Loading...
BLD2021-1056_Manufacturer_Specifications_and_Installation_Instructions_7.29.2021_11.09.43_AM_2328421Job Name: System Reference: FEATURES • Variable speed INVERTER -driven compressor • Blue Fin Coating on heat exchanger • Thermal Differential 1°F (with PAC-MKA32/52BC only) • Branch box for simplified piping and installation flexibility • Up to 8 indoor units connectable (six [6] if a PLA-A••EA7 is connected) • Optional base pan heater • Quiet outdoor unit operation as low as 54 dB(A) • High pressure protection • Compressor thermal protection • Compressor overcurrent detection • Fan motor overheating/voltage protection Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Indoor unit type Cooling Maximum Capacity BTU/H Non -Ducted 48,000 Mix 48,000 D u�cted 48,000 Rated Capacity BTU/H 48,000 48,000 48,000 Minimum Capacity BTU/H 15,500 15,500 15,500 Maximum Power Input W 3,930 4,320 4,800 Rated Power Input W 3,930 4,320 4,800 Power Factor (208V, 230V) % 98.6 / 98.6 98.9 / 98.9 99.2 / 99.2 Heating at 47°F2 Maximum Capacity BTU/H 54,000 54,000 54,000 Rated Capacity BTU/H 54,000 54,000 54,000 Minimum Capacity BTU/H 22,500 22,500 22,500 Maximum Power Input W 4,220 4,520 4,800 Rated Power Input W 4,220 4,520 4,800 Power Factor (208V, 230V) % 98.6 / 98.6 98.9 / 98.9 99.2 / 99.2 Heating at 17°F3 Maximum Capacity BTU/H 36,600 36,600 36,600 Rated Capacity BTU/H 33,000 33,000 33,000 Maximum Power Input W 5,200 5,550 5,200 Rated Power Input W 3,720 3,870 4,030 Heating at 5°F4 Maximum Capacity BTU/H 32,400 32,400 32,400 Maximum Power Input W 4,750 4,870 5,000 Efficiency SEER 20.00 18.00 16.00 EER1 12.20 11.10 10.00 HSPF (IV) 11.5 10.8 10.1 COP at 47° F2 3.75 3.50 3.30 COP at 17° F3 2.00 1.90 2.00 COP at 5° F4 2.00 1.90 1.90 ENERGY STAR® Certified NO NO NO Electrical Voltage, Phase, Frequency 208 / 230V1 1-phase, 60 Hz Guaranteed Voltage Range V AC 198-253 Voltage: Indoor - Outdoor, S1-S2 V AC 208 / 230 Voltage: Indoor - Outdoor, S2-S3 V DC 24 Short-circuit Current Rating (SCCR) 5kA 5 Recommended Fuse/Breaker Size (Outdoor) A 40 Recommended Wire Size (Indoor - Outdoor) AWG 16 Outdoor unit MCA A 35 MOCP A 50 Fan Motor Full Load Amperage A 0.6 + 0.6 Fan Motor Output W 74 Airflow Rate Cooling / Heating CFM 3,885 / 3,885 Refrigerant Control Linear Expansion Valve Defrost Method Reverse Cycle Heat Exchanger Type Plate Fin Coil Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Indoor unit type Sound Pressure Level, Coolingi dB(A) Non -Ducted 51 Sound Pressure Level, Heating2 dB(A) 54 Compressor Type Hermetic Compressor Model ANB33FNHMT Compressor Motor Output kW 3.4 Compressor Rated Load Amps A 19.0 Compressor Locked Rotor Amps A 22.0 Compressor Oil Type // Charge oz. FV50S // 78 External Finish Color Munsell 3Y 7.8/ 1.1 Base Pan Heater Optional (PAC-SJ20BH-E) Unit Dimensions W: In. [mm] 41-11132 [1,050] D: In. [mm] 13 [330] H: In. [mm] 52-11/16 [1,338] Package Dimensions W: In. [mm] 42-5/16 [1,090] D: In. [mm] 17-3/4 [450] H: In. [mm] 56-5/16 [1,430] Unit Weight Lbs.[kg] 271 [123] Package Weight Lbs.[kg] 295 [134] Outdoor unit operating temperature range Cooling Intake Air Temp (Maximum / Minimum*) °F 115 DB / 23*c DB Cooling Thermal Lock -out / Re -start Temperatures -1 / 3 Heating Intake Air Temp (Maximum / Minimum) °F 70 DB / -4 DB Heating Thermal Lock -out / Re -start Temperatures °F -9 / -4 Refrigerant Type R410A Charge Lbs, oz 10 Ibs, 9 oz Indoor unit connection Maximum Number of Connected IDU 8 (6*A) Minimum Number of Connected IDU 2 Maximum connected capacity BTU/H 62,000 Minimum connected capacity BTU/H 12,000 Piping Gas Pipe Size O.D. (Flared) In.[mm] 5/8 [15.88] Liquid Pipe Size O.D. (Flared) In.[mm] 3/8 [9.52] Total Piping Length Ft. [m] 492 [150] Maximum Height DifferencekB, ODU above IDU Ft. [m] 164 [50] Maximum Height Difference*B, ODU below IDU Ft. [m] 131 [40] Maximum Height Difference`B, between branch boxes Ft. [m] 49 [15] Maximum Height Difference*B, between branch boxes and IDU Ft. [m] 49 [15] Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Max. Piping Length between ODU and Branch Ft. [m] 180 [55] Farthest Piping Length from ODU to IDU Ft. [m] 262 [80] Farthest Piping Length after Branch Box Ft. [m] 82 [25] Total Piping Length between Branch Boxes and IDU Ft. [m] 311 [95] Maximum Number of Bends 15 Notes AHRI Rated Conditions Cooling (Indoor H Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB (Rated data is determined at a fixed 2Heating at 47°F (Indoor H Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB compressor speed) 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB Conditions 4Heating at YF (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 5 WB "Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions. *A when 1 or more PLA-A•EA7 connected :B Branch box should be placed within the level between the outdoor unit and indoor units ,c YF DB - 115°F DB when optional wind baffles are installed For reference to connected capacity charts, please refer MXC Series Operational Performance Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Distribution pipe for Branch box (Flare Connection) ❑ MSDD-50AR-E Distribution pipe for Branch box (Brazed Connection) ❑ MSDD-50BR-E Port Adapter size: 3/8" x 5/8" ❑ PAC-SG76RJ-E Port Adapter size: 1/4" x 3/8" ❑ PAC-493PI Port Adapter size: 3/8" X 1/2" ❑ MAC-A454JP-E Port Adapter size: 1/2" X 3/8" ❑ MAC-A455JP-E Port Adapter size: 1/2" X 5/8" ❑ MAC-A456JP-E Branch Box ❑ PAC-MKA52BC Branch Box ❑ PAC-MKA32BC Branch Box Outer Cover ❑ BBE-1 Air Outlet Guide ❑ PAC-SH96SG-E (two pieces are required) Front Wind Baffle ❑ WB-PA3 (two pieces are required) Optional Defrost Heater ❑ PAC-SJ20BH-E Centralized Drain Pan ❑ PAC-SH97DP-E Refrigeration Ball Valve-Flare/Schrader/Insulated —1/2" size ❑ BV12FFSI2 Refrigeration Ball Valve-Flare/Schrader/Insulated —1/4" size ❑ BV14FFSI2 Refrigeration Ball Valve-Flare/Schrader/Insulated-3/8" size ❑ BV38FFSI2 Refrigeration Ball Valve-Flare/Schrader/Insulated-5/8" size ❑ BV58FFSI2 Hail Guard ❑ HG-A2 Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic ❑ DSD-400P Condensing Unit Mounting Pad 16" x 36" x 3" ❑ ULTRILITE1 Outdoor Unit Stand —12" High ❑ QSMS1202M Outdoor Unit Stand —18" High ❑ QSMS1802M Outdoor Unit Stand —24"High ❑ QSMS2402M Heavy Duty Wall Mounting Bracket —Coated Steel ❑ QSWB2000M-1 Heavy Duty Wall Mounting Bracket —316 Series Stainless Steel ❑ QSWBSS 10' x 3/8" x 10' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-10 15' x 3/8" x 15' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-15 30' x 3/8" x 30' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-30 50' x 3/8" x 50' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-50 65' x 3/8" x 65' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-65 100' x 3/8" x 100' x 5/8" Lineset (Twin -Tube Insulation) ❑ MPLS385812T-100 Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Outdoor unit MXZ-4C36NAHZ2-U1 MXZ-5C42NAHZ2-U1 MXZ-8C48NAHZ2-U1 MXZ-8C48NA2-U 1 MXZ-8C60NA2-U1 4HP 4.5HP 5HP 7HP Rated capacity Cooling 36 42 48 60 (kBtu/h) Heating 45 48 54 66 Refrigerant R410A Connectable Capacity class Type 06 to Type 36 indoor unit aution: The indoor unit which rated capacity exceeds r 36 kBtu/ In (Type 36) can NOT be connected. Number of units 2(1) to 4 units 2(1) to 5 units 2(1) to 8 units 2(1) to 8 units Total system capacity range 33 to 130% of outdoor 29 to 130% of outdoor 25 to 130% of outdoor 20 to 130% of outdoor unit capacity unit capacity unit capacity unit capacity (12 to 46.8 kBtu/h) (12 to 54.6 kBtu/h) (12 to 62.4 kBtu/h) (12 to 78 kBtu/h) Connectable Number of units 1 or 2 units branch box Connectable indoor unit lineups (Heat pump inverter type) Model type Model name Capacity class [kBtu/h] 06 09 12 15 18 24 30 36 Deluxe Wall -mounted MSZ-FH06/09/12/15NA, 18NA2 Designer MSZ-EF09/12/15/18NA(W/B/S) Standard Wall -mounted MSZ-GL06/09/12/15/18/24NA Low static ducted `3.4 SEZ-KD09/12/15/18NA P-series mid static ducted`3 `4 PEAD-A09/12/15/18/24/30/36AA7 1-way cassette MLZ-KP09/12/18NA P-series 22*22 4-way cassette SLZ-KF09/12/15NA P-series 33*33 4-way cassette PLA-Al2/18/24/30/36EA7*5 Floor standing MFZ-KJ09/12/15/18NA Standard Multi -position air handler"2 SVZ-KP12/18/24/30/36NA i Branch box PAC-MKA52BC PAC-MKA32BC Number of branches (Indoor unit that can be connected) 5 branches (MAX. 5 units) 3 branches (MAX. 3 units) Note: A maximum of 2 branch boxes can be connected to 1 outdoor unit. 2- branch pipe Qoint): Optional parts In the case of using 1- branch box In the case of using 2- branch boxes No need Model name Connection method MSDD-50AR-E flare MSDD-50BR-E brazing Select a model according to the connection method. IODtion Alm IODtional accessories for indoor units and outdoor units are available. Only one unit connection is possible with ducted unit. z When connecting a multi -position unit(s), set additional constraints as follows. For connections other than those specified below, consult your dealer. • Models other than MXZ-8C60NA2 (For each connected branch box) • MXZ-8C60NA2 (For each connected branch box) Number of connecting multi -position unit Constraints 2 Any indoor units other than ducted units are not connectable. The total system wide capacity should be 130% or 1 below including the ducted unit. Only 1 ducted unit can be included in the connection. Number of connecting multi -position unit Constraints 2 Any indoor units other than ducted unit are not connectable. The total system wide capacity should be 100% or 1 below including the ducted unit. • Only 1 ducted unit can be included in the connection. -3 For MXZ-8C60NA2; When connecting the SEZ and PEAD-series units, the total system wide capacity per 1 branch box should be 100% or below including the ducted units. (Only if connecting to branch box) `4 When not outside units 60: A branch box can connect to maximum 3 of the ducted units. When connecting with 3 of the ducted units per 1 branch box, other indoor units cannot be connected. When outside units 60: A branch box can connect to maximum 2 of the ducted units. When connecting with 1 and over 1 of the ducted units, the total ability including of the ducted units is 100% and below 100%. 5 When the system includes 1 unit of ducted units, the number of the maximum connectable indoor units is decreased as follows: 3 for MXZ-4C36NAHZ2-U1, 4 for MXZ-5C42NAHZ2-U1, and 6 for 1VlXZ-8C48NA(HZ)2-1J1 and MXZ-8C60NA2-U1 IN NOTE Please refer to Application Note 1029 for more information and exceptions to these rules. Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Piping connection size A B Liquid 953/8 inch The piping connection size differs according to the type and capacity of indoor units. [9.52 mm] Match the piping connection size of branch box with indoor unit. If the piping connection size of branch box does not match the piping connection size of Gas 05/8 inch 03/4 inch* indoor unit, use optional different -diameter (deformed) joints to the branch box side. [15.88 mm] [19.05 mm] I (Connect deformed joint directly to the branch box side.) * MXZ-8C60 only ■ In case of using 1-branch box Flare connection employed (No brazing) ■ In case of using 2-branch boxes 7 hrnnnhoc nine fininfl Branch box #2 ■ Installation procedure (2 branches pipe (joint)) Refer to the installation manuals of MSDD-50AR-E and MSDD-50BR-E. Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. 1 FREESPACE( 13 FOUNDATION BOLTS 4PIPING-WIRING DIRECTIONS The diagram below shows a basicmmpn. Dimensions of space needed Pleasesecuretheunithrmfy Piping and wiringmnrrections Ritbratwn°fpartkulardetails are forserviceaccessare wAh4(oundaflon iM1O<W3/8>Iboks. an be madefmm4direcdons givenintheimtallationmanualsetc. showninthebebwdiagram. (Bons and washers must be Front Right, Rearand Below. purchased locally) <Foundation bolt height> ----------------- Services ace o .......... Min. q 5Do '19-11/16> RearAirintake SideAirinake nn: 7 1 1 1 f HM I Handle(or Handlefor Example of Notes m°°i" mom iO • • • RettlgemaWSppeconnectionlFlARQOA 2O • • • Redgeam UQUID pipe connection lFlARE)0952 Q/8F) X1 • • • ladnadon of STOP VALVE connection nation. Piping Knock Out Hole Details 11[--• 1 � >. RearAir Intake 2NU 225 600 V� 225 Fa <8-27/32> <23-5/8> <8-27/32> Imtlladon Feet Side Air Intake = M r 7o 12-3/4> 42<1-21 60.5<2-' 2X1 X36 lholes alhoks Air Discharge Foun36 <W3 Termuu Fan le 1050<41-11/32> ache Handleformadng 362<14-1/4> Ground for the power supply was Set the attachment to the inner side of each panel. mm <inch> Handlefor 56<2-7/32> 40<1-37/64> 0 53<2-3/32> Forconcentration cantr°I PAC-MKA52BC SUSPENSION BOLT PITCH 320 (12-19132) SUSPENSION BOLT: W318(M10) REFRIGERANTPIPE FLARED CONNECTION Unit: inch A IB C 1 D 1 E 1 TO OUTDOOR UNIT LIQUID PIPE 1/41P 114F 114E 1 1/4F 1 1/4F 1 3/8F GAS PIPE 318E 3/8F 3/8F 3/8F 1/2F I 5/8F PAC-MKA32BC SUSPENSION BOLT PITCH 320 02-19132) SUSPENSION BOLT. W3/8(M10) REFRIGERANT PIPE FLARED CONNECTION Unit: inch A B IC 1 1 TO OUTDOOR UNIT LIQUID PIPE I 114F 1/41' 1/4F 318F GAS PIPE 318E I 3/8F I 3/8F 518F FORM# MXZ-8C48NA2 - 202003 Unit: mm <inch> When installing the conduit. Set the attachment to the inner side of each panel. 58 (2-9o2) (ISI23B2J � <1332) i v2 ��rn co,wun anau,mam ts(tv3z) BBU-19B2) e J. 11.21 TERM IN&BLOCK TOM-NETUNIT TERMINALBLOCK TO INDOOR UNR •• EEQ— •• 1 TERMINPL BLOCK TOOUTDOOR UNIT When installing the conduit. Set the attachment to the inner side of each panel. 58 (2-9I82) (2W4 (13132) n�N �a 5-022OB) 1 qh C,n- 15 (19B2) e6 (2-1813y ,y — 11 TERMINA Ik K TO M-NET UNIT TERMINALBLOCK TO INDOOR UNM EEC•• TMINNL NK1 TOOUERTOOOR UNIT 1340 Satellite Boulevard, Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com ' C ETI US Intertek Specifications are subject to change without notice. © 2020 Mitsubishi Electric Tirane HVAC US LLC. All rights reserved.