APPROVED BLD PLN BLD2021-0693+Mechanical_SITE Plan+5.19.2021_1.43.25_PM+2206144MECHANICAL ABBREVIATIONS A AMPS AC AIR CONDITIONING ACH AIR CHANGES PER HOUR ACT ACOUSTICAL CEILING TILE AD ACCESS DOOR ADD'L ADDITIONAL AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AHU AIR HANDLING UNIT ALUM ALUMINUM AMP/AMPS AMPERAGE AP ACCESS PANEL ARCH ARCHITECT BC BEADED COLLAR BDD BACKDRAFT DAMPER BF BELOW FLOOR BHP BRAKE HORSEPOWER BLDG BUILDING BOD BOTTOM OF DUCT BOP BOTTOM OF PIPE BOT BOTTOM BS BIRD SCREEN / BLACK STEEL BTU BRITISH THERMAL UNIT BTUH BRITISH THERMAL UNITS PER HOUR CAP CAPACITY CBD CALIBRATED BALANCING DAMPER CC CONTROLS CONTRACTOR CD CEILING DIFFUSER/CONDENSATE DRAIN CDWR CONDENSER WATER RETURN CDWS CONDENSER WATER SUPPLY CFM CUBIC FEET PER MINUTE CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CLG CEILING COL COLUMN CONIC CONCRETE COND CONDENSATE CONN CONNECT/CONNECTED/CONNECTION CONT CONTINUOUS/CONTINUATION CONTR CONTRACTOR COORD COORDINATE COP COEFFICIENT OF PERFORMANCE CT COOLING TOWER CU CUBIC/CONDENSER UNIT CW DOMESTIC COLD WATER/CONDENSER WATER DB DUCTBOARD/DRY BULB/DECIBEL DDC DIRECT DIGITAL CONTROL DEFL DEFLECTION DEG DEGREE/DEGREES DIA DIAMETER DMPR DAMPER DN DOWN DOAS DEDICATED OUTSIDE AIR SYSTEM DWG DRAWING EXH EXHAUST EA EACH/EXHAUST AIR EAT ENTERING AIR TEMPERATURE EC EGGCRATE GRILLE/END CAP/ELEC CONTRACTOR EER ENERGY EFFICIENT RATING EF EXHAUST FAN EFF EFFICIENCY EL ELEVATION ELEC/ELECT ELECTRICAL/ELECTRIC EMCS ENERGY MANAGEMENT CONTROL SYSTEM ENT ENTERING EQUIP EQUIPMENT ESP EXTERNAL STATIC PRESSURE EWT ENTERING WATER TEMPERATURE EXIST/(E) EXISTING EXH EXHAUST F FAHRENHEIT FAC FIRE ALARM CONTRACTOR FD FIRE DAMPER FDC FIRE DEPARTMENT CONNECTION FF FINISHED FLOOR FIC FURNISHED AND INSTALLED BY CONTRACTOR FIO FURNISHED AND INSTALLED BY OWNER FLA FULL LOAD AMPS FLEX FLEXIBLE FLR FLOOR FOB FLAT ON BOTTOM FOIC FURNISHED BY OTHERS, INSTALLED BY CONTRACTOR FOS FLAT ON SIDE FOT FLAT ON TOP FP FIRE PROTECTION FPM FEET PER MINUTE FSD FIRE/SMOKE DAMPER FT FOOT/FEET FUT FUTURE FV FACE VELOCITY G GRILLE GA GAUGE/GALLON GALV GALVANIZED GC GENERAL CONTRACTOR GPM GALLONS PER MINUTE GRID GRILLE/REGISTER/DIFFUSER GWB GYPSUM WALL BOARD HD HEAD HORIZ HORIZONTAL HP HORSEPOWER HR HOUR HSPF HEATING SEASONAL PERFORMANCE FACTOR HT HEIGHT HWTG HIGH WALL TRANSFER GRILLE HWR HOT WATER RETURN HWS HOT WATER SUPPLY HX HEAT EXCHANGER HZ HERTZ IBC INTERNATIONAL BUILDING CODE ICW INDUSTRIAL COLD WATER ID INSIDE DIAMETER/DIMENSION IE INVERT ELEVATION IEER INTEGRATED ENERGY EFFICIENCY RATIO IMC INTERNATIONAL MECHANICAL CODE IN INCHES IN WG INCHES WATER GAUGE IPLV INTEGRATED PART LOAD VALUE KW KILOWATTS LAT LEAVING AIR TEMPERATURE LB/LBS POUND/POUNDS LF/LIN FT LINEAL FOOT/FEET LPG LIQUID PROPANE GAS LPS LOW PRESSURE STEAM LVG LEAVING LWA SOUND POWER RATING LEVEL (IN DB) LWG LOW WALL GRILLE LWT LEAVING WATER TEMPERATURE MAX MAXIMUM MAU MAKE UP AIR UNIT MBH 1000 BRITISH THERMAL UNITS/HOUR MCA MINIMUM CIRCUIT AMPACITY MD MOTORIZED DAMPER MFR MANUFACTURER MISC MISCELLANEOUS MIN MINIMUM/MINUTE MPS MEDIUM PRESSURE STEAM MT MOUNT MTD MOUNTED MUW MAKE-UP WATER NA NOT APPLICABLE NC NORMALLY CLOSED/NOISE CRITERIA NG/NGAS NATURAL GAS NIC NOT IN CONTRACT NO NORMALLY OPEN/NUMBER NPW NON -POTABLE WATER N-R NON-RESIDENTIAL OA/OSA OUTSIDE AIR OBD OPPOSED BLADE DAMPER OD OUTSIDE DIAMETER/DIMENSION PCF POUNDS PER CUBIC FOOT PD PRESSURE DROP PH PHASE POC POINT OF CONNECTION P/PRESS PRESSURE PSI POUNDS PER SQUARE INCH PSIG POUNDS PER SQUARE INCH GAUGE QTY QUANTITY R RETURN GRILLE/RELOCATED/RETURN RA RETURN AIR RD/RND ROUND REF REFERENCE REQ REQUIRED RESID RESIDENTIAL RF RELIEF RG REFRIGERANT DISCHARGE GAS RL REFRIGERANT LIQUID RPM REVOLUTIONS PER MINUTE RS REFRIGERANT SUCTION S SUPPLY SA SUPPLY AIR SAT SATURATION/SUPPLY AIR TEMPERATURE SD SMOKE DETECTOR S/D SLIP & DRIVE CONNECTION S_C SEATTLE CODE SEER SEASONAL ENERGY EFFICIENCY RATING SENS SENSIBLE SL SOUND LINED SM SHEETMETAL SPEC SPECIFICATION SO SCREENED OPENING SOG SLAB ON GRADE SP STATIC PRESSURE SF SQUARE FEET SS STAINLESS STEEL STRUC STRUCTURAL TA TRANSFER AIR TEMP TEMPERATURE/TEMPORARY TBD TO BE DETERMINED TOD TOP OF DUCT TOS TOP OF STEEL/TOP OF SLAB TOT TOTAL TSP TOTAL STATIC PRESSURE TSTAT THERMOSTAT TYP TYPICAL UH UNIT HEATER UNO UNLESS NOTED OTHERWISE V VOLT VA VENTILATION AIR VD VOLUME DAMPER VEL VELOCITY VERT VERTICAL VFD VARIABLE FREQUENCY DRIVE VOL VOLUME W WRAPPED DUCT WB WET BULB WG WATER GAUGE W/ WITH W/0 WITHOUT W/SF WATTS PER SQUARE FOOT WSEC WASHINGTON STATE ENERGY CODE �-CHWS/CHWRj CHILLED WATER SUPPLY/RETURN RL/RS----s REFRIGERANT LIQUID/SUCTION N G NATURAL GAS Z LPG LIQUID PROPANE GAS �--CDWS/CDWR-s CONDENSER WATER SUPPLY/RETURN z-HWS/HWR--S HEATING WATER SUPPLY/RETURN 2- COND CONDENSATE 2 FOV FUEL OIL VENT �--FOS/FORS FUEL OIL SUPPLY/RETURN zRDG REFRIGERANT DISCHARGE GAS MECHANICAL LEGEND t10"X10"M RECT SUPPLY AIR DUCT 10"X10" UP/TOWARD 10"X10" RECT SUPPLY AIR DUCT 10"X L D DN/AWAY 10"X10" P1 RECT RETURN DUCT 10"X10" UP/TOWARD 10"X10" RECT RETURN DUCT 10"X10 DN/AWAY t10"X10"M RECT EXHAUST 10"X10" UP/TOWARD 10"X10" RECT EXHAUST 10"X10" DN/AWAY 105 GD 10� ROUND DUCT - UP/TOWARD 10" o i 10 ROUND DUCT - DN/ AWAY 12"X10"O FLATOVAL DUCT - UP/ TOWARD 12"X10"O FLATOVAL DUCT - DN/ AWAY 10"0 o DUCT OVERLAP 10" o BOOT TAP 10" o 10" o 45° TAP 10"0 VOLUME DAMPER 10�� 1ONO i 1 CALIBRATED BALANCING DAMPER RLD- RISE(R) & DROP(D) TRANSITION TURNING VANES/SPLITTERS DUCT MOUNTED SMOKE DETECTOR BDD BACK DRAFT DAMPER FLEXIBLE DUCT n� AIR FLOW (FORCED AIR) �7 COMBINATION FSD FIRE DAMPER SMOKE DAMPER MOTOR OPERATED DAMPER 0 0 o t ACCESS DOORS SOUND TRAP FLEX CONNECTION El 6"X 16"0 aSLa ACOUSTICALLY LINED DUCT OD = OUTSIDE DIMENSIONS SL = SOUND LINING (THICKNESS) FABRIC DUCT CLEARANCE ® SUPPLY AIR DIFFUSER (WITH CORE BLANKOFF/ROTATE) ® CEILING EXHAUST AIR GRILLE CEILING RETURN OR TRANSFER AIR GRILLE o SLOTTED DIFFUSER (PLAN VIEW) Qx REVISION CLOUD & TRIANGLE ##"0 ROUND DUCT SYMBOL ##X##'O FLATOVAL DUCT SYMBOL ##° DEGREES SYMBOL S POINT OF CONNECTION CD1-100 GRID TAG IDENTIFIER = TYPE-CFM 8" 0 SIZE (DT'STAT/TEMP SENSOR CARBON DIOXIDE ( HUMIDITY SENSOR SENSOR sD SMOKE DETECTOR CO CARBON MONOXIDE SP STATIC PRESSURE SENSOR SENSOR OO OCCUPANCY SENSOR (D SENSOR EXISTING DUCTWORK DEMO DUCTWORK WALL -MOUNTED GRILLE PIPE ELBOW UP o PIPE ELBOW DN DIRECTION OF FLOW - DIRECTION OF SLOPE DOWN PLUG OR CAP PRESS REDUCING ASSEMBLY SOLENOID VALVE PUMP MECHANICAL GENERAL NOTES 1. WORK SHALL CONFORM TO APPLICABLE CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE 2018 IBC, 201AWPiuc- V D & SIMILAR YEAR WAC 296-104 BOILER RULES. JE 2. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN. DIMENSIONS ARE TO FACE OF STUD, CONCRETE, OR MASONRY N S MUST BE 3. LOCATION AND DETAILS OF EQUIPMENT, DUCT ROUTING AND CONNECTIONS ARE APPROXIMATE. COORDINATE FINAL LO 0 WITI� OTHER TRADES. INSTALL IN ACCORDANCE WITH APPROVED SUBMITTALS AND DETAIL DRAWINGS WHEN APPLICABLE. ON JOB SITE 4. VERIFY EXISTING CONDITIONS, DIMENSIONS, DETAILS, ETC. NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK. 5. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK, DETAILS SHALL BE THE AS FOR OTHER SIMILAR WORK. IF ADDITIONAL QUESTIONS REMAIN, CONTACT THE ENGINEER PRIOR TO PROCEEDING. 6. ALL STRUCTURAL OPENINGS AND PLATFORMS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR UNO. ALL WORK SUBJECT 7. DUCT SEALING AND CONSTRUCTION TO MEET SMACNA AND ENERGY CODE REQUIREMENTS. UNO: LOW PRESSURE D CTWORK DOWN�'fR'EAT1�d1=`bAV BOXES, CONSTANT VOLUME AC SYSTEMS, TOILET EXHAUSTS, ETC.) TO MEET 2" C,ONSTRUCTION CLASS WITH SEAL CLASS C. EDIU�P fe17I�ONR f OR (UPSTREAM >OF WI H BOXES, CLASS A). DUCT CTCITY EXHAUSTS, IN ETC.) WITH MEET DAM EREDT PENETRATIONS ONSCLASS TO MEET SEAL 6" CONTT U kamoll"_V�Ij _OUTDOOR INSTALLED SUPPLY & RETURN DUCTS TO HAVE SEAL CLASS A. C 8. ALL CEILING DIFFUSERS ARE 4-WAY THROW UNLESS NOTED OTHERWISE. 9. ALL DUCT DIMENSIONS ARE OUTSIDE DIMENSIONS BEFORE SOUND LINING HAS BEEN ACCOUNTED FOR (SOUND LINING @ 1", UNO) 10. OUTSIDE AIR INTAKES ON ALL AIR HANDLING UNITS SHALL BE 10 FEET AWAY FROM ANY VENTS, STREETS, LOADING DOCK, NEIGHBORING LOT LINES & FUEL BURNING EQUIPMENT OR 3 FEET BELOW OR 25' ABOVE ANY CONTAMINANT SOURCE WITHIN 10 FEET. 11. ALL AIR ECONOMIZERS SHALL BE CAPABLE OF THE FOLLOWING PER C403.3.1 & C403.2.4.7: -0% TO 100% OF THE DESIGN SUPPLY AIR WITH FAULT DETECTION & DIAGNOSTIC REPORTING. -CONTROLLED BY A CONTROL SYSTEM DETERMINING IF THE OUTSIDE AIR CAN MEET PART OR ALL OF THE BUILDING COOLING LOADS. -INTEGRATED TO PROVIDE PARTIAL COOLING EVEN WHEN MECHANICAL COOLING IS REQUIRED. 12. OUTSIDE AIR INTAKE, RELIEF, AND EXHAUST OPENINGS SHALL BE EQUIPPED WITH MOTORIZED CLASS 1 LOW LEAK (<4 CFM/SF @ 1" WG) DAMPERS (OR GRAVITY PER EXCEPTIONS IN C403.2.4.3) DAMPERS WHICH CLOSE AUTOMATICALLY WHEN SYSTEM IS OFF OR UPON POWER FAILURE, UNO FOR SMOKE CONTROL SYSTEM OPERATION. 13. THE CONTROL SYSTEM SHALL MEET C403 AND BE PROGRAMMABLE, CAPABLE OF BEING SET FOR DIFFERENT DAY TYPES PER WEEK, DEADBAND SETTING OF AT LEAST 57 (107 FOR RESIDENNfROL , BETWEEN THE HEATING AND COOLING SETPOINTS AND SETBACK TEMPERATURES WITH OPTIMAL START CONTROL. SYSTEM SHALL INCLUDE A MICROPROCESSOR AND BE CAPABLE OF VARYING FLOWS AND RESETTING SUPPLY AIR & WATER TEMPERATURES BY REPRESENTATIVE BUILDING LOADS WHERE REQUIRED IN C403.4. 14. WHERE REQUIRED BY C408, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS OF THE DATE OF SYSTEM ACCEPTANCE PER THE ENERGY CODE. AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER. ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCING REPORT SHALL BE PROVIDED TO THE OWNER. HVAC CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT THEY OPERATE IN ACCORDANCE WITH APPROVED PLANS. A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY. A COMPLETE FINAL COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PROVIDED TO THE OWNER. 15. MECHANICAL SYSTEMS SHALL COMPLY WITH SEISMIC RESTRAINT REQUIREMENTS OF THE BUILDING CODE, SMACNA AND ASCE 7. ALL LIFE SAFETY OR HAZARDOUS MATERIAL RELATED SYSTEMS SHALL BE DEEMED AN Ip=1.5 FOR RESTRAINT METHODS OR AS NOTED ON THE DRAWINGS. REFER TO CODES FOR INSTALLATION REQUIREMENTS AND EXCEPTIONS BASED ON SIZING, WEIGHTS AND MOUNTING HEIGHTS. 16. PROVIDE EARTHQUAKE RESTRAINTS FOR HVAC EQUIPMENT AS REQUIRED BY SMACNA SEISMIC RESTRAINT MANUAL, SEISMIC HAZARD B. WIRES FOR CEILING SYSTEM ETC. SHALL NOT BE HUNG OFF HVAC EQUIPMENT OR HVAC EQUIPMENT SUPPORTS. 17. PROVIDE FIRE AND COMBINATION FIRE/SMOKE DAMPERS WHERE SHOWN ON PLANS AND WHERE REQUIRED PER CODE, AT 1-1/2 HR RATING UNO. 18. ALL PIPING PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE SEALED WITH AN UL APPROVED FIRE CAULKING. ALL MATERIALS EXPOSED WITHIN PLENUMS SHALL BE NON-COMBUSTIBLE OR SHALL BE UL LISTED AND LABELED FOR INSTALLATION IN PLENUMS OR AS HAVING A FLAME SPREAD INDEX <- 25 AND A SMOKE -DEVELOPED INDEX OF <- 50. 19. SMOKE DETECTORS PROVIDING AUTOMATIC SHUTDOWN SHALL BE PROVIDED IN THE RETURN AIR, PER MECH CODE, SUCH AS HVAC EQUIPMENT DELIVERING (NOT EXHAUST) >2000 CFM (INCLUDING MULTIPLE UNITS DUCTED INTO COMMON DISTRIBUTION OR RETURN, WITH A TOTAL SUPPLY >2000 CFM) OR EACH STORY OF RETURN SYSTEMS OVER 15,000 CFM IN A MULTI -STORY INSTALLATION, NOT IN SYSTEMS SERVING SINGLE ROOMS/SPACES. SMOKE DETECTORS SHALL BE FIC (ELEC) UNO. POWER -WIRING AND INTERLOCK TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR AS APPLICABLE. VAV BOX (WITH FAN) SHUTDOWN CAN BE THROUGH CONTROLS SYSTEM. 20. ARCHITECTURAL ACCESS PANELS SHALL BE PROVIDED AND INSTALLED BY GC AT ALL CONCEALED EQUIPMENT AND DEVICE LOCATIONS, UNLESS NOTED OTHERWISE. 21. ALL MOTOR STARTERS NOT SHOWN IN EQUIPMENT SCHEDULES SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. MOTOR EFFICIENCIES TO MEET OR EXCEED CODE MINIMUM. 22. FOR ALL "SEALED AIR TGHT" OR PRESURZEDUSE SECTION 909.5I OF THE 2015 SBCI FOR SMAX AHAFTSLLOWABLE ROOMS �LEEAKAGE AREA,TFOLLOW NG D PRESSURE/EMERATURETHE GUIDELINES HUMIDITY NTFOR TIGHT OLLED ROOSTAIRTSHAFTLCONISTRUCTION.00CUR: -ALL VERTICAL JOINTS, CORNERS AND WALL TRACKS (TOP AND BOTTOM) SHALL BE PROVIDED WITH A CONTINUOUS SEAL FOR THE LENGTH OF THE JOINT (BY GC) -ANY FLOOR DECKING PERPENDICULAR TO THE CONSTRUCTION SHALL BE CAULKED (BY GC). FILLING WITH ROCK WOOL IS NOT ACCEPTABLE. -ANY PENETRATIONS OF THE CONSTRUCTION (DUCTWORK, CONDUIT, PIPING, ...) SHALL BE SEALED ON BOTH SIDES -ALL DOORS SHALL BE PROVIDED WITH TIGHT FITTING GASKETS AND THRESHOLD SWEEPS, AND OPEN AGAINST THE DIRECTION OF PRESSURE. -IN ADDITION TO ABOVE, ROOM ENVELOPE TO HAVE VAPOR BARRIER FOR HUMIDITY CONTROLLED ROOMS -ROOM ENVELOPE TO BE INSULATED (R-11 MIN) IF TEMPERATURE DIFFERENCE EXCEEDS 10°F TO AJACENT AREAS 23. ALL ADHESIVES, SEALANTS, PAINTS AND COATINGS USED DURING THE INSTALLATION/FINISH WORK SHALL MEET THE LEED REQUIREMENTS FOR IEQ. 24. MAXIMUM STANDARD LENGTH OF FLEXIBLE DUCT SHALL BE BUILDING STANDARDS OR 12' MAX; UP TO 25' MAXIMUM LENGTH IS ACCEPTABLE IF; FLEX DUCT (UL-181 TESTED & NOT "CONNECTOR") IS USED, DUCT 0 IS INCREASED BY 1 NOMINAL SIZE & BENDS DO NOT EXCEED 235° TOTAL. REFER TO INSTALLATION DETAILS FOR SUPPORT REQUIREMENTS. FLEXIBLE DUCT FLAME SPREAD RATING SHALL BE < 25 AND SMOKE DEVELOPED RATING SHALL BE < 50. USE THERMAFLEX MODEL G-KM FOR LOW AND MEDIUM PRESSURE APPLICATIONS OR APPROVED EQUAL. 25. ELECTRICAL METERING OF SYSTEMS AS REQUIRED BY ENERGY CODE SECTION C409 IS BY ELECTRICAL. THE ELECTRICAL DESIGN & CONTRACTOR TEAM WILL FURNISH THE NECESSARY ELECTRICAL DISTRIBUTION AND METERING COMPONENTS - SEE ELECTRICAL DRAWINGS. THE MECHANICAL CONTRACTOR WILL FURNISH A BUILDING MANAGEMENT SYSTEM CAPABLE OF COLLECTING AND STORING THE INFORMATION WITH A VISIBLE DISPLAY/NOTIFICATION READILY ACCESSIBLE TO OPERATION AND MANAGEMENT PERSONNEL AS REQUIRED. 26. THE PROJECT TEAM IS COLLECTIVELY RESPONSIBLE FOR COMPLIANCE WITH APPENDIX D, "RENEWABLE ENERGY SYSTEMS." AS WELL AS C406 "ADDITIONAL ENERGY PACKAGE OPTIONS" AS APPLICABLE AND AS COORDINATED DURING DESIGN WITH DESIGN/CONSTRUCTION TEAM. MINIMUM DUCT INSULATION LAST UPDATED 07/11/16 DUCT TYPE DUCT LOCATION (IN HEATED AND MECHANICALLY COOLED DUCT SYSTEM) INSULATION R-VALUE REMARKS SUPPLY & RETURN NOT WITHIN CONDITIONED SPACE: OUTSIDE BUILDING R-8 1,2,3 OUTSIDE AIR WITHIN CONDITIONED SPACE: INSIDE BUILDING SEE NOTES 4 & 5 1,2,3,4,5 SUPPLY & RETURN NOT WITHIN CONDITIONED SPACE: INSIDE BUILDING R-6 1,2 SUPPLY AIR <550 OR > 1050 WITHIN CONDITIONED SPACE R-3.3 1,2 1 REFER TO C403.2.8 FOR FURTHER REQUIREMENTS & ALSO R403 FOR RESIDENTIAL INSTALLATIONS 2 INSULATED COOLED DUCTS REQUIRED A VAPOR RETARDER (PERM < 0.5) AND SEALED JOINTS 3 WEATHERPROOF BARRIER REQUIRED AROUND DUCTWORK TO MAINTAIN WATER TIGHTNESS 4 INSULATE OUTSIDE AIR DUCTS TO BUILDING EXTERIOR WALL LEVEL PER ENERGY CODE SECTION: C403.2.8.1 UNTIL CONNECTED TO EQUIPMENT SERVED OR TO THE CODE REQUIRED SHUTOFF DAMPER (AND Z" THICK INSULATION MIN. TO PREVENT CONDENSATION ON DUCTS IN PLENUM UP TO THE HEATING OR COOLING EQUIPMENT) 5 R-7 CAN BE USED IN LIEU OF BUILDING ENVELOPE INSULATION LEVEL IF: DEDICATED OUTSIDE AIR SYSTEM AND <2,800 CFM SUPPLY AIR MINIMUM PIPE INSULATION LAST UPDATED: 07/11/16 FLUID DESIGN INSULATION CONDUCTIVITY NOMINAL PIPE DIAMETER (INCH) OPERATING TEMP OF CONDUCTIVITY RANGE MEAN TEMP RATING ` <1 1 TO <1-1/2 1-1/2 TO <4 4 TO <8 >8 HEATING SYSTEMS (STEAM, CONDENSATE, HYDRONIC HOT WATER, DOMESTIC HOT WATER & RECIRC) >350 0.32-0.34 250 4.5 5.0 5.0 5.0 5.0 251-350 0.29-0.32 200 3.0 4.0 4.5 4.5 4.5 201-250 0.27-0.30 150 2.5 2.5 2.5 3.0 3.0 141-200 0.25-0.29 125 1.5 1.5 2.0 2.0 2.0 105-140 0.21-0.28 100 1.0 1.0 1.5 1 1.5 1 1.5 DOMESTIC COLD WATER AND HORIZONTAL RAIN LEADERS TO FIRST VERTICAL RAIN LEADER (TO PREVENT CONDENSATION) N/A 0.21-0.27 75 0.5 0.5 0.5 0.5 0.5 COOLING SYSTEMS (CHILLED WATER, BRINE AND REFRIGERANT, WATERSIDE ECONOMIZER SYSTEMS)** 40-60 0.21-0.27 75 0.5 0.5 1.0 1.0 1.0 <40 0.20-0.26 75 0.5 1.0 1.0 1.0 1.5 DRAWING INDEX SHEET NO. SHEET TITLE CURRENT REVISION M0.00 COVER SHEET - HVAC M0.01 SCHEDULE SHEET - HVAC M1.01 SITE PLAN - HVAC M2.01 PARTIAL 1ST FLOOR PLANS - HVAC City Of Edmonds Building Department ---------- --------- Work MECHNICAL ---------------------------------------- Address 20903 70TH AVE W Owner COMPASSHEALTH ---------------------- Approved Date 6-2-2021 BuildingOfficial:Eri&C 4-fer 27042000302700 APPROVED BY PLANNING w'111� May 27 2021 3) Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ SPLIT SYSTEMS COMPASSHEALTH AURORA HOUSE 20903 70TH AVE. W. EDMONDS, WA 98026 LEGAL DESCRIPTION SEC 20 TWP 27 RGE 04 TH PTN E1/2 SE1/4 SW1/4 DAF COM AT NE COR OF SD SE1 /4 SW1 /4 TH S02*46 23E ALG E LN OF SD SUBDIV 3OFT TH S89*22 07W 672.13FT M/L TAP 1 OFT E OF W LN E1 /2 SE1 /4 SW1 /4 TH S02*33 23EALG E LN OF PRTY CONVYD TO SNO CO REC AF NO 1399049 DIST 357.42FT TAP THAT BEARS S89*22 07W FR SW COR LOT 12 PLAT OF HOYT ACRES TPB TH N89*22 07E 223.23FT TAP THAT BEARS NO2*33 23W FR SW COR LOT 7PLAT OF HOYT ACRES TH S02*33 23E 120FT TH S89*22 07W 223.23FT TAP 1 OFT E OF W LN OF SD E1 /2 SE1 /4 SW1 /4 TH NO2*33 23W 120FT TO TPB EXC W 20FT THOF (AURORA HSE EXEMPT WA ST REG#09380-003) cN�ooOR A,. �SSfoNAL E�`G May 18, 2021 Revisions a Lynnwood rya `11i ul Cr EDMONDS BOWL 4 A 3 Puget Sound - 2DathStswCedar Valley £ 9 Edmonds ALDERYI arCh Way 20903 70th Ave W, Mew EDMONDS WATERFRONT _ Edmonds, WA 98026 I'm St SW "�^• -'4th St SW 223;t. i; �;v - MELODY HILL Woodway m Esperance EASTTERRACE Brier ze FRUITLAND ACRES Terrace $ ? Firdale Abbey �T A View __________ _________ ------------Memorial_ � 2 N 236tr St N �QD,h St BALLINGER - Richmond Beach a - F 1 e HILLWOOD- crun..vc o� �0M VICINITY MAP NO SCALE 05/14/21 WSS ISSUE FOR PERMIT ti a No. Date By Description Z4 SITE MAP NO SCALE FOR CITY USE: 0 M � A z Q z ti ^ a RECEIVED May 19 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0693 Design Team Design WSS Drawn FVP Checked DTN Pre -Construction Number 14-21-19350 Construction Number Issue Date 05/14/21 COVER SHEET - HVAC M0000 ISSUE FOR PERMIT NOTE: * NOT REQUIRED FOR STRAINERS, CONTROL VALVES & BALANCING VALVES ASSOCIATED WITH PIPING 1" OR LESS IN DIA. ** TYPICAL CONDENSER WATER PIPE IN NON -ECONOMIZER SYSTEMS IS NOT INSULATED SEE R403 FOR RESIDENTIAL INSTALLATIONS. DEMO SPLIT SYSTEM INDOOR FAN COIL UNIT SCHEDULE LAST UPDATED: 051121 UNIT TAG LOCATION SERVES BASIS OF DESIGN ASSOCIATED CONDENSER SUPPLY CFM OSA CFM ESP IN WG MAX REFR FT HT HEATER KW ELECTRICAL SOUND dBA WEIGHT LBS REMARKS MCA V PH FCU-102 WALL DATA ROOM MITSUBISHI MSY-D30NA CU-SOS - - 0.00 - NA 1.0 208-230/1 - 40 1 REMARKS: 1 DEMO DEMO SPLIT SYSTEM OUTDOOR CONDENSING UNIT SCHEDULE LAST UPDATED: 05/11/21 UNIT TAG LOCATION AREA SERVED BASIS OF DESIGN ASSOCIATED FAN COIL UNIT COOLING CAPACITY BTUH HEATING CAPACITY ELECTRICAL SOUND dBA WEIGHT LBS REMARKS TOTAL I SENS. SEER I BTUH HSPF COP MCA V PH CU-101 AT GRADE DATA 101 MITSUBISHI MUY-D30N FCU-102 32000 26240 - N/A N/A 21.0 208-230/1 - 126 REMARKS: 1 DEMO DEMO SPLIT SYSTEM INDOOR FAN COIL UNIT SCHEDULE LAST UPDATED: 05/11/21 UNIT TAG LOCATION SERVES BASIS OF DESIGN ASSOCIATED CONDENSER SUPPLY CFM OSA CFM ESP IN WG MAX REFR LINE FT HEATER WATTS ELECTRICAL SOUND dBA WEIGHT LBS REMARKS MCA V PH FCU-101 CEILING KITCHEN SANYO TWH3672R HP-101 - 0.00 - NA 1.0 208-230/1 - 90 1 REMARKS: 1 DEMO DEMO SPLIT SYSTEM OUTDOOR HEAT PUMP UNIT SCHEDULE LAST UPDATED: 05/11/21 UNIT TAG LOCATION I AREA SERVED BASIS OF DESIGN ASSOCIATED FAN COIL I COOLING CAPACITY BTUH I HEATING CAPACITY I ELECTRICAL SOUND dBA WEIGHT LBS REMARKS TOTAL SENS SEER/EER BTUH HSPF/COP MCA V/PH HP-101 AT GRADE I KITCHEN SANYO CH3672R FCU-101 36,000 27,000 - 37,000 - 21.0 208-230/1 - - 1 REMARKS: 1 DEMO REPLACEMENT SPLIT SYSTEM INDOOR FAN COIL UNIT SCHEDULE LAST UPDATED: 05/11/21 UNIT TAG LOCATION SERVES BASIS OF DESIGN ASSOCIATED CONDENSER SUPPLY CFM OSA CFM ESP IN WG MAX REFR FT / HT HEATER KW ELECTRICAL SOUND dBA WEIGHT LBS REMARKS MCA V/PH FCU-102 WALL DATA ROOM DAIKIN FTX30NVJU CU-101 512/572/727/890 NA 0.00 98' / 65' NA 17.0 208-230/1 37-40-47-53 38 1-11 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. PROVIDE WITH WALL -MOUNTED WIRELESS PROGRAMMABLE T'STAT, REFER TO MFG'S REQUIREMENTS FOR REFRIGERANT PIPE SIZES 3 INDOOR UNIT POWERED FROM OUTDOOR UNIT BY ELECTRICAL CONTRACTOR 4 REFRIGERANT: R-410A. PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS 5 PROVIDE WALL MOUNTED FCU CONDENSATE DRAIN PUMP (GOBI 230-XL - 2.5 GPH @ 10 FT LIFT & < 100 FT HORIZ, 115V/1 PH @ 32W, 5 LBS). TERMINATE DRAIN LINE IN HUB DRAIN BY NEAREST SINK TAILPIECE OR INDIRECT AT NEAREST FLOOR DRAIN 6 OUTSIDE AIR INDICATES MINIMUM CFM PER ASHRAE. TAB WORK MUST MEET OR EXCEED INDICATED QUANTITY. 7 ECONOMIZER EXEMPT PER 2018 WSEC C403.5 EXCEPTION 11 (UNIT IS 15% MINIMUM HIGHER EFFICIENCY THAN THE 13 SEER REQUIREMENT IN TABLE C403.3.2(1)A) 8 UNIT TO BE CONFIGURED TO PROVIDE LOW AMBIENT COOLING AT BELOW 240F 9 PROVIDE FILTERS AT RETURN AIR OPENINGS OF NEW AND/OR EXISTING UNITS, UPSTREAM OF ANY HEAT EXCHANGER OR COILS PER SMC / IMC 605 10 PROVIDE SEISMIC BRACING PER ACSE 7, UNLESS: UNIT IS WALL MOUNTED OR <20 LBS OR IS RIGID MOUNTED INLINE WITH DUCT (NO FLEX) AND <75 LBS 11 HEATING & COOLING FANS/PUMPS SHALL SHUT OFF WHEN THERE IS NO CALL FOR HEATING AND COOLING IN THE ZONE PER WSEC 2018 C403.3.5.2, EXCEPT IF HEATING/COOLING FANS <0.12W/CFM SPLIT SYSTEM OUTDOOR CONDENSING UNIT SCHEDULE LAST UPDATED: 01 23 20 UNIT TAG LOCATION AREA SERVED BASIS OF DESIGN ASSOCIATED FAN COIL UNIT COOLING CAPACITY BTUH HEATING CAPACITY ELECTRICAL SOUND dBA WEIGHT LBS REMARKS TOTAL SENS. SEER BTUH HSPF/COP MCA V/PH CU-R01 AT GRADE DATA ROOM DAIKIN RK30NMVJUA FCU-102 31,400 21,030 17.5 N/A N/A 17.0 208-230/1 56 133 1-9 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION DIRECTION FOR EQUIPMENT AS REQUIRED BY LATEST APPROVED VERISON OF THE NATIONAL ELECTRICAL CODE, PRIOR TO ORDER. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM OR PER ELECTRICAL CONTRACTOR CALCULATION) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE- 2 SPLIT SYSTEM UNITS REQUIRE DISCONNECT AT THE CONDENSING UNIT BY ELECTRICAL CONTRACTOR 3 INVERTER DRIVEN COMPRESSOR, TEST CONDITIONS BASED ON AHRI 210/240 4 REFRIGERANT: R-410A. PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS 5 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. REFER TO MFG'S REQUIREMENTS FOR REFRIGERANT PIPE SIZES FOR EACH UNIT CONNECTION - CONFIRM CONTROL WIRE GAUGE (14 OR 16 AWG) WITH SUBMITTALS PRIOR TO INSTALLATION TO INDOOR UNIT 6 PROVIDE WITH WIND BAFFLE AND LOW AMBIENT OR HEAD PRESSURE CONTROL SUITABLE FOR LOW AMBIENT COOLING 7 ECONOMIZER EXEMPT PER 2018 WSEC C403.5 EXCEPTION 11 (UNIT IS 15% MINIMUM HIGHER EFFICIENCY THAN THE 13 SEER REQUIREMENT IN TABLE C403.3.2(1)A) 8 UNIT TO BE CONFIGURED TO PROVIDE LOW AMBIENT COOLING AT BELOW 240F 9 PROVIDE WITH AIREX PROSYSTEM KIT E-FLEX GUARD OR APPROVED EQUAL WHEN EXPOSED TO WEATHER IN COLOR TO MATCH SURROUNDING AREAS (BLACK OR WHITE) COLOR FROM EXTERIOR PENETRATION TO CONDENSING UNIT CONNECTION IN COMPLIANCE WITH WSEC C403.10.3 REPLACEMENT SPLIT SYSTEM INDOOR FAN COIL UNIT SCHEDULE LAST UPDATED: 05 11 21 UNIT TAG LOCATION SERVES BASIS OF DESIGN ASSOCIATED CONDENSER SUPPLY CFM OSA CFM ESP IN WG MAX REFR LINE FT HEATER WATTS ELECTRICAL SOUND dBA WEIGHT LBS REMARKS MCA V PH FCU-101 CEILING KITCHEN DAIKIN FXHQ36MVJU HP-101 670/830 - 0.00 65' NA 1.4 208-230/1 46 90 1-13 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION FOR EQUIPMENT AS REQUIRED BY NATIONAL ELECTRICAL CODE. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. PROVIDE WITH WALL -MOUNTED WIRELESS PROGRAMMABLE T'STAT, REFER TO MFG'S REQUIREMENTS FOR REFRIGERANT PIPE SIZES 3 INDOOR UNIT POWERED FROM OUTDOOR UNIT BY ELECTRICAL CONTRACTOR 4 REFRIGERANT: R-410A. PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS 5 PROVIDE WALL MOUNTED FCU CONDENSATE DRAIN PUMP (GOBI 230-XL - 2.5 GPH @ 10 FT LIFT & < 100 FT HORIZ, 115V/1PH @ 32W, 5 LBS). TERMINATE DRAIN LINE IN HUB DRAIN BY NEAREST SINK TAILPIECE OR INDIRECT AT NEAREST FLOOR DRAIN 6 PROVIDE PLENUM RATED OVERFLOW SHUT-OFF DEVICE CONFORMING TO UL-508 (I.E. RECTORSEAL SS2AP) IN LIEU OF SECONDARY DRAIN PAN 7 OUTSIDE AIR INDICATES MINIMUM CFM PER ASHRAE. TAB WORK MUST MEET OR EXCEED INDICATED QUANTITY. 8 ECONOMIZER EXEMPT PER 2018 WSEC C503.4.3 (SPLIT SYSTEM IS < 60,000 BTUH, AND +10% MORE EFFICIENT THAN THE 13 SEER REQUIREMENT IN TABLE C403.3.2(1)A) 9 HEAT PUMPS SHALL UTILIZE COMPRESSION HEATING AS FIRST STAGE OF HEAT AND AUXILIARY ELECTRIC HEAT SHALL NOT OPERATE ABOVE 40°F. 10 PROVIDE FILTERS AT RETURN AIR OPENINGS OF NEW AND/OR EXISTING UNITS, UPSTREAM OF ANY HEAT EXCHANGER OR COILS PER IMC 605 it PROVIDE SEISMIC BRACING PER ACSE 7, UNLESS: UNIT IS WALL MOUNTED OR <20 LBS OR IS RIGID MOUNTED INLINE WITH DUCT (NO FLEX) AND <75 LBS 12 PROVIDE WITH AIREX PROSYSTEM KIT E-FLEX GUARD OR APPROVED EQUAL WHEN EXPOSED TO WEATHER IN COLOR TO MATCH SURROUNDING AREAS (BLACK OR WHITE) COLOR FROM EXTERIOR PENETRATION TO CONDENSING UNIT CONNECTION IN COMPLIANCE WITH WSEC C403.2.9.1 13 HEATING & COOLING FANS/PUMPS SHALL SHUT OFF WHEN THERE IS NO CALL FOR HEATING AND COOLING IN THE ZONE PER WSEC 2018 C403.3.5.2, EXCEPT IF HEATING/COOLING FANS <0.12W/CFM REPLACEMENT SPLIT SYSTEM OUTDOOR HEAT PUMP UNIT SCHEDULE LAST UPDATED: 05/11/21 UNIT TAG LOCATION AREA SERVED BASIS OF DESIGN ASSOCIATED FAN COIL COOLING CAPACITY BTUH HEATING CAPACITY ELECTRICAL SOUND dBA I WEIGHT LBS REMARKS TOTAL SENS SEER/EER BTUH HSPF/COP MCA V/PH HP-101 AT GRADE KITCHEN DAIKIN RXTQ36TAV FCU-101 34,200 25,650 18 / - 37,000 10.3 / - 16.5 208-230/1 58 172 1-6 GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS (ELECTRICAL, WEIGHT, SIZE, ETC...) WITH APPROVED SUBMITTALS PRIOR TO INSTALLATION; FIELD COORDINATE FINAL LOCATION & INSTALL PER MANUFACTURERS REQUIREMENTS 1 ELECTRICAL CONTRACTOR TO PROVIDE SCCR PROTECTION DIRECTION FOR EQUIPMENT AS REQUIRED BY LATEST APPROVED VERISON OF THE NATIONAL ELECTRICAL CODE, PRIOR TO ORDER. MANUFACTURER TO PROVIDE SCCR LISTING (5 KAIC MINIMUM OR PER ELECTRICAL CONTRACTOR CALCULATION) INSIDE CONTROL PANEL AS REQUIRED BY NATIONAL ELECTRICAL CODE. 2 SPLIT SYSTEM UNITS REQUIRE DISCONNECT AT THE CONDENSING UNIT BY ELECTRICAL CONTRACTOR 3 INVERTER DRIVEN COMPRESSOR, TEST CONDITIONS BASED ON AHRI 210/240 4 SINGLE CONDENSING UNIT FOR EACH INDOOR FAN COIL UNIT. REFER TO MFG'S REQUIREMENTS FOR REFRIGERANT PIPE SIZES FOR EACH UNIT CONNECTION, WIND BAFFLE, LOW AMBIENT OR HEAD PRESSURE CONTROL SUITABLE FOR LOW AMBIENT COOLING - ADDITIONALLY, CONFIRM CONTROL WIRE GAUGE (14 OR 16 AWG) WITH SUBMITTALS PRIOR TO INSTALLATION TO INDOOR UNIT 5 REFRIGERANT: R-410A. PROVIDE ADDITIONAL CHARGING OF LINES AS REQUIRED FOR LONG LINE LENGTH APPLICATIONS 6 ECONOMIZER EXEMPT PER 2018 WSEC C503.4.3 (SPLIT SYSTEM IS < 60,000 BTUH, AND +10% MORE EFFICIENT THAN THE 13 SEER REQUIREMENT IN TABLE C403.3.2(1)A) FOR CITY USE: RECEIVED May 19 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT rir Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ SPLIT SYSTEMS COMPASSHEALTH AURORA HOUSE 20903 70TH AVE. W. EDMONDS, WA 98026 c��ODOk'," NO,��FGISTERV SSION May 18, 2021 Revisions 05/14/21 WSS ISSUE FOR PERMIT No. Date By Description Design Team Design WSS Drawn FVP Checked DTN Pre —Construction Number 14-21-19350 Construction Number Issue Date 05/14/21 SCHEDULE SHEET - HVAC WIT [I) to] I ISSUE FOR PERMIT PROPERTY LINE PROPERTY LINE 13' TO NEAREST PROPERTY LINE I I CU-101 I' II II I II I II I II --- ------ IL_----------------------------------------------- - ---------------------------------------------------------- - r I r r � I II II I ii ii I II II II II II II II II II II II II II II II II II II I II II I II II II II II II II II II ------ �� II I I I� -----i I I II II II II II I� II II II II II I I L�1 I I � I I L--------------JI IL-----------� IL J L-----————————---J----------- �I-------------------------------------J II II II II II II II II II II II II II 1, II II I� II r - I J r— II ------ L------------------- @95' TO PROPERTY LINE I I I ,I I ,I II r J I---J II ,7_j II II II I II �I I II II II II II II II II II II II II II II II II II II LL II L------- L------- -------- II II II II �I II II II II II II II II II II II I II II I II II II Il IL JI L J 1 I I I I I I I I I I I I I I I I PROPERTY LINE PROPERTY LINE BLD2021-0693 Zone Corner Flag Setbacks: Required Actual Front Sides Rear Other Height �1 oN C o� � A z SITE PLAN - HVAC { SCALE: 1/8" = 1'-0" ti FOR CITY USE: RECEIVED May 19 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ SPLIT SYSTEMS COMPASSHEALTH AURORA HOUSE 20903 70TH AVE. W. EDMONDS, WA 98026 c�ODOR A, NO ��GISTERV ��SSfUN May 18, 2021 Revisions 05/14/21 WSS ISSUE FOR PERMIT No. Date By Description Design Design Team WSS Drawn FVP Checked DTN Pre —Construction Number 14-21-19350 Construction Number Issue Date 05/14/21 SITE PLAN - HVAC M1.01 ISSUE FOR PERMIT Mir)RACK11C I_J 1Y■_JETSIM �1 Co o 4' PARTIAL ^ SCALE: 1/4" = 1'-0" ti ^ a OMEN'S STROOM MEN'S QGeTQnnnn I A Al ITOD MEN'S RESTROOM MED ROOM/ NURSE'S OFFICE U'DEMO EXIST UNIT DINING ROOM ET] 1ST FLOOR DEMO PLAN - HVAC F, REPLACE EXIST UNIT W/ NEW UNIT, OF "NAEN'S THE SAME CAPACITY. RE —CONNECT TO ;OOM EXIST DUCTWORK & UTILITIES, SEE EQUIPMENT SCHEDULE FOR DETAILS ON NEW UNIT (TYP 2) CU-102 CAH oN M 5 � PARTIAL SCALE: 1/4" = 1'-0" ti ^ a SCALE: 4"=1 ' OMEN'S 3TROOM MEN'S RGeTL2nnnn 1 A AI ITOD MEN'S RESTROOM REPLACE EXIST UNIT W/ NEW UNIT, OF THE SAME CAPACITY. RE —CONNECT TO EXIST DUCTWORK & UTILITIES, SEE EQUIPMENT SCHEDULE FOR DETAILS ON NEW UNIT (TYP 2) MED ROOM/ NURSE'S OFFICE ViTruCnI FCU-101 DINING ROOM 1 ST FLOOR PLAN - HVAC 1' 3' 5' 2' 4' 10' 25' 4 G J �1 o C C ti [� A z KEY PLAN { SCALE: NONE �v ^ a FOR CITY USE: RECEIVED May 19 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Hermanson Building Today, Defining Tomorrow Hermanson Company LLP 1221 2nd Avenue North Kent, Washington 98032 Tel: (206) 575-9700 Fax: (206) 575-9800 www.hermanson.com Contractor Reg #: HERMACLO05BJ SPLIT SYSTEMS COMPASSHEALTH AURORA HOUSE 20903 70TH AVE. W. EDMONDS, WA 98026 c�ODOR A, No ��crs�RV ��SSfUN May 18, 2021 Revisions 05/14/21 WSS ISSUE FOR PERMIT No. Date By Description Design Team Design WSS Drawn FVP Checked DTN Pre —Construction Number 14-21-19350 Construction Number Issue Date 05/14/21 PARTIAL 1ST FLOOR PLANS - HVAC M2001 ISSUE FOR PERMIT