Loading...
FIR2021-0005+Fire_Alarm_Equipment_Specification_Sheets+1.12.2021_1.24.03_PM+1985978SOUND CREDIT UNION FIRE ALARM SYSTEM INSTALL 202 5TH AVE. S. EDMONDS, WA 98020 SUBMITTALS NORTHWEST FIRE SYSTEMS 22645 83RD AVE. S. KENT, WA 98032 P: (206)772-7502 LICENSE # NORTHFS875MJ RECEIVED Jan 12 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT FIR2021-0005 GWF-7075 GWF-7075 Intelligent Fire Alarm Control Panel Analog and Networking Systems General The Gamewell-FCI®, GWF-7075 is an Addressable Fire Alarm Control Panel (FACP). The GWF-7075 has a signaling line circuit (SLC) loop that is used to connect the addressable detectors. The SLC loop is capable of supporting up to 75 detectors and 75 modules using the System Sensor® Velociti® Protocol, and it also offers the built-in support for the SWIFT™ wireless fire alarm devices. The GWF-7075 is equipped with two configurable Notification Appliance Circuits (NACs) that support a maximum output of 2.5A. This panel communicates with the built-in, dual-line digital and IP communicator including an optional cellular communication module. The GWF-7075 fire alarm control panel offers the following powerful features: The GWF-7075 panel supports a variety of devices, including the following accessories: FEATURES & BENEFITS • Built-in support for up to 75 detectors and 75 modules operating in Velociti® mode • Offers a four line LCD display with 40 characters per line • Available in a red or a black cabinet • GWF-7075 can be surface or flush mounted • Contains a built-in USB interface used for programming •Includes the programmable date setting for Daylight Saving Time • Uses a JumpStart Auto Programming® feature for easy programming • Reports events to the Central Station by point or by zone • System programmable from the front panel • Provides a built-in dual phone line, digital alarm communicator/ transmitter (DACT), IP or optional cellular technologies •Firmware can be upgraded in the field • Supports up to four SWIFT™ wireless gateways. Each gateway may include up to 49 wireless devices • Supports Class B (Style 4) and Class A (Style 6 or Style 7 configuration for SLC, and SBUS • Offers a built-in synchronization for some models, Note: To identify the compatible models, refer to the Compatibility Addendum to Gamewell- FCI Manuals, P/N:9000-0427-L8. • detector sensitivity • pre-trouble maintenance alert • day/night thresholds • calibration trouble alert •drift compensation • RA-1000 Remote Annunciator • 5880 - LED I/O Module • GFPS-6S Intelligent Remote Power Supply • 5824 Serial/Parallel Printer Interface Module (for printing system reports) 2 Optional Accessories RA-1000: Remote Annunciator The RA-1000 is a remote annunciator used to operate the GWF-7075 Fire Alarm Control Panel (FACP). It connects to the control panel via the RS-485 system bus. The RA-1000 is equipped with five status LEDs which indicate: GFPS-6S: Intelligent Remote Power Supply The GFPS-6S intelligent power supply delivers 6A of Notification Appliance Circuit (NAC) power and offers built-in synchronization for some appliances developed by the following manufacturers. The GFPS-6S provides its own AC power connection, battery charging circuit, and backup battery for use with the GWF-7075 FACP. The output circuits can be programmed as NACs or as auxiliary power (configurable for constant, resettable, or door holder power). 5824: Serial / Parallel Module The 5824 is equipped with one parallel and one RS- 232 serial port that allows the GWF-7075 to connect to virtually any standard PC-compatible printer to generate reports on site. 5880: LED I/O Module The 5880 provides 40 programmable LED outputs and eight supervised dry contact inputs. These devices offer an effective way to customize remote annunciation. The GWF-7075 supports up to eight 5880 modules to offer maximum flexibility. 5220: Direct Connect Module The 5220 is a direct connect module used to connect a fire alarm control panel (FACP) to a city box or polarity reversal communicator. COMPATIBLE DEVICES For a list of compatible devices, refer to the following documents: • Compatibility Addendum for Gamewell-FCI Manuals, P/N: 9000-0427-L8 • SWIFT™ Intelligent Wireless Detectors, P/N: 9021-60818 • SWIFT™ Intelligent Wireless Modules, P/N: 9021-60819 • SWIFT™ Wireless Gateway, P/N: 9021-60824 ORDERING INFORMATION GWF-7075: Intelligent Fire Alarm Control Panel. Red GWF-7075B: Intelligent Fire Alarm Control Panel, Black SBUS Accessories RA-1000: Remote Annunciator (Black) Dimensions: 7.4"H x 9.1"W x 1.5" (18.8 x 23.1 x 3.8) cm RA-1000R: Remote Annunciator (Red) GFPS-6S: Intelligent Remote Power Supply Dimensions: 16"H x 12.25"W 3"D (40.6 x 30.9 x 7.6) cm 5824: Serial / Parallel Module Dimensions: 6"H x 7.75"W x 1.44"D (15.0 x 19.4 x 3.6) cm 5880: LED I/O Module Dimensions: 7.75"H x 6"W x 1.94"D (19.4 x 15.0 x 4.8) cm 5220: Direct Connect Module Dimensions: 1.31"H x 6.5"W x 2.13"D (3.33 x 16.51 x 5.40)cm Miscellaneous Accessories HFSS: Software Suite. Provides programming, upload/ download and event reporting BB-17F: Remote Battery Box Cabinet. Holds up to two 18 Amp Hour batteries. Dimensions: 16" W x 10" H x 6" D (40.64 W x 25.40 H x 15.24 D) cm •Alarm •AC Power Loss • System Silenced • Trouble •Supervisory •System Sensor® •Faraday™ •Gentex® •AMSECO™ •Wheelock™ Note: Sync Feature Restriction: Not all devices can use the Sync Feature. To ensure that the selected device works with the Sync Feature, refer to the Compatibility Addendum to Gamewell-FCI Manuals, P/N: 9000-0427-L8. GWF-7075 Technical Specifications 9021-60966 | D | 01/20 ©2020 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Gamewell-FCI®, System Sensor® and Velociti® are registered trademarks and SWIFT ™ is a trademark of Honeywell International, Inc. AMSECO™ is a registered trademark of Kobishi America Inc. Asco® is a registered trademark of Asco Power Technologies Inc. Farraday™ is a trademark of Faraday LLC. Gentex® is a registered trademark of Gentex Corporation Inc. Microsoft, Windows®, and the Windows Logo® are registered trademarks or trademarks of Microsoft Corporation. UL® is a registered trademark of Underwriter’s Laboratories Inc. Wheelock™ is a trademark of Cooper-Wheelock Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s GWF-7075 and other products available by visiting www.Gamewell-FCI.com SYSTEMS PHYSICAL: Overall Dimensions: 15.12” H x 12.71" W x 3.33” D 38.40 H x 32.28 W x 8.46 D cm Weight: 25 lbs. Color: Red or Black Environmental Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity: 0 to 93% relative humidity (non-condensing) ELECTRICAL: GWF-7075 Primary AC: 120 VAC @ 60 Hz, 900mA Total Accessory Load: 2.5A @ 27.4 VDC Class A Power-Limited NAC Power: 1A per NAC, 2.5A Total Aux Power: 27.4 VDC Form C Trouble & Alarm Relay: 2.5A @ 27.4 VDC, Resistive Standby Current: 165 mA Alarm Current: 310 mA Battery Charging Capacity: 7 to 35 AH Battery Size: 7 A/H maximum allowed in the control panel cabinet. Larger capacity batteries can be housed in the BB-17F accessory cabinet. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The GWF-7075 is designed to comply with the following standard: UL Standard: UL 864 9th Edition NFPA STANDARDS NFPA 13 Sprinkler NFPA 15 Water Spray NFPA 16 Foam Water NFPA 70 NFPA 72 Central Station Remote Signaling Local Protective Signaling Systems Auxiliary Protected Premises Unit & Water Deluge Releasing Service AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S1869 CSFM: 7165-1703:0500 FDNY: COA-6255 OSHPD (CA) Approved Releasing Solenoids: Asco® T8210A107 24 VDC 3 A max. 0 Hz Asco® 8210G207 24 VDC 3 A max. 0 Hz ISO 9001 Certification aes-corp.com 7707 Fire Subscribers www.aes-corp.com Feature Highlights • Leverages state of the art technology • Applies advanced security protection • Offers flexible power and configuration options • Engineered for backward compatibility with legacy systems • Enables future ready capabilities • Provides instant subscriber status through front panel with Power and Trouble LEDs, a backlit LCD display, and Menu/Silence button • Includes robust Multiple Communication Technologies (MCT) feature • Emulates virtual keypad • Improves functionality with an adaptive Graphic User Interface (GUI) for programming via smartphones, tablets and PCs • Plus many more… Key Benefits • Built upon the solid foundation of AES-IntelliNet patented mesh radio technology for use in private licensed wireless networks • Protects subscriber units against unauthorized access and rogue activity with a password-protected Dealer Code • Makes programming and streamlined troubleshooting easy with user friendly interface • Adds integrated supervision of AES-IntelliPro full data module • Provides versatile power options: (1) Direct from the Fire Alarm Control Panel (FACP) without requiring an electrician onsite and without Subscriber backup battery; (2) Directly from the FACP with Subscriber backup battery; or (3) Traditional installation with plug in Class 2 low power transformer • Allows for enhancement upgrades and an expanded number of new features to be added easily with highly flexible and scalable alarm communications infrastructure • Rigorously tested to the highest industry standards and future ready to meet emerging NFPA code and UL standards A Newer, Smarter Alarm Communications Platform Enhanced Wireless Fire Alarm Monitoring Powered by AES enhanced mesh radio technology, IntelliNet 2.0 7707 Fire Subscribers are next generation universal wireless communicators that provide advanced security protection for any new or existing alarm monitoring network. The AES Model 7707 is ideal for commercial fire applications. With the AES-IntelliPro full data module option, they are the ideal drop-in replacement for Plain Old Telephone Service (POTS) lines. The red metal enclosure comes with a key lock and front panel LCD backlit display with intuitive view that provides an instant visual of the subscriber status. The user friendly GUI makes it easy to program AES subscriber units via a smartphone, laptop, tablet, or integrated Universal Serial Bus (USB)—without the need for special cables or having to use a handheld programmer. Additional knockouts make it easier to mount for faster installation. IntelliNet 2.0 Private Wireless Mesh Radio Network The IntelliNet 2.0 Fire Subscriber has an 8 Zone modular design for expansion with normal and reverse polarity, POTS and DACT interfaces with an option for the 7794A AES-IntelliPro full data module add-on accessory board. AES subscribers’ intelligent software automatically detects new hardware and devices to reduce installation time. An AES certified WiFi accessory allows seamless wireless connectivity for configuration and programming. A laptop, Ethernet cable, or a Wi-Fi USB dongle is required for IntelliNet 2.0 programming, handheld programmers will not work with 2.0 units. A FACP Power Supply Adapter is required for certain configurations when using flexible power options. The forward compatible design allows for feature add-ons, engineered to adapt seamlessly with future software upgrades as technology advances. IntelliNet 2.0 allows configuration cloning for faster installation time. The AES 7707 was designed with quick configuration and installation in mind to make it easier for field technicians to get in, out, and on to the next install. Visit our Fire Marshal Resources web page for official NFPA and UL Listings: aes-corp.com/products/fire/fire-marshal-resources www.aes-corp.com How to Order 7707 Fire www.aes-corp.com IntelliNet 2.0 Fire Subscribers 2.0 PREMIUM (UL & ULC Listed) 7707P-88-M IntelliNet 2.0 Fire Subscriber, 8 Zone with Multiple Communication Technologies (MCT), Red Enclosure 7707P-88-ULP-M IntelliNet 2.0 Fire Subscriber, 8 Zone with 7794A AES-IntelliPro, and integrated onboard Local Annunciator plus MCT, Red Enclosure 7707P-44-M IntelliNet 2.0 Fire Subscriber, 4x4 Zone (4 Reversing Polarity, 4 Supervised) with Multiple Communication Technologies (MCT), Red Enclosure 7707P-44-ULP-M IntelliNet 2.0 Fire Subscriber, 4x4 Zone (4 Reversing Polarity, 4 Supervised) with 7794A AES-IntelliPro, and integrated onboard Local Annunciator plus MCT, Red Enclosure 2.0 ACCESSORIES 7794A Standalone AES-IntelliPro Fire full data module add-on accessory board with firmware for new IntelliNet 2.0 units only, cannot be used in legacy units 77-WiFi AES certified WiFi adapter 77-FACPA FACP Power Supply Adapter for internal mount 77-FACPA-KIT External installation hardware for 2-way Junction Box Legacy Fire Subscribers 7706-ULF Integrated Fire Monitoring System, Red Enclosure 7788F-ULP-P Legacy Fire Subscriber, 8 Zone with 7795 AES-IntelliPro (7794 full data module, 7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure 7788F-ULP Legacy Fire Subscriber, 8 Zone, 8 Supervised Zones with 7794 AES-IntelliPro, Red Enclosure 7788F Legacy Fire Subscriber, 8 Zone, 8 Supervised Zones, Red Enclosure 7744F-ULP-P Legacy Fire Subscriber, 4 Zone with 7795 AES-IntelliPro (7794 full data module, 7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure 7744F-ULP Legacy Fire Subscriber, 4x4 Zone, 4 Supervised Zones with 7794 AES-IntelliPro, Red Enclosure 7744F Legacy Fire Subscriber, 4x4 Zone, 4 Reversing Polarity, 4 Supervised Zones, Red Enclosure LEGACY ACCESSORIES 7794 Standalone AES-IntelliPro Fire full data module add-on accessory board for legacy units only, please see 7794A above for IntelliNet 2.0 version www.aes-corp.com AES Corporation | 285 Newbury Street | Peabody, MA 01960 United States © Copyright 2018 AES Corporation and AES-IntelliNet ® are registered trademarks of AES Corporation 7707_03222018_F DIMENSIONS 13”H x 8.5”W x 4.5”D (33cmH x 21.5cmW x 11.4cmD) WEIGHT 5.8 lbs (2.6 kilograms) excluding battery 13 lbs (5.9 kilograms) with 10 Ah battery R ADIO FREQUENCY Standard Frequency Range: 450-470 MHz Contact AES for other UHF and VHF frequencies ANTENNA 2.5 dB tamper resistant antenna included, mounts on enclosure Optional remote mounting antenna available POWER INPUT AC SOURCES Transformer: Class 2 16.5V AC nominal output 1.9 A max current (40 VA MIN) ELK ELK-TRG1640, MG ELECTRONIC SALES MGT1640, or AES 1640 (not included) DC SOURCES (includes FACP) 24V DC Regulated Power Supply with Subscriber Rechargeable Battery 1.9 A max current BACKUP BAT TERY 10-12 Ah, UL recognized lead acid gel cell, size based on subscriber configuration PORTS Ethernet for configuration and message communication USB access for software upgrade REMOTE ANNUNCIATOR AES Model 7740 Remote Annunciator, supervised COMPATIBLE RECEIVERS 7705i AES-MultiNet Receiver CONFIGUR ATION INTERFACE Web browser capable device accessible via smartphone, tablet, laptop, or PC CURRENT CONSUMPTION Standby w/ charged backup battery: 200 mA (1.2 A Transmitting) Standby + charging backup battery: 900 mA (1.9 A Transmitting - MAX) POWER OUTPUT 2 or 5 Watts Factory set ENCLOSURE MATERIAL Steel with paint finish FINISH COLOR Red VISUAL INDICATORS Front panel LCD (2 x 20 alphanumeric character backlit display) Power and Trouble LEDs (ALM, Trouble, Tx, Rx, WA) AL ARM SIGNAL INPUTS/ZONES · 8 individually programmable E.O.L. type zone inputs · 4+4: 4 reverse polarity input and 4 individually programmable E.O.L. type zone inputs · Optional 7794A AES-IntelliPro for full data via Contact ID, Pulse, Modem IIe and Modem IIIa2 UL LISTINGS UL 864 10th Edition Standard for Control Units and Accessories for Fire Alarm Systems ULC S559-04 1st Edition Equipment for Fire Signal Receiving Centres and Systems TROUBLE OUTPUT—ACK DEL AY/ANTENNA CUT Form C relay, fail secure, rated 24V DC 1A resistive, unsupervised RESET BUT TON Located on main circuit board OPER ATING TEMPER ATURE 32 to 120°F (0 to 49°C) STOR AGE TEMPER ATURE 14 to 140°F (-10 to 60°C) REL ATIVE HUMIDIT Y 0 to 93%, non-condensing RECHARGE CAPABILIT Y Will charge 12V battery size from 10-12 Ah Technical Specifications 7707 Fire Contact Us For pricing and availability or to learn more about IntelliNet 2.0, please call your local AES Sales Representative at (800) 237-6387 or email sales@aes-corp.com. RA-1000 RA-1000 Remote Annunciator 7075 Series General The RA-1000 is a remote annunciator used to operate and program IFP-series fire alarm control panels (FACPs). The RA-1000’s keypad and display match the built-in annunciator of the GWF-7075 fire alarm control panel. The remote annunciator connects to the fire alarm control panel via the RS-485 system bus. When the system is in normal operation and has AC power, the Power LED is lit and all other LEDs are off. When any of the following conditions occur, the following LEDs turn on: Installation The RA-1000 can be surface or flush-mounted. Use the optional trim ring for surface mounts. The flush-mount electrical box is optional. If you require an electrical box, use a 4S, single-gang or double-gang box. Compatibility The RA-1000 is compatible with the following FACPs: • GWF-7075 Intelligent Fire Alarm Control Panel Ordering Information RA-1000R: Remote Annunciator. Four line LCD annunciator with 20 characters per line, red. RA-1000: Remote Annunciator. Four line LCD annunciator with 20 characters per line, gray. Accessories: 5860TR: Red Trim Ring for surface mounting. 5860TG: Gray Trim Ring for surface mounting. FEATURES & BENEFITS • Enclosure available in red or light gray • Produces audio feedback • Accepts the user codes or the fire fighter’s key • Offers an RS-485 interface to the panel • Displays large keypad buttons for system reset and silence • Includes the following five status LEDs: - alarm - supervisory - trouble - silence - AC power conditions • Has an 80-character backlit LCD display that shows 4 lines with 20 characters on each line •The remote annunciator operation and appearance is identical to the GWF-7075 built-in annunciator • Installs up to eight RA- 1000s per GWF-7075 •Supports a simultaneous use of multiple RA-1000s • Provides an on-board piezo sounder with audio that broadcasts alarms, troubles, and supervisories • Use wiring lengths up to 6,000 ft. from the FACP (depending on the wire gauge and the number of devices on the SBUS) •Alarms • Supervisories, •Troubles •System Silenced•AC power losses 2 Figure 1 RA-100 Panel Setup RA-1000 RA-1000 RA-1000 Note 1: Install up to 8 RA-1000s per System for the GWF-7075. Note 2: Includes an 80-character backlit LCD display. (4 lines with 20 characters each). Note 3: Use wiring lengths up to 6,000 ft. from the fire alarm control panel. RA-1000 Technical Specifications 9021-601007 | A | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Gamewell-FCI® and Honeywell® are registered trademarks and Farenhyte™ is a trademark of Honeywell International, Inc. Gentex® is a registered trademark of Gentex Corporation. Jumpstart is a registered trademark of Silent Knight. Microsoft, Windows®, and the Windows Logo®are registered trademarks or trademarks of Microsoft Corporation. System Sensor® is a registered trademark of System Sensor. UL® is a registered trademark of Underwriter’s Laboratories Inc. Wheelock® is a registered trademark of Wheelock, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s RA-1000 and other products available by visiting www.Gamewell-FCI.com SYSTEMS Physical: Height: 7.4” (18.8 cm) Width: 9.1” (23.1 cm) Depth: 1.5” (3.8 cm) Shipping Weight: 2.8 lbs (1.3 kg) Color: RA-1000R: Red RA-1000: Gray Electrical: Operating Voltage: 24 VDC Standby Current: 20 mA max Alarm Current: 25 mA Wiring Distance: 6,000 max. from FACP (depending on wire gauge and number of devices on the SBUS) Environmental: Operating Temperature: 32ºF – 120ºF (0ºC – 49ºC) Humidity: 10% – 93% non-condensing TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. Standards The GFPS-6S is designed to comply with the following standard: UL Standard: 864 9th Edition and 1481 Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: 864 1481 listed CSFM approved MEA approved ISO 9001 Certification MS-7 Series MS-7 Series Manual Fire Alarm Pull Stations Addressable Devices General The Gamewell-FCI, MS-7 Series manual fire alarm pull stations are available in a wide variety of configurations. The pull stations comply with the Americans with Disabilities Act (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille text are engraved in the handle. All pull stations include a key lock/reset which is keyed alike with the Gamewell-FCI fire alarm control panels and other manual fire alarm pull stations. MS-7AF Velociti Addressable Station The MS-7AF Velociti® Series addressable station is a double action pull station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the pull station causes its assigned address to register at the fire alarm control panel. The door contains an LED which flashes green in normal condition and lights steady red when the station has been activated.* The station features screw terminals. MS-7ASF Velociti Addressable Station The MS-7ASF Velociti® Series addressable pull station is a single action station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the pull station is activated.* The station features screw terminals. The Velociti® Series pull stations use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and focuses on the single device. The net effect offers a response speed up to five times greater than earlier designs. MS-7 Double Action Station The MS-7 double action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit. FEATURES & BENEFITS • Addressable stations compatible with all Gamewell-FCI analog addressable fire alarm controls • Conventional stations suitable for use with any UL® Listed control panel • The pull stations (MS- 7LOB) are Listed for outdoor applications • Complies with ADA pull force requirements • Offers surface or semi- flush mounting • Shock and vibration resistant • Both single and double action pull stations available • Includes a tumbler lock for test and reset keyed alike with analog addressable fire alarm controls *Only the red LED is operative in panels that do not operate in Velociti mode 2 MS-7S Single Action Station The MS-7S single action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and wire leads for connection to an initiating circuit. MS-7SP Double Action Station The MS-7SP is a double action pull station similar to the MS-7 station, with the additional feature of including both English and Spanish instructions molded into the unit. MS-7LR Dual-action Agent Release Station The MS-7LR is designed for use with the Gamewell-FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems. It features a set of single pole contacts and screw terminals used to connect to an initiating circuit. MS-7LRA Agent Release Station with Abort The MS-7LRA is designed for use with the Gamewell- FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems where system abort capabilities are required. It consists of the following: • An MS-7LR mounted on a plate with an abort switch • LED indicators that signal system normal and system activated status MS-7LOB Double Action Station (Listed for Outdoor Applications) The MS-7LOB station must be mounted on a Model SB-I/O backbox. In retrofit applications, the pull station is UL Listed for use with the WP-10 backbox. It is intended for use with conventional control panels and has a set of single pole contacts and screw terminals. Mounting The MS-7 interior pull stations may be surface mounted or semi-flush mounted on a standard double-gang, or 4-inch (10.2 cm) square electrical box. An optional trim ring (BG12TR) may also be used for semi-flush mounting. NYC-Plate The NYC-Plate provides the backplate for the manual pull station. (See Figure 1). Figure 1 NYC-Plate Ordering Information MS-7: Double action station MS-7AF**: Velociti addressable double action station MS-7ASF**: Velociti addressable single action station MS-7S: Single action station, wire leads MS-7SP: Double action station, English and Spanish instructions MS-7LR: Agent release station, dual-action MS-7LRA: Agent release station with abort switch, LED indicators, dual- action MS-7LOB: Double action station, outdoor use (Includes SB-I/O - Indoor/outdoor use backbox) SB-I/O: Indoor/outdoor use backbackbox SB-10: Surface backbox BG12TR: Trim ring for semi-flush mount, plastic NY-PLATE: NYC backplate for manual pull station **For use with the Gamewell-FCI analog addressable control panels only. MS-7 Series Technical Specifications 9020-0616 | F | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company. Velociti® and Gamewell-FCI are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s MS-7 Series and other products available by visiting www.Gamewell-FCI.com SYSTEMS Material: Lexan® Contact Ratings: 0.25 amps. @ 30 VAC/VDC (resistive) Dimensions: 5 5/8” H x 4 1/4” W x 1 1/4” D (14 x 10.1 x 3.2 cm) Operating Temperature: (MS-7AF, MS-7ASF): 32° to 120° F (0° to 49° C) (MS-7LOB): -30° to 150° F (-35° to 66° C) Relative Humidity : (MS-7AF, MS-7ASF): 10 to 93% (non-condensing) (MS-7LOB): 85% ± 5% @ 86° ± 3.6° (30° ± 2° C) Alarm Current: .0030 amp. 0.007 for LED Supervisory Current: (MS-7AF, MS-7ASF): .00030 amps. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The MS-7 Series is designed to comply with the following standard: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2465 FM: 3023594 MEA FDNY: 67-02-E Vol. VII CSFM: 7160-1703:0119 7160-1703:0170 7160-1703:0109 ISO 9001 Certification ASD-PL2F/ASD-PTL2F ASD-PL2FR Velociti® Series 3 Detectors Photoelectric Detectors Addressable Devices Photoelectric Detector Description The Gamewell-FCI, Velociti® Series 3 intelligent photoelectric detectors with integral communication provide point location for alarm communication and selective maintenance. Designed in a modern bright white color, the Velociti Series 3 is aesthetically pleasing for today's contemporary buildings. The Velociti Series 3 smoke detectors are intelligent addressable detectors with point ID capability that enable each detector address to be set with rotary address switches providing exact device locations. The photoelectric detector continually monitors the detected temperature and reports it to the fire alarm control panel. The modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. The Gamewell-FCI, ASD-PL3 photoelectric detector's re-designed optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. The sensitivity of Velociti series detectors can be programmed using the control panel software to suit the environment. The ASD-PL3R photoelectric detector is also remote test capable that may be used with a DNR (DNRW) duct smoke detector housing. The ASD-PTL3 multi- sensor detector offers either photoelectric detection or thermal detection through dual electronic thermistors at 135°F fixed temperature thermal sensing. For legacy installations, service detectors are available in the classic ivory color that will operate in both Velociti and CLIP protocol for backwards compatibility. Service models are designated by the -IV part number after the detector model. Note: Although the E3 Series® and S3 Series panels support both the Velociti® and CLIP™ protocols, the GWF-7075 panel does not support the CLIP protocol. To obtain a complete list of panels that are listed to Velociti Series 3 detectors, refer to the Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8. FEATURES & BENEFITS • Complies with UL® Standard 268 7th Edition • Designed with a new profile to offer modern and improved aesthetics • Contains a built-in functional test switch activated by external magnet • Supports a low standby current • Provides rotary address switches (01-159) • Supplies optional relay, isolator, or sounder bases (standard or low frequency) • Includes dual LEDs for 360° visibility • Offers expanded color options 2 Ordering Information NOTE: "-IV" suffix indicates Ivory color model. NOTE: "-BL" suffix indicates Black color model. NOTE: “WH” suffix indicates Bright White color model. ASD-PL3: Photoelectric smoke detector, bright white, Velociti ASD-PL3R: Photoelectric smoke detector, remote test capable, for use with DNR(W) duct smoke detectors, bright white, Velociti ASD-PTL3: Photoelectric smoke detector with thermal sensing, bright white, Velociti ASD-PL3-IV : Photoelectric smoke detector, ivory, Velociti/ CLIP ASD-PL3R-IV: Photoelectric smoke detector, remote test capable, for use with DNR(W) duct smoke detectors, ivory, Velociti/CLIP ASD-PTL3-IV : Photoelectric smoke detector with thermal sensing, ivory, Velociti/CLIP Intelligent Bases For details on intelligent bases, refer to Data Sheet P/N: 9021-60540. Note: “IV” suffix indicates Flashscan and CLIP devices. “WH” suffix indicates bright white B501-WHITE: 4” Flangeless mounting base, bright white B501-WHITE-BP: 4” Flangeless mounting base bulk pack, bright white B501-IV: 4” Flangeless mounting base, ivory B300-6: 6” Flanged mounting base, bright white B300-6-IV: 6” Flanged mounting base, ivory B300-6-BP: 6” Flanged mounting base bulk (Pack of 10) B200SR-WH: Standard sounder base, bright white B200SR-IV: Standard sounder base, ivory B200S-WH: Intelligent addressable sounder base, bright white B200S-IV: Intelligent addressable sounder base, ivory B200SR-LF-WH: Standard low frequency sounder base, bright white B200SR-LF-IV: Standard low frequency sounder base, ivory B200S-LF-WH: Intelligent addressable low frequency sounder base, bright white B200S-LF-IV: Intelligent addressable low frequency sounder base, ivory B224RB-WH: Relay base, bright white B224RB-IV: Relay base, ivory B224BI-WH: Isolator base, bright white B224BI-IV: Isolator base, ivory DNR: Intelligent duct detector housing, non-relay DNRW: Intelligent duct detector housing, non-relay, watertight Ordering Information Accessories SMB600: Surface Mounting Kit (flanged) TR300: Accessory Flange Ring for B300 6” Base, bright white TR300-IV: Accessory Flange Ring for B300 6” Base, ivory RA100Z: Remote LED annunciator, 3-32 VDC The annunciator mounts to a U.S. single-gang electrical box. For use with B501 and B300-6. CK300: Bright White detector kit (Pack of 10) CK300-IR: White, detector color kit for use with MCS-COF Series Detectors. (Pack of 10) CK300-IV: Ivory, detector color kit. (Pack of 10) CK300-IR-IV: Ivory, detector color kit for use with MCSCOF Series detectors. (Pack of 10) CK300-BL: Black detector kit. (Pack of 10) CK300-IR-Bl: Black, detector color kit for use with MCSCOF Series detectors. (Pack of 10) M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows the installation and/ or removal of the detector heads from the bases in high ceiling applications. XP-4: Extension pole for XR2B. Shipped with three, 5-foot (1.524,m) sections. Velociti® Series 3 Detectors Technical Specifications 9020-0617 | K | 04/2018 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Velociti® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series 3 Detectors and other products available by visiting www.Gamewell-FCI.com SYSTEMS Photoelectric Intelligent Detector: Physical Specifications Height: 2.0 inches (51 mm) installed in B300-6 base Diameter: 6.1 inches (15.49 cm) installed in B300-6 base 4 inches (10.16 cm) installed in B501 base Shipping Weight: 3.4 oz (96.4 g) Operating Temperature Range: Photo: 32° F to 122° F (0° C to 50° C) Photo in Duct Applications: -4° F to 158° F (-20° C to 70° C) Photo with Thermal: 32° F to 100° F (0° C to 38° C) Operating Humidity Range: 10% to 93% non-condensing Rate-of-Rise Detection: Responds to greater than 15°F/minute or 135°F (8.3° C/minute or 57°C Air Velocity Range: 0 to 4,000 ft/min (0 to 1219.2 m/min) Electrical Specifications Voltage Range: 15 to 32 VDC Standby Current (@ 24 VDC): 200 UA (one communication every 5 seconds with green LED enabled) Max Alarm Current (max.): 2 mA @ 24 VDC (one communication every 5 seconds with red LED enabled) Max Current (max.): 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED enabled) Isolator Load Rating: 0.0063 STANDARDS The Velociti® Series 3 Photoelectric Detectors are designed to comply with the following standard: UL Standard: UL 268 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2332 FM: 3023594 MEA FDNY: COA-219-02-E Vol. VI CSFM: 7272-1703:0501 ISO 9001 Certification Thermal Detector Velociti® Series 3 Detectors Thermal Detectors Addressable Devices Description The Gamewell-FCI, Velociti® Series 3 intelligent thermal detectors with integral communication provide point location for alarm communication and selective maintenance. Designed in a modern bright white color, the Velociti Series 3 is aesthetically pleasing for today's contemporary buildings. The Velociti Series 3 heat detectors are intelligent addressable detectors with point ID capability that enable each detector address to be set with rotary address switches providing exact device locations. The thermal detector continually monitors the detected temperature and reports it to the fire alarm control panel. The modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. Velociti Series 3 thermal detectors provide cost-effective, intelligent property protection using the following single thermistor: • ATD-L3 offers 135°F fixed thermal detection. • ATD-L3R offers 135°F fixed and rate-of-rise thermal detection. • ATD-L3H provides fixed high-temperature detection at 190°F . For legacy installations, service detectors are available in the classic ivory color that will operate in both Velociti and CLIP protocol for backwards compatibility. Service models are designated by the -IV part number that appears after the detector model. Note: The E3 Series® and S3 Series panels support both the Velociti® and CLIP™ protocols, and the GWF-7075 panel supports only the Velociti® protocol. To obtain a complete list of panels that are listed to Velociti Series 3 detectors, refer to the Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8. FEATURES & BENEFITS • Complies with UL® 268 7th Edition • Designed with a new profile to offer modern and improved aesthetics • Contains a built-in functional test switch activated by an external magnet • Supports a low standby current • Provides rotary address switches (01-159) • Supplies optional relay, isolator, or sounder bases (standard or low frequency) •Includes dual LEDs used for 360° visibility • Offers expanded color options 2 Ordering Information NOTE: "-IV" suffix indicates Ivory color model. NOTE: "-BL" suffix indicates Black color model. NOTE: “WH” suffix indicates Bright White color model. ATD-L3: Thermal heat detector, 135°F fixed, bright white, Velociti ATD-L3-IV: Thermal heat detector, 135°F fixed, ivory, Velociti/CLIP ATD-L3R: Thermal heat detector, 135°F rate of rise, bright white, Velociti ATD-L3R-IV: Thermal heat detector, 135°F rate of rise, ivory, Velociti/CLIP ATD-L3H: Thermal heat detector, 190°F high temp, bright white, Velociti ATD-L3H-IV: Thermal heat detector, 190°F high temp, ivory, Velociti/CLIP Intelligent Bases For details on intelligent bases, refer to Data Sheet P/N: 9021-60540. B501-White: 4" Flangeless mounting base, bright white B501-White-BP: 4" Flangeless mounting base bulk pack, bright white B501-IV: 4" Flangeless mounting base, ivory B501-BL 4" Flangeless mounting base, B300-6: 6" Flanged mounting base, bright white B300-6-IV: 6" Flanged mounting base, ivory B300-6-BP: 6" Flanged mounting base bulk pack B200SR-WH: Standard sounder base, bright white B200SR-IV: Standard sounder base, ivory B200S-WH: Intelligent addressable sounder base, bright white B200S-IV: Intelligent addressable sounder base, ivory B200SR-LF-WH: Standard low frequency sounder base, bright white B200SR-LF-IV: Standard low frequency sounder base, ivory B200S-LF-WH: Intelligent addressable low frequency sounder base, bright white B200S-LF-IV: Intelligent addressable low frequency sounder base, ivory B224RB-WH: Relay base, bright white B224RB-IV: Relay base, ivory B224BI-WH: Isolator base, bright white B224BI-IV: Isolator base, ivory Ordering Information Accessories SMB600: Surface Mounting Kit (flanged) TR300: Accessory Flange Ring for B300 6" Base, bright white TR300-IV: Accessory Flange Ring for B300 6" Base, ivory RA100Z: Remote LED annunciator, 3-32 VDC The annunciator mounts to a U.S. single-gang electrical box. For use with B501 and B300-6. CK300: Bright White detector kit (Pack of 10) CK300-IR: White, detector color kit for use with MCS-COF Series Detectors. (Pack of 10) CK300-IV: Ivory, detector color kit. (Pack of 10) CK300-IR-IV: Ivory, detector color kit for use with MCS- COF Series detectors. (Pack of 10) CK300-BL: Black detector kit (Pack of 10) CK300-IR-Bl: Black, detector color kit for use with MCS- COF Series detectors. (Pack of 10) M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows the installation and/or removal of the detector heads from the bases in high ceiling applications. XP-4: Extension pole for XR2B. Shipped with three, 5- foot (1.524,m) sections. Velociti® Series 3 Detectors Technical Specifications 9020-0620 | G | 04/2018 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Velociti® and Gamewell-FCI® are registered trademarks and CLIP™ is a trademark of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series 3 Detectors and other products available by visiting www.Gamewell-FCI.com SYSTEMS Thermal Intelligent Detector Physical Specifications Height: 2.0 inches (51 mm) installed in B300-6 base Diameter: 6.1 inches (15.6 cm) installed in B300-6 base 4 inches (10.2 cm) installed in B501 base Shipping Weight: 3.4 oz (95 g) Operating Temperature Range: Thermal 135° F fixed: -4° F to 100° F (-20° C to 38° C) Thermal 135° F rate-of-rise: -4° F to 100° F (-20° C to 38° C) Thermal 190° F rate-of-rise: -4° F to 135° F (-20° C to 57° C) Operating Humidity Range: 10% to 93% non- condensing Rate-of-Rise Detection: : Responds to greater than 15°F/minute or 135°F (8.3° C/minute or 57°C Electrical Specifications Voltage Range: : 15 to 32 VDC Standby Current (@ 24 VDC): 200 uA (one communication every 5 seconds with green LED enabled) Max Alarm Current (max.): : 2 mA @ 24 VDC (one communication every 5 seconds with red LED enabled) Max Current (max.): : 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED enabled) Isolator Load Rating: : 0.0063 STANDARDS The Velociti® Series 3 Thermal Detectors are designed to comply with the following standard: UL Standard: UL 268 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2332 FM: 3023594 MEA-FDNY: 219-02-E Vol. VI CSFM: 7270-1703-0502 ISO 9001 Certification Features • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 30 candela • Field-selectable candela settings on ceiling units: 15, 30, 75, 95, 115, 150, and 177 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and two volume selections • Universal mounting plate for ceiling units • Mounting plate shorting spring feature checks wiring continuity before device installation • Electrically Compatible with legacy SpectrAlert and SpectrAlert Advance devices • Compatible with MDL3 sync module • Listed for ceiling mounting only The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, wall and ceiling mounting options, System Sensor L-Series can meet virtually any application requirement. The entire L-Series product line of ceiling-mount strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature a plug-in design with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time- consuming ground faults. To further simplify installation, the L-Series utilizes a universal mounting plate so installers can mount them to a wide array of back boxes. With an onboard shorting spring, installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Indoor Selectable- Output Strobes and Horn Strobes for Ceiling Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Agency Listings 7125-1653:0504 7135-1653:0503 S5512 S4011 FM approved except for ALERT models 3057383 AVDS86800 L-Series Specifications Architect/Engineer Specifications General L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double- gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, and 177. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11 ⁄16 × 4 11 ⁄16 × 2 1 ⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3)8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions (including lens)6.8" diameter × 2.5" high (173 mm diameter × 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions (SBBCRL, SBBCWL) 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. AVDS86800 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC DC FWR 15 87 41 60 30 153 63 86 75 N/A 111 142 95 N/A 134 164 115 N/A 158 191 150 N/A 189 228 177 N/A 226 264 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe DC Input 8-17.5 Volts 16-33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non-Temporal High 106 173 71 90 141 165 187 230 273 Non-Temportal Low 95 166 54 71 124 161 170 216 258 3.1K Temporal High 111 164 69 94 147 163 184 229 257 3.1K Temporal Low 103 163 54 88 143 155 185 212 252 3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271 3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259 FWR Input 16-33 Volts 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non-Temporal High 107 135 179 198 223 254 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1K Temporal High 108 135 179 200 225 255 289 3.1K Temporal Low 79 101 150 171 196 229 260 3.1K Non-Temporal High 108 135 179 200 225 255 289 3.1K Non-Temporal Low 79 101 150 171 196 229 260 UL Current Draw Data Horn Strobe Tones and Sound Output Data 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2017 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS86801 • 03/17 L-Series Dimensions Model Description Ceiling Horn Strobes PC2RL 2-Wire, Horn Strobe, Red PC2WL 2-Wire, Horn Strobe, White L-Series Ordering Information Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box Model Description Ceiling Strobes SCRL Strobe, Red SCWL Strobe, White SCWL-CLR-ALERT Strobe, White, ALERT Accessories TRC-2 Universal Ceiling Trim Ring Red TRC-2W Universal Ceiling Trim Ring White SBBCRL Ceiling Surface Mount Back Box, Red SBBCWL Ceiling Surface Mount Back Box, White Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box Agency Listings 7125-1653:0504 7135-1653:0503 S5512 S4011 FM approved except for ALERT models 3057383, 3057072 Features • Updated Modern Aesthetics • Small profile devices for Horns and Horn Strobes • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 30 candela • Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and two volume selections • Mounting plate for all standard and all compact wall units • Mounting plate shorting spring checks wiring continuity before device installation • Electrically Compatible with legacy SpectrAlert and SpectAlert Advance devices • Compatible with MDL3 sync module • Listed for wall mounting only The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, standard and compact devices, and plain, FIRE, and FUEGO-printed devices, System Sensor L-Series can meet virtually any application requirement. The L-Series line of wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. L-Series Specifications Architect/Engineer Specifications General L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 1 7/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 17⁄8 -inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411 ⁄16 × 411 ⁄16 × 21 ⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1,2 Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D) Compact Wall-Mount Dimensions (including lens)5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D) Compact Horn Dimensions 5.25” L x 3.45” W x 1.25” D (133mm L x 88mm W x 32mm D) 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9*Coded High 85 90 90 10*3.1 KHz Coded High 84 89 89 * Settings 9 and 10 are not available on the 2-wire horn strobes. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC DC FWR Candela Range 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Candela Range (15–115 cd) DC Input 8-17.5 Volts 16-33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.1K Temporal High 93 156 53 73 119 140 164 190 242 3.1K Temporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 FWR Input 16-33 Volts 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 83 107 156 177 198 234 287 Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non-Temporal High 43 47 54 Non-Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Current Draw Data Horn Tones and Sound Output Data 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2017 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS86503 • 03/17 L-Series Dimensions Model Description Wall Horn Strobes P2RL 2-Wire, Horn Strobe, Red P2WL 2-Wire, Horn Strobe, White P2GRL 2-Wire, Compact Horn Strobe, Red P2GWL 2-Wire, Compact Horn Strobe, White P2RL-P 2-Wire, Horn Strobe, Red, Plain P2WL-P 2-Wire, Horn Strobe, White, Plain P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO P2WL-SP 2-Wire, Horn Strobe, White, FUEGO Wall Strobes SRL Strobe, Red SWL Strobe, White SGRL Compact Strobe, Red SGWL Compact Strobe, White SRL-P Strobe, Red, Plain SWL-P Strobe, White, Plain SRL-SP Strobe, Red, FUEGO SWL-CLR-ALERT Strobe, White, ALERT L-Series Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover) All -SP models have “FUEGO” marking on cover All -ALERT models have “ALERT” marking on cover Compact Strobe / Horn Strobe Strobe / Horn Strobe Compact Horn Horn Model Description Horns HRL Horn, Red HWL Horn, White HGRL Compact Horn, Red HGWL Compact Horn, White Accessories TR-2 Universal Wall Trim Ring Red TR-2W Universal Wall Trim Ring White SBBRL Wall Surface Mount Back Box, Red SBBWL Wall Surface Mount Back Box, White SBBGRL Compact Wall Surface Mount Back Box, Red SBBGWL Compact Wall Surface Mount Back Box, White Agency Listings Features • Weatherproof per NEMA 4X, IP56 • Listed to UL 1638 (strobe) and UL 464 (horn) • Compatible with System Sensor synchronization protocol and legacy SpectrAlert products • Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Rotary switch for horn tone and three volume selections • Horn rated at 88+ dBA at 16 volts • Rated from –40°F to 151°F • Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Listed for ceiling or wall mounting SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic housings, wall or ceiling mounting options, and plain or FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from −40°F to 151°F. Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes for wall applications include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, automatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. Next, SpectrAlert Advance devices use a universal mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and- out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box. Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. MEA452-05-E3023572 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) S4011 (chimes, horn strobes, horns) S3593 (outdoor and alert strobes) AVDS01201 SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between −40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature –40°F to 151°F (–40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D) Wall-Mount Weatherproof Back Box Dimensions (SA-WBB)5.7˝ L × 5.1˝ W × 2.0˝ D (145 mm L × 130 mm W × 51 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS01201 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non- Temporal High 82 82 88 88 93 92 100 100 5 Non- Temporal Medium 78 78 85 85 90 90 98 98 6 Non- Temporal Low 75 75 81 81 88 84 96 92 7†Coded High 82 82 88 88 93 92 101 101 8†Coded Medium 78 78 85 85 90 90 97 98 9†Coded Low 75 75 81 81 88 85 96 92 †Settings 7, 8, and 9 are not available on 2-wire horn strobe. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) DC Input 8–17.5 Volts 16–33 Volts 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC FWR DC FWR Temporal High 57 55 69 75 Temporal Medium 44 49 58 69 Temporal Low 38 44 44 48 Non-Temporal High 57 56 69 75 Non-Temporal Medium 42 50 60 69 Non-Temporal Low 41 44 50 50 Coded High 57 55 69 75 Coded Medium 44 51 56 69 Coded Low 40 46 52 50 UL Current Draw Data Horn Tones and Sound Output DataCandela Derating For K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table. Strobe Output (cd) Listed Candela Candela rating at –40°F 15 Do not use below 32°F15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2012 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS01201 • 3/12 SpectrAlert Advance Diagrams Model Description Wall Horn Strobes P2RK*†2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P2RHK*†2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) P2WK*†2-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2WHK*†2-Wire Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) P4RK†4-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe, High cd, Red, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK*†Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) SRHK*†Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) SWK*†Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) SWHK*†Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) Horns HRK†Horn, Red, Outdoor (includes plastic weatherproof back box) Accessories SA-WBB Red, Metal Weatherproof Back Box SA-WBBW White, Metal Weatherproof Back Box SpectrAlert Advance Ordering Information Notes: * Add “-P” to model number for plain housing (no “FIRE” marking on cover), e.g., P2RK-P. † Add “-R” to model number for weatherproof replacement device (no back box included), only for use with weatherproof outdoor flush mounting plate, WTP and WTPW. “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. 4.7˝ 5.6˝ 2.5˝ Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Wall-Mount Horn Strobe with Plastic Weatherproof Back Box