Approved set of plans must be on site at the time of inspection.
Failure to provide the approved set may result in a re-inspection
fee. System drain(s) required at riser and must drain to the
exterior. If riser is above lowest grade, 2nd drain required and
signage at riser indicating location. Flow Through systems
require signage IAW NFPA 13D. Coverage required to the
following areas:
Clothes closets, linen closets and pantries exceeding 24 square
feet in area, with the smallest dimension greater the 3’ and having
wall and ceiling surfaces of gypsum board.
Bathrooms more than 55 square feet in area.
When fuel fired equipment is present on covered decks or
porches, at least one quick-response intermediate temperature
sprinkler shall be installed above the equipment.
All fuel fired appliances, except attics if above all living areas.