Loading...
FIR2020-0086+Fire_Sprinkler_Equipment_Specification_Sheets+10.19.2020_6.25.10_AMBulletin 006 May 2019 Reliable Features cULus Listed as Residential Sprinklers Push -On cover plate installation Low water flow requirements Product Description Model RFC Series residential sprinklers are flat cover plate, concealed pendent sprinklers intended for installation in accordance with NFPA 13, NFPA 13R, or NFPA 13D. The sprinklers are cULus Listed as Residential Sprinklers in ac- cordance with UL 1626. In addition, Model RFCLL Series sprinklers are cULus Certified for Health Effects to NSF/ANSI standard 61 Annex G (LL) and Australian WaterMark Certified (WMCS). Model RFC30 sprinklers have a 1650F (74°C) temperature rated fusible -link operating element. Model RFC43, RFC49, RFC58, and RFC76 sprinklers are offered with either a 1650F (74°C) or 212OF (100°C) temperature rated fusible -link oper- ating element. Sprinklers with a 1650F (74°C) temperature rating are ordinary temperature classification and are listed for use with a 1350F (57°C) temperature rated cover plate. Sprinklers with a 212OF (100°C) temperature rating are inter- mediate temperature classification and are listed for use with a 1650F (74°C) temperature rated cover plate. Model RFC Series sprinklers are installed with a Model RFC cover plate. Model RFC cover plates may be installed by ei- ther pushing or threading the cover plate into the sprinkler cup. Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49 and RFC49LL sprinklers allow 1/2" (13 mm) of cover plate adjust- ment. Model RFC58 and RFC76 sprinklers allow 3/4" (19 mm) of cover plate adjustment. Model RFC cover plates are avail- able in a variety of finishes as listed in Table H. Model RFC Series Residential Sprinklers Flat Concealed Pendent Model RFC30 & RFC30LL Model RFC49 & RFC49LL Model RFC76 cULus Listed Model RFC43 & RFC43LL Model RFC58 )M Model RFC Cover Plate Sprinkler Model Nominal K-Factor gpm/psi (1/min/bary/Z ) Max. Coverage Area ft x ft (m x m) Listings & Approvals Sprinkler Identification Number (SIN) RFC30 3.0(43) 14 x 14 (4.3 x 4.3) cULus RA0611 RFC30LL 3.0(43) 14 x 14 (4.3 x 4.3) cULus, LL, WMCS RA3211 RFC43 4.3(62) 20 x 20 (6.1 x 6.1) cULus RA0612 RFC43LL 4.3(62) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3212 RFC49 4.9(71) 20 x 20 (6.1 x 6.1) cULus RA0616 RFC49LL 4.9(71) 20 x 20 (6.1 x 6.1) cULus, LL, WMCS RA3216 RFC58 5.8(84) 20 x 20 (6.1 x 6.1) cULus RA0613 RFC76 7.6(109) 20 x 20 (6.1 x 6.1) cULus RA0618 cULus: cULus Listed to UL1626, Residential Sprinklers for Fire Protection Service. LL: cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (Less than 0.25% Lead content). WMCS: Australian WaterMark Certified. www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1 R1/2 Nominal K-Factor: 3.0 (43 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Rating 165°F (74°C) sprinkler 135°F (57°C) cover plate Cover Plate Model RFC cover plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed to UL 1626 cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (RFC30LL only) Watermark Certified (RFC30LL only) Model RFC30 & RFC30LL Sprinkler Components and Dimensions Threads — Body Cup —� Tower Fusible Link — Deflector (retracted) Pin (extended) - Deflector (extended) 1-3/4" (44 mm) +/- 1/4" (6 mm) Nominal face of fitting to ceiling Bottom View 2-5/16" (58 mm) Dia. 3/16"(5mm' Model RFC Cover Plate i 3-5/16" (84 mm) Dia. —►{ N Ceiling Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria Minimum Flow and Residual Pressure Max. Coverage Area (2) Flow Pressure ft. x ft. gpm psi (m x m) (1/min) (bar) 12 x 12 9 9.0 (3.6 x 3.6) (34) (0.62) 14 x 14 10 7 11.0 (4.3 x 4.3) (38) (0.76) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Reliable Page 2 of 8 May 2019 www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1 R1/2 Nominal K-Factor: 4.3 (62 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Rating Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model RFC cover plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed to UL 1626 cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (RFC43LL only) Watermark Certified (RFC43LL only) Model RFC43 & RFC43LL Sprinkler Components and Dimensions Threads Body Cup Tower Fusible Link Deflector (retracted) Pin (extended) Deflector (extended) - 1-3/4" (44 mm) +/- 1/4" (6 mm) Nominal face of fitting to ceiling Model RFC Cover Plate Model RFC43 & RFC43LL Sprinkler Hydraulic Design Criteria r Bottom View , 2-5/16" (58 mm) Dia. - a-1 3-5/16" (84 mm) Dia. 3/16" (5 mm' Ceiling Minimum Flow and Residual Pressure Max. Coverage Area (2) Ordinary Temperature Intermediate Temperature Flow Pressure Flow Pressure ft. x ft. (m x m) gpm psi gpm psi (1/min) (bar) (1/min) (bar) 15 x 15 12 7.8 12 7.8 (4.6 x 4.6) (45) (0.54) (45) (0.54) 16 x 16 13 9.1 13 9.1 (4.9 x 4.9) (49) (0.63) (49) (0.63) 18 x 18 18 17.5 (5.5 x 5.5) (68) (1.21) 20 x 20 21 23.8 (6.1 x 6.1) (79) (1.64) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Reliable Page 3 of 8 May 2019 www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1 R1/2 Nominal K-Factor: 4.9 (71 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Sensitivity Fast -response Temperature Rating Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model RFC cover plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Cover Plate Finishes Listings and Approvals cULus Listed to UL 1626 (See Table H) cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (RFC49LL only) Watermark Certified (RFC49LL onlv) Model RFC49 & RFC49LL Sprinkler Components and Dimensions Threads Body — Cup Tower Fusible Link Deflector (retracted) Pin (extended) Deflector (extended) 1-3/4" (44 mm) +/- 1/4" (6 mm) Nominal face of fitting to ceiling Bottom View 2-5/16" (58 mm) Dia. Model RFC Cover Plate 3-5/16" (84 mm) Dia. �-- Ceiling Model RFC49 & RFC49LL Sprinkler Hydraulic Design Criteria Minimum Flow and Residual PressureM Max. Coverage Area (Z) Ordinary Temperature Intermediate Temperature Flow Pressure Flow Pressure ft. x ft. (m x m) gpm psi gpm psi (1/min) (bar) (1/min) (bar) 16 x 16 13 7.0 13 7.0 (4.9 x 4.9) (49.0) (0.48) (49.0) (0.48) 18 x 18 17 12.0 17 12.0 (5.5 x 5.5) (64.3) (0.83) (64.3) (0.83) 20 x 20 20 16.7 21 18.4 (6.1 x6.1) (75.7) (1.15) (79.5) (1.27) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table D above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Reliable Page 4 of 8 May 2019 www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 1/2" NPT or ISO 7-1 R1/2 Nominal K-Factor: 5.8 (84 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Chrome Plated Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Ratings Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model RFC Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed Model RFC58 Sprinkler Components and Dimensions Bottom View 2-5/16" (58 mm) y Dia. Threads _ Body _ Cup =_ Tower Fusible Link 1-7/8" (48 mm) +/- 3/8" (9 mm) Deflector (retracted) Nominal face of fitting to ceiling � Pin (extended) 7", 3/16"(5mm, """` Deflector (extended) Model RFC Cover Plate 3-5/16" (84 mm) Dia. Ceiling Model RFC58 Sprinkler Hydraulic Design Criteria Minimum Flow and Residual Pressure') Max. Coverage Area (2) Flow Pressure ft. x ft. gpm psi (m x m) (1/min) (bar) 16 x 16 16 7.6 (4.9 x 4.9) (60.6) (0.53) 18 x 18 18 9.6 (5.5 x 5.5) (68.1) (0.66) 20 x 20 20 11.9 (6.1 x 6.1) (75.7) (0.82) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Reliable Page 5 of 8 May 2019 www.reliablesprinkler.com Technical Specifications Style: Flat Concealed Pendent Threads: 3/4" NPT or ISO 7-1 R3/4 Nominal K-Factor: 7.6 (109 metric) Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m) Material Specifications Thermal Sensor: Nickel Alloy Solder Link Sprinkler Body: Brass Alloy Levers: Bronze Alloy Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Towers: Copper Alloy Pins: Stainless Steel Deflector: Bronze Alloy Cup: Steel Cover Plate Finishes (See Table H) Sensitivity Fast -response Temperature Ratings Ordinary: 165°F (74°C) sprinkler 135°F (57°C) cover plate Intermediate: 212°F (100°C) sprinkler 165°F (74°C) cover plate Cover Plate Model RFC Cover Plate Sprinkler Wrench Model FC (without wrench -able cap) Model W3 (with wrench -able cap) Listings and Approvals cULus Listed Model RFC76 Sprinkler Components and Dimensions Three Body Cup Towei Fusible Li Deflector (retra Pin (extern Deflector (extend 1-7/8" (48 mm) +/- 3/8" (9 mm) Nominal face of fitting to ceiling Model RFC Cover Plate Model RFC76 Flat Concealed Sprinkler Hydraulic Design Criteria /o Bottom View ti 2-5/16" (58 mm) Dia. 3-5/16" (84 mm) Dia. 3/16" (5 mm) Ceiling Minimum Flow and Residual PressureN Max. Coverage Area (2) Flow Pressure ft. x ft. gpm psi (m x m) (1/min) (bar) 16 x 16 21 7.6 (4.9 x 4.9) (79.5) (0.52) 18 x 18 24 9.9 (5,5 x 5.5) (90.8) (0.68) 20 x 20 34 20 (6,1 x 6.1) (128.7) (1.4) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Bulletin 006 Reliable Page 6 of 8 May 2019 www.reliablesprinkler.com Cover Plate Finishes(') Standard Finishes Special Application Finishes White Polyester Off White Paint Black Paint Raw Brass Chrome Plated Bright Brass Finished Bronze Black Plated Satin Chrome Stainless Steel Clad (3) Custom Color Paint(2) Notes: 1. Paint or any other coating applied over the factory finish will void all approvals and warranties. 2. Custom color paint is semi -gloss, unless specified otherwise. 3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the backside. Cover plates are not listed or approved as corrosion resistant. Stainless steel clad cover plates are not available perforated. Installation Dimensions Recommended Min. to Min. to Max. Sprinkler Cover Cover Plate Hole Diameter Cover Plate Max. Face Dropped Deflector Cover Plate Model Plate Diameter in Ceiling Adjustment of Fitting to Distance below Temperature Model inch (mm) inch (mm) inch (mm) Ceilings') Ceiling Rating inch (mm) inch (mm) RFC30, RFC 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 1350F RFC30LL (84) (67) (13) (38 to 51) (13 to 25) (57°C) RFC43, 1350F(2) RFC43LL, RFC 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 (57°C) RFC49, (84) (67) (13) (38 to 51) (13 to 25) or 1650F 3 RFC49LL (74°C) 1350F(2) RFC58, RFC 3-5/16 2-5/8 3/4 1-1/2 to 2-1/4 1/4 to 1 (57°C) RFC76 (84) (67) (19) (38 to 57) (6 to 25) or 165°F3 (74°C) Notes: 1. Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method prior to installation. A 1/2" x 1/2" brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing sprinklers. 2. For use with 165°F (74°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F (38°C). 3. For use with 212°F (100°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 150°F (66°C). Installation Model RFC series sprinklers are intended to be installed in ac- cordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the requirements of applicable authorities having jurisdiction. Mod- el RFC series sprinklers must not be installed in ceilings with positive pressure in the space above. Ensure that the 4 slots in the cup are open and unobstructed following installation. Model RFC series sprinklers are shipped with a wrench -able protec- tive cap that should remain on the sprinkler until the sprinkler system is placed in service following construction. Model RFC series sprinklers can be installed without removing the wrench -able protective cap using the Model W3 wrench. Alternatively, Model RFC series sprinklers can be installed us- ing the Model FC wrench by temporarily removing the protec- tive cap during installation of the sprinkler. The use of any other wrench to installed Model RFC series sprinklers is not permit- ted and may damage the sprinkler. Fully insert the Model W3 wrench over the cap until it reaches the bottom of the cup, or the Model FC wrench over the sprinkler until the wrench engag- es the body. Do not wrench any other part of the sprinkler/cup assembly. The Model W3 and FC wrenches are designed to be turned with a standard 1/2" square drive. Tighten the sprinkler into the fitting after applying a PTFE based thread sealant to the sprinkler's threads. Recommended installation torque is 8 to 18 ft-Ibs (11 to 24 N-m) for 1/2" thread sprinklers and 14 to 20 ft-Ibs (19 to 27 N-m) for 3/4" thread sprinklers. Do not exceed the maximum recommended torque. Exceeding the maximum recommended torque may cause leakage or im- pairment of the sprinkler. Use care when inserting or removing the wrench from the sprinkler to avoid damage to the sprinkler. Install the cover plate by hand by pushing the cover plate into the cup and turning the cover in the clockwise direction until it is tight against the ceiling. Application Model RFC series sprinklers are intended for installation where residential sprinklers are permitted or required by NFPA 13, NFPA 13R, and NFPA 13D. The sprinklers are concealed pen- dent residential sprinklers. Model RFC 30 and RFC30LL sprinklers are available in ordinary temperature classification for installation where the Maximum Ceiling Temperature does not exceed 100OF (380C). Model RFC43, RFC43LL, RFC49, RFC49LL, RFC58, and RFC76 sprin- klers are available in either ordinary or intermediate tempera- ture classification for installation where the Maximum Ceiling Temperature does not exceed 100OF (38°C) or 150OF (660C), respectively. Bulletin 006 May 2019 Page 7 of 8 www.reliablesprinkler.com Model FC For use with Model RFC Series sprinklers without wrench -able cap installed Maintenance Model RFC series sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by gentle vacuuming. Replace any sprinkler cover plate assembly which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replace- ment of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non -oper- ation. Listings and Approvals Listed by Underwriters Laboratories, Inc. and UL Certified for Canada to UL1626, Residential Sprinklers for Fire -protection Service (cULus). Certified by Underwriters Laboratories, Inc. and Underwrit- ers Laboratories of Canada for Health Effects to NSF/ANSI Standard 61 Annex G (LL) (RFC30LL, RFC43LL, and RFC49LL only). Australian WaterMark Certified (RFC30LL, RFC43LL, and RFC49LL only). Model W3 For use with Model RFC Series sprinklers with wrench -able cap installed Guarantee For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, and conditions, visit www.reliablesprinkler.com. Patents Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL, RFC58, and RFC76 sprinklers are covered by U.S. Patent No. 9,248,327 and U.S. Patent No. 7,275,603. Model RFC30, RFC30LL, RFC43 and RFC43LL sprinklers are additionally covered by U.S. Patent No. 8,776,903. Ordering Information Specify the following when ordering. Sprinkler • Model (RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL, RFC58, RFC76) • Temperature Rating Cover Plate • Model RFC • Temperature Rating • Finish (See Table H) Sprinkler Wrench • Model FC • Model W3 v co co co co 0 N Bulletin 006 Reliable Page 8 of 8 May 2019 www.reliablesprinkler.com Bulletin 157 Rev.F ® Model F3QR R Imab Quick Response Dry Sprinklers CD Features 1. The Model F30R sprinkler utilizes Belleville Spring Closure Technology. Reliable is the first in the industry to produce a Quick Response Dry Concealed sprinkler utilizing this technology. 2. Styles available • Pendent • Recessed Pendent • Concealed • Horizontal Sidewall • Recessed Horizontal Sidewall 3. 11/2" (38mm) escutcheon adjustment on pendent sprinkler. 4. 1/2' (13mm) escutcheon adjustment on recessed sprinkler with push -on/ thread -off FP Model Escutcheon ring. 5. %" (9.5mm) cover plate adjustment on concealed sprinkler with push-on/thread-off CCP Cover Plate. 6. Attractive appearance. Employs 3mm frangible glass bulb and galvanized nipple. 7. Lengths available to accommodate installation dimensions from 2" - to - 48" (51 mm - to-1219mm), in'/4' (6mm) increments. 8. Available in avariety of plated and painted finishes. U.S. Patent Numbers 5,775,431 and 5,967,240. Approvals 1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) Style Response Sprinkler System T Hazard Pendent Recessed Pendent CCP Concealed Wet Pipe Light R5714 Quick Dry Pipe Ordinary Horizontal Sidewall All Preaction Recessed Horizontal Sidewall R5734 2. Certified by FM Approvals Style Response Sprinkler System Type Hazard Pendent Quick Wet Pipe, Single Interlock Light Ordinary, (R5714) Preaction G1 ps & Horizontal Sidewall Wet Pipe, (R5734) Quick Single Interlock Light Preaction 3. NYC MEA 258-93-E Concealed Recessed Pendent Pendent Horizontal Sidewall The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552 Model F3QR Dry Pendent Concealed Sprinkler "A" Dim. 1 31 " to 48"(89mm to 1219mm) in W' 6mm increments CCP Cover Plate(" Finishes(21 Standard Finishes Special Application Finishes Chrome Plated Bright Brass Plated White Black Plated Black Paint Off White Satin Chrome Utilizes the 112" cover plate with %" total adjustment. 2' Other finishes and colors are available on special order. Consult factory for details. Standard Temperature Ratinas Sprinkler Temperature Cover Plate Max. Classification Rating Temp. Rating Ambient Temp. Ordinary 135-F (57oC) 135-F (57oC) 100-F (38-C) Ordinary 155-F (68oC) 135-F (57oC) 100-F (38oC) Intermediate 200-F (93oC) 165-F (74oC) 150-F (66oC) High* 286oF (141-C) 165-F (74oC) 150-F (66oC) " Listed and Certified only by cULus. Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench Sprinkler Identification Number (SIN): R5714 Inlet Protrusion Elevated Above Inside Pipe } �- --IIII'r— l ---T----r iII<II,ItIF---i�� ==VtM+}rI� --YR--=7 rL L J System Tee 1" NPT 2 1/2" Dia. [6.35mm] "A" Dimension Hole in Ceiling Adjustment Range f 3/16" 2 19/64" Dia. [t4.76mm] [58.34mm] Nominal Position Sprinkler of Coverplate Cup Assembly Coverplate 1 Ceiling Assembly Ceiling i 3/16" [4.76mm] Coverplate Adjustment Note: Do not install the Model F30R Dry Pendent Concealed Sprinkler in ceilings which have positive pressure in the space above. Model F3QR Dry Horizontal Sidewall Sprinkler "A" Dim. 2" to 48" (51 mm to 1219mm) in 1W (6mm) increments Finishes(') Sprinkler Escutcheon Bronze Brass Chrome Plated Chrome Plated White Painted) White Other finishes and colors are available on special order. Consult factory for details. (2) White painted sprinklers will have chrome plated can. Standard Temperature Ratinas Sprinkler Temperature Max. Bulb Classification Rating Ambient Tem . Color Ordinary 135-F (57-C) 100-F (38°C) Orange Ordinary 155-F (68oC) 100-F (38oC) Red Intermediate 200-F (93oC) 150-F (661C) Green High 286oF (141-C) 225oF (107C) Blue Sprinkler Installation Wrench: Model G3 Sprinkler Wrench Sprinkler Identification Number (SIN): R5734 1 1/2" [38.10mm] Total Adjustment _ _ T i r Ceiling �j 4" [101.60mm] Min. 1 1/4" [31.75mm] 12" [304.80mm] Max Escutcheon Adjustment I System Tee I I-_ 1 Escutcheon Adjustment r 1" NPT __, --- 2 1/8" Dia. [53.98mm] 3 I Hole in Wall Sprinkler Can "A" Dimension Adjustment rsarcoa-c Range + 1/4" [+6.35mm] 2 3/ [53.18mm] �DA_ 3" [76.20mm] 1/4" [6.35mm] Protrusion Nominal Position of Escutcheon Note: The sprinkler Can protrudes 1/4" when escutcheon is in nominal position. Escutcheon adjustment pro- vides +1/4' (+6mm) to -1'/4" (-32mm) "A" dimension adjustment range. 3. Model F3QR Dry Horizontal Recessed Sidewall Sprinkler "A" Dim. 31/2" to 48" (89mm to 1219mm) in'W (6mm) increrwis Finishes') Sprinkler 7FEscutcheon Bronze Brass Chrome Plated Chrome Plated White Painted White Other finishes and colors are available on special order. Consult factory for details. Cup remains unfinished. "See page 2" Standard Temperature Ratings Sprinkler Temperature Max. Bulb Classification RaUng Ambient Temp. Color Ordinary 135OF (57oC) 100°F (38oC) Orange Ordinary 1551F (68oC) 100-F (38oC) Red Intermediate 200OF (93oC) 150-F (66°C) Green High* 2860F (1411C) 2251F (1071C) Blue Listed and Certified only by cULus. Sprinkler Installation Wrench: Model G3 R/C Sprinkler Wrench Sprinkler Identification Number (SIN): R5734 Technical Data: Orifice Size:'/2' (15mm) Thread Size: 1" NPT per ANSI 132.1 Working Pressure: 175 psi (12 bar) Nominal K Factor - US / (Metric): 5.6 / (80) Product Description Reliable Model F3QR Dry Sprinklers are quick response sprinklers utilizing a durable 3mm frangible glass bulb. This quick response enables these sprinklers to apply water to a fire much sooner than standard response sprinklers of the similar temperature rating. Model F3QR Dry Sprinklers are intended for use in enclosed dry and preaction systems and in enclosed areas subjected to freezing temperatures, such as freezers and unheated portions inside buildings. Environments wherein dry sprinklers are employed can be corrosive. For this reason, Model F3 Sprinklers have a special wax fillet placed in the gap between the cup that supports the bulb and the wrenching boss. This wax will not interfere with the operation of the sprinkler, and it prevents contaminents from entering the internal portion of the drop nipple. The wax must not be removed. Operation The glass bulb consists of an accurately controlled amount of special fluid hermetically sealed Inside a precisely manufactured glass capsule. This glass bulb is specially constructed to provide fast thermal response. When the temperature increases sufficiently, due to a fire, the bulb shatters allowing operating parts to clear the waterway. This enables the inlet seal to release air or water and subsequently, cause water flow over the deflector in a uniform spray pattern, controlling or extinguishing the fire. B F Ceiling I.-F 1 13/32- Escutcheon [35.7mmm] f-yT 4- [101.6mm]Min. — System Tee Cup ; l 12" 1304.8mm]Mo ," N7T [51.a m] ;�- --Y -- z 1 /z" Mai.- [63.5mm] Hole in WallL 2 19/64- Dia. [58.3mm] 1/2" [12.7mm] "A" Dimension Escutcheon Adjustment Adjustment Range 157FG05 +1/2" —0 [+12.7mm —0] * FOR FACTORY MUTUAL (FM) 4" — 6" FOR UNDERWRITERS LABORATORIES (UL) Notes: Do not install the Model F30R Dry Horizontal Recessed Sidewall Sprinkler in walls which have positive pressure in their side space. Listed by cULus for Quick Response. Approved by FM for Standard Response. Recessed Horizontal sidewall sprinklers are listed with cULus for installation of min. 4" (100mm) - to - max. 6" (150mm) below ceiling and approved by FM for installation of min. 4" (100mm) - to - max. 12" (300mm) below ceiling. Ordering Information Specify: 1. Sprinkler Type (select one): (a) Model F30R Dry Pendent (b) Model F3QR Dry Recessed Pendent (c) Model F30R Dry Concealed Pendent (d) Model F3QR Dry Horizontal Sidewall (e) Model F3QR Dry Recessed Horizontal Sidewall 2. Sprinkler Temperature Rating. 3. Sprinkler Finish. 4. Cover Plate/Escutcheon Finish. 5. Length: "A" Dimension (face of tee to face of ceiling or wall) in (6mm) increments. 6. Model F30R Dry Pendent (a) is available without sprinkler can and escutcheon. Note: 1. The "A" dimension is based on a nominally gauged pipe thread "make-up" of 0.600" (15mm) per ANSI 132.1 [71/2 threads approximately]. 2. All platings and paintings are decorative and intended for interior use. General Installation Instructions Model F3QR dry sprinklers must be installed only in standard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125) pipe tees even at branch line ends. They should not be installed into elbows and pipe couplings located on drop nipples to the sprinklers. For these and other fittings including CPVC*, the dry sprinkler should be installed into a fitting to conform to protrusion into the fitting in ac- cordance with the diagrams. The "A" dimension of the dry sprinkler, which extends into the freezers or a freezing zone from wet pipe systems, should be selected to pro- vide, as a minimum, the specified lengths in inches shown in the following chart, between face of the fitting and the outside wall or ceiling of the protected area. The following chart is used for freezing zones when the ambi- ent temperature around the wet pipe system is kept at 40 OF/ 4°C), and specifies the minimum length for fitting face to ceiling or wall (outside) for different protected area temperatures. Length Face to Ceilin all Temperature Protected Area' 12 inches / 300 mm -20°F / -29°C 18 inches / 450 mm -40°F / -40°C 24 inches / 600 mm -600F / -51 °C ** For temperatures falling between those in the above chart, the minimum length may be determined by interpolation. During installation, the following steps must be followed 1. Cut the specified size hole (see illustrations) for the sprinkler in the ceiling or wall directly in line with the tee. 2. Apply pipe joint compound to the 1" (25mm) pipe threads and install sprinkler using the Model G3 or G3 R/C Sprinkler Wrench as specified. 3. Install the Model FP push -on / thread -off escutcheon or CCP cover plate if required. Note: Installation of the Model F3QR Sprinklers is not rec- ommended in copper pipe systems, as this may reduce the life expectancy of the sprinklers. Model F3QR Concealed and Recessed Installation Instructions The Model G3 R/C wrench (Fig. 1) is designed to locate on the wrenching pads of the recessed sprinkler while centering in the cup. A standard'/z' drive ratchet may be used to drive this wrench. Figures 1 and 2 show sequentially the insertion of the wrench. First the wrench, with its jaws above the sprinkler deflector, is moved laterally until centered with the cup. Then raise the wrench inside of the cup until its jaws engage the sprinkler's square wrenching pads (Fig. 3). To remove the wrench, follow this procedure in reverse order. Care should be taken to avoid striking the deflector, with the wrench. Model G3 Wrench (Fig. 4) is used for installation of Pendent and Horizontal Sidewall sprinklers. Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Removal of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. Maintenance The Model F3QR Quick Response Dry Sprinklers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25. Do not remove the factory applied thermally sensitive wax fillet between the bulb supporting cup and the wrenching boss. Do not replace this wax with a substitute substance. An Alternate substance may interfere with proper operation of the sprinkler. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gently vacuuming. Remove any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non -operation. * Spears CPVC sprinkler adapter tees (with steel thread insert) can only be used with horizontal sidewall sprinklers which do not require protrusion into tees to prevent ice or debris blockage of sprinkler inlets. These CPVC tees do not permit sufficient sprinkler inlet protrusion as required for pendent installation. 5. UponorAquaPEX®White, coils Submittal information Revision M: Sept. 18, 2018 Project information Job name: Location: Part no. ordered: Uponof Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: Approved by: Technical data Material: Crosslinked polyethylene PEX-a Engel Method; PEX 5106 Standard grade hydrostatic ratings (PPI): 200°F (93°C) at 80 psi (551 kPa) 180°F (82°C) at 100 psi (689 kPa) 73.4°F (23°C) at 160 psi (1,103 kPa) '/2", %", 1", 1'/4", 1'/2" and 2" UponorAquaPEX® White only: --- 120°F (49°C) at 130 psi (896 kPa) Linear expansion rate: 1.1'/10°F/100' (27.94mm/5.56°C/30.48m) Product information and application use Uponor AquaPEX White is used for hot and cold domestic potable water distribution and residential fire safety as well as radiant heating/cooling and hydronic piping systems containing no ferrous corrodible components or where ferrous components are isolated from the piping. ✓ Description Part number I.D. O.D. Weight '/4' Uponor AquaPEX White, 100-ft. coil F1040250 0.241" 0.375" 4.0 lbs. Uponor AquaPEX White, 400-ft. coil F1090375 0.350" 0.500" 20.0 lbs. Uponor AquaPEX White, 1,000-ft. coil F1120375 0.350" 0.500" 44.0 lbs. ''/2" Uponor AquaPEX White, 100-ft. coil F1040500 0.475" 0.625" 6.0 lbs. %" Uponor AquaPEX White, 300-ft. coil F1060500 0.475" 0.625" 18.0 lbs. ''/z" Uponor AquaPEX White, 500-ft. coil F1100500 0.475" 0.625" 27.6 lbs. ''/z" Uponor AquaPEX White, 1,000-ft. coil F1120500 0.475" 0.625" 54.0 lbs. Uponor AquaPEX White, 300-ft. coil F1060625 0.574" 0.750" 28.0 lbs. Uponor AquaPEX White, 1000-ft. coil F1120625 0.574" 0.750" 86.0 lbs. Uponor AquaPEX White, 100-ft. coil F1040750 0.671" 0.875" 10.0 lbs. Y44" Uponor AquaPEX White, 300-ft. coil F1060750 0.671" 0.875" 34.0 lbs. %" Uponor AquaPEX White, 500-ft. coil F1100750 0.671" 0.875" 54.0 lbs. 1" Uponor AquaPEX White, 100-ft. coil F1041000 0.862" 1.125" 20.0 lbs. 1" Uponor AquaPEX White, 300-ft. coil F1061000 0.862" 1.125" 56.0 lbs. 1" Uponor AquaPEX White, 500-ft. coil F1101000 0.862" 1.125" 93.0 lbs. 1'/4' Uponor AquaPEX White, 100-ft. coil F1061250 1.054" 1.375" 34.0 lbs. 1'/4" Uponor AquaPEX White, 300-ft. coil F1021250 1.054" 1.375" 106.0 lbs. 1'/z" Uponor AquaPEX White, 100-ft. coil F1061500 1.244" 1.625" 44.0 lbs. 1'/z" Uponor AquaPEX White, 300-ft. coil F1021500 1.244" 1.625" 133.0 lbs. 2" Uponor AquaPEX White, 100-ft. coil F1062000 1.629" 2.125" 68.2 lbs. 2" Uponor AquaPEX White, 200-ft. coil F1052000 1.629" 2.125" 136.4 lbs. 2" Uponor AquaPEX White, 300-fit. coil F1022000 1.629" 2.125" 204.6 lbs. 2'/i' Uponor AquaPEX White, 100-ft. coil F1062500 2.011" 2.625" 88.0 lbs. 2'/i' Uponor AquaPEX White, 300-ft. coil F1022500 2.011" 2.625" 264.0 lbs. 3" Uponor AquaPEX White, 100-ft. coil F1063000 2.400" 3.125" 128.0 lbs. 3" Uponor AquaPEX White, 300-ft. coil F1023000 2.400" 3.125" 384.0 lbs. Installation Use ProPEX® fittings for %" through 3" pipe.' Refer to the ProPEX Connections Instructional Guide, Uponor Piping Pocket Guide, Plumbing Design Assistance Manual (PDAM), Complete Design Assistance Manual (CDAM), Hydronic Piping Design Assistance Manual (HPDAM) or AquaSAFET1A Residential Fire Sprinkler Installation Guide for more information. Listings2 Codes Standards cNSFus-fs3; cNSFus-pw; cQAlus P321; UL; IAPMO; ICC; IPC; IMC; IRC; ANSI/NSF 14; ANSI/NSF 61; ASTM F876; ASTM F877; ASTM F1960; ASTM CSA; PPI TR-4; ICC-ES; BMEC; CCMC UPC; UMC; NSPC; HUD; F2023; ASTM E84; CAN/ULC S102.2; ASTM E119/UL 263; CAN/ULC S101; UFGS; NPC of Canada; ASTM E814/ULC S115; CSA B137.5; CSA B214; NBC of Canada UL 18213; ULC/ORD-C199P3; AWWA C9044 Related applications Contact information PEX-a plumbing systems Uponor, Inc. Uponor Ltd. AquaSAFETM fire safety systems 5925 148"' Street West 6510 Kennedy Road Radiant heating and cooling systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Hydronic piping systems Phone: 800.321.4739 Phone: 888.994.7726 Fax: 952.891.2008 Fax: 800.638.9517 uponorpro.com uponorpro.com 'ProPEX® is a registered trademark of Uponor, Inc. ProPEX- is a trademark of Uponor Ltd. 2Visit listing agency's website for complete information. 3For 3/4", 1" and 1'W pipe only. 4For %" to 3" pipe. ProPEX° Ring Submittal information Revision I: Nov. 1, 2018 Project information Job name: Location: Part no. ordered: Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: Approved by: Technical data Material: Engel -method crosslinked polyethylene (PEX-a) Density: 926 to 940 kg/m3 Degree of crosslinking: 70% to 89% Product information and application use Uponor ProPEX® rings are required to make a proper ProPEX connection.' The ProPEX ring with stop includes a leading edge chamfer and stop edge. ✓ Description Part number ProPEX Ring, %" ProPEX Ring with Stop, '/2" ProPEX Ring with Stop, %" ProPEX Ring with Stop, 3/4" ProPEX Ring with Stop, 1" ProPEX Ring with Stop, 1'/4" ProPEX Ring with Stop, 1'/2" ProPEX Ring with Stop, 2" ProPEX Ring with Stop, 2'/2" ProPEX Ring with Stop, 3" Installation Q4690302 Q4690512 Q4690625 Q4690756 Q4691000 Q4691250 Q4691500 Q4692000 Q4692500 Q4693000 uponof Length I.D. O.D. Weight 0.54" 0.49" 0.74" 0.005lbs. 0.63" 0.63" 0.87" 0.006lbs. 0.79" 0.75" 1.00" 0.008lbs. 0.87" 0.88" 1.13" 0.012lbs. 1.10" 1.13" 1.42" 0.020lbs. 1.35" 1.38" 1.66" 0.030lbs. 1.61" 1.63" 1.91" 0.040 lbs. 1.97" 2.14" 2.61" 0.133lbs. 2.61" 2.66" 3.25" 0.230lbs. 3.12" 3.16" 3.87" 0.400lbs. Square cut the Uponor PEX tubing. Remove excess material. Slide the ProPEX ring over the end of the tubing (maximum 'lid' over -hang for rings without stop). When using the ProPEX ring with stop, slide the ring on the tubing with the chamfered edge first until the end of the tubing contacts the stop edge. Expand the tubing and ring. If using the ProPEX Manual Expander Tool, rotate the tool a quarter turn after each expansion to prevent the formation of grooves. Remove the expansion tool and fully seat the tubing and ring against the shoulder of the fitting. Make ProPEX connections at temperatures above 5°F/-15°C. For more information, refer to the Uponor ProPEX Connections Instructional Guide. Listings' cNSFus-fs3; cNSFus-pw; cNSFus-rfh; cQAlus; UL; CSA; PPI TR-4; ICC-ES; IAPMO; BMEC; CCMC; cQAlus P321 Codes ICC; IPC; IMC; IRC; UPC; UMC; NSPC; HUD; UFGS; NPC of Canada; NBC of Canada Standards ANSI/NSF 14; ANSI/NSF 61; ASTM F876; ASTM F877; ASTM F1960; ASTM F2023; ASTM E84; CAN/ULC S102.2; ASTM E119/UL 263; CAN/ULC S101; ASTM E814/ULC S115; CSA 13137.5; CSA B214; UL 18213; ULC/ORD-C199P3 Related applications Contact information PEX-a plumbing systems Uponor Inc. Uponor Ltd. AquaSAFE fire safety systems 5925 148"' Street West 6510 Kennedy Road Hydronic radiant heating and cooling systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Snow melting systems Phone: 800.321.4739 Phone: 888.994.7726 Turf conditioning systems Fax: 952.891.2008 Fax: 800.638.9517 Permafrost prevention systems uponorpro.com uponorpro.com 'ProPEX® is a registered trademark of Uponor, Inc. ProPEXT" is a trademark of Uponor Ltd. 2Visit listing agency's website for complete information; 3For '/2",'/", 1", 11/", 1'/2" and 2" tubing only ProPEXO Engineered Submittal information Revision H: May 23, 2019 Project information Job name: Polymer (EP) Tee Location: Part no. ordered: Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: Approved bv: Technical data Material: Engineered polymer (EP) Maximum temperature (no pressure): 320°F (160°C) Maximum working temperature/pressure: 210*F (99*C) at 150 psi (1,034 kPa) Product information and application use ProPEX® engineered polymer (EP) tees make diverting connections for Uponor crosslinked polyethylene (PEX-a)tubing for use in hot and cold domestic potable water systems, residential fire sprinkler systems and hydronic radiant heating and cooling systems. Each end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor AquaPEX® or Wirsbo hePEXTM tubing.' Note: Branch size is listed last in the part descriptions. Uponof Part ✓ Equivalent Equivalent cv cv Description number A B Weight length (ft.) length (ft.) through branch through branch ProPEX EP Tee, ''M." PEX x'/z' PEX x'/" PEX Q4755060 2.50" 1.53" 0.02 lbs. 1.0 6.3 7.7 3.4 ProPEX EP Tee, %" PEX x'/:' PEX x'/:' PEX* Q4757575 3.30" 1.94" 0.05 lbs. 1.5 15.6 15.7 5.4 ProPEX EP Tee, 1" PEX x 1" PEX x 1" PEX* Q4751010 4.10" 2.47" 0.07 lbs. 1.3 12.7 30.5 11.3 ProPEX EP Tee, 1'/4" PEX x 1'/4" PEX x 1'/4" PEX* Q4751313 4.80" 3.22" 0.15 lbs. 3.8 8.6 34.0 23.9 ProPEX EP Tee, 1 Yz' PEX x 1'/." PEX x 1'M." PEX Q4751515 5.80" 3.82" 0.25 lbs. 1.8 10.6 63.7 31.0 ProPEX EP Tee, 2" PEX x 2" PEX x 2" PEX Q4752000 7.45" 4.79" 0.38 lbs. 0.8 15.5 150.7 52.5 ProPEX EP Tee, 21/' PEX x 21/z' PEX x 21/z' PEX Q4752500 10.56" 5.45" 1.14 lbs. 2.7 22.3 197.2 81.5 ProPEX EP Tee, 3" PEX x 3" PEX x 3" PEX Q4753000 12.26" 6.37" 1.86 lbs. 2.8 23.9 286.6 122.8 Installation Use the appropriate ProPEX Ring for PEX-a tubing. Refer to the Uponor Professional Plumbing Installation Guide, AquaSAFET"^ Residential Fire Sprinkler Installation Guide or Uponor Radiant Installation Handbook for additional information. Standards ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM F1960; CAN/CSA B137.5; NSF 14; NSF 61 Codes IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC Listings cNSFus-pw; *cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code Related applications Contact information PEX-a plumbing systems Uponor, Inc. Uponor Ltd. Hydronic radiant heating and cooling systems 5925 148t' Street West 6510 Kennedy Road Snow and ice melting systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Turf conditioning systems Phone: 800.321.4739 Phone: 888.994.7726 Permafrost prevention systems Fax: 952.891.2008 Fax: 800.638.9517 AquaSAFETm fire safety systems uponorpro.com uponorpro.com 'ProPEX® is a registered trademark of Uponor, Inc. ProPEXT" is a trademark of Uponor Ltd. ProPEX° Engineered Polymer (EP) Reducing Tee (up to 11/2") uponof Submittal information Revision I: Sept. 16, 2019 Project information Job name: Location: Part no. ordered: Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: Approved by: Technical data Material: Engineered polymer (EP) n� Maximum temperature (no pressure): 320°F (160°C) Max. working temperature/pressure: 210°F (99°C) at 150 psi (1,034 kPa) Product information and application use ProPEX® engineered polymer (EP) reducing tees make diverting connections for Uponor PEX-a pipe for use in hot and cold B domestic potable water systems, residential fire sprinkler systems and hydronic radiant heating and cooling systems. Each end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor AquaPEX11 or Wirsbo hePEXTM pipe.' Note: Branch size is listed last in the part descriptions. ✓ Description Part A B Weight Equiv, length (ft.) Equiv. length Cv Cv number through (ft.) branch through branch ProPEX EP Reducing Tee,''/2" PEX x'/i' PEX x %" PEX Q4755575 2.86" 1.76" 0.03 lbs. 1.0 15.6 7.7 5.4 ProPEX EP Reducing Tee, '/<" PEX x'/i' PEX x'/i' PEX Q4757555 3.10" 1.70" 0.04 lbs. 3.5 6.4 4.6 3.4 ProPEX EP Reducing Tee, '/<" PEX x'/z' PEX x'/;' PEX* Q4757557 3.10" 1.94" 0.04 lbs. 2.3 16.1 5.4 5.4 ProPEX EP Reducing Tee, '/<" PEX x'/;' PEX x PEX Q4757563 3.30" 1.85" 0.05 lbs. N/A N/A N/A N/A ProPEX EP Reducing Tee, '/<" PEX x'/;' PEX x'/z' PEX* Q4757550 3.30" 1.70" 0.04 lbs. 2.0 7.6 14.2 3.1 ProPEX EP Reducing Tee, '/<" PEX x'/;' PEX x 1" PEX* Q4757710 3.64" 2.32" 0.08 lbs. 1.5 5.7 15.7 8.7 ProPEX EP Reducing Tee, 1" PEX x'/i' PEX x 1" PEX Q4751501 3.71" 2.43" 0.09 lbs. 1.98 9.7 12.3 5.7 ProPEX EP Reducing Tee, 1" PEX x'/d' PEX x'/ PEX Q4751750 3.65" 1.96" 0.07 lbs. 2.27 6.69 3.1 13.2 ProPEX EP Reducing Tee, 1" PEX x'/<" PEX x'/4" PEX* Q4751775 3.90" 2.24" 0.08 lbs. 2.4 16.7 12.8 5.3 ProPEX EP Reducing Tee, 1" PEX x'/<" PEX x 1" PEX* Q4751751 3.90" 2.47" 0.08 lbs. 2.4 15.1 12.9 10.5 ProPEX EP Reducing Tee, 1" PEX x'/;' PEX x 1%" PEX Q4751753 4.15" 2.95" 0.12 lbs. 2.74 19.48 14.7 12.0 ProPEX EP Reducing Tee, 1" PEX x 1" PEX x'/;' PEX* Q4751150 4.10" 2.00" 0.08 lbs. 1.2 6.5 32.2 3.4 ProPEX EP Reducing Tee, 1" PEX x 1" PEX x %" PEX* Q4751175 4.10" 2.24" 0.09 lbs. 1.7 6.4 27.8 8.2 ProPEX EP Reducing Tee, 1" PEX x 1" PEX x 1 '/;' PEX* Q4751113 4.38" 2.95" 0.13 lbs. 6.52 5.37 15.0 28.0 ProPEX EP Reducing Tee, 1%" PEX x'/<" PEX x'/<" PEX* Q4751377 4.11" 2.38" 0.09 lbs. 2.74 7.41 7.3 12.0 ProPEX EP Reducing Tee, 1%" PEX x'/<" PEX x 1" PEX* Q4751371 4.37" 2.62" 0.11 lbs. 2.70 7.59 13.9 12.1 ProPEX EP Reducing Tee, 1%" PEX x'/<" PEX x 1Y<" PEX* Q4751373 4.61" 2.88" 0.13 lbs. 2.74 11.91 18.8 12.0 ProPEX EP Reducing Tee, 1'/<" PEX x 1" PEX x %" PEX* Q4751317 4.50" 2.73" 0.11 lbs. 3.4 5.2 21.0 9.3 ProPEX EP Reducing Tee, 11/;' PEX x 1" PEX x 1" PEX* Q4751311 4.70" 2.97" 0.12 lbs. 11.0 23.0 11.7 8.4 ProPEX EP Reducing Tee, 11/;' PEX x 11/4" PEX x'/;' PEX* Q4751350 4.40" 2.15" 0.10 lbs. 1.9 3.9 45.2 4.1 ProPEX EP Reducing Tee, 11/4" PEX x 11/4" PEX x %" PEX* Q4751337 4.70" 2.73" 0.13 lbs. 2.3 5.7 43.4 8.9 ProPEX EP Reducing Tee, 11/4" PEX x 11/4" PEX x 1" PEX* Q4751331 5.00" 2.97" 0.14 lbs. 4.2 6.3 33.0 15.8 ProPEX EP Reducing Tee, 1'/z" PEX x'/<" PEX x %" PEX Q4751577 4.37" 2.64" 0.13 lbs. 2.88 7.41 7.3 11.7 ProPEX EP Reducing Tee, 1'/z" PEX x'/<" PEX x 1'/z" PEX Q4751575 4.97" 3.39" 0.19 lbs. 2.74 19.10 22.9 12.0 ProPEX EP Reducing Tee, 1'/z" PEX x 1" PEX x %" PEX Q4751517 5.25" 3.06" 0.17 lbs. 4.0 5.1 19.5 9.3 ProPEX EP Reducing Tee, 1'/z" PEX x 1" PEX x 1" PEX Q4751511 5.25" 3.30" 0.18 lbs. 4.3 6.5 18.9 15.6 ProPEX EP Reducing Tee, 11/2" PEX x 1" PEX x 11/2" PEX Q4751505 5.40" 3.45" 0.20 lbs. 4.2 14.9 19.0 26.5 ProPEX EP Reducing Tee, 11/2" PEX x 11/4" PEX x %" PEX Q4751537 5.50" 2.65" 0.18 lbs. 4.2 11.3 33.1 6.3 ProPEX EP Reducing Tee, 11/2" PEX x 11/4" PEX x 1" PEX Q4751531 5.50" 2.85" 0.19 lbs. 3.1 13.1 36.4 11.2 ProPEX EP Reducing Tee, 11/2" PEX x 11/4" PEX x 11/4" PEX Q4751533 5.50" 3.15" 0.21 lbs. 2.0 17.7 45.4 17.0 ProPEX EP Reducing Tee, 1'/z" PEX x 1'/2" PEX x'/i' PEX Q4751550 4.95" 2.30" 0.14 lbs. 2.4 6.3 60.5 3.4 ProPEX EP Reducing Tee, 1'/z" PEX x 1'/2" PEX x %" PEX Q4751557 5.30" 3.06" 0.20 lbs. 2.9 5.4 56.0 9.0 ProPEX EP Reducing Tee, 1'/2" PEX x 1'/2" PEX x 1" PEX Q4751551 5.75" 3.30" 0.21 lbs. 3.1 6.9 53.8 15.3 ProPEX EP Reducing Tee, 1'/2" PEX x 1'/2" PEX x 11/4" PEX Q4751553 5.80" 3.56" 0.22 lbs. 3.2 4.1 54.3 33.7 Installation Use the appropriate ProPEX ring for PEX-a pipe. Refer to the Uponor Piping Systems Installation Guide, the AquaSAFETm Residential Fire Sprinkler Installation Guide or the Uponor Radiant Installation Handbook for additional information. Standards Codes Listings ASTM E84; ASTM E119; ASTM E814; IBC; IMC; IPC; IRC; NPC of Canada; cNSFus-pw; *cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ASTM F877; ASTM F1960; NSPC; UMC; UPC ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code CAN/CSA B137.5; NSF 14; NSF 61 Related applications Contact information PEX-a plumbing systems Uponor Inc. Uponor Ltd. Hydronic radiant heating and cooling systems 5925 1481h Street West 6510 Kennedy Road Snow and ice melting systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Turf conditioning systems Phone: 800.321.4739 Phone: 888.994.7726 Permafrost prevention systems Fax: 952.891.2008 Fax: 800.638.9517 AquaSAFETM fire safety systems uponorpro.com uponorpro.com 'ProPEX® is a registered trademark of Uponor Inc. ProPEX" is a trademark of Uponor Ltd. ProPEX® Engineered Polymer (EP) Elbow Submittal information Revision J: June 21, 2019 Project information Job name: Location: Part no. ordered: Engineer: Date submitted: Contractor: Submitted by: Manufacturer's representative: ADDroved bv: Technical data Material: Engineered polymer (EP) Maximum temperature (no pressure): 320°F (160°C) Maximum working temperature/pressure: 210°F (99°C) at 150 psi (1,034 kPa) Product information and application use ProPEX® engineered polymer (EP) elbows make 90-degree connections for Uponor crosslinked polyethylene (PEX-a) tubing for use in hot and cold domestic potable water systems, residential fire safety and hydronic radiant heating and cooling systems. Each end of the elbow is manufactured with an Uponor ProPEX fitting for connections to Uponor AquaPEX® or Wirsbo hePEXTm tubing.' Uponof ✓ Description Part number A B Weight Equivalent Cv length (ft.) ProPEX EP Elbow, '/z" PEX x'/z" PEX Q4760500 1.30" 1.30" 0.02 lbs. 10.4 2.6 ProPEX EP Elbow, 3/4° PEX x 3/4" PEX* Q4760750 1.60" 1.60" 0.03 lbs. 10.8 6.7 ProPEX EP Elbow, 1" PEX x 1" PEX* Q4761000 2.10" 2.10" 0.07 lbs. 11.5 11.9 ProPEX EP Elbow, 1'/4" PEX x 1'/4" PEX* Q4761250 2.45" 2.45" 0.11 lbs. 10.0 22.2 ProPEX EP Elbow, 1'/z" PEX x 1'/z" PEX Q4761500 2.77" 2.77" 0.18 lbs. 11.5 29.7 ProPEX EP Elbow, 2" PEX x 2" PEX Q4762000 3.76" 3.76" 0.30 lbs. 17.1 50.2 ProPEX EP Elbow, 2'/z" PEX x 2'/z" PEX Q4762500 4.93" 4.93" 0.85 lbs. 20.0 86.0 ProPEX EP Elbow, 3" PEX x 3" PEX Q4763000 5.88" 5.88" 1.44 lbs. 23.2 125.0 ProPEX EP 45 Elbow, 1'/2' PEX x 1'/2" PEX Q4761515 2.32" 2.32" 0.13 lbs. 9.3 33.1 ProPEX EP 45 Elbow, 2" PEX x 2" PEX Q4762020 2.91" 2.91" 0.32 lbs. 8.8 68.9 ProPEX EP 45 Elbow, 2'/2' PEX x 2'/2" PEX Q4762525 3.83" 3.83" 0.65 lbs. 7.0 136.8 ProPEX EP 45 Elbow, 3" PEX x 3" PEX Q4763030 4.48" 4.48" 1.07 lbs. 8.3 195.5 Installation Use the appropriate ProPEX ring for PEX-a tubing. Refer to the Uponor Piping Pocket Guide, AquaSAFETm Residential Fire Sprinkler Installation Guide or Uponor Radiant Installation Handbook for additional information. Standards ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM F1960; CAN/CSA B137.5; NSF 14; NSF 61 Codes IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC Listings cNSFus-pw; *cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code Related applications Contact information PEX-a plumbing systems Uponor Inc. Uponor Ltd. Hydronic radiant heating and cooling systems 5925 148t' Street West 6510 Kennedy Road Snow and ice melting systems Apple Valley, MN 55124 USA Mississauga, ON L5T 2X4 CANADA Turf conditioning systems Phone: 800.321.4739 Phone: 888.994.7726 Permafrost prevention systems Fax: 952.891.2008 Fax: 800.638.9517 AquaSAFE fire safety systems uponorpro.com uponorpro.com 1 ProPEX® is a registered trademark of Uponor, Inc. ProPEX- is a trademark of Uponor Ltd. ProPEX° Fire Sprinkler Adapter Submittal Information Revision B: March 17, 2009 Project Information Job Name: Location: Part No. Ordered: Engineer: Date Submitted: Contractor: Submitted By: Manufacturer's Representative: Approved By: Technical Data Material: 300 Series Stainless Steel Product Information and Application Use Use the ProPEX° Fire Sprinkler Adapter in conjunction with the appropriate sprinkler to provide a multi -purpose residential fire sprinkler system'. For residential applications, the system is installed with the cold -potable portion of the Uponor plumbing system. Make connections with Uponor ProPEX fittings. These fittings are designed for use only with 3/4" or 1" AquaPEX° White tubing in the Uponor AQUASAFE° Looped System. uponof ✓ Description Part A B C D E Weight Number ProPEX Fire Sprinkler Adapter, 3/4" PEX x 1/2" FNPT Q7517550 0.75" 1.88" 2.50" 1.82" 1.41" 0.268 lbs. ProPEX Fire Sprinkler Adapter, 1" PEX x 1/2" FNPT Q7511050 0.75" 1.88" 2.50" 2.06" 1.54" 0.408 lbs. Installation Use appropriate ProPEX Ring for connecting the tubing. Refer to the AquaPEX Installation Handbook or the Uponor AQUASAFE° Installation Guide for additional information. Standards CAN/CSA B137.5; ASTM F877; ASTM F 1960 Codes IPC; UPC; NSPC; IRC; IMC; NPC of Canada Listings ANSI/NSF 14- and 61-certified; U.P. Code; ICC ESR 1099; HUD MR 1269; UL 1821; ULC/ORD - C 199 P Related Applications PEX-a Plumbing Systems AQUASAFE Fire Safety Systems Contact Information Uponor, Inc. 5925 1481h Street West Apple Valley, MN 55124 USA Phone: (800) 321-4739 Fax: (952) 891-2008 www.uponor-usa.com Uponor Ltd. 2000 Argentia Rd., Plaza 1, Ste. 200 Mississauga, ON L5N 1W1 CANADA Phone: (888) 994-7726 Fax: (800) 638-9517 www.uponor.ca 'ProPEX° is a registered trademark of Uponor, Inc. ProPEXTM is a trademark of Uponor Ltd.