FIR2020-0107+Fire_Alarm_Voltage_Calculations+12.2.2020_11.48.29_AMFire Alarm System Secondary Battery-set Calculation Worksheet AES Product Standby Current (Amps) QTY Total Standby Current (Amps) Alarm/Transmit Current (Amps)QTY Total Alarm Current (Amps) 7707P-88-ULP-M 0.4000 X 1 =0.400 1.5500 X 1 =1.550 ## Hour Standby Time **** Standby Current (Amps) Required Standby Capacity (Amp-Hours) Required Alarm Time (Hours) Alarm/Transmit Current (Amps) Required Alarm Capacity (Amp-Hours) 24 X 0.400 =9.600 1 X 1.5500 =1.550 Required Standby Capacity (Amp-Hours) Required Alarm Capacity (Amp-Hours) Total Capacity (Amp-Hours) 9.60 +1.550 =11.150 1.5500.400 Total System Alarm Current (Amps) Total System Standyby Current (Amps) The battery requirements presented are not AES recommendations. For UL listed battery requirements please read the products Installation and Operation Manual.