BLD2020-1301 AAftiMOS7itodwd HEATING & AIR CONDITIONING Product Data RECEIVED Dec 04 2020 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT REVIEWED BY CITY OF EDMONDS Variable Speed Accul-inkTM Side Discharge Heat Pump For coastal applications where units are installed within one (1) mile of salt water, epoxy coated models are recommended. These models have an 8 week lead time after order. 4A61-9024A1000A 4A61-9036A1000A 4A61-9048A1000A 4A6L9060A1000A Epoxy Coated Model 4A61-9024A1 COTA 4A61-9036A1 COTA 4A61-9048A1 COTA 4A61-9060A1 COTA Note: "Graphics in this document are for representation only. Actual model may differ in appearance. " March 2020 12-1399-1 C-EN �cati, �S'7 iw HEATING & AIR CONDITIONING Mechanical Specification Options General The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. This unit is designed to operate at outdoor ambient temperatures from 55' F to 120' F in cooling. From —10' F to 66' F in heating. Only AHRI approved indoor matches are approved for use with these models. This outdoor unit contains the Accul-inkT" digital communication with 2 wire connection to outdoor and Plug-n-Play set up. Casing Unit is painted with a glossy corrosion resistant finish on all panels. Refrigerant Controls Refrigeration system controls include condenser fan, high and low pressure switches. A factory supplied, field installed filter drier is standard. Compressor Output Capacity by Tonnage 024,036 50 to 100% 048 35 to 100% 060 30 to 100% Noise enclosure minimizes sound levels and built in compressor protection will reduce operating speed and current draw to maintain operation while protecting the compressor. Condenser Coil The copper tube, aluminum fin outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected by a wire guard. Low Ambient Cooling As manufactured, this system has built in freeze protection that will allow cooling operation down to 45°F but will reduce capacity or shut down completely to prevent operation under adverse conditions. Comfort Control The 1050/950/850 Control is required and provides Plug-n-Play setup and 3 wire connection. 12-1399-1 C-E N HEATING & AIR CONDITIONING Product Specifications OUTDOOR UNIT fie) 4A6L9024A1XXXA 4A6L9036A1XXXA POWER CONNS. — V/PH/HZ (b) 208-230/1/60 208-230/1/60 MIN. BIRCH. CIR. AMPACITY 19.1 26.9 BR. CIR. PROT. RTG. — MAX. (AMPS) 25 30 COMPRESSOR DURATION@- SCROLL DURATION@- SCROLL NO. USED — NO. STAGES 1 —Variable 1 — Variable VOLTS/PH/HZ 208-230/1/60 208-230/1/60 R. L. AM PS W / L. R. AM PS 8.5 / 48.9 12.4 / 48.9 FACTORY INSTALLED STARTCOMPONENTS NO NO INSULATION/SOUND BLANKET YES YES SUMP HEAT YES YES OUTDOOR FAN PROPELLER DIA. (IN.) — NO. USED 27.5 - 1 27.5 — 1 TYPE DRIVE — NO. SPEEDS DIRECT— VARIABLE DIRECT —VARIABLE CFM @ 0.0 IN. W.G. (d) 2400 2400 NO. MOTORS — HP 1-1/2 1-1/2 MOTOR SPEED R. P.M. 200-1050 200-1050 VOLTS/PH/HZ 325-385 VDC/3/60 325-385 VDC/3/60 F.L. AMPS 2.3 2.3 OUTDOOR COIL — TYPE PLATE FIN PLATE FIN ROWS—F.P.I. 1-16 2-16 FACE AREA (SQ. FT.) 12.88 12.88 TUBE SIZE (IN.) 5/16 5/16 REFRIGERANT LBS. — R-410A (O.D. UNIT) (e) 6LBS., 8 OZ 8 LBS, 0 OZ FACTORY SUPPLIED YES YES OLINE SIZE — IN. O.D. GAS M (9) 5/8 3/4 LINE SIZE — IN. O.D. LIQ. 3/8 3/8 CHARGING SPECIFICATIONS SUBCOOLING COOLING MODE 10°F 100 F DIMENSIONS HXWXD HXWXD CRATED (IN.) 42 x 56 x 24 42 x 56 x 24 UNCRATED (IN.) 36-3/4 X 47 X 17-1/2 36-3/4 X 47 X 17-1/2 WEIGHT SHIPPING (LBS.) 229 250 NET (LBS.) 204 226 0) Certified in accordance with the Air -Source Unitary Air -conditioner Equipment certification program, which is based on AHRI standard 210/240; Rated in accordance with AHRI standard 275; (b) Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses. W This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current. (d) Standard Air — Dry Coil — Outdoor (e) This value approximate. For more precise value see unit nameplate. M Reference the outdoor unit ship -with literature for refrigerant piping length and lift guidelines. Reference the refrigerant piping software pub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denotes latest revision). (9) The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. Always verify proper system charge via subcooling (TXV/EEV) or superheat (fixed orifice) per the unit nameplate. 12-1399-1 C-EN 4*w a" S7iwdard HEATING & AIR CONDITIONING Product Specifications OUTDOOR UNIT (a) 4A6L9048A1XXXA 4A6L9060A1XXXA POWER CON NS. — V/PH/HZ (b) 208-230/1/60 208-230/1/60 MIN. BRCH. CIR. AMPACITY 31.8 36.1 BR. CIR. PROT. RTG. — MAX. (AMPS) 35 40 COMPRESSOR DURATION@- SCROLL DURATION@- SCROLL NO. USED — NO. STAGES 1 — Variable 1 — Variable VOLTS/PH/HZ 208-230/1/60 208-230/1/60 R. L. AM PS (_) / L. R. AM PS 12.4 / 48.9 12.4 / 48.9 FACTORY INSTALLED START COMPONENTS NO NO INSULATION/SOUND BLANKET YES YES SUMP HEAT YES YES OUTDOOR FAN PROPELLER PROPELLER DIA. (IN.) — NO. USED 27.5 — 1 27.5 — 1 TYPE DRIVE — NO. SPEEDS DIRECT— VARIABLE DIRECT— VARIABLE CFM @ 0.0 IN. W.G. (d) 3500 4000 NO. MOTORS — HP 1-1/2 1-1/2 MOTOR SPEED R. P.M. 200-1050 200-1050 VOLTS/PH/HZ 325-385 VDC/3/60 325-385 VDC/3/60 F.L. AMPS 2.3 2.3 OUTDOOR COIL — TYPE PLATE FIN PLATE FIN ROWS—F.P.I. 2-16 2-16 FACE AREA (SQ. FT.) 15.02 15.02 TUBE SIZE (IN.) 5/16 5/16 REFRIGERANT LBS. — R-410A (O.D. UNIT) (e) 9 LBS, 0 OZ. 9 LBS, 0 OZ. FACTORY SUPPLIED YES YES LINE SIZE — IN. O.D. GAS M 7/8 (g) 7/8 (h) LINE SIZE — IN. O.D. LIQ. 3/8 3/8 CHARGING SPECIFICATIONS SUBCOOLING COOLING MODE 100 F 10°F DIMENSIONS HXWXD HXWXD CRATED (IN.) 48 x 56 x 24 48 x 56 x 24 UNCRATED (IN.) 42-3/4 X 47 X 17-1/2 42-3/4 X 47 X 17-1/2 WEIGHT SHIPPING (LBS.) 269 269 NET (LBS.) 245 245 (a) Certified in accordance with the Air -Source Unitary Air -conditioner Equipment certification program, which is based on AHRI standard 210/240; Rated in accordance with AHRI standard 275. (b) Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses. W This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current. (d) Standard Air — Dry Coil — Outdoor (e) This value approximate. For more precise value see unit nameplate. M The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. Always verify proper system charge via subcooling (TXV/EEV) or superheat (fixed orifice) per the unit nameplate. (9) Reference the outdoor unit ship -with literature for refrigerant piping length and lift guidelines. Reference the refrigerant piping software pub # 32-3312-xx or refrigerant piping application guide SS-APG006-xx for long line sets or specialty applications (xx denotes latest revision). (h) Max. linear length 150 ft,; Max. lift - Suction 50 ft,; Max. lift - Liquid 50 ft. 12-1399-1 C-E N �c icati, �S'7 iw HEATING & AIR CONDITIONING Sound Pressure Level Outdoor Unit T ft 5' ft Table 1. 2.0 Ton Heating Reflective Surface (Back wall) Sound Pressure Level dB(A) per ARI 275 (Max Heating) # Reflective Surfaces 3 from Property Line 5' from Property Line 7' from Property Line 0 46 41 1 49(a) 44 2 52 47 44 W Lab tested as per the illustration shown above Table 2. 2.0 Ton Cooling Sound Pressure Level dB(A) per ARI 275 (Max Cooling) # Reflective Surfaces 3' from Property Line S' from Property Line 7' from Property Line 0 47 42 1 50(a) 45 2 53 48 45 0) Lab tested as per the illustration shown above Table 3. 3.0 Ton Heating Sound Pressure Level dB(A) per ARI 275 (Max Heating) # Reflective Surfaces 3' from Property Line S' from Property Line 7' from Property Line 0 46 41 1 49(a) 44 2 52 47 44 la) Lab tested as per the illustration shown above Table 4. 3.0 Ton Cooling Sound Pressure Level dB(A) per ARI 275 (Max Cooling) # Reflective Surfaces 3' from Property Line 5' from Property Line 7' from Property Line 0 45 1 48W 43 2 51 46 43 W Lab tested as per the illustration shown above 12-1399-1 C-E N 5 71*i eao Svdctrd® HEATING & AIR CONDITIONING Sound Pressure Level Table 5. 4.0 Ton Heating Sound Pressure Level dB(A) per ARI 275 (Max Heating) # Reflective Surfaces 3' from Property Line S' from Property Line 7' from Property Line 9' from Property Line 0 49 44 1 52(a) 47 44 2 55 50 47 45 (a) Lab tested as per the illustration shown above Table 6. 4.0 Ton Cooling Sound Pressure Level dB(A) per ARI 275 (Max Cooling) # Reflective Surfaces 3' from Property Line 5' from Property Line 7' from Property Line 9' from Property Line 15' from Property Line 0 51 46 43 1 54(a) 49 46 44 2 57 52 49 47 43 (a) Lab tested as per the illustration shown above Table 7. 5.0 Ton Heating Sound Pressure Level dB(A) per ARI 275 (Max Heating) # Reflective Surfaces 3' from Property Line 5' from Property 7' from Property 9' from Property 15' from Property 20' from Property Line Line Line Line Line 0 54 49 46 44 1 570) 52 49 47 43 2 60 55 52 50 46 43 (a) Lab tested as per the illustration shown above Table 8. 5.0 Ton Cooling Sound Pressure Level dB(A) per ARI 275 (Max Cooling) # Reflective Surfaces 3' from Property Line 5' from Property Line 7' from Property Line 9' from Property Line 15' from Property Line 0 53 48 45 1 56(a) 51 48 46 42 2 59 54 51 49 45 (a) Lab tested as per the illustration shown above Notes: • Measuring place: Hemi-Anechoic chamber • Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed. • Operation sound level may differ depending on operation and ambient conditions. 6 12-1399-1 C-E N HEATING & AIR CONDITIONING Sound Pressure Level 4A6L9024A15ound Characteristics 4A6L9036A15ourid Characteristics Cooling Heating Cooling Heating 0 0 r — r-- r -2 J A -3 ' -3 j u / J m -4 b m M j J � -4 -5 r -6 -5 -7 0 20 40 60 w 100 0 20 40 6D 80 1�1� % Demand X Demand 4A6L9048A15aund Characteristics 4A6L9060A15ound Characteristics Cooling Heating — — Cooling Heating r - l -2 -2 f r -3 J _3 r y ► `y A y r-4 j A s s r -7 c J A 7 -g .. -10 _ 0 20 40 60 BO 100 0 20 40 60 > :Lc' % Demand % Demand 12-1399-1 C-EN 00 LEGEND LINE :lwTS,T PMa PLTERRM NAS,NGDGING 11} POL LELEU7NpuLE HOUSING LINE J WIA�XG ® [uA E IXAL51 ----- FACTORI A NG �—A.aro or NlvL Brc/BL MAGNETIC COIL _ R'. or xAIIN GROUND JUNCTION rx rINN xR NeA Ix n vuxv¢ 0 WIPE XUi OR O TEAMINAL TNERNISTOR r—o INTERNAL OVERLOAD PROTECTION PRESS RE CON RES ISIiEA OR NEATDI N6 SWITCH E CEMENT - L^T[D D 0 MOTOR WINDINGFENIILl NGDR ED -ILGIE CABLE 0 FERAIiED BEAD ENTER COxTAOL noL N W 1p n r!n z EEV sc RD— — BLB�— l lmi i V\ CLII HE ----------------------- ®R AOC �BBLAD R EEV � CLII E M0C 1, (PRINTED FROM DI60092P01 RENA Notes 12-1399-1 C-EN Aw ew Si�uidsrd HEATING & AIR CONDITIONING About American Standard Heating and Air Conditioning American Standard has been creating comfortable and affordable living environments for more than a century. For more information, please visit www.americanstandardair.com. c@us LISTED The AHRI Certified mark indicates company participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory.org. The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. 12-1399-1C-EN 19Mar202O Supersedes 12-1399-1 B-EN (July 2018) © 2020 American Standard Heating and Air Conditioning