FIR2020-0086+Fire_Sprinkler_Equipment_Specification_Sheets+10.19.2020_6.25.10_AMBulletin 006 May 2019
Reliable
Features
cULus Listed as Residential Sprinklers
Push -On cover plate installation
Low water flow requirements
Product Description
Model RFC Series residential sprinklers are flat cover plate,
concealed pendent sprinklers intended for installation in
accordance with NFPA 13, NFPA 13R, or NFPA 13D. The
sprinklers are cULus Listed as Residential Sprinklers in ac-
cordance with UL 1626. In addition, Model RFCLL Series
sprinklers are cULus Certified for Health Effects to NSF/ANSI
standard 61 Annex G (LL) and Australian WaterMark Certified
(WMCS).
Model RFC30 sprinklers have a 1650F (74°C) temperature
rated fusible -link operating element. Model RFC43, RFC49,
RFC58, and RFC76 sprinklers are offered with either a 1650F
(74°C) or 212OF (100°C) temperature rated fusible -link oper-
ating element. Sprinklers with a 1650F (74°C) temperature
rating are ordinary temperature classification and are listed
for use with a 1350F (57°C) temperature rated cover plate.
Sprinklers with a 212OF (100°C) temperature rating are inter-
mediate temperature classification and are listed for use with
a 1650F (74°C) temperature rated cover plate.
Model RFC Series sprinklers are installed with a Model RFC
cover plate. Model RFC cover plates may be installed by ei-
ther pushing or threading the cover plate into the sprinkler
cup. Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49 and
RFC49LL sprinklers allow 1/2" (13 mm) of cover plate adjust-
ment. Model RFC58 and RFC76 sprinklers allow 3/4" (19 mm)
of cover plate adjustment. Model RFC cover plates are avail-
able in a variety of finishes as listed in Table H.
Model RFC Series Residential Sprinklers
Flat Concealed Pendent
Model RFC30 & RFC30LL
Model RFC49 & RFC49LL
Model RFC76
cULus Listed
Model RFC43 & RFC43LL
Model RFC58
)M
Model RFC Cover Plate
Sprinkler Model
Nominal K-Factor
gpm/psi (1/min/bary/Z )
Max. Coverage Area
ft x ft (m x m)
Listings &
Approvals
Sprinkler Identification
Number (SIN)
RFC30
3.0(43)
14 x 14 (4.3 x 4.3)
cULus
RA0611
RFC30LL
3.0(43)
14 x 14 (4.3 x 4.3)
cULus, LL, WMCS
RA3211
RFC43
4.3(62)
20 x 20 (6.1 x 6.1)
cULus
RA0612
RFC43LL
4.3(62)
20 x 20 (6.1 x 6.1)
cULus, LL, WMCS
RA3212
RFC49
4.9(71)
20 x 20 (6.1 x 6.1)
cULus
RA0616
RFC49LL
4.9(71)
20 x 20 (6.1 x 6.1)
cULus, LL, WMCS
RA3216
RFC58
5.8(84)
20 x 20 (6.1 x 6.1)
cULus
RA0613
RFC76
7.6(109)
20 x 20 (6.1 x 6.1)
cULus
RA0618
cULus: cULus Listed to UL1626, Residential Sprinklers for Fire Protection Service.
LL: cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (Less than 0.25% Lead content).
WMCS: Australian WaterMark Certified.
www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 3.0 (43 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast -response
Temperature Rating
165°F (74°C) sprinkler
135°F (57°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC30LL only)
Watermark Certified (RFC30LL only)
Model RFC30 & RFC30LL Sprinkler Components and Dimensions
Threads —
Body
Cup —�
Tower
Fusible Link —
Deflector (retracted)
Pin (extended) -
Deflector (extended)
1-3/4" (44 mm) +/- 1/4" (6 mm)
Nominal face of fitting to ceiling
Bottom View
2-5/16" (58 mm)
Dia.
3/16"(5mm'
Model RFC Cover Plate i 3-5/16" (84 mm) Dia. —►{ N Ceiling
Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure
Max. Coverage Area (2)
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
12 x 12
9
9.0
(3.6 x 3.6)
(34)
(0.62)
14 x 14
10
7
11.0
(4.3 x 4.3)
(38)
(0.76)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliable Page 2 of 8
May 2019 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 4.3 (62 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast -response
Temperature Rating
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC43LL only)
Watermark Certified (RFC43LL only)
Model RFC43 & RFC43LL Sprinkler Components and Dimensions
Threads
Body
Cup
Tower
Fusible Link
Deflector (retracted)
Pin (extended)
Deflector (extended) -
1-3/4" (44 mm) +/- 1/4" (6 mm)
Nominal face of fitting to ceiling
Model RFC Cover Plate
Model RFC43 & RFC43LL Sprinkler Hydraulic Design Criteria
r
Bottom View ,
2-5/16" (58 mm)
Dia.
- a-1
3-5/16" (84 mm) Dia.
3/16" (5 mm'
Ceiling
Minimum Flow and Residual Pressure
Max. Coverage Area (2)
Ordinary Temperature
Intermediate Temperature
Flow
Pressure
Flow
Pressure
ft. x ft.
(m x m)
gpm
psi
gpm
psi
(1/min)
(bar)
(1/min)
(bar)
15 x 15
12
7.8
12
7.8
(4.6 x 4.6)
(45)
(0.54)
(45)
(0.54)
16 x 16
13
9.1
13
9.1
(4.9 x 4.9)
(49)
(0.63)
(49)
(0.63)
18 x 18
18
17.5
(5.5 x 5.5)
(68)
(1.21)
20 x 20
21
23.8
(6.1 x 6.1)
(79)
(1.64)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliable Page 3 of 8
May 2019 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 4.9 (71 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Sensitivity
Fast -response
Temperature Rating
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Cover Plate Finishes Listings and Approvals
cULus Listed to UL 1626
(See Table H) cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC49LL only)
Watermark Certified (RFC49LL onlv)
Model RFC49 & RFC49LL Sprinkler Components and Dimensions
Threads
Body —
Cup
Tower
Fusible Link
Deflector (retracted)
Pin (extended)
Deflector (extended)
1-3/4" (44 mm) +/- 1/4" (6 mm)
Nominal face of fitting to ceiling
Bottom View
2-5/16" (58 mm)
Dia.
Model RFC Cover Plate 3-5/16" (84 mm) Dia. �-- Ceiling
Model RFC49 & RFC49LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual PressureM
Max. Coverage Area (Z)
Ordinary Temperature
Intermediate Temperature
Flow
Pressure
Flow
Pressure
ft. x ft.
(m x m)
gpm
psi
gpm
psi
(1/min)
(bar)
(1/min)
(bar)
16 x 16
13
7.0
13
7.0
(4.9 x 4.9)
(49.0)
(0.48)
(49.0)
(0.48)
18 x 18
17
12.0
17
12.0
(5.5 x 5.5)
(64.3)
(0.83)
(64.3)
(0.83)
20 x 20
20
16.7
21
18.4
(6.1 x6.1)
(75.7)
(1.15)
(79.5)
(1.27)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table D above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliable Page 4 of 8
May 2019 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 5.8 (84 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Chrome Plated Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast -response
Temperature Ratings
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC Cover Plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Listings and Approvals
cULus Listed
Model RFC58 Sprinkler Components and Dimensions
Bottom View
2-5/16" (58 mm) y
Dia.
Threads _
Body _
Cup =_
Tower
Fusible Link 1-7/8" (48 mm) +/- 3/8" (9 mm)
Deflector (retracted) Nominal face of fitting to ceiling
� Pin (extended) 7", 3/16"(5mm,
"""`
Deflector (extended)
Model RFC Cover Plate 3-5/16" (84 mm) Dia. Ceiling
Model RFC58 Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure')
Max. Coverage Area (2)
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
16 x 16
16
7.6
(4.9 x 4.9)
(60.6)
(0.53)
18 x 18
18
9.6
(5.5 x 5.5)
(68.1)
(0.66)
20 x 20
20
11.9
(6.1 x 6.1)
(75.7)
(0.82)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliable Page 5 of 8
May 2019 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 3/4" NPT or ISO 7-1 R3/4
Nominal K-Factor: 7.6 (109 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast -response
Temperature Ratings
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC Cover Plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Listings and Approvals
cULus Listed
Model RFC76 Sprinkler Components and Dimensions
Three
Body
Cup
Towei
Fusible Li
Deflector (retra
Pin (extern
Deflector (extend
1-7/8" (48 mm) +/- 3/8" (9 mm)
Nominal face of fitting to ceiling
Model RFC Cover Plate
Model RFC76 Flat Concealed Sprinkler Hydraulic Design Criteria
/o
Bottom View
ti
2-5/16" (58 mm)
Dia.
3-5/16" (84 mm) Dia.
3/16" (5 mm)
Ceiling
Minimum Flow and Residual PressureN
Max. Coverage Area (2)
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
16 x 16
21
7.6
(4.9 x 4.9)
(79.5)
(0.52)
18 x 18
24
9.9
(5,5 x 5.5)
(90.8)
(0.68)
20 x 20
34
20
(6,1 x 6.1)
(128.7)
(1.4)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliable Page 6 of 8
May 2019 www.reliablesprinkler.com
Cover Plate Finishes(')
Standard Finishes Special Application Finishes
White Polyester Off White Paint Black Paint Raw Brass
Chrome Plated Bright Brass Finished Bronze Black Plated
Satin Chrome Stainless Steel Clad (3) Custom Color Paint(2)
Notes:
1. Paint or any other coating applied over the factory finish will void all approvals and warranties.
2. Custom color paint is semi -gloss, unless specified otherwise.
3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the backside. Cover plates
are not listed or approved as corrosion resistant. Stainless steel clad cover plates are not available perforated.
Installation Dimensions
Recommended
Min. to
Min. to Max.
Sprinkler
Cover
Cover Plate
Hole Diameter
Cover Plate
Max. Face
Dropped Deflector
Cover Plate
Model
Plate
Diameter
in Ceiling
Adjustment
of Fitting to
Distance below
Temperature
Model
inch (mm)
inch (mm)
inch (mm)
Ceilings')
Ceiling
Rating
inch (mm)
inch (mm)
RFC30,
RFC
3-5/16
2-5/8
1/2
1-1/2 to 2
1/2 to 1
1350F
RFC30LL
(84)
(67)
(13)
(38 to 51)
(13 to 25)
(57°C)
RFC43,
1350F(2)
RFC43LL,
RFC
3-5/16
2-5/8
1/2
1-1/2 to 2
1/2 to 1
(57°C)
RFC49,
(84)
(67)
(13)
(38 to 51)
(13 to 25)
or 1650F 3
RFC49LL
(74°C)
1350F(2)
RFC58,
RFC
3-5/16
2-5/8
3/4
1-1/2 to 2-1/4
1/4 to 1
(57°C)
RFC76
(84)
(67)
(19)
(38 to 57)
(6 to 25)
or 165°F3
(74°C)
Notes:
1. Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method
prior to installation. A 1/2" x 1/2" brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing
sprinklers.
2. For use with 165°F (74°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F (38°C).
3. For use with 212°F (100°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 150°F (66°C).
Installation
Model RFC series sprinklers are intended to be installed in ac-
cordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the
requirements of applicable authorities having jurisdiction. Mod-
el RFC series sprinklers must not be installed in ceilings with
positive pressure in the space above. Ensure that the 4 slots in
the cup are open and unobstructed following installation. Model
RFC series sprinklers are shipped with a wrench -able protec-
tive cap that should remain on the sprinkler until the sprinkler
system is placed in service following construction.
Model RFC series sprinklers can be installed without removing
the wrench -able protective cap using the Model W3 wrench.
Alternatively, Model RFC series sprinklers can be installed us-
ing the Model FC wrench by temporarily removing the protec-
tive cap during installation of the sprinkler. The use of any other
wrench to installed Model RFC series sprinklers is not permit-
ted and may damage the sprinkler. Fully insert the Model W3
wrench over the cap until it reaches the bottom of the cup, or
the Model FC wrench over the sprinkler until the wrench engag-
es the body. Do not wrench any other part of the sprinkler/cup
assembly. The Model W3 and FC wrenches are designed to be
turned with a standard 1/2" square drive. Tighten the sprinkler
into the fitting after applying a PTFE based thread sealant to the
sprinkler's threads. Recommended installation torque is 8 to 18
ft-Ibs (11 to 24 N-m) for 1/2" thread sprinklers and 14 to 20 ft-Ibs
(19 to 27 N-m) for 3/4" thread sprinklers.
Do not exceed the maximum recommended torque. Exceeding
the maximum recommended torque may cause leakage or im-
pairment of the sprinkler. Use care when inserting or removing
the wrench from the sprinkler to avoid damage to the sprinkler.
Install the cover plate by hand by pushing the cover plate into
the cup and turning the cover in the clockwise direction until it
is tight against the ceiling.
Application
Model RFC series sprinklers are intended for installation where
residential sprinklers are permitted or required by NFPA 13,
NFPA 13R, and NFPA 13D. The sprinklers are concealed pen-
dent residential sprinklers.
Model RFC 30 and RFC30LL sprinklers are available in ordinary
temperature classification for installation where the Maximum
Ceiling Temperature does not exceed 100OF (380C). Model
RFC43, RFC43LL, RFC49, RFC49LL, RFC58, and RFC76 sprin-
klers are available in either ordinary or intermediate tempera-
ture classification for installation where the Maximum Ceiling
Temperature does not exceed 100OF (38°C) or 150OF (660C),
respectively.
Bulletin 006
May 2019
Page 7 of 8
www.reliablesprinkler.com
Model FC
For use with Model RFC Series sprinklers
without wrench -able cap installed
Maintenance
Model RFC series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by gentle vacuuming. Replace
any sprinkler cover plate assembly which has been painted
(other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or non -oper-
ation.
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and UL Certified for
Canada to UL1626, Residential Sprinklers for Fire -protection
Service (cULus).
Certified by Underwriters Laboratories, Inc. and Underwrit-
ers Laboratories of Canada for Health Effects to NSF/ANSI
Standard 61 Annex G (LL) (RFC30LL, RFC43LL, and RFC49LL
only).
Australian WaterMark Certified (RFC30LL, RFC43LL, and
RFC49LL only).
Model W3
For use with Model RFC Series sprinklers
with wrench -able cap installed
Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Patents
Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL,
RFC58, and RFC76 sprinklers are covered by U.S. Patent No.
9,248,327 and U.S. Patent No. 7,275,603.
Model RFC30, RFC30LL, RFC43 and RFC43LL sprinklers are
additionally covered by U.S. Patent No. 8,776,903.
Ordering Information
Specify the following when ordering.
Sprinkler
• Model (RFC30, RFC30LL, RFC43, RFC43LL,
RFC49, RFC49LL, RFC58, RFC76)
• Temperature Rating
Cover Plate
• Model RFC
• Temperature Rating
• Finish (See Table H)
Sprinkler Wrench
• Model FC
• Model W3
v
co
co
co
co
0
N
Bulletin 006 Reliable Page 8 of 8
May 2019 www.reliablesprinkler.com
Bulletin 157 Rev.F
® Model F3QR
R Imab
Quick Response
Dry Sprinklers
CD
Features
1. The Model F30R sprinkler utilizes Belleville Spring
Closure Technology. Reliable is the first in the
industry to produce a Quick Response Dry
Concealed sprinkler utilizing this technology.
2. Styles available
• Pendent
• Recessed Pendent
• Concealed
• Horizontal Sidewall
• Recessed Horizontal Sidewall
3. 11/2" (38mm) escutcheon adjustment on pendent
sprinkler.
4. 1/2' (13mm) escutcheon adjustment on recessed
sprinkler with push -on/ thread -off FP Model
Escutcheon ring.
5. %" (9.5mm) cover plate adjustment on concealed
sprinkler with push-on/thread-off CCP Cover Plate.
6. Attractive appearance. Employs 3mm frangible
glass bulb and galvanized nipple.
7. Lengths available to accommodate installation
dimensions from 2" - to - 48" (51 mm - to-1219mm),
in'/4' (6mm) increments.
8. Available in avariety of plated and painted finishes.
U.S. Patent Numbers 5,775,431 and 5,967,240.
Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
Style
Response
Sprinkler
System T
Hazard
Pendent
Recessed Pendent
CCP Concealed
Wet Pipe
Light
R5714
Quick
Dry Pipe
Ordinary
Horizontal Sidewall
All Preaction
Recessed Horizontal Sidewall
R5734
2. Certified by FM Approvals
Style
Response
Sprinkler
System Type
Hazard
Pendent
Quick
Wet Pipe,
Single Interlock
Light
Ordinary,
(R5714)
Preaction
G1 ps
&
Horizontal Sidewall
Wet Pipe,
(R5734)
Quick
Single Interlock
Light
Preaction
3. NYC MEA 258-93-E
Concealed
Recessed Pendent
Pendent
Horizontal Sidewall
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
Model F3QR Dry Pendent Concealed Sprinkler
"A" Dim. 1 31 " to 48"(89mm to 1219mm) in W' 6mm increments
CCP Cover Plate(" Finishes(21
Standard Finishes
Special Application Finishes
Chrome Plated
Bright Brass Plated
White
Black Plated
Black Paint
Off White
Satin Chrome
Utilizes the 112" cover plate with %" total adjustment.
2' Other finishes and colors are available on special order.
Consult factory for details.
Standard Temperature Ratinas
Sprinkler
Temperature
Cover Plate
Max.
Classification
Rating
Temp. Rating
Ambient Temp.
Ordinary
135-F (57oC)
135-F
(57oC)
100-F (38-C)
Ordinary
155-F (68oC)
135-F
(57oC)
100-F (38oC)
Intermediate
200-F (93oC)
165-F
(74oC)
150-F (66oC)
High*
286oF (141-C)
165-F
(74oC)
150-F (66oC)
" Listed and Certified only by cULus.
Sprinkler Installation Wrench:
Model G3 R/C Sprinkler Wrench
Sprinkler Identification Number (SIN): R5714
Inlet Protrusion Elevated
Above
Inside Pipe
}
�- --IIII'r— l ---T----r iII<II,ItIF---i��
==VtM+}rI�
--YR--=7
rL
L
J System Tee
1" NPT
2 1/2" Dia.
[6.35mm]
"A" Dimension
Hole in Ceiling
Adjustment Range
f 3/16"
2 19/64" Dia.
[t4.76mm]
[58.34mm]
Nominal Position
Sprinkler
of Coverplate
Cup Assembly
Coverplate
1 Ceiling
Assembly
Ceiling i
3/16" [4.76mm]
Coverplate Adjustment
Note: Do not install the Model F30R Dry Pendent
Concealed Sprinkler in ceilings which have
positive pressure in the space above.
Model F3QR Dry Horizontal Sidewall Sprinkler
"A" Dim. 2" to 48" (51 mm to 1219mm) in 1W (6mm) increments
Finishes(')
Sprinkler
Escutcheon
Bronze
Brass
Chrome Plated
Chrome Plated
White Painted)
White
Other finishes and colors are available on special order.
Consult factory for details.
(2) White painted sprinklers will have chrome plated can.
Standard Temperature Ratinas
Sprinkler
Temperature
Max.
Bulb
Classification
Rating
Ambient Tem .
Color
Ordinary
135-F (57-C)
100-F (38°C)
Orange
Ordinary
155-F (68oC)
100-F (38oC)
Red
Intermediate
200-F (93oC)
150-F (661C)
Green
High
286oF (141-C)
225oF (107C)
Blue
Sprinkler Installation Wrench:
Model G3 Sprinkler Wrench
Sprinkler Identification Number (SIN): R5734
1 1/2" [38.10mm]
Total Adjustment _ _ T
i r Ceiling
�j 4" [101.60mm] Min.
1 1/4" [31.75mm] 12" [304.80mm] Max
Escutcheon Adjustment I
System Tee I I-_ 1 Escutcheon Adjustment
r 1" NPT
__, --- 2 1/8" Dia.
[53.98mm] 3 I
Hole in Wall
Sprinkler Can
"A" Dimension
Adjustment
rsarcoa-c Range + 1/4" [+6.35mm]
2 3/
[53.18mm]
�DA_ 3"
[76.20mm]
1/4" [6.35mm]
Protrusion
Nominal Position
of Escutcheon
Note: The sprinkler Can protrudes 1/4" when escutcheon is
in nominal position. Escutcheon adjustment pro-
vides +1/4' (+6mm) to -1'/4" (-32mm) "A" dimension
adjustment range.
3.
Model F3QR Dry Horizontal Recessed Sidewall Sprinkler
"A" Dim. 31/2" to 48" (89mm to 1219mm) in'W (6mm) increrwis
Finishes')
Sprinkler 7FEscutcheon
Bronze
Brass
Chrome Plated
Chrome Plated
White Painted
White
Other finishes and colors are available on special order. Consult
factory for details. Cup remains unfinished. "See page 2"
Standard Temperature Ratings
Sprinkler
Temperature
Max.
Bulb
Classification
RaUng
Ambient Temp.
Color
Ordinary
135OF (57oC)
100°F (38oC)
Orange
Ordinary
1551F (68oC)
100-F (38oC)
Red
Intermediate
200OF (93oC)
150-F (66°C)
Green
High*
2860F (1411C)
2251F (1071C)
Blue
Listed and Certified only by cULus.
Sprinkler Installation Wrench:
Model G3 R/C Sprinkler Wrench
Sprinkler Identification Number (SIN): R5734
Technical Data:
Orifice Size:'/2' (15mm)
Thread Size: 1" NPT per ANSI 132.1
Working Pressure: 175 psi (12 bar)
Nominal K Factor - US / (Metric): 5.6 / (80)
Product Description
Reliable Model F3QR Dry Sprinklers are quick response
sprinklers utilizing a durable 3mm frangible glass bulb. This
quick response enables these sprinklers to apply water to a
fire much sooner than standard response sprinklers of the
similar temperature rating.
Model F3QR Dry Sprinklers are intended for use in enclosed
dry and preaction systems and in enclosed areas subjected
to freezing temperatures, such as freezers and unheated
portions inside buildings.
Environments wherein dry sprinklers are employed can be
corrosive. For this reason, Model F3 Sprinklers have a special
wax fillet placed in the gap between the cup that supports the
bulb and the wrenching boss. This wax will not interfere with
the operation of the sprinkler, and it prevents contaminents
from entering the internal portion of the drop nipple. The wax
must not be removed.
Operation
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed Inside a precisely
manufactured glass capsule. This glass bulb is specially
constructed to provide fast thermal response. When the
temperature increases sufficiently, due to a fire, the bulb
shatters allowing operating parts to clear the waterway. This
enables the inlet seal to release air or water and subsequently,
cause water flow over the deflector in a uniform spray pattern,
controlling or extinguishing the fire.
B
F Ceiling
I.-F
1 13/32-
Escutcheon [35.7mmm]
f-yT
4- [101.6mm]Min.
— System Tee Cup ; l 12" 1304.8mm]Mo
," N7T
[51.a m]
;�- --Y --
z 1 /z" Mai.-
[63.5mm]
Hole in WallL
2 19/64- Dia.
[58.3mm]
1/2" [12.7mm]
"A" Dimension Escutcheon Adjustment
Adjustment Range
157FG05 +1/2" —0
[+12.7mm —0]
* FOR FACTORY MUTUAL (FM)
4" — 6" FOR UNDERWRITERS LABORATORIES (UL)
Notes: Do not install the Model F30R Dry Horizontal
Recessed Sidewall Sprinkler in walls which have
positive pressure in their side space.
Listed by cULus for Quick Response. Approved
by FM for Standard Response.
Recessed Horizontal sidewall sprinklers are listed
with cULus for installation of min. 4" (100mm) - to -
max. 6" (150mm) below ceiling and approved by
FM for installation of min. 4" (100mm) - to - max.
12" (300mm) below ceiling.
Ordering Information
Specify:
1. Sprinkler Type (select one):
(a) Model F30R Dry Pendent
(b) Model F3QR Dry Recessed Pendent
(c) Model F30R Dry Concealed Pendent
(d) Model F3QR Dry Horizontal Sidewall
(e) Model F3QR Dry Recessed Horizontal Sidewall
2. Sprinkler Temperature Rating.
3. Sprinkler Finish.
4. Cover Plate/Escutcheon Finish.
5. Length:
"A" Dimension (face of tee to face of ceiling or wall)
in (6mm) increments.
6. Model F30R Dry Pendent (a) is available without
sprinkler can and escutcheon.
Note:
1. The "A" dimension is based on a nominally gauged
pipe thread "make-up" of 0.600" (15mm) per ANSI
132.1 [71/2 threads approximately].
2. All platings and paintings are decorative and
intended for interior use.
General Installation Instructions
Model F3QR dry sprinklers must be installed only in
standard (ANSI B 16.3 class 150 and ANSI B 16.4 class
125) pipe tees even at branch line ends. They should not
be installed into elbows and pipe couplings located on
drop nipples to the sprinklers. For these and other fittings
including CPVC*, the dry sprinkler should be installed
into a fitting to conform to protrusion into the fitting in ac-
cordance with the diagrams. The "A" dimension of the dry
sprinkler, which extends into the freezers or a freezing
zone from wet pipe systems, should be selected to pro-
vide, as a minimum, the specified lengths in inches
shown in the following chart, between face of the fitting
and the outside wall or ceiling of the protected area. The
following chart is used for freezing zones when the ambi-
ent temperature around the wet pipe system is kept at 40
OF/ 4°C), and specifies the minimum length for fitting face
to ceiling or wall (outside) for different protected area
temperatures.
Length Face to Ceilin all
Temperature Protected Area'
12 inches / 300 mm
-20°F / -29°C
18 inches / 450 mm
-40°F / -40°C
24 inches / 600 mm
-600F / -51 °C
** For temperatures falling between those in the above chart, the
minimum length may be determined by interpolation.
During installation, the following steps must be followed
1. Cut the specified size hole (see illustrations) for the
sprinkler in the ceiling or wall directly in line with the
tee.
2. Apply pipe joint compound to the 1" (25mm) pipe
threads and install sprinkler using the Model G3 or
G3 R/C Sprinkler Wrench as specified.
3. Install the Model FP push -on / thread -off escutcheon or
CCP cover plate if required.
Note: Installation of the Model F3QR Sprinklers is not rec-
ommended in copper pipe systems, as this may reduce
the life expectancy of the sprinklers.
Model F3QR Concealed and Recessed
Installation Instructions
The Model G3 R/C wrench (Fig. 1) is designed to locate
on the wrenching pads of the recessed sprinkler while
centering in the cup. A standard'/z' drive ratchet may
be used to drive this wrench. Figures 1 and 2 show
sequentially the insertion of the wrench. First the wrench,
with its jaws above the sprinkler deflector, is moved
laterally until centered with the cup. Then raise the
wrench inside of the cup until its jaws engage the
sprinkler's square wrenching pads (Fig. 3). To remove
the wrench, follow this procedure in reverse order. Care
should be taken to avoid striking the deflector, with the
wrench.
Model G3 Wrench (Fig. 4) is used for installation of
Pendent and Horizontal Sidewall sprinklers.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and
installation. REMOVE THIS PROTECTION AT THE TIME
THE SPRINKLER SYSTEM IS PLACED IN SERVICE
FOR FIRE PROTECTION. Removal of the protectors
before this time may leave the bulb vulnerable to
damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE
PROTECTORS BY UNDOING THE CLASP BY HAND.
DO NOT USE TOOLS TO REMOVE THE
PROTECTORS.
Maintenance
The Model F3QR Quick Response Dry Sprinklers should
be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not remove
the factory applied thermally sensitive wax fillet between
the bulb supporting cup and the wrenching boss. Do not
replace this wax with a substitute substance. An Alternate
substance may interfere with proper operation of the
sprinkler. Do not clean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by
using a soft brush or gently vacuuming. Remove any
sprinkler which has been painted (other than factory
applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior to
installation, sprinklers should be maintained in the original
cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper
operation or non -operation.
* Spears CPVC sprinkler adapter tees (with steel thread
insert) can only be used with horizontal sidewall
sprinklers which do not require protrusion into tees to
prevent ice or debris blockage of sprinkler inlets. These
CPVC tees do not permit sufficient sprinkler inlet
protrusion as required for pendent installation.
5.
UponorAquaPEX®White, coils
Submittal information
Revision M: Sept. 18, 2018
Project information
Job name:
Location: Part no. ordered:
Uponof
Engineer: Date submitted:
Contractor: Submitted by:
Manufacturer's representative: Approved by:
Technical data
Material: Crosslinked polyethylene PEX-a Engel Method; PEX 5106
Standard grade hydrostatic ratings (PPI): 200°F (93°C) at 80 psi (551 kPa)
180°F (82°C) at 100 psi (689 kPa)
73.4°F (23°C) at 160 psi (1,103 kPa)
'/2", %", 1", 1'/4", 1'/2" and 2" UponorAquaPEX® White only:
---
120°F (49°C) at 130 psi (896 kPa)
Linear expansion rate: 1.1'/10°F/100' (27.94mm/5.56°C/30.48m)
Product information and application use
Uponor AquaPEX White is used for hot and cold domestic potable water distribution and residential fire safety as well
as radiant heating/cooling and hydronic piping systems containing no ferrous corrodible components or where ferrous
components are isolated from the piping.
✓ Description
Part number
I.D.
O.D.
Weight
'/4' Uponor AquaPEX White, 100-ft. coil
F1040250
0.241"
0.375"
4.0 lbs.
Uponor AquaPEX White, 400-ft. coil
F1090375
0.350"
0.500"
20.0 lbs.
Uponor AquaPEX White, 1,000-ft. coil
F1120375
0.350"
0.500"
44.0 lbs.
''/2" Uponor AquaPEX White, 100-ft. coil
F1040500
0.475"
0.625"
6.0 lbs.
%" Uponor AquaPEX White, 300-ft. coil
F1060500
0.475"
0.625"
18.0 lbs.
''/z" Uponor AquaPEX White, 500-ft. coil
F1100500
0.475"
0.625"
27.6 lbs.
''/z" Uponor AquaPEX White, 1,000-ft. coil
F1120500
0.475"
0.625"
54.0 lbs.
Uponor AquaPEX White, 300-ft. coil
F1060625
0.574"
0.750"
28.0 lbs.
Uponor AquaPEX White, 1000-ft. coil
F1120625
0.574"
0.750"
86.0 lbs.
Uponor AquaPEX White, 100-ft. coil
F1040750
0.671"
0.875"
10.0 lbs.
Y44" Uponor AquaPEX White, 300-ft. coil
F1060750
0.671"
0.875"
34.0 lbs.
%" Uponor AquaPEX White, 500-ft. coil
F1100750
0.671"
0.875"
54.0 lbs.
1" Uponor AquaPEX White, 100-ft. coil
F1041000
0.862"
1.125"
20.0 lbs.
1" Uponor AquaPEX White, 300-ft. coil
F1061000
0.862"
1.125"
56.0 lbs.
1" Uponor AquaPEX White, 500-ft. coil
F1101000
0.862"
1.125"
93.0 lbs.
1'/4' Uponor AquaPEX White, 100-ft. coil
F1061250
1.054"
1.375"
34.0 lbs.
1'/4" Uponor AquaPEX White, 300-ft. coil
F1021250
1.054"
1.375"
106.0 lbs.
1'/z" Uponor AquaPEX White, 100-ft. coil
F1061500
1.244"
1.625"
44.0 lbs.
1'/z" Uponor AquaPEX White, 300-ft. coil
F1021500
1.244"
1.625"
133.0 lbs.
2" Uponor AquaPEX White, 100-ft. coil
F1062000
1.629"
2.125"
68.2 lbs.
2" Uponor AquaPEX White, 200-ft. coil
F1052000
1.629"
2.125"
136.4 lbs.
2" Uponor AquaPEX White, 300-fit. coil
F1022000
1.629"
2.125"
204.6 lbs.
2'/i' Uponor AquaPEX White, 100-ft. coil
F1062500
2.011"
2.625"
88.0 lbs.
2'/i' Uponor AquaPEX White, 300-ft. coil
F1022500
2.011"
2.625"
264.0 lbs.
3" Uponor AquaPEX White, 100-ft. coil
F1063000
2.400"
3.125"
128.0 lbs.
3" Uponor AquaPEX White, 300-ft. coil
F1023000
2.400"
3.125"
384.0 lbs.
Installation
Use ProPEX® fittings for %" through 3" pipe.' Refer to the ProPEX Connections Instructional
Guide, Uponor
Piping Pocket Guide,
Plumbing Design Assistance
Manual (PDAM), Complete Design Assistance Manual (CDAM), Hydronic Piping
Design Assistance Manual (HPDAM) or AquaSAFET1A Residential
Fire Sprinkler
Installation Guide for more information.
Listings2
Codes
Standards
cNSFus-fs3; cNSFus-pw; cQAlus P321; UL;
IAPMO; ICC; IPC; IMC; IRC;
ANSI/NSF 14; ANSI/NSF 61; ASTM F876; ASTM F877; ASTM F1960; ASTM
CSA; PPI TR-4; ICC-ES; BMEC; CCMC
UPC; UMC; NSPC; HUD;
F2023; ASTM E84; CAN/ULC S102.2; ASTM
E119/UL 263; CAN/ULC S101;
UFGS; NPC of Canada;
ASTM E814/ULC S115;
CSA B137.5; CSA B214;
NBC of Canada
UL 18213; ULC/ORD-C199P3;
AWWA C9044
Related applications Contact information
PEX-a plumbing systems Uponor, Inc. Uponor Ltd.
AquaSAFETM fire safety systems 5925 148"' Street West 6510 Kennedy Road
Radiant heating and cooling systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA
Hydronic piping systems Phone: 800.321.4739 Phone: 888.994.7726
Fax: 952.891.2008 Fax: 800.638.9517
uponorpro.com uponorpro.com
'ProPEX® is a registered trademark of Uponor, Inc. ProPEX- is a trademark of Uponor Ltd.
2Visit listing agency's website for complete information. 3For 3/4", 1" and 1'W pipe only. 4For %" to 3" pipe.
ProPEX° Ring
Submittal information
Revision I: Nov. 1, 2018
Project information
Job name:
Location: Part no. ordered:
Engineer: Date submitted:
Contractor: Submitted by:
Manufacturer's representative: Approved by:
Technical data
Material: Engel -method crosslinked polyethylene (PEX-a)
Density: 926 to 940 kg/m3
Degree of crosslinking: 70% to 89%
Product information and application use
Uponor ProPEX® rings are required to make a proper ProPEX connection.' The ProPEX
ring with stop includes a leading edge chamfer and stop edge.
✓ Description Part number
ProPEX Ring, %"
ProPEX Ring with Stop, '/2"
ProPEX Ring with Stop, %"
ProPEX Ring with Stop, 3/4"
ProPEX Ring with Stop, 1"
ProPEX Ring with Stop, 1'/4"
ProPEX Ring with Stop, 1'/2"
ProPEX Ring with Stop, 2"
ProPEX Ring with Stop, 2'/2"
ProPEX Ring with Stop, 3"
Installation
Q4690302
Q4690512
Q4690625
Q4690756
Q4691000
Q4691250
Q4691500
Q4692000
Q4692500
Q4693000
uponof
Length
I.D.
O.D.
Weight
0.54"
0.49"
0.74"
0.005lbs.
0.63"
0.63"
0.87"
0.006lbs.
0.79"
0.75"
1.00"
0.008lbs.
0.87"
0.88"
1.13"
0.012lbs.
1.10"
1.13"
1.42"
0.020lbs.
1.35"
1.38"
1.66"
0.030lbs.
1.61"
1.63"
1.91"
0.040 lbs.
1.97"
2.14"
2.61"
0.133lbs.
2.61"
2.66"
3.25"
0.230lbs.
3.12"
3.16"
3.87"
0.400lbs.
Square cut the Uponor PEX tubing. Remove excess material. Slide the ProPEX ring over the end of the tubing (maximum 'lid' over -hang for rings without stop).
When using the ProPEX ring with stop, slide the ring on the tubing with the chamfered edge first until the end of the tubing contacts the stop edge. Expand the
tubing and ring. If using the ProPEX Manual Expander Tool, rotate the tool a quarter turn after each expansion to prevent the formation of grooves. Remove the
expansion tool and fully seat the tubing and ring against the shoulder of the fitting. Make ProPEX connections at temperatures above 5°F/-15°C. For more
information, refer to the Uponor ProPEX Connections Instructional Guide.
Listings'
cNSFus-fs3; cNSFus-pw; cNSFus-rfh; cQAlus; UL; CSA; PPI TR-4; ICC-ES; IAPMO; BMEC; CCMC; cQAlus P321
Codes
ICC; IPC; IMC; IRC; UPC; UMC; NSPC; HUD; UFGS; NPC of Canada; NBC of Canada
Standards
ANSI/NSF 14; ANSI/NSF 61; ASTM F876; ASTM F877; ASTM F1960; ASTM F2023; ASTM E84; CAN/ULC S102.2; ASTM E119/UL 263; CAN/ULC S101; ASTM
E814/ULC S115; CSA 13137.5; CSA B214; UL 18213; ULC/ORD-C199P3
Related applications Contact information
PEX-a plumbing systems
Uponor Inc.
Uponor Ltd.
AquaSAFE fire safety systems
5925 148"' Street West
6510 Kennedy Road
Hydronic radiant heating and cooling systems
Apple Valley, MN 55124 USA
Mississauga, ON L5T 2X4 CANADA
Snow melting systems
Phone: 800.321.4739
Phone: 888.994.7726
Turf conditioning systems
Fax: 952.891.2008
Fax: 800.638.9517
Permafrost prevention systems
uponorpro.com
uponorpro.com
'ProPEX® is a registered trademark of Uponor, Inc. ProPEXT" is a trademark of Uponor Ltd.
2Visit listing agency's website for complete information; 3For '/2",'/", 1", 11/", 1'/2" and 2" tubing only
ProPEXO Engineered
Submittal information
Revision H: May 23, 2019
Project information
Job name:
Polymer (EP) Tee
Location: Part no. ordered:
Engineer: Date submitted:
Contractor: Submitted by:
Manufacturer's representative: Approved bv:
Technical data
Material: Engineered polymer (EP)
Maximum temperature (no pressure): 320°F (160°C)
Maximum working temperature/pressure: 210*F (99*C) at 150 psi (1,034 kPa)
Product information and application use
ProPEX® engineered polymer (EP) tees make diverting connections for Uponor crosslinked
polyethylene (PEX-a)tubing for use in hot and cold domestic potable water systems,
residential fire sprinkler systems and hydronic radiant heating and cooling systems. Each
end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor
AquaPEX® or Wirsbo hePEXTM tubing.'
Note: Branch size is listed last in the part descriptions.
Uponof
Part
✓
Equivalent Equivalent
cv
cv
Description
number
A B Weight
length (ft.) length (ft.)
through
branch
through branch
ProPEX EP Tee, ''M." PEX x'/z' PEX x'/" PEX Q4755060
2.50" 1.53" 0.02 lbs.
1.0 6.3
7.7
3.4
ProPEX EP Tee, %" PEX x'/:' PEX x'/:' PEX* Q4757575
3.30" 1.94" 0.05 lbs.
1.5 15.6
15.7
5.4
ProPEX EP Tee, 1" PEX x 1" PEX x 1" PEX* Q4751010
4.10" 2.47" 0.07 lbs.
1.3 12.7
30.5
11.3
ProPEX EP Tee, 1'/4" PEX x 1'/4" PEX x 1'/4" PEX* Q4751313
4.80" 3.22" 0.15 lbs.
3.8 8.6
34.0
23.9
ProPEX EP Tee, 1 Yz' PEX x 1'/." PEX x 1'M." PEX Q4751515
5.80" 3.82" 0.25 lbs.
1.8 10.6
63.7
31.0
ProPEX EP Tee, 2" PEX x 2" PEX x 2" PEX Q4752000
7.45" 4.79" 0.38 lbs.
0.8 15.5
150.7
52.5
ProPEX EP Tee, 21/' PEX x 21/z' PEX x 21/z' PEX Q4752500
10.56" 5.45" 1.14 lbs.
2.7 22.3
197.2
81.5
ProPEX EP Tee, 3" PEX x 3" PEX x 3" PEX Q4753000
12.26" 6.37" 1.86 lbs.
2.8 23.9
286.6
122.8
Installation
Use the appropriate ProPEX Ring for PEX-a tubing. Refer to the Uponor Professional Plumbing Installation Guide, AquaSAFET"^ Residential Fire
Sprinkler Installation
Guide or Uponor Radiant Installation Handbook for additional information.
Standards
ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM F1960; CAN/CSA B137.5; NSF 14; NSF 61
Codes
IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC
Listings
cNSFus-pw; *cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code
Related applications
Contact information
PEX-a plumbing systems
Uponor, Inc.
Uponor Ltd.
Hydronic radiant heating and cooling systems
5925 148t' Street West
6510 Kennedy Road
Snow and ice melting systems
Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA
Turf conditioning systems
Phone: 800.321.4739
Phone: 888.994.7726
Permafrost prevention systems
Fax: 952.891.2008
Fax: 800.638.9517
AquaSAFETm fire safety systems
uponorpro.com
uponorpro.com
'ProPEX® is a registered trademark of Uponor, Inc. ProPEXT" is a trademark of Uponor Ltd.
ProPEX° Engineered Polymer (EP) Reducing Tee (up to 11/2") uponof
Submittal information
Revision I: Sept. 16, 2019
Project information
Job name:
Location: Part no. ordered:
Engineer: Date submitted:
Contractor: Submitted by:
Manufacturer's representative: Approved by:
Technical data
Material: Engineered polymer (EP) n�
Maximum temperature (no pressure): 320°F (160°C)
Max. working temperature/pressure: 210°F (99°C) at 150 psi (1,034 kPa)
Product information and application use
ProPEX® engineered polymer (EP) reducing tees make diverting connections for Uponor PEX-a pipe for use in hot and cold B
domestic potable water systems, residential fire sprinkler systems and hydronic radiant heating and cooling systems. Each
end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor AquaPEX11 or Wirsbo hePEXTM
pipe.' Note: Branch size is listed last in the part descriptions.
✓ Description
Part
A
B
Weight
Equiv, length (ft.)
Equiv. length
Cv
Cv
number
through
(ft.) branch
through
branch
ProPEX EP Reducing Tee,''/2" PEX x'/i' PEX x %" PEX
Q4755575
2.86"
1.76"
0.03 lbs.
1.0
15.6
7.7
5.4
ProPEX EP Reducing Tee, '/<" PEX x'/i' PEX x'/i' PEX
Q4757555
3.10"
1.70"
0.04 lbs.
3.5
6.4
4.6
3.4
ProPEX EP Reducing Tee, '/<" PEX x'/z' PEX x'/;' PEX*
Q4757557
3.10"
1.94"
0.04 lbs.
2.3
16.1
5.4
5.4
ProPEX EP Reducing Tee, '/<" PEX x'/;' PEX x PEX
Q4757563
3.30"
1.85"
0.05 lbs.
N/A
N/A
N/A
N/A
ProPEX EP Reducing Tee, '/<" PEX x'/;' PEX x'/z' PEX*
Q4757550
3.30"
1.70"
0.04 lbs.
2.0
7.6
14.2
3.1
ProPEX EP Reducing Tee, '/<" PEX x'/;' PEX x 1" PEX*
Q4757710
3.64"
2.32"
0.08 lbs.
1.5
5.7
15.7
8.7
ProPEX EP Reducing Tee, 1" PEX x'/i' PEX x 1" PEX
Q4751501
3.71"
2.43"
0.09 lbs.
1.98
9.7
12.3
5.7
ProPEX EP Reducing Tee, 1" PEX x'/d' PEX x'/ PEX
Q4751750
3.65"
1.96"
0.07 lbs.
2.27
6.69
3.1
13.2
ProPEX EP Reducing Tee, 1" PEX x'/<" PEX x'/4" PEX*
Q4751775
3.90"
2.24"
0.08 lbs.
2.4
16.7
12.8
5.3
ProPEX EP Reducing Tee, 1" PEX x'/<" PEX x 1" PEX*
Q4751751
3.90"
2.47"
0.08 lbs.
2.4
15.1
12.9
10.5
ProPEX EP Reducing Tee, 1" PEX x'/;' PEX x 1%" PEX
Q4751753
4.15"
2.95"
0.12 lbs.
2.74
19.48
14.7
12.0
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x'/;' PEX*
Q4751150
4.10"
2.00"
0.08 lbs.
1.2
6.5
32.2
3.4
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x %" PEX*
Q4751175
4.10"
2.24"
0.09 lbs.
1.7
6.4
27.8
8.2
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x 1 '/;' PEX*
Q4751113
4.38"
2.95"
0.13 lbs.
6.52
5.37
15.0
28.0
ProPEX EP Reducing Tee, 1%" PEX x'/<" PEX x'/<" PEX*
Q4751377
4.11"
2.38"
0.09 lbs.
2.74
7.41
7.3
12.0
ProPEX EP Reducing Tee, 1%" PEX x'/<" PEX x 1" PEX*
Q4751371
4.37"
2.62"
0.11 lbs.
2.70
7.59
13.9
12.1
ProPEX EP Reducing Tee, 1%" PEX x'/<" PEX x 1Y<" PEX*
Q4751373
4.61"
2.88"
0.13 lbs.
2.74
11.91
18.8
12.0
ProPEX EP Reducing Tee, 1'/<" PEX x 1" PEX x %" PEX*
Q4751317
4.50"
2.73"
0.11 lbs.
3.4
5.2
21.0
9.3
ProPEX EP Reducing Tee, 11/;' PEX x 1" PEX x 1" PEX*
Q4751311
4.70"
2.97"
0.12 lbs.
11.0
23.0
11.7
8.4
ProPEX EP Reducing Tee, 11/;' PEX x 11/4" PEX x'/;' PEX*
Q4751350
4.40"
2.15"
0.10 lbs.
1.9
3.9
45.2
4.1
ProPEX EP Reducing Tee, 11/4" PEX x 11/4" PEX x %" PEX*
Q4751337
4.70"
2.73"
0.13 lbs.
2.3
5.7
43.4
8.9
ProPEX EP Reducing Tee, 11/4" PEX x 11/4" PEX x 1" PEX*
Q4751331
5.00"
2.97"
0.14 lbs.
4.2
6.3
33.0
15.8
ProPEX EP Reducing Tee, 1'/z" PEX x'/<" PEX x %" PEX
Q4751577
4.37"
2.64"
0.13 lbs.
2.88
7.41
7.3
11.7
ProPEX EP Reducing Tee, 1'/z" PEX x'/<" PEX x 1'/z" PEX
Q4751575
4.97"
3.39"
0.19 lbs.
2.74
19.10
22.9
12.0
ProPEX EP Reducing Tee, 1'/z" PEX x 1" PEX x %" PEX
Q4751517
5.25"
3.06"
0.17 lbs.
4.0
5.1
19.5
9.3
ProPEX EP Reducing Tee, 1'/z" PEX x 1" PEX x 1" PEX
Q4751511
5.25"
3.30"
0.18 lbs.
4.3
6.5
18.9
15.6
ProPEX EP Reducing Tee, 11/2" PEX x 1" PEX x 11/2" PEX
Q4751505
5.40"
3.45"
0.20 lbs.
4.2
14.9
19.0
26.5
ProPEX EP Reducing Tee, 11/2" PEX x 11/4" PEX x %" PEX
Q4751537
5.50"
2.65"
0.18 lbs.
4.2
11.3
33.1
6.3
ProPEX EP Reducing Tee, 11/2" PEX x 11/4" PEX x 1" PEX
Q4751531
5.50"
2.85"
0.19 lbs.
3.1
13.1
36.4
11.2
ProPEX EP Reducing Tee, 11/2" PEX x 11/4" PEX x 11/4" PEX
Q4751533
5.50"
3.15"
0.21 lbs.
2.0
17.7
45.4
17.0
ProPEX EP Reducing Tee, 1'/z" PEX x 1'/2" PEX x'/i' PEX
Q4751550
4.95"
2.30"
0.14 lbs.
2.4
6.3
60.5
3.4
ProPEX EP Reducing Tee, 1'/z" PEX x 1'/2" PEX x %" PEX
Q4751557
5.30"
3.06"
0.20 lbs.
2.9
5.4
56.0
9.0
ProPEX EP Reducing Tee, 1'/2" PEX x 1'/2" PEX x 1" PEX
Q4751551
5.75"
3.30"
0.21 lbs.
3.1
6.9
53.8
15.3
ProPEX EP Reducing Tee, 1'/2" PEX x 1'/2" PEX x 11/4" PEX
Q4751553
5.80"
3.56"
0.22 lbs.
3.2
4.1
54.3
33.7
Installation
Use the appropriate ProPEX ring for PEX-a pipe. Refer to the Uponor Piping Systems
Installation
Guide,
the AquaSAFETm Residential Fire
Sprinkler Installation Guide or the Uponor
Radiant Installation Handbook for additional information.
Standards Codes
Listings
ASTM E84; ASTM E119; ASTM E814; IBC; IMC; IPC; IRC;
NPC of Canada;
cNSFus-pw; *cNSFus-pw-fs;
cQAlus P321;
HUD MR 1269; ICC-ES-PMG-1006;
ASTM F877; ASTM F1960; NSPC; UMC; UPC
ICC-ES-PMG-1012;
*UL 1821; *ULC/ORD-C199P; U.P. Code
CAN/CSA B137.5; NSF 14; NSF 61
Related applications
Contact information
PEX-a plumbing systems
Uponor Inc.
Uponor Ltd.
Hydronic radiant heating and cooling systems
5925 1481h Street West
6510 Kennedy Road
Snow and ice melting systems
Apple Valley,
MN 55124
USA
Mississauga, ON L5T 2X4
CANADA
Turf conditioning systems
Phone: 800.321.4739
Phone: 888.994.7726
Permafrost prevention systems
Fax: 952.891.2008
Fax: 800.638.9517
AquaSAFETM fire safety systems
uponorpro.com
uponorpro.com
'ProPEX® is a registered trademark of Uponor Inc. ProPEX" is a trademark of Uponor Ltd.
ProPEX® Engineered Polymer (EP) Elbow
Submittal information
Revision J: June 21, 2019
Project information
Job name:
Location: Part no. ordered:
Engineer: Date submitted:
Contractor: Submitted by:
Manufacturer's representative: ADDroved bv:
Technical data
Material: Engineered polymer (EP)
Maximum temperature (no
pressure): 320°F (160°C)
Maximum working
temperature/pressure: 210°F (99°C) at 150 psi (1,034 kPa)
Product information and application use
ProPEX® engineered polymer (EP) elbows make 90-degree connections for Uponor
crosslinked polyethylene (PEX-a) tubing for use in hot and cold domestic potable water
systems, residential fire safety and hydronic radiant heating and cooling systems. Each end
of the elbow is manufactured with an Uponor ProPEX fitting for connections to Uponor
AquaPEX® or Wirsbo hePEXTm tubing.'
Uponof
✓ Description
Part number
A
B
Weight
Equivalent
Cv
length (ft.)
ProPEX EP Elbow, '/z" PEX x'/z" PEX
Q4760500
1.30"
1.30"
0.02 lbs.
10.4
2.6
ProPEX EP Elbow, 3/4° PEX x 3/4" PEX*
Q4760750
1.60"
1.60"
0.03 lbs.
10.8
6.7
ProPEX EP Elbow, 1" PEX x 1" PEX*
Q4761000
2.10"
2.10"
0.07 lbs.
11.5
11.9
ProPEX EP Elbow, 1'/4" PEX x 1'/4" PEX*
Q4761250
2.45"
2.45"
0.11 lbs.
10.0
22.2
ProPEX EP Elbow, 1'/z" PEX x 1'/z" PEX
Q4761500
2.77"
2.77"
0.18 lbs.
11.5
29.7
ProPEX EP Elbow, 2" PEX x 2" PEX
Q4762000
3.76"
3.76"
0.30 lbs.
17.1
50.2
ProPEX EP Elbow, 2'/z" PEX x 2'/z" PEX
Q4762500
4.93"
4.93"
0.85 lbs.
20.0
86.0
ProPEX EP Elbow, 3" PEX x 3" PEX
Q4763000
5.88"
5.88"
1.44 lbs.
23.2
125.0
ProPEX EP 45 Elbow, 1'/2' PEX x 1'/2" PEX
Q4761515
2.32"
2.32"
0.13 lbs.
9.3
33.1
ProPEX EP 45 Elbow, 2" PEX x 2" PEX
Q4762020
2.91"
2.91"
0.32 lbs.
8.8
68.9
ProPEX EP 45 Elbow, 2'/2' PEX x 2'/2" PEX
Q4762525
3.83"
3.83"
0.65 lbs.
7.0
136.8
ProPEX EP 45 Elbow, 3" PEX x 3" PEX
Q4763030
4.48"
4.48"
1.07 lbs.
8.3
195.5
Installation
Use the appropriate ProPEX ring for PEX-a tubing. Refer to the Uponor Piping
Pocket Guide,
AquaSAFETm
Residential Fire Sprinkler Installation Guide
or Uponor
Radiant Installation Handbook for additional information.
Standards
ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM F1960; CAN/CSA B137.5; NSF
14; NSF 61
Codes
IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC
Listings
cNSFus-pw; *cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code
Related applications Contact information
PEX-a plumbing systems
Uponor Inc.
Uponor Ltd.
Hydronic radiant heating and cooling systems
5925 148t' Street West
6510 Kennedy Road
Snow and ice melting systems
Apple Valley, MN 55124 USA
Mississauga, ON L5T 2X4 CANADA
Turf conditioning systems
Phone: 800.321.4739
Phone: 888.994.7726
Permafrost prevention systems
Fax: 952.891.2008
Fax: 800.638.9517
AquaSAFE fire safety systems
uponorpro.com
uponorpro.com
1 ProPEX® is a registered trademark of Uponor, Inc. ProPEX- is a trademark of Uponor Ltd.
ProPEX° Fire Sprinkler Adapter
Submittal Information
Revision B: March 17, 2009
Project Information
Job Name:
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer's Representative: Approved By:
Technical Data
Material: 300 Series Stainless Steel
Product Information and Application Use
Use the ProPEX° Fire Sprinkler Adapter in conjunction with the
appropriate sprinkler to provide a multi -purpose residential fire
sprinkler system'. For residential applications, the system is
installed with the cold -potable portion of the Uponor plumbing
system. Make connections with Uponor ProPEX fittings. These
fittings are designed for use only with 3/4" or 1" AquaPEX°
White tubing in the Uponor AQUASAFE° Looped System.
uponof
✓ Description Part A B C D E Weight
Number
ProPEX Fire Sprinkler Adapter, 3/4" PEX x 1/2" FNPT Q7517550 0.75" 1.88" 2.50" 1.82" 1.41" 0.268 lbs.
ProPEX Fire Sprinkler Adapter, 1" PEX x 1/2" FNPT Q7511050 0.75" 1.88" 2.50" 2.06" 1.54" 0.408 lbs.
Installation
Use appropriate ProPEX Ring for connecting the tubing. Refer to the AquaPEX Installation Handbook or the Uponor AQUASAFE°
Installation Guide for additional information.
Standards
CAN/CSA B137.5; ASTM F877; ASTM F 1960
Codes
IPC; UPC; NSPC; IRC; IMC; NPC of Canada
Listings
ANSI/NSF 14- and 61-certified; U.P. Code; ICC ESR 1099; HUD MR 1269; UL 1821; ULC/ORD - C 199 P
Related Applications
PEX-a Plumbing Systems
AQUASAFE Fire Safety Systems
Contact Information
Uponor, Inc.
5925 1481h Street West
Apple Valley, MN 55124 USA
Phone: (800) 321-4739
Fax: (952) 891-2008
www.uponor-usa.com
Uponor Ltd.
2000 Argentia Rd., Plaza 1, Ste. 200
Mississauga, ON L5N 1W1 CANADA
Phone: (888) 994-7726
Fax: (800) 638-9517
www.uponor.ca
'ProPEX° is a registered trademark of Uponor, Inc. ProPEXTM is a trademark of Uponor Ltd.