Loading...
BLD2021-0581_Manufacturer_Specifications_and_Installation_Instructions_3.30.2021_3.53.06_PM_2118892Amw?wo s7Iit"dard® HEATING & AIR CONDITIONING Product Data Split System Cooling 4A7A3018H1000N 4A7A3024H1000N 4A7A3030H1000N 4A7A3036H1000N 4A7A3042E1000N 4A7A3043A1000N 4A7A3048E1000N 4A7A3049A1000N 4A7A3060D1000P August2017 12-1298-9J-EN "HingersollRand ,��ce�rca� �S�iaara! HEATING & AIR CONDITIONING Outline Drawing SERVICE PANE ELECTRICAL AND REI COMPONENT CLEAR, PER PREVAILING CO[ TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 1524 (5 FEET) ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT AND SHOULD BE AT LEAST 305 (12") FROM WALL AND ALL SURROUNDING SHRUBBERY ONTWO SIDES. r OTHERTWO SIDES UNRESTRICTED ELECTRICAL SERVICE - PANEL 22.2 (7/8) DIA. HOLE LOW VOLTAGE 28.6 (1-1/8) DIA. K.O. WITH 22.2 (7/8) DIA. HOLE IN CONTROL BOX BOTTOM FOR ELECTRICAL POWER SUPLY LIQUID LINE SERVICE VALVE, „E•' I.D. FEMALE BRAZE CONNECTION WITH 1/4" SAE FLARE PRESSURETAP FITTINGS G FIG. 1 K.O. FOR ALTERNATE ELECTRICAL ROUTING From Dwg. D152898 GAS LINE 1/4TURN BALL SERVICE VALVE, "D" I.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.A Model Base A B C D E F G H J K 4A7A3018H 2 730 724 651 3/4 3/8 127 57 194 38 457 (28-3/4) (28-1/2) (25-5/8) (5) (2-1/4) (7-5/8) (1-1/2) (18) 4A7A3024H 2 730 724 651 3/4 3/8 137 65 210 57 457 (28-3/4) (28-1/2) (25-5/8) (5-3/8) (2-5/8) (8-1/4) (2-1/4) (18) 4A7A3030H 2 730 724 651 3/4 3/8 137 65 210 57 457 (28-3/4) (28-1/2) (25-5/8) (5-3/8) (2-5/8) (8-1/4) (2-1/4) (18) 4A7A3036H 3 730 829 756 3/4 3/8 137 79 197 60 508 (28-3/4) (32-5/8) (29-3/4) (5-3/8) (3-1/8) (7-3/4) (2-3/8) (20) 4A7A3042E 3 730 829 756 7/8 3/8 152 98 219 86 508 (28-3/4) (32-5/8) (29-3/4) (6) (3-7/8) (8-5/8) (3-3/8) (20) 4A7A3043A 4.2 741 (29-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20) 4A7A3048E 3 933 829 756 7/8 3/8 152 98 219 86 508 (36-3/4) (32-5/8) (29-3/4) (6) (3-7/8) (8-5/8) (3-3/8) (20) 4A7A3049A 4.2 741 (29-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20) 4A7A3060D 4.4 943 (37-1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20) 2 12-1298-9J-EN �c icati, �S'7 iw HEATING & AIR CONDITIONING Product Specifications Model No. W 4A7A3018H1000N 4A7A3024H1000N 4A7A3030H1000N POWER CONNS. — V/PH/HZ (b) 208/230/1/60 208/230/1/60 208/230/1/60 MIN. BIRCH. CIR. AMPACITY 12 18 16 BR. CIR. PROT. RTG. — MAX. (AMPS) 20 30 25 COMPRESSOR DURATION@- SCROLL DURATION®- SCROLL DURATION®- SCROLL RL AMPS — LR AMPS 9 — 48 12.8 — 58.3 12.3 — 63 Outdoor Fan FL AMPS 0.64 0.64 0.9 Fan HP 1/8 1/8 1/8 Fan Dia (inches) 23.0 23.0 18.9 Coil SPINE FINTM SPINE FINTM SPINE FIN"" Refrigerant R-410A 5 LBS., 11 OZ 5 LBS., 9 OZ 4 LBS., 10 OZ LINE SIZE — IN. O.D. GAS (c) 3/4 3/4 3/4 LINE SIZE — IN. O.D. LIQ. (0 3/8 3/8 3/8 Charge Spec. Subcooling 10OF 10OF 10OF Dimensions H x W X D Crated (IN.) 34 x 30.1 x 33 34 x 30.1 x 33 30 x 27 x 30 Weight — Shipping (lbs.) 167 169 157 Weight — Net (lbs.) 140 142 137 Optional Accessories: Anti -short Cycle Timer TAYASCT501A TAYASCT501A TAYASCT501A Evaporator Defrost Control AY28XO79 AY28XO79 AY28XO79 Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101 Extreme Condition Mount Kit BAYECMT023 BAYECMT023 BAYECMT023 Start Kit BAYKSKT263 BAYKSKT263 BAYKSKT263 Crankcase Heater Kit BAYCCHT302 BAYCCHT302 BAYCCHT302 Seacoast Kit BAYSEAC001 BAYSEAC001 BAYSEAC001 Low Ambient Kit BAYLOAM103 BAYLOAM103 BAYLOAM103 Refrigerant Lineset (d) TAYREFLN950 TAYREFLN950 TAYREFLN7* Service Valve Panel Cover W Certified in accordance with the Unitary Air -conditioner equipment certification program which is based on AHRI standard 210/240. (b) Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses. M Standard line lengths — 60', Standard lift — 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0* (* denotes latest revision).. (d) * = 15, 20, 25, 30, 40 and 50 foot lineset available. 12-1298-9J-E N 71* eao S-lavda rd® HEATING & AIR CONDITIONING Product Specifications Model No.0) 4A7A3036H1000N 4A7A3042E1000N 4A7A3043A1000N POWER CONNS. — V/PH/HZ (b) 208/230/1/60 208/230/1/60 208/230/1/60 MIN. BRCH. CIR. AMPACITY 18 22 22 BR. CIR. PROT. RTG. — MAX. (AMPS) 30 35 35 COMPRESSOR DURATION®- SCROLL DURATION®- SCROLL DURATION®- SCROLL RL AMPS — LR AMPS 14.1— 75 17.0 — 124 16.7 — 109 Outdoor Fan FL AMPS 0.7 0.7 1.05 Fan HP 1/8 1/8 1/5 Fan Dia (inches) 23.0 23 27.5 Coil SPINE FINTIA SPINE FINTN SPINE FINTIM Refrigerant R-410A 4 LBS., 13 OZ 5 LBS., 8 OZ 6 LBS., 7 OZ LINE SIZE — IN. O.D. GAS (c) 3/4 7/8 7/8 LINE SIZE — IN. O.D. LIQ. (c) 3/8 3/8 3/8 Charge Spec. Subcooling 10OF 10OF 12°F Dimensions H x W X D Crated (IN.) 34 x 30.1 x 33 34 x 30.1 x 33 34.4 x 35.1 x 38.7 Weight — Shipping (lbs.) 175 200 216 Weight — Net (lbs.) 147 172 184 Optional Accessories: Anti -short Cycle Timer TAYASCT501A TAYASCT501A TAYASCT501A Evaporator Defrost Control AY28XO79 AY28XO79 AY28XO79 Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101 Extreme Condition Mount Kit BAYECMT023 BAYECMT004 BAYECMT004 Start Kit BAYKSKT263 BAYKSKT263 BAYKSKT263 Crankcase Heater Kit BAYCCHT302 BAYCCHT301 BAYCCHT301 Seacoast Kit BAYSEAC001 BAYSEAC001 BAYSEAC001 Low Ambient Kit BAYLOAM103 BAYLOAM103 BAYLOAM103 Refrigerant Lineset (d) TAYREFLN7* TAYREFLN7* TAYREFLN3* Service Valve Panel Cover AAYSVPANL0032AA AAYSVPANL0032AA AAYSVPANL3343AA W Certified in accordance with the Unitary Air -conditioner equipment certification program which is based on AHRI standard 210/240. (b) Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses. (c) Standard line lengths — 60', Standard lift — 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0* (* denotes latest revision).. (d) * = 15, 20, 25, 30, 40 and 50 foot lineset available. 12-1298-9J-EN 74*w? o �Sif r idard HEATING & AIR CONDITIONING Product Specifications Model No. (a) 4A7A3048E1000N 4A7A3049A1000N 4A7A3060D1000P POWER CONNS. - V/PH/HZ (b) 208/230/1/60 208/230/1/60 208/230/1/60 MIN. BRCH. CIR. AMPACITY 28 24 32 BR. CIR. PROT. RTG. - MAX. (AMPS) 45 40 50 COMPRESSOR DURATION@- SCROLL DURATION- SCROLL DURATION- SCROLL RL AMPS - LR AMPS 21.8 - 117 18-5 - 124 26.8 - 134 Outdoor Fan FL AMPS 0.93 1.05 1.05 Fan HP 1/5 1/5 1/5 Fan Dia (inches) 23 27.5 27.5 Coil SPINE FINTM SPINE FIN- SPINE FINT`" Refrigerant R-410A 6 LBS., 7 OZ 6 LBS., 9 OZ 8 LBS., 0 OZ LINE SIZE - IN. O.D. GAS (c) 7/8 7/8 7/8 LINE SIZE - IN. O.D. LIQ. (c) 3/8 3/8 3/8 Charge Spec. Subcooling 10OF 10°F 10OF Dimensions H x W X D Crated (IN.) 42 x 30.1 x 33 34.4 x 35.1 x 38.7 42.4 x 35.1 x 38.7 Weight - Shipping (lbs.) 233 212 261 Weight - Net (lbs.) 197 189 226 Optional Accessories: Anti -short Cycle Timer TAYASCT501A TAYASCT501A TAYASCT501A Evaporator Defrost Control AY28XO79 AY28XO79 AY28XO79 Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101 Extreme Condition Mount Kit BAYECMT004 BAYECMT004 BAYECMT004 Start Kit BAYKSKT263 BAYKSKT263 BAYKSKT263 Crankcase Heater Kit BAYCCHT301 BAYCCHT301 BAYCCHT301 Seacoast Kit BAYSEAC001 BAYSEAC001 BAYSEAC001 Low Ambient Kit BAYLOAM103 BAYLOAM103 BAYLOAM103 Refrigerant Lineset (d) TAYREFLN3* TAYREFLN3* TAYREFLN3* Service Valve Panel Cover AAYSVPANL0044AA AAYSVPANL0044AA AAYSVPANL0044AA (a) Certified in accordance with the Unitary Air -conditioner equipment certification program which is based on AHRI standard 210/240. (b) Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses. (c) Standard line lengths - 60', Standard lift - 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0* (* denotes latest revision).. (d) * = 15, 20, 25, 30, 40 and 50 foot lineset available. Sound Power Level MODEL A -Weighted Sound Power Level [dB(A)] Full Octave Sound Power(dB) 63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 4A7A3018H1 72 73.7 71.4 65.4 68 67.3 62.9 56 50.3 4A7A3024H1 74 47.9 60.5 64.1 71.2 71.2 69.0 58.2 51.5 4A7A3030H1 72 69.9 69.6 69.1 68.6 68.7 60.9 56.2 48.9 4A7A3036H1 68 74.7 65.0 65.2 66.4 63.6 58.7 56.3 52.8 4A7A3042E1 72 77.6 68.3 67.4 65.6 67.4 58.2 54.1 47.6 4A7A3043A1 72 77.6 68.3 67.4 65.6 67.4 58.2 54.1 47.6 4A7A3048E1 74 72.5 72.3 69.2 67.5 72.3 60.2 55.2 54.2 4A7A3049A1 74 72.5 72.3 69.2 67.5 72.3 60.2 55.2 54.2 4A7A3060D1 80 47.3 55.7 69 72.7 75.8 69.4 62.2 53.3 Note: Rated in accordance with *For Reference Only AHRI Standard 270-2008 12-1298-9J-EN �c icati, �S'7 iw HEATING & AIR CONDITIONING Accessory Description and Usage Anti -Short Cycle Timer — Solid state timing device that prevents compressor recycling until five (5) minutes have elapsed after satisfying call or power interruptions. Use in area with questionable power delivery, commercial applications, long lineset, etc. Evaporation Defrost Control — SPST Temperature actuated switch that cycles the condenser off as indoor coil reaches freeze-up conditions. Used for low ambient cooling to 30°F with TXV. Rubber Isolators — Five (5) large rubber donuts to isolate condensing unit from transmitting energy into mounting frame or pad. Use on any application where sound transmission needs to be minimized. Hard Start Kit — Start capacitor and relay to assist compressor motor startup. Use in areas with marginal power supply, on long linesets, low ambient conditions, etc. Extreme Condition Mount Kit — Bracket kits to securely mount condensing unit to a frame or pad without removing any panels. Use in areas with high winds, or on commercial roof tops, etc. AHRI Standard Capacity Rating Conditions AHRI Standard 210/240 Rating Conditions 1. Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. 2. High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. 3. Low Temperature Heating 17°F DB air entering indoor coil. 4. Rated indoor airflow for heating is the same as for cooling. AHRI Standard 270 Rating Conditions — (Noise rating numbers are determiend with the unit in cooling operations.) Standard Noise Rating number is at 95°F outdoor air. Model Nomenclature Outdoor Units 1 2 3 4 4 A 6 V Refrigerant Type 2 = R-22 4 = R-410A A,T = American Standard Product Type 6, W = Split Heat Pump 7, T = Split Cooling Product Family V = Variable Speed M or B = Basic Z = Leadership —Two Stage A = Light Commercial X = Leadership L = Side Discharge R = ReplacemenURetail Family SEER — 3=13 6=16 4=14 8=18 5=15 9=19 0=20 Split System Connections 1-6 Tons 0 = Brazed Nominal Capacity in 1000s of BTUs Major Design Modifications Power Supply 1 = 200-230/1/60 or 208-230/1/60 3 = 200-230/3/60 4 = 460/3/60 Secondary Function Minor Design Modifications Unit Parts Identifier s6 0 7 8 9 10 1112 13 14 15 3 6 A 1 0 0 0 A A 12-1298-9J-EN ,��Ice�rca� �S�iaara! HEATING & AIR CONDITIONING Schematic Diagrams Figure 1. 1.5 — 4.0 Ton Models TO POWER SUPPLY PER UNIT NAMEPLATE AND LOCAL CODES I I i I --------- 1 CF FAN CAPACITOR — — — — — SEE PRODUCT DATA CN WIRE CONNECTOR r--FOR OPTIONAL START — —— CPR COMPRESSOR KIT ACCESSORY � , m CR RUN CAPACITOR m CS I r CS STARTING CAPACITOR CSR-I CSR i 0O -------RD-------------1 BR-a�-�\,o-l----BK/BL------ MS-2 CSR CAPACITOR SWITCHING RELAY I � I 5 I ODT OUTDOOR THERMOSTAT R------------- - -J BK/BL HPCO HIGH PRESSURE CUTOUT SWITCH CAPACITOR LPCO LOW PRESSURE CUTOUT SWITCH OD BR t R MS COMPRESSOR MOTOR CONTACTOR PR 101 TNS TRANSFORMER MTR BK F C p CPR I IOL INTERNAL OVERLOAD PROTECTOR THERMALLY — — — — . m PROTECTED I INTERNALLY TYPICAL HPCOz LPCO J II AIR OIR HANDLER I TYPICALI ®WARNING THERMOSTAT I¢ HAZARDOUS VOLTAGE! I DISCONNECT ALL ELECTRICAL POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. d cY — Y i----1+--�Y NOTES 1&2 _ HEAT (OPT I � O' —� I W3 CONTROLS' DT- I X2 , I ODT-A (OPTIONAL) (31----I-� WI -- I I I I I I B —B I, TNS B L 24V I--RDO ____♦ I TO POWER SUPPLY fr I I PER LOCAL CODES ` ----T I_ Failure fo disconnect power before servicing can Cause severe personal injury or death. ®CAUTION USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. Failure to do so may cause damage to fhe equipment. I ,,-COLOR OF WIRE BK/BL '----COLOR OF MARKER OK BLACK RD RED OR ORANGE BL BLUE WH WHITE GR GREEN OR BROWN YL YELLOW PR PURPLE PK PINK NOTES: I. IF ODT-B IS NOT USED, ADD JUMPER BETWEEN W2 & W3 AT AIR HANDLER. IF USED, ODT-B MUST BE MOUNTED REMOTE OF CONTROL BOX IN AN APPROVED WEATHER PROOF ENCLOSURE. 2. IF ODT-A IS NOT USED. ADD JUMPER BETWEEN I WI & W2 AT AIR HANDLER. 3. LOW VOLTAGE (24 V) FIELD WIRING MUST BE IS AWG MINIMUM. 4. USE COPPER CONDUCTORS ONLYI FOR CANADIAN INSTALLATIONS POUR INSTALLATIONS CANADIENNES - J ETENN SUITABLE FOR USE ON EDING 150V-TO-GROUND CONVIENT PAS AUX DE PLUS DE 150 V A PRINTED FROM D157047P03 REVA 12-1298-9J-EN Amwe " S7iwdid, HEATING & AIR CONDITIONING Schematic Diagrams Figure 2. 5.0 Ton Models TO POWER SUPPLY PER UNIT NAMEPLATE AND LOCAL CODES CIF FAN CAPACITOR CN WIAECONNECTOR CPR COMPRESSOR i I i CR RUN CAPACITOR CS STARTING CAPACITOR CSR F CAPACITOR SNITCHING RELAY INDOOR FAX RELAY START KIT HPCO HIGH PRESSURE CUTOUT SNITCH BAYKSKT263 m LPCO LOW PRESSURE CUTOUT SWITCH J c.7 m I CS z MS- CSR- CSR _ RD____________� BRo-L___BK/BL------ MSFp.I , I N2 B IOL SM HIS INTERNAL OVERLOAD PROTECTOR SYSTEM ON -OFF SWITCH COMPRESSOR MOTOR CONTACTOR Q� OFT OUTDOOR ANTICIPATOR 1 R BK/BL OFT OUTDOOR FAN THERMOSTAT _ CR — OD ODS OUTDOOR TEMPERATURE SENSOR OLC I PR B ODT OUTDOOR THERMOSTAT MTRBK CF� 5 R R I1V I SC TDL SNITCH OVER VALVE SOLENOID DISCHARGE LINE THERMOSTAT — — — —CPR — — — —CPR THERMALLY P R R m — �— TX$ TRANSFORMER PROTECTED _ INTERNALLY ,,—CO OR OF WIRE BK/BL _ _ _ I T P ---COLOR OF MARKER Y ICAL TYPICAL HPCO LPCO AIR HANDLER I THERMOSTAT I J J � O r O J Y— Yi -----� --� Lw I NOTES 1&2 __�_� HEAT (OPTIONAL I W3 CONTROLS ODT- —' X2 I-�O -BK - - -}- W2 I — — — — l i — — — W2 I , ODT-Ai (OPTIONAL)i Ci._— O-BK------- � I I � I I II II II I B BLS-----JTIISzev—� i— RD—O I TO POWER SUPPLY PER LOCAL CODES ----—w PRINTED FROM D157048POl UK BLACK RD RED OR ORANGE BL BLUE Will WHITE GR GREEN OR BROWN YL YELLOW PR PURPLE PK PINK ® WARNING HAZARDOUS VOLTAGEI DISCONNECT ALL ELECTRICAL POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to disconnect power be Tore servicing can cause severe personal injury or death. ®CAUTION USE COPPER CONDUCTORS ONLYI UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. Failure to do so may cause damage fo the equipment. I NOTES: I. IF ODT-B IS NOT USED. ADD JUMPER BETWEEN W2 & W3 AT AIR HANDLER. IF USED, ODT-B MUST BE MOUNTED REMOTE OF CONTROL BOX IN AN APPROVED WEATHER PROOF ENCLOSURE, 2. IF ODT-A IS NOT USED. ADD JUMPER BETWEEN MI & W2 AT AIR HANDLER. 3. LOW VOLTAGE 124 VI FIELD WIRING MUST BE 18 AWG MIN. FOR CANADIAN INSTALLATIONS POUR INSTALLATIONS CANADIENNES ETSENN SUITABLE FOR USE ON EDING ISOV-TO-GROUND 12-1298-9J-EN �c icati, �S'7 iw HEATING & AIR CONDITIONING Mechanical Specification Options General The Outdoor Units are fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. Casing Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather -resistant powder paint finish. The corner panels are prepainted. All panels are subjected to our 1,000 hour salt spray test . Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and low and high pressure switches. A factory supplied, field installed liquid line drier is standard. 12-1298-9J-E N 71* eaM S-lavdard® HEATING & AIR CONDITIONING Mechanical Specification Options Compressor The compressor features internal over temperature and pressure protection. Other features include: Centrifugal oil pump and low vibration and noise. Condenser Coil The aluminum plate fin, copper tube outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected with a corrosion resistant mesh coil guard. Low Ambient Cooling As manufactured, this system has a cooling capacity to 55°F. The addition of an evaporator defrost control permits operation to 40°F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30°F. The addition of the BAYLOAM107A low ambient kit permits ambient cooling to 20°F. Thermostats —Cooling only and heat/cooling (manual and automatic change over). Sub -base to match thermostat and locking thermostat cover. 10 12-1298-9J-EN Notes 12-1298-9J-E N 4j:Pingersoll Rand® Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands — including Club CarT), Ingersoll RandID, Thermo Kings and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results. m. oG'Pingersoll Rand T THERMO KING � =WE' ingersollrand.com c0%_us Intertek The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products, go to www.ahridirectory.org. Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. 12-1298-9J-EN 31 Aug 2017 Supersedes 12-1298-9H-EN (May 2017) ©2016 Ingersoll Rand