BLD2021-0872_Manufacturer_Specifications_and_Installation_Instructions_6.23.2021_10.33.22_AM_2265224
System Reference: r={ W-S FEATURES • Variable speed INVERTER -driven compressor • Blue Fin Coating on heat exchanger • Thermal Differential 1°F (with PAC-MKA32/52BC only) • Branch box for simplified piping and installation flexibility • Up to 8 indoor units connectable (six [6] if a PLA-A"EA7 is connected) • Optional base pan heater • Quiet outdoor unit operation as low as 54 dB(A) • High pressure protection • Compressor thermal protection • Compressor overcurrent detection • Fan motor overheating/voltage protection Date: Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Cooling Maximum Capacity BTU/H 48,000 48,000 48,000 Rated Capacity BTU/H 48,000 48,000 48,000 Minimum Capacity BTU/H 15,500 15,500 15,500 Maximum Power Input W 3,930 4,320 4,800 Rated Power Input W 3,930 4,320 4,800 Power Factor (208V, 230V) % 98.6 / 98.6 98.9 / 98.9 99.2 / 99.2 Heating at 47°FZ Maximum Capacity BTU/H 54,000 54,000 54,000 Rated Capacity BTU/H 54,000 54,000 54,000 Minimum Capacity BTU/H 22,500 22,500 22,500 Maximum Power Input W 4,220 4,520 4,800 Rated Power Input W 4,220 4,520 4,800 Power Factor (208V, 230V) % 98.6 / 98.6 98.9 / 98.9 99.2 / 99.2 Heating at 17°F3 Maximum Capacity BTU/H 36,600 36,600 36,600 Rated Capacity BTU/H 33,000 33,000 33,000 Maximum Power Input W 5,200 5,550 5,200 Rated Power Input W 3,720 3,870 4,030 Heating at 5°F4 Maximum Capacity BTU/H 32,400 32,400 32,400 Maximum Power Input W 4,750 4,870 5,000 Efficiency SEER 20.00 18.00 16.00 EERY 12.20 11.10 10.00 HSPF (IV) 11.5 3.75 10.8 3.50 10.1 3.30 COP at 47° F2 COP at 17° F3 2.00 1.90 2.00 COP at 5° F4 2.00 1.90 1.90 ENERGY STAR® Certified NO NO NO Electrical Voltage, Phase, Frequency 208 / 230V1 1-phase, 60 Hz Guaranteed Voltage Range V AC 198-253 Voltage: Indoor - Outdoor, S1-S2 V AC 208 / 230 Voltage: Indoor - Outdoor, S2-S3 V DC 24 Short-circuit Current Rating (SCCR) 5kA 5 Recommended Fuse/Breaker Size (Outdoor) A 40 Recommended Wire Size (Indoor - Outdoor) AWG 16 Outdoor unit MCA A 35 MOCP A 50 Fan Motor Full Load Amperage A 0.6 + 0.6 Fan Motor Output W 74 Airflow Rate Cooling / Heating CFM 3,885 / 3,885 Refrigerant Control Linear Expansion Valve Defrost Method Reverse Cycle Heat Exchanger Type Plate Fin Coil Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Indoor Sound Pressure Level, Coolingi dB(A) 51 Sound Pressure Level, Heating2 dB(A) 54 Compressor Type Hermetic Compressor Model ANB33FNHMT Compressor Motor Output kW 3.4 Compressor Rated Load Amps A 19.0 Compressor Locked Rotor Amps A 22.0 Compressor Oil Type // Charge oz. FV50S // 78 External Finish Color Munsell 3Y 7.8/ 1.1 Base Pan Heater Optional (PAC-SJ20BH-E) Unit Dimensions W: In. [mm] 41-11/32 [1,050] D: In. [mm] 13 [330] H: In. [mm] 52-11/16 [1,338] 42-5/16 [1,090] Package Dimensions W: In. [mm] D: In. [mm] 17-3/4 [450] H: In. [mm] 56-5/16 [1,430] Unit Weight Lbs.[kg] 271 [123] 295 [134] Package Weight Lbs.[kg] Outdoor unit operating temperature range Cooling Intake Air Temp (Maximum / Minimum*) IF 115 DB / 23*c DB Cooling Thermal Lock -out / Re -start Temperatures -1 / 3 Heating Intake Air Temp (Maximum / Minimum) IF 70 DB / -4 DB Heating Thermal Lock -out / Re -start Temperatures IF -9 / -4 Refrigerant Type R410A Charge Lbs, oz 10 Ibs, 9 oz Indoor unit connection Maximum Number of Connected IDU 8 (6*A) Minimum Number of Connected IDU 2 Maximum connected capacity BTU/H 62,000 Minimum connected capacity BTU/H 12,000 Piping Gas Pipe Size O.D. (Flared) In.[mm] 5/8 [15.88] Liquid Pipe Size O.D. (Flared) In.[mm] 3/8 [9.52] Total Piping Length Ft. [m] 492 [150] Maximum Height Difference"B, ODU above IDU Ft. [m] 164 [50] Maximum Height Difference"B, ODU below IDU Ft. [m] 131 [40] Maximum Height Difference*B, between branch boxes Ft. [m] 49 [15] Maximum Height Difference"B, between branch boxes and IDU Ft. [m] 49 [15] Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Indoor •• Max. Piping Length between ODU and Branch Ft. [m] 180 [55] Box Farthest Piping Length from ODU to IDU Ft. [m] 262 [80] Farthest Piping Length after Branch Box Ft. [m] 82 [25] Total Piping Length between Branch Boxes and Ft. [m] 311 [95] IDU Maximum Number of Bends 15 Notes AHRI Rated Conditions 'Cooling (Indoor // Outdoor) °F 80 DB, 67 WB H 95 DB, 75 WB (Rated data is zHeating at 47°F (Indoor H Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB determined at a fixed compressor speed) 31-leating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB H 17 DB, 15 WB Conditions 41-leating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 5 WB `Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions. *A when 1 or more PLA-A-EA7 connected `B Branch box should be placed within the level between the outdoor unit and indoor units *c 5°F DB - 115°F DB when optional wind baffles are installed For reference to connected capacity charts, please refer MXC Series Operational Performance Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Distribution pipe for Branch box (Flare Connection) ❑ MSDD-50AR-E Distribution pipe for Branch box (Brazed Connection) Port Adapter size: 3/8" x 5/8" ❑ MSDD-50BR-E ❑ PAC-SG76RJ-E Port Adapter size: 1/4" x 3/8" ❑ PAC-493PI Port Adapter size: 3/8" X 1/2" ❑ MAC-A454JP-E Port Adapter size: 1/2" X 3/8" ❑ MAC-A455JP-E Port Adapter size: 1/2" X 5/8" ❑ MAC-A456JP-E Branch Box ❑ PAC-MKA52BC Branch Box ❑ PAC-MKA32BC Branch Box Outer Cover ❑ BBE-1 Air Outlet Guide ❑ PAC-SH96SG-E (two pieces are required) Front Wind Baffle ❑ WB-PA3 (two pieces are required) ❑ PAC-SJ20BH-E Optional Defrost Heater Centralized Drain Pan ❑ PAC-SH97DP-E Refrigeration Ball Valve- Flare/Schrader/Insulated-1/2" size ❑ BV12FFSI2 Refrigeration Ball Valve- Flare/Schrader/Insulated-1/4" size ❑ BV14FFSI2 Refrigeration Ball Valve- Flare/Schrader/Insulated-3/8" size ❑ BV38FFSI2 Refrigeration Ball Valve- Flare/Schrader/Insulated-5/8" size ❑ BV58FFSI2 Hail Guard ❑ HG-A2 Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic ❑ DSD-400P Condensing Unit Mounting Pad 16" x 36" x 3" ❑ ULTRILITE1 Outdoor Unit Stand —12" High ❑ QSMS1202M Outdoor Unit Stand —18" High ❑ QSMS1802M Outdoor Unit Stand —24"High ❑ QSMS2402M Heavy Duty Wall Mounting Bracket —Coated Steel ❑ QSWB2000M-1 Heavy Duty Wall Mounting Bracket —316 Series Stainless Steel ❑ QSWBSS 10' x 3/8" x 10' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-10 15' x 3/8" x 15' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-15 30' x 3/8" x 30' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-30 50' x 3/8" x 50' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-50 65' x 3/8" x 65' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-65 1 00'x 3/8" x 1 00'x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-100 Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Outdoor unit MXZ-4C36NAHZ2-U1 MXZ-5C42NAHZ2-U1 MXZ-8C48NAHZ2-U1 MXZ-8C48NA2-U1 MXZ-8C60NA2-U1 4HP 4.5HP 5HP 7HP Rated capacity Cooling 36 42 48 60 (kBtu/h) Heating 45 48 54 66 Refrigerant R410A Connectable Capacity class Type 06 to Type 36 indoor unit Caution: The indoor unit which rated capacity exceeds 36 kBtu/ h (Type 36) can NOT be connected. Number of units 2('') to 4 units 2('') to 5 units 2('') to 8 units 2(1) to 8 units Total system capacity range 33 to 130% of outdoor 29 to 130% of outdoor 25 to 130% of outdoor 20 to 130% of outdoor unit capacity unit capacity unit capacity unit capacity (12 to 46.8 kBtu/h) (12 to 54.6 kBtu/h) (12 to 62.4 kBtu/h) (12 to 78 kBtu/h) Connectable Number of units 1 or 2 units branch box G2 Connectable indoor unit lineups (Heat pump inverter type) JL Model type Model name Capacity class [kBtu/h] 06 09 12 15 18 24 30 36 Deluxe Wall -mounted MSZ-FH06/09/12/15NA, 18NA2 Designer 1VSZ-EF09/12/15/18NA(W/B/S) Standard Wall -mounted MSZ-GL06/09/12/15/18/24NA Low static ducted *3.4 SEZ-KD09/12/15/18NA P-series mid static ducted`3'4 PEAD-A09/12/15/18/24/30/36AA7 1-way cassette MLZ-KP09/12/18NA P-series 22*22 4-way cassette SLZ-KF09/12/15NA P-series 33*33 4-way cassette PLA-Al2/18/24/30/36EA7'5 Floor standing MFZ-KJ09/12/15/18NA Standard Multi -position air handler`2 SVZ-KP12/18/24/30/36NA Branch box PAC-MKA52BC PAC-MKA326C Number of branches 5 branches 3 branches (Indoor unit that can be connected) (MAX. 5 units) (MAX. 3 units) Note: A maximum of 2 branch boxes can be connected to 1 outdoor unit. 2- branch pipe (joint): Optional parts In the case of using 1- branch box In the case of using 2- branch boxes No need Model name Connection method MSDD-50AR-E flare MSDD-50BR-E brazing Select a model according to the connection method. (Option (Optional accessories for indoor units and outdoor units are available. I *' Only one unit connection is possible with ducted unit. '2 When connecting a multi -position unit(s), set additional constraints as follows. For connections other than those specified below, consult your dealer. • Models other than MXZ-8C60NA2 (For each connected branch box) • MXZ-8C60NA2 (For each connected branch box) Number of connecting multi -position unit Constraints 2 Any indoor units other than ducted units are not connectable. The total system wide capacity should be 130% or 1 below including the ducted unit. Only 1 ducted unit can be included in the connection. Number of connecting multi -position unit Constraints 2 Any indoor units other than ducted unit are not connectable. The total system wide capacity should be 100% or 1 below including the ducted unit. Only 1 ducted unit can be included in the connection. 3 For MXZ-8C60NA2; When connecting the SEZ and PEAD-series units, the total system wide capacity per 1 branch box should be 100% or below including the ducted units. (Only if connecting to branch box) •4 When not outside units 60: A branch box can connect to maximum 3 of the ducted units. When connecting with 3 of the ducted units per 1 branch box, other indoor units cannot be connected. When outside units 60: A branch box can connect to maximum 2 of the ducted units. When connecting with 1 and over 1 of the ducted units, the total ability including of the ducted units is 100% and below 100%. '5 When the system includes 1 unit of ducted units, the number of the maximum connectable indoor units is decreased as follows: 3 for MXZ-4C36NAHZ2-1J1, 4 for MXZ-5C42NAHZ2-1J1, and 6 for MXZ-8C48NA(HZ)2-U1 and MXZ-8C60NA2-U1 13 NOTE Please refer to Application Note 1029 for more information and exceptions to these rules. Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Piping connection size A B Liquid 03/8 inch The piping connection size differs according to the type and capacity of indoor units. [9.52 mm] Match the piping connection size of branch box with indoor unit. p�p� g If the piping connection size of branch box does not match the piping connection size of Gas 05/8 inch /03/4 inch* indoor unit, use optional different -diameter (deformed) joints to the branch box side. [15.88 mm] [19.05 mm] I (Connect deformed joint directly to the branch box side.) * MXZ-8C60 only ■ In case of using 1-branch box Flare connection employed (No brazing) ■ In case of using 2-branch boxes 7 hrnnnhnz nines finintl Branch box #2 ■ Installation procedure (2 branches pipe (joint)) Refer to the installation manuals of MSDD-50AR-E and MSDD-50BR-E. Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. 1 FREE SPACE(Around the unit) 2 SERVICE SPACE 3 FOUNDATION BOLTS 4 PIPING -WIRING DIRECTIONS The diagram below shows a bask example. Dimensions of space needed Pleasesecuretheunkhmlfy Piping and wiling connections Explanation of particular details are forseniceaccessare with 4foundation (MlO<W3/8>)Into, can be made from directions: given in the 1nsrollation manualsetc shown in the below diagram. (Bolts and washers must be Front Right Rear and Below. {� purchased locally) <Foundation bolt height> Aga Service7.M e ------------------------------ Min. 500 <1&11/16> �"""'W✓ Rear Air Intake Side Air Intake ' nn 11 Handle for Handlefor Example of Notes lO • • •Refrigrant GAS pipe conneNon(FLARQO A n O • • • Refrigerant LIQUID Ode connection (FLAKE) 09.52(3/8n M1 • • .Indication of STOP VALVE connection location. Piping Knoc I I[--�• - i.,I R. RearAir Intake 2%U Shaped notched holes 225 600 225 (Foundation Bolt M10<W3/8>) <8-27/32> <23-5/8> <8-27/32> Insulation Feet Side Air Intake M 56<2-7/32> PEW 40<1-37/64> 0 53<2-3/32> r 70 Q-3/4> 42<1- 21/32> 60.5<2-3/8> �Airl)ischapgie 2A1 R36 valholes \ (Foun1ationaoItMto<W3/8>) ry erminalconneaion From khto right 1050<41-11/32> Forthe Forthe orthe Fora Handleformovin 362<14-1/4> Ground for the power supply powersupply banch box ansmissron line cant^ r R`markun sound) powersupply Ground for the transmission line Ground for concentration control Service and • Handlefor WheninszllingthemAdt. SettheaMchmenttothe inner side of each panel. 60<2-3/8> 74<15/16> > Ilrach Oncuh arcxhmem !,.!f22.2,77/8> 1015<4> Sole 15 min <inch> PAC-MKA52BC SUSPENSION BOLT PITCH 320 <12-10132) SUSPENSION BOLT: W3/8(M10) REFRIGERANT PIPE FLARED CONNECTION Unit: inch A B C D E TOOUTDOORUNIT LIQUID PIPE 114E 114E 114E 114E 114E 3/8F GAS PIPE 3/8F 3/8F 3/8F 3/8F 1/2F 5/8F E. PAC-M KA32 BC SUSPENSION BOLT PITCH 320 02.100 SUSPENSION BOLT. W3/8(M10) REFRIGERANT PIPE FLARED CONNECTION Unit: inch A B C TO OUTDOOR UNIT LIQUID PIPE 1/4F 114E 1/4F 318F GAS PIPE 3/8F 3/8F 1318F I I I 518F FORM# MXZ-8C48NA2 - 202003 Unit: mm <inchh> When installing the conduit. 1 Set the attachment to the inner side of each panel. 50 (]-g132) (z5�3� (1aFszJ a m � Sm22C]I8) 37 1n mph cona�n anacnmem 15 C18I32) Pw' 00(2-1.2) y TERMINAL BLOCK TO M-NET UNIT TERMINALBLOCK TO INDOOR UNIT I TERMINALBLOCK TO OUTDOOR UNIT When installing the conduit. Set the attachment to the inner side of each panel. 58 Q-8I32) (2232) <1.2 2. �b «a e —A 1���Contlue 15 C19132i _ BB(2-19132) f (1:21 TERMINA 131- K TO M-NET UNIT TERMINALBLOCK TO INDOOR UNIT •• ®m •• TERMINAL BLOCK TO OUTDOOR UNIT 1340 Satellite Boulevard, Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com C ETI US Intertek Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.