City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
March 3, 2020
Mike Colyn
Kevin Bloomfield, Plans Examiner
Plan Check: BLD2020-0207
Project Address: 7708 234t" St SW
Scope: Remodel
(425)771-0220
Thank you for submitting your plans to the City of Edmonds for review. We have completed an
initial review of the project mentioned above. For this project to move forward a few items will
need to be addressed.
Once a revised set of plans, including a written response to the list of the items contained in this
letter are resubmitted, we can complete the review. Some items may require a review by other
divisions, such as Planning, Engineering, or Fire and will be noted as such.
Resubmittals can be made at the Development Services Department on the 2"d Floor of City Hall.
Permit Center hours are M, T, Th, & F from 8am-4:30pm and from 8:30am-12pm on
Wednesdays.
To complete the review the following items will need to be addressed:
General:
Include sheet numbers on all sheets.
Sheet: "Proposed Floor Plan"
There shall be a landing or floor on each side of each exterior door. The width of each
landing shall be not less than the door served. Every landing shall have a dimension of not
less than 36 inches (914 mm) measured in the direction of travel. The slope at exterior
landings shall not exceed 1/4 unit vertical in 12 units horizontal (2 percent).
IRC Code Reference: R311.3 Floors and Landings at Exterior Doors
Local exhaust shall be provided in each kitchen, bathroom, water closet, laundry room,
indoor swimming pool, spa, and other rooms where water vapor or cooking odor is
produced. Local exhaust systems shall be designed to have the capacity to exhaust the
minimum air flow rate determined in accordance with Table M1507.4.
IRC Code Reference: M1507.4 Local Exhaust Rates
3. Exhaust fans providing local exhaust shall have a minimum fan flow rating not less than 100
cfm at 0.25 inches water gauge for kitchens. Manufacturers' fan flow ratings shall be
determined as per HVI 916 (April 1995) or AMCA 210.
IRC Code Reference: M1507.4.1 Local exhaust fans
4. Where domestic kitchen cooking appliances are equipped with ducted range hoods or
down -draft exhaust systems, the fans shall be sized in accordance with Section M1507.4.
IRC Code Reference: M1503.3 Kitchen Exhaust Rates
Exhaust hood systems capable of exhausting in excess of 400 cubic feet per minute (0.19
m3/s) shall be mechanically or naturally provided with makeup air at a rate approximately
equal to the exhaust air rate. Such makeup air systems shall be equipped with not less than
one damper. Each damper shall be a gravity damper or an electrically operated damper
that automatically opens when the exhaust system operates. Dampers shall be accessible
for inspection, service, repair and replacement without removing permanent construction
or any other ducts not connected to the damper being inspected, serviced, repaired or
replaced.
IRC Code Reference: M1503.4 Makeup Air Required
6. Please indicate on the plans all shearwalls with a detail to match the "Shearwall Schedule"
on sheet S2. Include location for all holddowns to match the "Holddown Schedule" on
sheet S2.
Sheet S2:
7. Calculations have a call out for a SW 4. The shearwall schedule on the plans does not match
the parameters set by the calculations package. Schedule on sheet S2 states the bottom
plate connection should be 4" oc. The calculation package states this should be 6" oc.
Please clarify which is correct.
If you need any clarification or have any questions at all, please feel free to call anytime.
Kevin Bloomfield