FIR2020-0112+Fire_Sprinkler_Plan+12.16.2020_8.24.36_AMRECEIVED Dec 16 2020 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT FIR2020-0112 Approved set of plans must be on site at the time of inspection. Failure to provide the approved set may result in a re-inspection fee. System drain(s) required at riser and must drain to the exterior. If riser is above lowest grade, 2nd drain required and signage at riser indicating location. Flow Through systems require signage IAW NFPA 13D. Coverage required to the following areas: Clothes closets, linen closets and pantries exceeding 24 square feet in area, with the smallest dimension greater the 3’ and having wall and ceiling surfaces of gypsum board. Bathrooms more than 55 square feet in area. When fuel fired equipment is present on covered decks or porches, at least one quick-response intermediate temperature sprinkler shall be installed above the equipment. All fuel fired appliances, except attics if above all living areas. Approved By Fire DFM17 PBrough 12\30\20