APPROVED BLD PLN BLD2021-0037+Mechanical_Plan+1.8.2021_2.16.32_PM+19813171.1 ALL DUCT DIMENSIONS ON PLAN ARE CLEAR INSIDE DIMENSIONS, ADD 2" TO EACH
DIMENSION TO OBTAIN OUTSIDE DIMENSION. ADD 4" TO EACH DIMENSION IF THE
DUCTWORK IS ON THE INTERIOR OF THE BUILDING.
1.2 THE FIRST NUMBER ON ALL DUCT DIMENSIONS IS THE WIDTH AND THE SECOND IS
THE HEIGHT.
1.3 MATERIALS WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME SPREAD RATING LESS
THAN 25 AND A FLAME SMOKE DEVELOPMENT LESS THEN 50, PER IMC 602.2.1.
1.4 SEAL ALL TRANSVERSE JOINTS FOR DUCTWORK WITH STATIC PRESSURE BETWEEN
1/2 INCHES AND 2 INCHES. DUCTWORK WHICH IS DESIGNED TO OPERATE AT
PRESSURES ABOVE 1/2 WATER COLUMN SHALL BE SEALED IN ACCORDANCE WITH
STANDARD RS-7.
1.5 ALL DUCT GAUGES PER SMACNA, IMC 603-4.
1.6 ALL DUCT SUPPORTS PER SMACNA, IMC 603-10.
1.7 ATTACH DIFFUSERS AND GRILLES TO T-BAR PER WA STATE & LOCAL CODES.
1.8 BALANCING DAMPERS ARE TO BE INSTALLED ON ALL BRANCH DUCTS OR DIFFUSERS.
GENERAL NOTES
DUCTWORK
2.1 INSULATE OR LINE DUCTWORK PER WA. STATE ENERGY AND MECHANICAL CODES.
2.2 INSULATE REFRIGERANT & CONDENSATE PIPING PER STATE & LOCAL ENERGYCODES.
INSULATION
3.1 GENERAL CONTRACTOR TO PROVIDE AND CUT OPENINGS FOR ALL ROOFTOP, CEILING,FLOOR, AND WALL PENETRATIONS, INCLUDING WEATHERPROOF SEALING AND FIRE PROOFLININGS PER IMC & IBC.
3.2 GENERAL CONTRACTOR TO VERIFY PENETRATION LOCATION AND DIMENSIONS WITH ERLBEFORE FRAMING OPENINGS.
3.3 GENERAL CONTRACTOR TO PROVIDE ALL DEMOLITION, PATCHING, AND PAINTING ASREQUIRED FOR MECHANICAL WORK.
3.4 GENERAL CONTRACTOR TO PROVIDE ADEQUATE STRUCTURAL SUPPORT AS REQUIRED FORMECHANICAL WORK.
3.5 GENERAL CONTRACTOR TO PROVIDE SERVICE ACCESS PER CODE TO ALL MECHANICALEQUIPMENT.
3.6 GENERAL CONTRACTOR TO LEVEL ALL FACTORY CURBS PROVIDED BY ERL PROVIDE ALLCANT STRIPS AND CURB INSULATION, AND SEAL AGAINST LEAKS.
3.7 GENERAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING OR T-BAR CEILING ASREQUIRED FOR HVAC INSTALLATION.
3.8 GENERAL CONTRACTOR TO PROTECT ALL OPENINGS THROUGH FLOORS PROVIDED FORDUCTWORK INSTALLATION IN ACCORDANCE WITH TABLE 601 OF INTERNATIONAL BUILDINGCODE, WHERE REQUIRED BY SECTION 707 OF IBC.
GENERAL CONTRACTOR
4.1 ERL TO INSTALL ALL LOW VOLTAGE CONTROL WIRING, CONDUIT WILL BE PROVIDEDBY ELECTRICAL CONTRACTOR.
4.2 ELECTRICAL CONTRACTOR TO PROVIDE ALL ELECTRICAL CONNECTIONS,DISCONNECTS, AND STARTERS FOR MECHANICAL EQUIPMENT.
4.3 ELECTRICAL CONTRACTOR TO VERIFY EQUIPMENT SIZES, LOADS AND LOCATIONS,WITH ERL MECHANICAL PLAN AND WITH FIELD LOCATIONS.
4.4 ELECTRICAL CONTRACTOR TO INTERLOCK BATHROOM EXHAUST FANS WITH LIGHTSWITCH.
4.5 ERL TO PROVIDE 7-DAY NIGHT SETBACK, PROGRAMMABLE TYPE T-STAT WITHCAPABILITY OF 5°F DEADBAND.
4.6 ERL TO VERIFY FINAL LOCATION OF THERMOSTAT WITH CUSTOMER.
4.7 ELECTRICAL CONTRACTOR TO PROVIDE ELECTRICAL GCFI OUTLET WITHIN 25 FT OFEACH PIECE OF MECHANICAL EQUIPMENT.
ELECTRICAL
5.1 PLUMBING CONTRACTOR OFFSETS VENTS 10 FEET MINIMUM FROM ALL HVAC FRESH AIRINTAKES OR 3' ABOVE HIGHEST POINT OF INTAKE, IMC 401.4.1
5.2 CONDENSATE DRAINS FROM RTU BY ERL TO DRAIN WITHIN 12" OF UNIT. CONDENSATE DRAINSFOR AIR HANDLERS BY PLUMBER.
PLUMBING
6.1 THE SUPPLY HEATING AND COOLING ENERGY TO EACH ZONE SHALL BE CONTROLLED BYINDIVIDUAL THERMOSTATIC CONTROLS CAPABLE OF RESPONDING TO TEMPERATURE WITHINTHE ZONE. AT MINIMUM, EACH FLOOR SHALL BE CONSIDERED A ZONE.
6.2 OUTDOOR AIR SUPPLY, EXHAUST OPENINGS AND RELIEF OUTLETS SHALL BE PROVIDED WITHCLASS 1A MOTORIZED DAMPERS WHICH CLOSE AUTOMATICALLY WHEN THE SYSTEM IS OFFPER WSEC SECTION C403.2.4.3.
ENERGY CODE COMPLIANCE
7.1 WHERE REQUIRED PROVIDE AUTOMATIC SHUTOFF ACTIVATED BY SMOKE DETECTORS INEACH SYSTEM DELIVERING HEATING OR COOLING AIR IN EXCESS OF 2000 CFM. DETECTORSSHALL BE LOCATED IN THE MAIN RETURN AIR PER IMC 606.
MECHANICAL CODE COMPLIANCE
WA2015
M
T
SD
S
10"x20"
10"Ø
SYMBOL LEGEND
NOTE: NOT ALL SYMBOLS SHOWN ON THIS LEGEND MAY
PERTAIN TO THIS PROJECT.
RECTANGULAR DUCT
ROUND DUCT
FLEXIBLE DUCT
SUPPLY DUCT SECTION
RETURN DUCT SECTION
FIRE SMOKE DAMPER
(120V POWER REQ.)
EXHAUST DUCT SECTION
SUPPLY DIFFUSER
RETURN/EXHAUST GRILLE
SIDEWALL DIFFUSER
INLINE FAN
MANUAL VOLUME DAMPER
ZONE DAMPER
MOTORIZED DAMPER
CEILING MOUNTED
EXHAUST FAN
FIRE DAMPER
THERMOSTAT
SMOKE DETECTOR
SENSOR
RTU
1
CD-1
250 CFM
EQUIPMENT TAG
DIFFUSER/GRILLE TAG
UNDER CUT DOOR
COMMISSIONING PLAN
ALL COMMISSIONING OF HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS ASREQUIRED BY SECTION C408 "SYSTEM COMMISSIONING" OF THE 2015 WASHINGTON STATE
ENERGY CODE (WSEC) SHALL BE PERFORMED BY EVERGREEN REFRIGERATION, LLC. THEACTIVITIES TO BE ACCOMPLISHED ARE PER THE SECTIONS LISTED IN THE"COMMISSIONING COMPLIANCE CHECKLIST" SHOWN BELOW. AT THE COMPLETION OF THEACTIVITIES REQUIRED FOR COMMISSIONING AS DEFINED BY SECTION C408 OF WSEC THE"COMMISSIONING COMPLIANCE CHECKLIST" WILL BE REVIEWED WITH THE BUILDINGOWNER OR THE OWNER'S REPRESENTATIVE AND THIS CERTIFICATION WILL BE SIGNEDAND DATED. THIS WILL SATISFY TO THE CODE OFFICIAL THAT THE REPORT HAS BEENACCEPTED AS REQUIRED BY SECTION C408.1.3 OF WSEC.
Commissioning Plan was used during construction and included items below
·A narrative description of activities and the personnel intended to accomplish each one
·Measurable criteria for performance
·Functions to be tested
Systems Balancing has been completed
·Air and Hydronic systems are proportionately balanced in a manner to first minimize throttling losses
·Test ports are provided on each pump for measuring pressure across the pump
PROJECT
INFORMATION
COMMISSIONING
PLAN
(SECTION C408.1.2)
SYSTEMS
BALANCING
(SECTION C408.2.2)
FUNCTIONAL
TESTING
(SECTION C408.2.3)
SUPPORTING
DOCUMENTS
(SECTION C103.6)
COMMISSIONING
REPORT
(SECTION C408.1.4.1)
CERTIFICATION
HVAC Equipment Functional Testing has been completed (Section C408.2.3.1)
HVAC equipment has been tested to demonstrate the installation and operation of components, systems
and system-by-system interfacing relationships in accordance with approved plans and specifications
COMMISSIONING COMPLIANCE CHECKLIST
Project Name:
Project Address:
Commissioning Authority:
HVAC Controls Functional Testing has been completed (Section C408.2.3.2)
HVAC controls have been tested to ensure that control devices are calibrated, adjusted and operate
properly.
sequences of operations have been functionally tested to ensure they operate in accordance with
approved plans and specifications
Economizers Functional Testing has been completed (Section C408.2.3.3)
economizers operate in accordance with manufacturer's specifications
Manuals, record documents and training have been completed or are scheduled
·System documentation has been provided to the owner or scheduled date:
·Record documents have been submitted to owner or scheduled date:
·Training has been completed or scheduled date:
Preliminary Commissioning Report submitted to Owner and includes items below
·deficiencies found during testing required by this section which have not been corrected at the time
of report preparation
·deferred tests, which cannot be performed at the time of report preparation due to climatic
conditions.
I hereby certify that all requirements for Commissioning have been completed in accordance with the
Washington State Energy Code, including all the items above.
Building Owner or Owner's Representative Date
1 VICINITY MAP
NOT TO SCALE
DUCT INSULATION TABLE
DUCT THICKNESS WSEC REQUIRED INSULATION
R-VALUES
WSEC 2015
SECTION
SYSTEMEXPOSED SUPPLY - INSIDE BUILDING ENVELOPE NONE NONE C403.2.8.2
SQ/RECT SUPPLY - INSIDE BUILDING ENVELOPE 1.0"R-3.3 C403.2.8.2
ROUND SUPPLY/FRESH AIR - INSIDE BUILDING ENVELOPE 1.5"R-3.3 C403.2.8.2
OUTSIDE AIR - INSIDE BUILDING ENVELOPE 2.0"R-7.0 C403.2.8.1 ex 1
SUPPLY/RETURN - OUTSIDE BUILDING ENVELOPE 2.0"R-8.0 C403.2.8.2
RETURN - INSIDE BUILDING ENVELOPE NONE NONE C403.2.8.2 ex 2
ERV - SUPPLY NONE REQUIRED
ERV - EXHAUST - OUTSIDE BUILDING ENVELOPE 2.0"R-8.0 C403.2.8.2
RELIEF NONE REQUIRED
EXHAUST NONE REQUIRED
AIR TERMINAL UNIT SCHEDULE
ITEM MARK MANF.MODEL MATERIAL FINISH SIZE NOTES
CEILING DIFFUSER CD-1 PRICE SMCD STEEL WHITE SEE SCHEDULE BORDER TYPE 36 = T-BAR
BORDER TYPE 6 = HARD LID
CEILING GRILLE CG-1 PRICE 80 ALUMINUM WHITE NECK SIZE SQ.BORDER TYPE F = T-BAR
BORDER TYPE F = HARD LID
NOTES:
ADD MECHANICAL VOLUME DAMPER TO EACH SUPPLY DIFFUSER BRANCH.
ADD MECHANICAL VOLUME DAMPER TO EACH EXHAUST INTAKE GRILLE BRANCH.
SUPPLY DIFFUSER SIZE
SIZE RANGE
6" X 6"0 - 100 CFM
8" X 8"101 - 250 CFM
10" X 10"251 - 425 CFM
12" X 12"426 - 650 CFM
GAS HEAT / ELECTRIC COOL PACKAGED EQUIPMENT SCHEDULE
MARK MANF.MODEL TONS
AIRFLOW SP MOTOR DRIVE
STYLE
COOLING HEATING ELECTRICAL
WEIGHT FILTER SIZES
NOTESTOTAL
SEER EER
INPUT OUTPUT AFUE VOLTS
PHASE
M.C.A.
(CFM)(in. W.G.)(hp)(BTU/h)(BTU/h)(BTU/h)(%)(V)(A)(lb)No. (LxWxD)
RTU-1 TRANE YSC036G3EMB 3 1,200 0.5 0.75 DD 36,970 14.0 12.0 100,000 81,000 81 208 3 19.9 747 2 (20x35x2)1,2,3,4
NOTES:
1. THE ROOFTOP UNIT COMES COMPLETE WITH AN ECONOMIZER
2. CONDENSATE BY PLUMBING CONTRACTOR.
3. WIRING BY ELECTRICAL CONTRACTOR.
4. CONNECT TO EXISTING DUCT DROPS
SPLIT SYSTEM HEAT PUMP UNIT SCHEDULE
MARK MANF.MODEL TONS
AIRFLOW
COOLING HEATING ELECTRICAL
WEIGHT TYPE
NOTESTOTAL
SEER EER
TOTAL VOLTS
PHASE
M.C.A.
(CFM)(BTU/h)(BTU/h)HSPF (V)(A)(lb)
IU-1 MITSUBISHI MSZ-GL09NA .75 399 9,000 10,900 208 1 1 22 WALL MOUNTED 1,2,3
OU-1 MITSUBISHI MUZ-GL09NA .75 9,000 24.6 15.4 10,900 12.8 208 1 9 81 1,2
IU-2A MITSUBISHI MSZ-GL09NA .75 399 9,000 10,900 208 1 1 22 WALL MOUNTED 1,2,3
IU-2B MITSUBISHI MSZ-GL09NA .75 399 9,000 10,900 208 1 1 22 WALL MOUNTED 1,2,3
OU-2 MITSUBISHI MXZ-2C20NA2 1.5 20,000 20.0 12.7 25,000 10.0 208 1 17.2 126 1,2
IU-3 MITSUBISHI MSZ-GL12NA 1 406 12,000 14,400 208 1 1 22 WALL MOUNTED 1,2,3,4
OU-3 MITSUBISHI MUZ-GL12NA 1 12,000 23.1 13.0 14,400 12.5 208 1 1 22 1,2,3
IU-4 MITSUBISHI MSZ-GL09NA .75 399 9,000 10,900 208 1 1 22 WALL MOUNTED 1,2,3
OU-4 MITSUBISHI MUZ-GL09NA .75 9,000 24.6 15.4 10,900 12.8 208 1 9 81 1,2
IU-5 MITSUBISHI MSZ-GL18NA 1.5 646 18,000 21,600 1 28 WALL MOUNTED 1,2,3
OU-5 MITSUBISHI MUZ-GL18NA 1.5 18,000 20.5 13.4 21,600 11.2 208 1 14 121 1,2
IU-6 MITSUBISHI MSZ-GL09NA .75 399 9,000 10,900 208 1 1 22 WALL MOUNTED 1,2,3
OU-6 MITSUBISHI MUZ-GL09NA .75 9,000 24.6 15.4 10,900 12.8 208 1 9 81 1,2
IU-7 MITSUBISHI MSZ-GL12NA 1 406 12,000 14,400 208 1 1 22 WALL MOUNTED 1,2,3
OU-7 MITSUBISHI MUZ-GL12NA 1 12,000 23.1 13.0 14,400 12.5 208 1 1 22 1,2,3
IU-8A MITSUBISHI MSZ-GL09NA .75 399 9,000 10,900 208 1 1 22 WALL MOUNTED 1,2,3
IU-8B MITSUBISHI MSZ-GL09NA .75 399 9,000 10,900 208 1 1 22 WALL MOUNTED 1,2,3
OU-8 MITSUBISHI MXZ-2C20NA2 1.5 20,000 20.0 12.7 25,000 10.0 208 1 17.2 126 1,2
IU-9A MITSUBISHI MSZ-GL24NA 2 738 22,500 27,600 208 1 1 37 WALL MOUNTED 1,2,3
IU-9B MITSUBISHI MSZ-GL24NA 2 738 22,500 27,600 208 1 1 37 WALL MOUNTED 1,2,3
IU-9C MITSUBISHI MSZ-GL12NA 1 406 12,000 14,400 208 1 1 22 WALL MOUNTED 1,2,3
OU-9 MITSUBISHI MXZ-8C60NA 5 60,000 17.4 12.5 66,000 10.5 208 1 46 309 1,2
NOTES:
1. CONDENSATE PUMP BY ERL, CONDENSATE TO DRAIN TO APPROVED LOCATION BY PLUMBING CONTRACTOR.
2. WIRING BY ELECTRICAL CONTRACTOR.
3. ECONOMIZER NOT REQUIRED PER 2015 WSEC C403.3 EXCEPTION #1
4. WITH EXISTING CONDENSING UNIT
ENERGY RECOVERY VENTILATOR SCHEDULE
MARK MANF.MODEL CFM S.P.EFF. RATE VOLTS PHASE MCA NOTES
ERV-1 PANASONIC FV-04VE1 40 0.1 55%120 1Ø 0.15 1,2
ERV-2 PANASONIC FV-04VE1 40 0.1 55%120 1Ø 0.15 1,2
ERV-3 PANASONIC FV-04VE1 40 0.1 55%120 1Ø 0.15 1,2
ERV-4 PANASONIC FV-04VE1 40 0.1 55%120 1Ø 0.15 1,2
ERV-5 PANASONIC FV-04VE1 40 0.1 55%120 1Ø 0.15 1,2
ERV-6 PANASONIC FV-04VE1 40 0.1 55%120 1Ø 0.15 1,2
ERV-7 PANASONIC FV-04VE1 40 0.1 55%120 1Ø 0.15 1,2
ERV-8 RUSKIN EVT O11-02 300 0.5 72%208 1Ø 20.8 1,3
ERV-9 RUSKIN EVT O11-02 300 0.5 72%208 1Ø 20.8 1,3
NOTES:
1. SET TO RUN AT HIGH SPEED
2. SET TO RUN CONTINUOUSLY
3. MOUNT ON FACTORY SUPPLIED CURB
GOVERNING CODE INFORMATION
2015 INTERNATIONAL BUILDING CODE WITH STATEWIDE AMENDMENTS
2015 INTERNATIONAL MECHANICAL CODE WITH STATEWIDE AMENDMENTS
2015 INTERNATIONAL FIRE CODE WITH STATEWIDE AMENDMENTS
2015 INTERNATIONAL ENERGY CONSERVATION CODE/WASHINGTON STATE ENERGY CODE
2015 INTERNATIONAL EXISTING BUILDING CODE WITH STATEWIDE AMENDMENTS FOUND IN THE IBC
DWG BY:
CKD BY:
JOB NO.:
SHEET:
NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS,
DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE
PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE
DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE
PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN
REFRIGERATION LLC. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR
SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE
RESTRICTIONS.
PERMIT SET
DATE:
ISSUED FOR
DATE:
AS BUILT
DATE:
CONSTRUCTION 727 SOUTH KENYON STREETSEATTLE, WASHINGTON 98108PHONE: (206)-763-1744www.evergreenhvac.comEVERGRL954R2520292
12-22-20
----
----21500 72ND AVE WEDMONDS, WA 98026SUNRISE OF LYNWOODENGINEER'S STAMP HEREREV.DATEDESCRIPTION11/5/21PERMIT DRAWINGSM001
SUNRISE OF LYNWOOD
JV
MG/AFCOVER SHEETCOVER SHEET
1
AREA OF WORK
NOT TO SCALE
UP
UP
REF.REF.REF.REF.REF.REF.REF.REF.REF.
REF.
REF.
REF.
REF.
REF.
REF.REF.REF.REF.11
2 2
33
4 4
55
11
12
1.11.1
3.9 3.9
6 6
7
8
9
10
A
A
A.1
A.1
B
B C
C D
D D.9
D.9
E
E F
F
G
G
H J K L M N
STUDIO-01
U101
STUDIO-01
U103
STUDIO-01
U105
2 BEDROOM RESIDENT
UNIT
U108
STUDIO-01
U106
STUDIO-01
U104
STUDIO-01
U102
STUDIO-01
U100
STUDIO-01
U125
STUDIO-01
U123
STUDIO-01
U121
STUDIO-01
U115
STUDIO-01
U122
STUDIO-01
U120
STUDIO-01
U118
2 BEDROOM RESIDENT
UNIT
U116
STUDIO-01
U119
LIVING
113
STUDIO-01
U124
STUDIO-01
U107
LIVING
110
SOILED RM
E134
CLEAN UTIL
E135
SPA/ TOILET
E109
JANITOR
E125
STORAGE
E124
VESTIBULE
E144
LOBBY
150
CORRIDOR123CORRIDOR
122
CRAWL SPACE
E136A
LAUNDRY
E136
ELECTRICAL
E137
ELEC. AND TELE.
E147
ELEV. EQUIP.
E148
MECH
E149 OFFICE
E130
OFFICE
E131
CORRIDOR
E128 CORRIDORE129STORAGE
E146
STAIR
E143
STAIR
E141
STAIR
E142
BISTRO
151
CONCIERGE
152OFFICE
153
City Of Edmonds
Building Department
Work
Address
Owner
Approved Date
Building Official
Permit Number
MECHANIICAL
21 00 2ND AVE W
SUNRISE
RECEIVED
Jan 12 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BLD2021-0037
APPROVED BY PLANNING
Jan 21 2021
All Fire Rated assemblies shall be
maintained and inspected prior to
cover.
ALL WORK SUBJECT
TO FIELD
INSPECTION FOR
CODE COMPLIANCE
APPROVED
PLANS MUST BE
ON JOB SITE
1-28-2021
Eric Carter
UP REF.REF.REF.REF.REF.REF.REF.REF.
REF.
REF.
REF.REF.REF.REF.11
2 2
33
4 4
55
1.11.1
3.9 3.9
6 6
7
8
9
A A.1 B C D D.9 E F G H J K L M N
STUDIO-01
U103
STUDIO-01
U105
2 BEDROOM RESIDENT
UNIT
U108
STUDIO-01
U106
STUDIO-01
U104
STUDIO-01
U102
STUDIO-01
U125
STUDIO-01
U123
STUDIO-01
U121
STUDIO-01
U115
STUDIO-01
U122
STUDIO-01
U120
STUDIO-01
U118
2 BEDROOM RESIDENT
UNIT
U116
STUDIO-01
U119
LIVING
113
STUDIO-01
U124
STUDIO-01
U107
LIVING
110
SOILED RM
E134
CLEAN UTIL
E135
SPA/ TOILET
E109
JANITOR
E125
STORAGE
E124
VESTIBULE
E144
LOBBY
150
CORRIDOR123CORRIDOR
122
CRAWL SPACE
E136A
LAUNDRY
E136
ELECTRICAL
E137
ELEC. AND TELE.
E147
ELEV. EQUIP.
E148
MECH
E149 OFFICE
E130
OFFICE
E131
CORRIDOR
E128 CORRIDORE129STORAGE
E146
STAIR
E143
STAIR
E142
BISTRO
151
CONCIERGE
152OFFICE
153
1 1ST FLOOR HVAC PLAN
SCALE: 1/8"=1'
ERV
1
ERV
2
ERV
3
IU
1
IU
2A
IU
2B
4Ø UP TO SECOND FLOOR
3.5"x10" UP TO ROOF
DUCT TO RUN UP THROUGH WALL
DWG BY:
CKD BY:
JOB NO.:
SHEET:
NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS,
DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE
PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE
DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE
PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN
REFRIGERATION LLC. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR
SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE
RESTRICTIONS.
PERMIT SET
DATE:
ISSUED FOR
DATE:
AS BUILT
DATE:
CONSTRUCTION 727 SOUTH KENYON STREETSEATTLE, WASHINGTON 98108PHONE: (206)-763-1744www.evergreenhvac.comEVERGRL954R2520292
12-22-20
----
----21500 72ND AVE WEDMONDS, WA 98026SUNRISE OF LYNWOODENGINEER'S STAMP HEREREV.DATEDESCRIPTION11/5/21PERMIT DRAWINGSM201
SUNRISE OF LYNWOOD
JV
MG/AFFIRST FLOOR HVAC PLAN1ST FLOOR PLAN
1
1
RECEIVED
Jan 12 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
DN REF.REF.REF.REF.REF.REF.REF.REF.REF.
REF.
REF.REF.REF.
11
2 2
33
4 4
55
1.11.1
3.9 3.9
6 6
7
8
9
A A.1 B C D D.9 E F G H J K L M N
STUDIO-01
U202
STUDIO-01
U203
STUDIO-01
U204
STUDIO-01
U205
STUDIO-01
U206
1 BEDROOM RESIDENT
UNIT
U208
1 BEDROOM RESIDENT
UNIT
U209
KITCHEN STORAGE
E210A
STAFF
E210B
STUDIO-01
U215
1 BEDROOM RESIDENT
UNIT
U216
1 BEDROOM RESIDENT
UNIT
U217
STUDIO-01
U218
STUDIO-01
U219
STUDIO-01
U220
STUDIO-01
U221
STUDIO-01
U222
STUDIO-01
U223
STUDIO-01
U224
STUDIO-01
U225
CORRIDOR
E222
CORRIDOR
E223
CORRIDOR
E228 CORRIDOR229LAUNDRY
E224
TOILET
E225
TOILET
E226
OFFICE
227
LOUNGE
230KITCHEN
E236
DINING ROOM
235
STAFF
E234
STORAGE
E233
VESTIBULE
E237
STAIR
E242
STAIR
E243
STORAGE
E247
JANITOR
E248
MECH
E249
SHAFT
SH 2B
SHAFT
SH 2A
SHAFT
SH 2C
SHAFT
SH 2D
STUDIO-01
U207 1 2ND FLOOR HVAC PLAN
SCALE: 1/8"=1'
ERV
5
ERV
4
IU
3
IU
4
IU
5
OU
3
CD-1
100 CFM
CG-1
100 CFM
4Ø
4Ø
4Ø 4Ø
REBALANCE
TO 600 CFM EACH
6Ø
6Ø
3.5"x10" UP TO ERV-12
6Ø UP TO ROOF
DWG BY:
CKD BY:
JOB NO.:
SHEET:
NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS,
DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE
PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE
DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE
PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN
REFRIGERATION LLC. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR
SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE
RESTRICTIONS.
PERMIT SET
DATE:
ISSUED FOR
DATE:
AS BUILT
DATE:
CONSTRUCTION 727 SOUTH KENYON STREETSEATTLE, WASHINGTON 98108PHONE: (206)-763-1744www.evergreenhvac.comEVERGRL954R2520292
12-22-20
----
----21500 72ND AVE WEDMONDS, WA 98026SUNRISE OF LYNWOODENGINEER'S STAMP HEREREV.DATEDESCRIPTION11/5/21PERMIT DRAWINGSM202
SUNRISE OF LYNWOOD
JV
MG/AFSECOND FLOOR HVAC PLAN2ND FLOOR PLAN
WALL MOUNT
WALL CAP
WALL CAP
1
1
RECEIVED
Jan 12 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
REF.REF.REF.REF.REF.REF.REF.REF.REF.
REF.
REF.REF.REF.
REF.
11
2 2
33
4 4
55
1.11.1
3.9 3.9
6 6
7
8
9
A A.1 B C D D.9 E F G H J K L M N
STUDIO-01
U302
STUDIO-01
U303
STUDIO-01
U304
STUDIO-01
U305
STUDIO-01
U306
STUDIO-01
U307
1 BEDROOM RESIDENT
UNIT
U308
1 BEDROOM RESIDENT
UNIT
U309
STUDIO-01
U310
STUDIO-01
U315
1 BEDROOM RESIDENT
UNIT
U316
1 BEDROOM RESIDENT
UNIT
U317
STUDIO-01
U318
STUDIO-01
U319
STUDIO-01
U320
STUDIO-01
U321
STUDIO-01
U322
STUDIO-01
U323
STUDIO-01
U324
STUDIO-01
U325
CORRIDOR
E322
CORRIDOR
E323
LAUNDRY
E324
TOILET
E325
TOILET
E326
CORRIDOR
E327
CORRIDOR
328
OFFICE
E329
HAIR SALON
E330
LOUNGE
E331A
WET ACTIVITY
332
LIVING ROOM
333
STUDIO-02
U334
STUDIO-02
U335
STORAGE
E347
JANITOR
E348
MECH
E349
STAIR
E342
STAIR
E343SHAFT
SH 3B
SHAFT
SH 3C
SHAFT
SH 3D
SHAFT
SH 3A
NURSING
E331B
CD-1
300 CFM
1 3RD FLOOR HVAC PLAN
SCALE: 1/8"=1'
ERV
6
ERV
7
IU
6
IU
7 IU
8A
IU
10
IU
9A
IU
9C
IU
9B
CG-1
DUCT TO RUN ON ROOF
4Ø UP TO ROOF
4Ø UP TO ROOF
4Ø UP TO ROOF
CD-1
100 CFM
CG-1
100 CFM
DWG BY:
CKD BY:
JOB NO.:
SHEET:
NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS,
DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE
PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE
DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE
PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN
REFRIGERATION LLC. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR
SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE
RESTRICTIONS.
PERMIT SET
DATE:
ISSUED FOR
DATE:
AS BUILT
DATE:
CONSTRUCTION 727 SOUTH KENYON STREETSEATTLE, WASHINGTON 98108PHONE: (206)-763-1744www.evergreenhvac.comEVERGRL954R2520292
12-22-20
----
----21500 72ND AVE WEDMONDS, WA 98026SUNRISE OF LYNWOODENGINEER'S STAMP HEREREV.DATEDESCRIPTION11/5/21PERMIT DRAWINGSM203
SUNRISE OF LYNWOOD
JV
MG/AFTHIRD FLOOR HVAC PLAN3RD FLOOR PLAN
1
1
RECEIVED
Jan 12 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
11
2 2
33
4 4
55
1.11.1
3.9 3.9
6 6
7
8
9
A A.1 B C D D.9 E F G H J K L M N
1 ROOF HVAC PLAN
SCALE: 1/8"=1'
RTU
1
OU
7
OU
4
OU
1
OU
6
OU
2
OU
8
OU
9 OU
5
ERV
8
10x8 10x8
ATTACH NEW RTU
TO EXISTING DUCT DROPS
CAP ALL DUCT WORK
NOT SERVING DINING ROOM 235
NEW ROOFTOP DUCT
ERV
9
NEW ROOFTOP DUCT
8Ø 8Ø
10x8
10x8
DWG BY:
CKD BY:
JOB NO.:
SHEET:
NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS,
DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE
PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE
DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE
PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN
REFRIGERATION LLC. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR
SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE
RESTRICTIONS.
PERMIT SET
DATE:
ISSUED FOR
DATE:
AS BUILT
DATE:
CONSTRUCTION 727 SOUTH KENYON STREETSEATTLE, WASHINGTON 98108PHONE: (206)-763-1744www.evergreenhvac.comEVERGRL954R2520292
12-22-20
----
----21500 72ND AVE WEDMONDS, WA 98026SUNRISE OF LYNWOODENGINEER'S STAMP HEREREV.DATEDESCRIPTION11/5/21PERMIT DRAWINGSM204
SUNRISE OF LYNWOOD
JV
MG/AFROOF PLANROOF PLAN
1
1
RECEIVED
Jan 12 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
PANASONIC FV-04VE1 ERV
MATERIAL LIST (PER UNIT)
PANASONIC FV-04VE1 PER EQUIPMENT SCHEDULE1
SCALE: NONE
FV-04VE1
SEQUENCE OF OPERATIONS
- TIME CLOCK ENERGIZES
G GREEN
WHT
BLK
YEL
ORG
BLU
JUMPER SWITCH TERMINALS
INTERMATIC GM40AV-QW 120 V TIME CLOCK1
- DAMPERS OPEN AND UNIT TURNS ON
MOTORIZED DAMPER
TIME CLOCK
ACTUATOR-BELIMO LF120-US
120 VOLT
BY ERL
MOTORIZED DAMPER
ACTUATOR-BELIMO LF120-US
OUTSIDE AIR
EXHAUST AIR
H 120 VOLT N
- TIME CLOCK DE-ENERGIZES
- DAMPERS CLOSES AND UNIT TURNS OFFBELIMO LF120-US ACTUATOR2
ALL EQUIPMENT AND CONTROLS PROVIDED BY ERL
AND WIRED BY ELECTRICAL CONTRACTOR.
TIME CLOCK TO BE SET FOR OCCUPIED HOURS.
SCALE : NONE
PANASONIC ERV/ MOTORIZED DAMPER DETAIL
MOTORIZED DAMPER
TIME CLOCK
ACTUATOR-BELIMO LF120-US
120 VOLT
BY ERL
ALL EQUIPMENT AND CONTROLS PROVIDED BY ERL
AND WIRED BY ELECTRICAL CONTRACTOR.
TIME CLOCK TO BE SET FOR OCCUPIED HOURS.
MOTORIZED DAMPER
ACTUATOR-BELIMO LF120-USL
N
PANASONIC ERV
OUTSIDE AIR
EXHAUST AIR
H 120 VOLT N
MATERIAL LIST
PANASONIC FV-10VE1 ERV
INTERMATIC GM40AV-QW 120 V TIME CLOCK
BELIMO LF120-US ACTUATOR
1
1
2
G
1020
30
40
50
60
5060
70
80
90
100
5060
70
80
90
100
FILTER
RESET
BUTTON
EXHAUST
AIR
CFM
SUPPLY
AIR
CFM
MIN/H
CONTROL PANEL
FV-10VE1
SEQUENCE OF OPERATIONS
- TIME CLOCK ENERGIZES
- DAMPER OPENS AND UNIT TURNS ON
- TIME CLOCK DE-ENERGIZES
- DAMPER CLOSES AND UNIT TURNS OFF
SCALE : NONE
TIME CLOCK
120 VOLT
BY ERL
UNIT TRANSFORMER
RELAY
RUSKIN ERV
24V+ WIRING BY ERL
MATERIAL LIST
RUSKIN ERV
INTERMATIC GM40AV-QW 120 V TIME CLOCK
FUN RIBU1C RELAY
1
1
1
SEQUENCE OF OPERATIONS
-TIME CLOCK ENERGIZES
-DAMPERS OPEN AND UNIT TURNS ON
-TIME CLOCK DE-ENERGIZES
-DAMPERS CLOSE AND UNIT TURNS OFF
1
TERMINAL BLOCK
RUSKIN ERV WIRING DETAIL
NOTE:
ON/OFF SWITCH TIMER:
WIRE 24V+ FROM TRANSFORMER ONTO THE INPUT OF THE SWITCH AND
CONNECT THE OUTPUT OF THE SWITCH TO TERMINAL 1 ON THE
CONTROL BOARD. THE ERV CAN BE TURNED ON MANUALLY OR BE
SET TO TURN ON AT REGULAR SCHEDULE WHEN BUILDING IS
OCCUPIED
24V+ WIRING BY ERL
DWG BY:
CKD BY:
JOB NO.:
SHEET:
NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS,
DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE
PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE
DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE
PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN
REFRIGERATION LLC. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR
SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE
RESTRICTIONS.
PERMIT SET
DATE:
ISSUED FOR
DATE:
AS BUILT
DATE:
CONSTRUCTION 727 SOUTH KENYON STREETSEATTLE, WASHINGTON 98108PHONE: (206)-763-1744www.evergreenhvac.comEVERGRL954R2520292
12-22-20
----
----21500 72ND AVE WEDMONDS, WA 98026SUNRISE OF LYNWOODENGINEER'S STAMP HEREREV.DATEDESCRIPTION11/5/21PERMIT DRAWINGSM601
SUNRISE OF LYNWOOD
JV
MG/AFWIRING DIAGRAMWIRING DIAGRAMS
RECEIVED
Jan 12 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
DWG BY:
CKD BY:
JOB NO.:
SHEET:
NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS,
DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE
PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE
DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE
PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN
REFRIGERATION LLC. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR
SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE
RESTRICTIONS.
PERMIT SET
DATE:
ISSUED FOR
DATE:
AS BUILT
DATE:
CONSTRUCTION 727 SOUTH KENYON STREETSEATTLE, WASHINGTON 98108PHONE: (206)-763-1744www.evergreenhvac.comEVERGRL954R2520292
12-22-20
----
----21500 72ND AVE WEDMONDS, WA 98026SUNRISE OF LYNWOODENGINEER'S STAMP HEREREV.DATEDESCRIPTIONSUNRISE OF LYNWOOD
JV
MG/AF
WIRING DIAGRAMS
INC
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512(V)
(206) 285-0618(F)
bmccann@ctengineering.com
#20227
Structural Construction Documents For:
SUNRISE OF LYNNWOOD
RTU SUPPORT
AT
21500 72nd Ave W
Edmonds, WA 98026
Client: Evergreen Refrigeration & HVAC
727 S. Kenyon St.
Seattle, WA 98108
Design Criteria: IBC 2015
Wind: Wind Speed = 110 mph, Kzt = 1.00
Seismic: Sds = .9
Roof Snow Load = 25 psf
C T E N G I N E E R I N G
09/28/202012/23/2020
RTU TO BE
REMOVED AND
REPLACED WITH
NEW. NO CURB
ADAPTER.(E) 2X10 @24 " O.C.(E) PRIMARY BEAM LINESREFERENCE DETAIL A NEXT
SHEET FOR ANCHORAGE
REQUIREMENTS.
Sunrise of Lynnwood 12/23/2020
M701STRUCTURAL DETAILSRECEIVED
Jan 12 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT