HEATING & AIR CONDITIONING
Submittal
Split System Heat Pump
4A6H5042H1000A
Note: "Graphics in this document are for representation only. Actual model may
differ in appearance."
TAG:
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
December 2016 4A6H5042H-SUB-1 B-EN 4 OUR Ingersoll Rand
S
H EATING & Al R CONDITIONING
SERVICE PANEL
ELECTRICAL AND REF
COMPONENT CLEARANC
PER PREVAILING COD
TOP DISCHARGE AREA SHOULD BE
UNRESTRICTED FOR AT LEAST 1524 (5 FEET)
ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF
RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT,
AND SHOULD BE AT LEAST 305 (12") FROM WALL AND
ALL SURROUNDING SHRUBBERY ON TWO SIDES.
OTHER TWO SIDES UNRESTRICTED.
ELECTRICAL SERVI
PAN
22.2 (7/8) D
LOW
28.6 (1-1/8) DIA. 1
22.2 (7/8) DIA. HOLE II
BOX BOTTOM FOR El
POW[
LIQUID LINE SERVIC
'E' I.D. FEMALE BR
CONNECTION WITH 1/4" SAE
FLARE PRESSURE TAP FITTINGS.
GAS LINE 1/4 TURN BALL SERVICE VALVE, 'D"
I.D. FEMALE BRAZED CONNECTION WITH 1/4' SAE
FLARE PRESSURE TAP FITTING.
Model
Base
A
B
C
D
E
F
G
H
J
K
4A6H5042H
4
1147
946
870
7/8
3/8
152
98
219
86
813
(45-1/8)
(37-1/4)
(34-1/4)
(6)
(3-7/8)
(8-5/8)
(3-3/8)
(32)
SOUND POWER LEVEL
Model
A -Weighted Sound
Power Level [dB(A) ]
Full Octave Sound Power [dB]
63 Hz*
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
4A6H5042H
72
77
75
72
70
67
62
59
52
Note: Rated in accordance with AHRI Standard 270-2008 *For reference only.
4A6H5042H-SUB-1 B-EN
S
H EATING & Al R CONDITIONING
Product Specifications
OUTDOOR UNIT (a) (b)
4A6H5042H1000A
POWER CONNS. — V/PH/HZ (c)
208/230/1/60
MIN. BRCH. CIR. AMPACITY
22
BR. CIR. PROT. RTG. — MAX. (AMPS)
35
COMPRESSOR
DURATION-_ SCROLL
NO. USED — NO. STAGES
I— 1
VOLTS/PH/HZ
208/230/1/60
R.L. AMPS (d)— L.R. AMPS
16.7— 109
FACTORY INSTALLED
START COMPONENTS (e)
NO (Uses BAYKSKT263)
INSULATION/SOUND BLANKET
NO
COMPRESSOR HEAT
NO
OUTDOOR FAN
PROPELLER
DIA. (IN.) — NO. USED
26.6 — 1
TYPE DRIVE — NO. SPEEDS
DIRECT— 1
CFM @ 0.0 IN. W.G. M
4171
NO. MOTORS — HP
1-1/5
MOTOR SPEED R.P.M.
850
VOLTS/PH/HZ
200/230/1/60
F.L. AMPS
.93
OUTDOOR COIL — TYPE
SPINE FINT
ROWS—F.P.I.
2-24
FACE AREA (SQ. FT.)
29.15
TUBE SIZE (IN.)
3/8
REFRIGERANT CONTROL
EXPANSION VALVE
REFRIGERANT
LBS. — R-410A (O.D. UNIT) (g)
10 LBS., 5 OZ
FACTORY SUPPLIED
YES
LINE SIZE — IN. O.D. GAS (h) (i)
7/8
LINE SIZE — IN. O.D. LIQ.
3/8
CHARGING SPECIFICATIONS
SUBCOOLING
8°F
DIMENSIONS
H X W X D
CRATED (IN.)
51 x 35.1 x 38.7
WEIGHT
SHIPPING (LBS.)
277
NET (LBS.)
227
(a) Certified in accordance with the Air -Source Unitary Air -conditioner
Equipment certification program, which is based on AHRI standard
210/240.
(b) Rated in accordance with AHRI standard 270.
W Calculated in accordance with Natl. Elec. Codes. Use only HACR
circuit breakers or fuses.
(d) This value shown for compressor RLA on the unit nameplate and on
this specification sheet is used to compute minimum branch circuit
ampacity and max. fuse size. The value shown is the branch circuit
selection current.
(e) No means no start components. Yes means quick start kit
components. PTC means positive temperature coefficient starter.
Optional kit shown.
M Standard Air — Dry Coil — Outdoor
(9) This value approximate. For more precise value see unit nameplate.
(h) Reference the outdoor unit ship -with literature for refrigerant piping
length and lift guidelines. Reference the refrigerant piping software
pub # 32-3312-xx or refrigerant piping application guide SS-
APG006-xx for long line sets or specialty applications (xx denotes
latest revision).
0) Trane outdoor condensing units are factory charged with the system
charge required for the outdoor condensing unit and 15 feet of tested
connecting lines. If connecting line length exceeds 15 feet, then final
refrigerant charge adjustment is necessary. Each additional foot over
15 feet requires 0.6 ozs of refrigerant. See the Installer's Guide for
full charging instructions.
4A6H5042H-SUB-1 B-EN
l�cP�`Ic�rti! s7 iw
HEATING & AIR CONDITIONING
Mechanical Specification Options
General
The Outdoor Units are fully charged from the factory
for up to 15 feet of piping. This unit is designed to
operate at outdoor ambient temperatures as high as
115°F. Cooling capacities are matched with a wide
selection of air handlers and furnace coils that are AHRI
certified. The unit is certified to UL 1995. Exterior is
designed for outdoor application.
Casing
Unit casing is constructed of heavy gauge, galvanized
steel and painted with a weather -resistant powder paint
finish on all louvered panels and the fan top panel. The
corner panels are prepainted. All panels are subjected
to our 1,000 hour salt spray test. The base is made of a
CMBP-G30 weatherproof material to resist corrosion.
Refrigerant Controls
Refrigeration system controls include condenser fan,
compressor contactor and high pressure switch. High
and low pressure controls are inherent to the
compressor. A factory supplied liquid line drier is
standard. Some models may require field installation.
A*M Wff SAwdwde
HEATING & AIR CONDITIONING
Compressor
The compressor features internal over temperature,
pressure protection and total dipped hermetic motor.
Other features include: Centrifugal oil pump and low
vibration and noise.
Condenser Coil
The outdoor coil provides low airflow resistance and
efficient heat transfer. The coil is protected on all four
sides by louvered panels.
Low Ambient Cooling
As manufactured, this system has a cooling capacity to
55°F. The addition of an evaporator defrost control
permits operation to 40°F. The addition of an
evaporator defrost control with TXV permits low
ambient cooling to 30°F.
Thermostats —Cooling only and heat/cooling (manual
and automatic change over). Sub -base to match
thermostat and locking thermostat cover.
Evaporator Defrost Control — See Low Ambient
Cooling.
041TSus
TE
Intertek Globally Recognized. Industry Respected.
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments.
Our people and our family of brands —including Club Caro, Ingersoll Rand®, Thermo King® and Trane@—work together
to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and
increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress
and enduring results. For more information, visit www.ingersollrand.com.
Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
The AHRI Certified mark indicates Ingersoll Rand participation in the AHRI Certification program. For verification of individual certified products, go to
www.ahridirectory.org.
(D2016 Ingersoll Rand All rights reserved 4A6H506H5042H-SUB-SUB-16-EN 01 Dec2016 ,../ Ingersoll Rand 4A6H5042H-SUB-IA-EN (August 2016)