
certain conditions, can now be protected with
7 "'" °" residential sprinklers based upon a maximum
two (2) sprinkler demand that has the same
flow rate as the sprinklers smooth, flat ceiling
listing.
The TIA No.1028R revises NFPA 13D - 2010 edition sections 8.1.2, 8.1.3, A.8.1.2, and A.8.1.3.
Please read and adhere to these sections for the complete new design criteria.
A brief recap:
The sprinklers in the design area shall be all of the sprinklers in a compartment, up to a maximum of
two, which require the greatest demand for:
• Smooth, flat ceilings to a maximum 24 feet in height.
• Smooth, ceilings (with no beams) sloped up to 8/12 and a maximum ceiling
height of 24' above the floor.
• A ceiling with beams up to 14" deep sloped up to 8/12 and a maximum ceiling
height of 24' above the floor. Pendent sprinklers shall be installed under the beams and
the compartment cannot exceed 600 square feet.
• A ceiling with beams of any depth sloped up to 8/12 and a maximum ceiling
height of 24' above the floor. Sidewall or pendent sprinklers shall be installed in each pocket
formed by the beams and the compartment cannot exceed 600 square feet.
Ail Reliable residential sprinklers can be used for these applications bas4
pressure as listed for smooth and flat ceilings. {See Bulletins: 135, 006,
This TIA is for 13D applications only. Changes to 13R will be in the 2013 Edition. Our special 10' x 10'
spacing listings for sloped ceilings are still advantageous for 13R installations. (See Table 9, Bulletin
035).
For any questions, please contact Technical Services at 1-800-55-RASCO.
The Reliable Automatic Sprinkler Co., Inc. • Manufacturer & Distributor of Fire Protection Equipment
wwwreliablesprinklercom • 1.800.431.1588