FIR2020-0083+Fire_Sprinkler_Equipment_Specification_Sheets+9.29.2020_12.02.12_PMFIR2020-0083 RECEIVED Sep 30 2020 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT MATERIAL SUBMITTAL AND HYDRAULIC CALCULATIONS FOR DRIESSEN RESIDENCE 9229 OLYMPIC VIEW DRIVE EDMONDS, WA 98020 m Cascadia FIRE PROTECTION PO BOX 206 PUYALLUP, WA 98371 CASCAFP8331-2 DRIESSEN RESIDENCE TABLE OF CONTENTS FIRE SPRINKLERS TYCO SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER TYCO SERIES RFII "ROYAL FLUSH II" CONCEALED PENDENT SPRINKLER FIRE SPRINKLER VALVES AMES 2000B DOUBLE CHECK VALVE ASSEMBLY PIPE AND FITTINGS HARVEL CPVC FIRE SPRINKLER PIPE SPEARS FLAMEGUARD CPVC FITTINGS HANGERS TOLCO FIGURE 24 CPVC HANGER TOLCO FIGURE 28 "STAND-OFF" CPVC HANGER TOLCO FIGURE 28M OFFSET CPVC HANGER MICELLANEOUS MATERIALS POTTER VSR-SG FLOW SWITCH HYDRAULIC CALCULATIONS UPPER FLOOR - HALL (RESIDENTIAL) FIRE SPRINKLERS tqC00 Worldwide I www.tyco-fire.com Contacts RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description The TYCO RAPID RESPONSE Series LFII Residential 4.9K Concealed Pendent Sprinklers (TY3596) are dec- orative, fast response, fusible solder sprinklers designed for use in residen- tial occupancies such as homes, apart- ments, dormitories, and hotels. The cover plate assembly conceals the sprinkler operating components above the ceiling. The flat profile of the cover plate provides the optimum aes- thetically appealing sprinkler design. In addition, the concealed design of the Series LFII Residential Con- cealed Pendent Sprinklers provides 1/2 in. (12,7 mm) vertical adjustment. This adjustment provides a measure of flexibility when cutting fixed sprin- kler drops. The Series LFII Residential Concealed Pendent Sprinklers are intended for use in the following scenarios: • Wet and dry pipe residential sprin- kler systems for one and two fam- ily dwellings and mobile homes per NFPA 13D • Wet and dry pipe residential sprin- kler systems for residential occupan- cies up to and including four stories in height per NFPA 13R • Wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 The Series LFII Residential Concealed Pendent Sprinklers have been designed with heat sensitivity and water distri- bution characteristics proven to help IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. in the control of residential fires and to improve the chance for occupants to escape or be evacuated. The Series LFII Residential Con- cealed Pendent Sprinklers (TY3596) are shipped with a Disposable Protec- tive Cap. The Protective Cap is tem- porarily removed for installation, and then it can be replaced to help protect the sprinkler while the ceiling is being installed or finished. The tip of the Pro- tective Cap can also be used to mark the center of the ceiling hole into the plaster board, ceiling tiles, and so on, by gently pushing the ceiling product against the Protective Cap. When the ceiling installation is complete the Pro- tective Cap is removed and the Cover Plate Assembly is installed. Dry Pipe System Application The Series LFII Residential Concealed Pendent Sprinklers offer a laboratory approved option for designing dry pipe residential sprinkler systems, whereas, most residential sprinklers are labora- tory approved for wet systems only. Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Concealed Pendent Sprinklers need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is accustomed for density/ area sprinkler systems designed per NFPA 13. Consequently, the Series LFII Residen- tial Concealed Pendent Sprinklers offer the features of non -water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R. NOTICE The Series LFII Residential Concealed Pendent Sprinklers (TY3596) described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protection Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the perfor- mance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Number (SIN) TY3596 Page 1 of 6 MAY 2018 TFP442 TFP442 Page 2 of 6 Technical Data Approvals UL and C-UL Listed NYC Approved under MEA 44-03-E-2NSF Certified to all requirements of NSF/ANSI 61 The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers are Listed only when installed with LFII/RFIII Concealed Cover Plates having factory - applied finishes. Sprinklers and Cover Plates are separately ordered. Refer to the Ordering Procedure section for more information. Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K=4.9 GPM/psi' (70,6 LPM/bar") Temperature Rating 160OF (71°C) Sprinkler 139°F (59°C) Cover Plate Vertical Adjustment 112 in. (12,7 mm) Finishes Refer to Ordering Procedure section Physical Characteristics Body..............................Brass Cap..............................Bronze Saddle.............................Brass Sealing Assembly. Beryllium Nickel w/TEFLON Soldered Link Halves ................ Nickel Lever.............................Bronze Compression Screw .................. Brass Deflector .................. Copper or Brass Guide Pin Housing ..................Bronze Guide Pins ......... Stainless Steel or Bronze Support Cup ....................... Steel Cover Plate ....................... Copper Retainer ...........................Brass Cover Plate Ejection Spring .... Stainless Steel Operation When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Retainer at three points, falls away to expose the sprinkler assembly. At this point the Deflector supported by the Arms drops down to its operated position. The fusible link of the sprin- kler assembly is comprised of two link halves that are soldered together with a thin layer of solder. When the rated temperature is reached, the solder melts and the two link -halves separate allowing the sprinkler to activate and flow water. BODY (1/2" NP CAP SADDLI SUPPOF CUP W11 ROLL FOR THREAC GUIDE PIN GUIDE P HOUSIN THREADINTO SUPPOR CUP UNT MOUNTIN SURFACE FLUSH WI' CEILING SOLDEF TAB SPRINKLER ASSEMBLY ASSEMBLY FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY3596) Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers (TY3596) are UL and C-UL Listed for installation in accordance with this section. Note: When conditions exist that are outside the scope of the provided cri- teria, refer to the Residential Sprinkler Design Guide TFP490 for the manu- facturer's recommendations that may be acceptable to the authority having jurisdiction. System Types Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized. Refer to Technical Data Sheet TFP485 about the use of residential sprinklers in residential dry pipe systems. ;EALING )SEMBLY 'RINKLER IENCHING AREA 1PRESSION SCREW LEVER -DER LINK LEMENT FLECTOR PERATED OSITION) RETAINER H THREAD )IMPLES JECTION SPRING COVER PLATE Ceiling Types Smooth flat horizontal, beamed, or sloped in accordance with the 2013 Edition of NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the minimum required sprin- kler flow rates are given in Tables A and B as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of "design sprinklers" as specified in NFPA 13D or NFPA 13R. The number of "design sprinklers" specified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. TFP442 Page 3 of 6 WET PIPE SYSTEM Minimum Flow and Residual Pressurez,3 Maximum Coverage Maximum Spacing Ordinary Temp. Rating 160°F(71°C) Minimum ft Notes: 1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. 2. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. 3. For NFPA 13 residential applications, the greater of 0.1 GPM/ft2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT SPRINKLER (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA Area ft x ft Deflector to Installation Spacing Flow Pressure (m x m) (m) Ceiling Type ft GPM psi (m) (LPM) (bar) 12 x 12 12 13 7.0 (3,7 x 3,7) (3,7) (49,2) (0,48) Smooth Ceilings 14 x 14 14 13 7.0 7/8 to 1-1/8 in. (4,3 x 4,3) (4,3) (49,2) (0,48) Beamed Ceilings per 8 16 x 16 16 13 7.0 (4,9 x 4,9) (4,9) (49,2) (0,48) NFPA 13D or Concealed (2 4) 13R, or 13. Installed in 18 x 18 18 17 12.0 beam (5,5 x 5,5) (5,5) (64,3) (0,83) 7/8 to 1-1/8 in. below bottom 20 x 20 20 20 16.7 of beam (6,1 x 6,1) (6,1) (75,7) (1,15) DRY PIPE SYSTEM Minimum Flowand Residual Pressure 2,3 Maximum Maximum Coverage Area Spacing Ordinary Temp. Rating 160°F(71°C) Minimum ft x ft ft Deflector to Installation Spacing Flow Pressure (m x m) (m) Ceiling Type ft GPM psi (m) (LPM) (bar) 12 x 12 12 13 7.0 (3,7 x 3,7) (3,7) (49,2) (0,48) Smooth Ceilings 14 x 14 14 14 8.2 7/8 to 1-1/8 in. (4,3 x 4,3) (4,3) (53,0) (0,57) Beamed Ceilings per NFPA 13D or Concealed 8 16 x 16 16 15 9.4 (4,9 x 4,9) (4,9) (56,8) (0,65) 13R, or 13. Installed in (2,4) 18 x 18 18 18 13.5 beam (5,5 x 5,5) (5,5) (68,1) (0,93) 7/8 to 1-1/8 in. below bottom 20 x 20 20 21 18.4 of beam (6,1 x 6,1) (6,1) (79,5) (1,27) Notes: a. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated us- ing the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. c. For NFPA 13 residential applications, the greater of 0.1 GPM/ft2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA TFP442 Page 4 of 6 2-1/2" DIA. _ SPRINKLER- (63,5 mm) 1/2" (12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT \ ADJUSTMENT FITTING OPERATED SPRINKLER - --__ 1-7/8"t1/4" _ —_---- PLATE -_-- COVER (47,6 mm -----_ RETAINER 1/8" GAP t6,4 mm)-------_ (3,21mm) COVER- SPRINKLER- 5/8" (15,9 mm) RETAINER SUPPORT CUP MOUNTING 1-1/8" (28,6 mm) ASSEMBLY ASSEMBLY 3/16" SURFACE (4,8 mm) \\\ 3-3/16" DIA. _ DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 2 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY3596) INSTALLATION DIMENSIONS, PROTECTIVE CAP, AND ACTIVATED DEFLECTOR Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis- charge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Tables A and B as a function of temperature rating and the maximum allowable cover- age area • A minimum discharge of 0.1 GPM/ft2 over the design area comprised of the four most hydrauli- cally demanding sprinklers for actual coverage areas protected by the four sprinklers The number of design sprinklers speci- fied in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. Dry Pipe System Water Delivery When using the Series LFII Residen- tial Concealed Pendent Sprinklers in dry pipe sprinkler systems, the time for water delivery must not exceed 15 seconds for the most remote operat- ing sprinkler. Obstruction to Water Distribution Sprinklers are to be located in accor- dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational Sensitivity The sprinklers are to be installed rela- tive to the ceiling mounting surface as shown in Figure 2. Sprinkler Spacing The minimum spacing between sprin- klers is 8 ft (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (Ref. Table A or B) being hydraulically calculated (e.g., maximum 12 ft for a 12 ft x 12 ft coverage area, or 20 feet for a 20 ft x 20 ft coverage area). The Series LFII must not be used in applications where the air pres- sure above the ceiling is greater than that below. Down drafts through the Support Cup could delay sprinkler operation in a fire situation. Installation The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers (TY3596) must be installed in accordance with this section. General Instructions Damage to the fusible Link Assembly during installation can be avoided by handling the sprinkler by the support cup only. Therefore, do not apply pres- sure to the fusible Link Assembly. A 1/2 in. NPT sprinkler joint should be obtained with a minimum to maximum torque of 7 to 14 lb-ft (9,5 to 19,0 Nm). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Cover Plate Assembly by under -or over -tightening the Sprinkler. Re- adjust the position of the sprinkler fitting to suit. Step 1. The sprinkler must only be installed in the pendent position and with the centerline of the sprinkler per- pendicular to the mounting surface. WRENCH RECESS 0 t PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 3 W-TYPE 18 SPRINKLER WRENCH Step 2. Remove the Protective Cap. Step 3. With pipe thread sealant applied to the pipe threads, and using the W-Type 18 Wrench shown in Figure 3, install and tighten the Sprinkler/ Support Cup Assembly into the fitting. The W-Type 18 Wrench will accept a 1/2 in. ratchet drive. Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protec- tive Cap helps prevent damage to the Deflector and Guide Pins during ceiling installation and/or during application of the finish coating of the ceiling. It may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Cap. Note: As long as the protective Cap remains in place, the system is consid- ered to be "Out Of Service." TFP442 Page 5 of 6 Step 5. After the ceiling has been com- pleted with the 2-1/2 in. (63 mm) diam- eter clearance hole and in preparation for installing the Cover Plate Assembly, remove and discard the Protective Cap, and verify that the Deflector moves up and down freely. If the sprinkler has been damaged and the Deflector does not move up and down freely, replace the entire sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler. Step 6. Push on the Cover Plate Assembly until its flange comes in contact with the ceiling. Do not continue to push on the Cover Plate Assembly such that it lifts a ceiling panel out of its normal position. If the Cover Plate Assembly cannot be engaged with the Mounting Cup or the Cover Plate Assembly cannot be engaged sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. Care and Maintenance The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers (TY3596) must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system which it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Absence of a Cover Plate may delay the sprinkler operation in a fire situation. When properly installed, there is a nominal 1/8 in. (3,2 mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 2. This air gap is necessary for proper oper- ation of the sprinkler by allowing heat flow from a fire to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a fire situation. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted units. Non -factory applied paint may adversely delay or prevent sprinkler operation in the event of a fire. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi- fied or over heated sprinklers must be replaced. Care must be exercised to avoid damage before, during, and after instal- lation. Sprinklers damaged by drop- ping, striking, wrench twist/slippage, or the like, must be replaced. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso- ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or product manufacturer with any questions. The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non - operation in the event of a fire or inad- vertent operation may result. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and part number (P/N). Sprinkler Assemblies Specify: Series LFII (TY3596) 4.91K Res- idential Concealed Pendent Sprinkler, P/N 51-112-1-160 Note: Sprinkler and Cover Plates are separately sold. See below for Cover Plate ordering information. Cover Plate Assemblies Specify: LFII/RFIII Concealed Sprinkler Cover Plate Assembly, (specify finish), P/N (specify): Ivory (RAU 015) ............... 56-204-0-135 Beige (RAL1001) .............. 56-204-2-135 Pure White (RAL9010)* .........56-204-3-135 Signal White (RAL9003)`........ 56-204-4-135 Grey White (RAL9002).......... 56-204-5-135 Brown(RAL8028)..............56-204-6-135 Black (RAL9005) .............. 56-204-7-135 Brushed Brass ................56-204-8-135 Brushed Chrome ..............56-204-9-135 Brass.......................56-204-1-135 Custom Paint .................56-204-X-135 *Eastern Hemisphere sales only **Previously known as Bright White Note: All Custom Cover Plates are painted using Sherwin Williams Interior Latex Paint. Contact Tyco Customer Service with any questions related to custom orders. Sprinkler Wrench Specify: W-Type 18 Sprinkler Wrench, P/N 56-000-1-265 TFP442 Page 6 of 6 1400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone A-215-362-0700 m 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson I nson ORO TEFLON Is a reglst—d trademark of DuPont Controls Tyco Fire Protection Products Series RFII — 5.6 K-factor Worldwide I www.tyco-fire.com Contacts "Royal Flush 11" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General Description The TYCO Series RFII 5.6 K-factor, "Royal Flush ll" Concealed Pendent Sprinklers Quick Response (3-mm bulb) and Standard Response (5-mm bulb), are decorative sprinklers fea- turing a flat cover plate designed to conceal the sprinkler. These sprinklers are optimal for architecturally sensi- tive areas such as hotel lobbies, office buildings, churches, and restaurants. Each sprinkler includes a Cover Plate/ Retainer Assembly and a Sprinkler/ Support Cup Assembly. The separa- ble, two-piece assembly design pro- vides the following benefits: • Allows installation of the sprinklers and pressure testing of the fire pro- tection system prior to installation of a suspended ceiling or application of the finish coating to a fixed ceiling. • Permits the removal of suspended ceiling panels for access to building service equipment without having to first shut down the fire protection system and remove sprinklers. • Provides for 1/2 inch (12,7 mm) of vertical adjustment to allow a measure of flexibility in determining the length of fixed piping to cut for the sprinkler drops. The Series RFII Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap is temporarily removed during installation and replaced to help protect the sprinkler during ceiling installation or finish. The tip of the Pro- IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. tective Cap can be used to mark the center of the ceiling hole into plaster board or ceiling tiles by gently pushing the ceiling product against the Pro- tective Cap. When ceiling installa- tion is complete, the Protective Cap is removed and the Cover Plate/Retainer Assembly is installed. As an option, the Series RFII Standard Response (5-mm bulb) "Royal Flush II" Concealed Pendent Sprinklers can be fitted with a silicone Air and Dust Seal. (Refer to Figure 5.) The Air and Dust Seal is intended for sensitive areas where it is desirable to prevent air and dust from the area above the ceiling to pass through the cover plate. The Series RFII Concealed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identification Number (SIN) TY3531 — 3 mm bulb TY3551 — 5 mm bulb Technical Data Sprinkler Approvals Approvals apply only to the service conditions indicated in the Design Criteria section. • TY3531 (3 mm Bulb) is UL Listed, C-UL Listed and NYC Approved (MEA 353-01-E) as Quick Response. • TY3531 (3 mm Bulb) is VdS Approved (Certificate No. G4090007). • TY3531 (3 mm Bulb) is FM and LPCB Approved (Ref. No. 094a/10) as Standard Response. Note: FM and LPCB do not approve concealed sprinklers for quick response. • TY3551 (5 mm Bulb) is UL Listed, C-UL Listed, FM Approved, LPCB Approved (Ref. No. 094a/9), and NYC Approved (MEA 353-01-E) as Standard Response. Approvals for Air and Dust Seal UL and C-UL Listed for use with the RFII Standard Response Concealed Sprinkler (TY3551) Maximum Working Pressure Maximum 250 psi (17,3 bar) by UL, C-UL, and NYC Maximum 175 psi (12,1 bar) by FM, VdS, and LPCB Temperature Rating 155°F (68°C) Sprinkler with 139T (59°C) Plate 200oF (93°C) Sprinkler with 165°F (74°C) Plate Discharge Coefficient K= 5.6 GPM/psis/2 (80,6 LPM/barli2) Page 1 of 4 APRIL 2016 TFP181 TFP181 Page 2 of 4 Adjustment 1/2 inch (12,7 mm) Finishes See the Ordering Procedure section. Physical Characteristics Frame ............................Bronze Support Cup ............Chrome Plated Steel Guide Pins .................. Stainless Steel Deflector..........................Bronze Compression Screw .................. Brass Bulb...............................Glass Cap.....................Bronze or Copper Sealing Assembly. Beryllium Nickel w/TEFLON Cover Plate .........................Brass Retainer............................Brass Ejection Spring .............. Stainless Steel Design Criteria The TYCO Series RFII 5.6 K-factor, "Royal Flush ll" Concealed Pendent Sprinklers are intended for fire protec- tion systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency; for example, UL Listing is based on NFPA 13 and VdS Approval is based on the CEA 4001. For more information on LPCB and VdS Approvals, contact Tyco Fire Protection Products at the following office: Enschede, Netherlands Telephone: 31-53-428-4444 Fax:31-53-428-3377 The Series RFII Concealed Pendent Sprinklers are only listed and approved with the Series RFII Concealed Cover Plates having a factory applied finish. FITUM Do not use the Series RFII in applica- tions where the air pressure above the ceiling is greater than that below. Down drafts through the Sprinkler/Support Cup Assembly can delay sprinkler operation in a fire situation. Operation When exposed to heat from a fire, the Cover Plate, normally soldered to the Retainer at three points, falls away to expose the Sprinkler/Support Cup Assembly. The Deflector — supported by the Guide Pins — then drops down to its operational position. The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, activating the sprinkler and allowing water to flow. 112" NPT FRAME SUPPOR' CUP WITI ROLL FORK THREAD: GUIDE PINS (2) DEFLECTOR SPRINKLER/SUPPORT CUP ASSEMBLY EALING SEMBLY CAP BULB PRESSION ;CREW -LECTOR SOPPED POSITION) THREAD INTO RETAINER SUPPORT WITH THREAD CUP UNTIL O O = DIMPLES MOUNTING SURFACE IS EJECTION FLUSH WITH SPRING CEILING i SOLDER' —-------------- COVER TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY FIGURE 1 MODEL RFII CONCEALED SPRINKLER ASSEMBLY Installation The TYCO Series RFII 5.6 K-factor, "Royal Flush ll" Concealed Pendent Sprinklers must be installed in accor- dance with this section. General Instructions Do not install any bulb -type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 155°F (68°C) and 3/32 inch (2,4 mm) for the 200°F (93°C) tem- perature ratings. A leak -tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum to maximum torque of 7 to 14 ft.-Ibs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Sprinkler by under- or over -tightening the Sprin- kler/Support Cup Assembly. Re -adjust the position of the sprinkler fitting to suit. Step 1. Install the sprinkler only in the pendent position with the center -line of the sprinkler perpendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe thread sealant applied to the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. Step 4. Wrench -tighten the sprinkler using only the RFII Sprinkler Wrench. (Refer to Figure 3.) Apply the RFII Sprinkler Wrench to the Sprinkler as shown in Figure 3. TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE SPRINKLER DIAMETER FITTING DIMENSION C SPRINKLER --- SUPPORT CUP lit ASSEMBLY 1/2" (12,7 mm) THREADED--------- D ADJUSTMENT -- ---------- FACE ----------------- OF CEILING, RETAINING RING ---------- ------- MOUNTING ----------------- f SURFACE ?/----------------- ==i =__ ---- L 3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY COVER PLATE PROFILE DEPTH DIMENSION B A: 3-1/4 inches (82,6 mm) B: 3/16 inches (4,8 mm) COVER PLATE DIAMETER DIMENSION A C: 2-3/8 to 2-5/8 inches (60,3 to 66,7 mm) D: 1-3/4 to 2-1/4 inches (44,5 to 57,2 mm) FIGURE 2 SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Step 5. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. (Refer to Figure 4.) The Protective Cap helps prevent damage to the Deflector and Arms during ceiling installation and/or finish. You can also use the Protective Cap to locate the center of the clear- ance hole by gently pushing the ceiling material up against the center point of the Protective Cap. FITUM As long as the Protective Cap remains in place, the system is considered "Out of Service". Step 6. After the ceiling has been completed with the 2-1/2 inch (63,5 mm) diameter clearance hole and in preparation for installing the Cover Plate/Retainer Assembly, remove and discard the Protective Cap. Verify that the Deflector moves up and down freely. If the Sprinkler is damaged and the Deflector does not move up and down freely, replace the entire Sprinkler. Do not attempt to modify or repair a damaged sprinkler. Step 7. When installing an Air and Dust Seal, refer to Figure 5; otherwise, proceed to Step 8. To attach the Air and Dust Seal, verify the angle of the outside edge of the seal is oriented according to Figure 5. Start the edge of the Retainer in the grooved slot of the Air and Dust Seal and continue around the retainer until the entire Air and Dust Seal is engaged. TFP181 Page 4 of 4 Step 8. Screw on the Cover Plate/ Retainer Assembly until the Retainer (shown in Figure 2) or the Air and Dust Seal (shown in Figure 5) contacts the ceiling. Do not continue to screw on the Cover Plate/Retainer Assembly so that it lifts a ceiling panel out of its normal position. If you cannot engage the Cover Plate/Retainer Assembly with the Support Cup or you cannot engage the Cover Plate/Retainer Assembly suf- ficiently to contact the ceiling, you must reposition the Sprinkler Fitting. Care and Maintenance The TYCO Series RFII 5.6 K-factor, "Royal Flush II" Concealed Pendent Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection system from the proper authorities and notify all personnel who may be affected by this action. Absence of the Cover Plate/Retainer Assembly can delay sprinkler opera- tion in a fire situation. When properly installed, there is a nominal 3/32 inch (2,4 mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 2. This air gap is necessary for proper operation of the sprinkler. If the ceiling requires repainting after sprinkler installation, ensure that the new paint does not seal off any of the air gap. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. SUPPORT SPRINKLER FACE OF ORIENT CUP / CEILING SEAL / BEVEL AS COVER SHOWN / PLATE RETAINER ASSEMBLY AIR AND DUST LIP OF COVER SEAL RETAINER PLATE FIGURE 5 OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551) Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin- kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa- tion Section.) Exercise care to avoid damage to sprin- klers before, during, and after instal- lation. Replace sprinklers damaged by dropping, striking, wrench twist- ing, wrench slipping, or the like. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Refer to the Installation section.) If you must remove a sprinkler, do not reinstall it or a replacement without reinstalling the Cover Plate/Retainer Assembly. If a Cover Plate/Retainer Assembly becomes dislodged during service, replace it immediately. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso- ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or sprinkler manufac- turer regarding any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national code. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name. Sprinkler/Support Cup Assembly Specify: Series RFII (specify SIN), K=5.6, "Royal Flush II" Pendent Sprin- klers (specify) temperature rating and (specify) finish, P/N" (specify): 155°F(68°C) 200oF(93oCl TY3531 51-792-1-155 51-792-1-200 TY3551 51-790-1-155 51-790-1-200 Use Suffix "I" for ISO 7-1 connection; for example, 51-792-1-155-I Separately Ordered Cover Plate/ Retainer Assembly: Specify: (temperature rating from below) Series RFII Concealed Cover Plate with (finish), P/N (specify). 139°F (59°C)(a) 165°F (74°C)(b) Grey White (RAL9002) .... 56-792-0-135 56-792-0-165 Brass.......... 56-792-1-135 56-792-1-165 Pure White (c) (RAL9010) .... 56-792-3-135 56-792-3-165 Signal White (RAL9003) .... 56-792-4-135 56-792-4-165 Jet Black (RAL9005) .... 56-792-6-135 59-792-6-165 Brushed Chrome........ 56-792-8-135 56-792-8-165 Chrome........ 56-792-9-135 56-792-9-165 Custom ........ 56-792-X-135 56-792-X-165 (a) For use with 155°F (68°C) sprinklers. (b) For use with 200oF (93°C) sprinklers. (c) Eastern Hemisphere sales only. Sprinkler Wrench Specify: RFII Sprinkler Wrench, P/N 56-000-1-075 Air and Dust Seal Specify: Air and Dust Seal, P/N 56-908-1-001 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 Copyright © 2016 Tyco Fire Products, LP. All rights reserved. t�CO TEFLON is trademark of The DuPont Corporation Fire Protection Products FIRE SPRINKLER VALVES ES-A-2000B Series 2000B Double Check Valve Assemblies Sizes: 1/2" — 2" (15 — 50mm) Features • Ease of maintenance with only one cover • Top entry • Replaceable seats and seat discs • Modular construction • Compact design • '/2" — 2" (15 — 50mm) Cast bronze body construction • Top mounted ball valve test cocks • Low pressure drop • No special tools required • 1/2" — 1 " (15 — 25 mm) have tee handles Available Models Suffix: B - Quarter turn ball valves LBV - less ball valves SH - stainless steel ball valve handles HC - 2'/2" inlet/outlet fire hydrant fitting (2" valve) Pressure — Temperature Temperature Range: 33°F — 140°F (0.5°C — 60°C) Maximum Working Pressure: 175psi (12.1 bar) Standards AWWA Std. C510, IAPMO PS31 It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing standard material prod- uct, consult your local water authority, building and plumbing codes. Job Name Job Location Engineer Approval A A M E S FIRE & WATERWORKS 2" 2000B HC (50mm) �1 KI �r #G, 3/411 2000E (20mm) Series 2000B Double Check Valve Assemblies are designed to protect drinking water sup- plies for dangerous cross -connections in accordance with national plumbing codes and water authority requirements for non -health -hazard non -potable service applications such as irrigation, fire line, or industrial processing. These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are approved by the Foundation for Cross -Connection Control and Hydraulic Research at the University of Southern California. Specifications A Double Check Valve Assembly shall be installed at each noted location. The assembly shall consist of two positive seating check modules with captured springs and rubber seat discs. The check module seats and seat discs shall be replaceable. Service of all internal components shall be through a single access cover secured with stainless steel bolts. The assembly shall also include two resilient seated isolation valves and four top mounted, resilient seated test cocks. The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std. C510. Approved by the Foundation for Cross -Connection Control and Hydraulic Research at the University of Southern California. Assembly shall be an Ames Company Series 2000B. Approvals �pS I CS100 Fj�o SACPC ®® C us c us B64.5 3/4" - 2" (LBV Models Only) Approved by the Foundation for Cross -Connection Control and Hydraulic Research at the University of Southern California. LBV models not listed. Horizontal and vertical "flow up" approval on all sizes. Contractor Approval Contractor's P.O. No. Representative Ames product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Ames Technical Service. Ames reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. amesfirewater.com Dimensions - Weights Suffix HC - Fire Hydrant Fittings dimension "A" = 23'/2" (594mm) SIZE i DIMENSIONS in. mm A in. mm in. B mm C in. mm F in. mm G in. mm H in. mm in. I mm lbs. kgs. '/2 15 10 254 4% 117 2'/16 62 5 127 3% 85 26/16 59 2'/16 52 4.5 2 3/4 20 11 % 282 4 102 3'/6 79 63/ 6 157 V16 87 2% 54 16/ 6 33 5 2.3 1 25 13'/4 337 1 5Y6 130 1 4 102 1 7'/2 191 1 3% 85 11'/6 43 111/6 43 1 12 5.4 1'/4 32 16% 416 5 127 36/6 84 91h 241 5 127 3 76 2 50 15 6.8 11/2 40 163/4 425 4'/6 124 31h 89 93/4 248 51Y16 148 3% 79 2"/6 68 15.86 7.2 2 50 19'/2 495 6'/4 159 4 102 13% 340 6'/6 156 37/6 87 2"/16 68 25.75 11.7 Strainer sold separately Capacities As compiled from documented Foundation for Cross -Connection Control and Hydraulic Research at the University of Southern California lab tests. ATypical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.) kPa psi 112" (15mm) y 83 12 O 69 10 m 55 8 41 6 N 28 4 aNi 14 2 a 0 0 0 2 4 6 8 10 12 gpm OP 0 7.6 15.2 22.8 30.4 38 45.6 Ipm 5 7.5 10 fps 1.5 2.3 3.0 mps Flow Rate IIIIIIIIIIIII■IIIIIIIIIIIII■■ IIII■IIIIIIIIIIIII■IIIIIIIIIIIII■IIIIIIIIIIIII■■ IIIIIIIIIIIII■IIIIIIIIIIIII■■ IIII■IIIIIIIIIIIII■IIIIIIIIIIIII■IIIIIIIIIIIII■■ 69 1 ��■ ����� IIIIIIIIIIIII■IIIIIIIIIIIII■■ IIII■IIIIIIIIIIIII■IIIIIIIIIIIII■Illlllllllr� 41 ��■ ���r■ 14 ��■ ����■ kPa psi 11/4" (32MM) 96 14 A 83 12 N o 69 10 y 55 8 7 41 6 N28 4 14 2 d 0 0 AP 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps Flow Rate kPa psi 83 12 y 69 10 O 55 8 y 41 6 3 28 4 d14 2 n n LL AP 0 5 10 15 20 25 30 35 40 45 50 gpm 0 19 38 57 76 95 114 133 152 171 190 Ipm 7.5 15 fps 2.3 4.6 mps Flow Rate w kPapsi 1 " (25mm) O y 110 110 16 A J J 83 12 i m 69 10 W 7 55 8 H 41 6 m 28 4 d IL 14 2 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm AP 0 19 38 57 76 95 114 133 152 171 190 209 228 Ipm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 Flow Rate mps A M E S A Watts Water Technologies Company pp0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps Flow Rate kPa psi Q ° (50mm) 83 12 69 10 55 8 41 6 28 4 14 2 0 0 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 Ipm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps Flow Rate USA: Backflow Tel: (978) 689-6066 • Fax: (978) 975-8350 • AmesFireWater.com USA: Control Valves Tel: (713) 943-0688 • Fax: (713) 944-9445 • AmesFireWater.com Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • AmesFireWater.ca Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • AmesFireWater.com FS-A-2000B 1410 © 2014 Ames Fire & Waterworks PIPE AND FITTINGS Product Specifications Harvel° Blazemaster° CPVC Fire Sprinkler Pipe /1 MARVEL® v 0 W E W N M GO i cd Application: Corrosion resistant fire sprinkler pipe, IPS sizes 3/4" through 3", for use in wet automatic fire sprinkler systems. When installed in accordance with Harvel's Installation Instructions, this pipe is Listed by Underwriters Laboratories (UL) for use in: Light Hazard Occupancies as defined in the Standard for Installation of Sprinkler systems (NFPA 13); Residential Occupancies up to and including four stories in height (NFPA 13R); and Residential Occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings and Mobile Homes (NFPA 13D). Harvel B1azeMaster, pipe is UL Listed for use in Return Air Plenums (NFPA 90A), System Risers per NFPA 13 Light Hazard, 13R and 13D, Exposed installations, Garages per NFPA 13R, and for use as Underground Fire Service Mains (NFPA 24) when installed in accordance with Harvel CPVC Fire Sprinkler Pipe Installation Instructions. Scope: This specification outlines minimum manufacturing requirements for Chlorinated Polyvinyl Chloride (CPVC) standard dimension ratio (SDR) 13.5 series iron pipe size (IPS) fire sprinkler pressure pipe. Pipe is intended for use in wet automatic fire sprinkler sys- tems when installed in accordance with Harvel Plastics, Inc. CPVC Fire Sprinkler Piping Products Installation Instructions. Harvel, BlazeMaster, pipe carries a maximum working pressure of 175 psi @ 150°F. Pipe meets or exceeds applicable industry standards and requirements as set forth by the American Society for Rsting and Materials (ASTM), the National Sanitation Foundation (NSF), and Underwriters Laboratories (UL). Harvel, B1azeMaster, fire sprinkler pipe is approved by the Factory Mutual Corporation (FM) and the Loss Prevention Certification Board (LPCB). Refer to current approval guide and installation and design manual for installation limitations. CPVC Materials: The material used in the manufacture of the pipe shall be a rigid chlorinated polyvinyl chloride (CPVC) compound, I�pe IV Grade I, with a Cell Classification of 23447 as defined in ASTM D1784. The compound and the finished product shall be orange in color, and shall be approved by the National Sanitation Foundation (NSF) for use with potable water. Material used shall be domestically produced B1azeMaster, CPVC material as provided by Noveon, Inc. (formerly the BFGoodrich Company). System Design: The CPVC sprinkler system shall be hydraulically calculated using a Hazen -Williams C factor of 150, and shall be designed in strict accordance with the Standard for Installation of Sprinkler Systems, NFPA 13 Light Hazard, NFPA 13R, and NFPA 13D as applicable. Dimensions: Harvel B1azeMaster, CPVC fire sprinkler pipe shall be manufactured to Standard Dimension Ratio (SDR) 13.5 dimensions in strict accordance to the requirements of ASTM F442 for physical dimensions and tolerances. Each production run of pipe manufactured in compliance to this standard, shall also meet the test requirements for materials, workmanship, burst pressure, flattening, and extrusion quality defined in ASTM F442. Furthermore, this pipe shall consistently meet or exceed the physical performance test requirements of the appropriate approval/listing agency(s) follow-up procedures established for the product. Marking: Product marking shall meet the requirements of ASTM F 442 and the Listing agency. Marking shall include: the phrase Harvel® B1azeMaster® (or the manufacturers' trademark when privately labeled); the nominal pipe size; the type of material and material designation code; the SDR series and pressure rating for water (SDR 13.5; 175 psi @ 150 ° F); the ASTM designation F 442; the logo of the Listing and Approval agencies (UL, FM, LPCB, etc.); the independent laboratory's seal of approval for potable water usage (NSF-pw); the date and time of manufacture; and the UL assigned control number (2N95). Installation Procedures: All installation procedures such as storage and handling, solvent cement joining techniques, pipe support spacing, bracing, allowance for thermal expansion/contraction, component assembly techniques, and testing etc. shall be in strict accordance with Harvel Plastics, Inc. Installation Instructions and the UL Listing which includes installation limitations. System Components: Fittings used shall be UL Listed CPVC fittings and shall meet or exceed the requirements of ASTM F437 (Sch 80 threaded), ASTM F437 (Sch 80 socket), or ASTM F438 (Sch 40 socket) as applicable, such as those manufactured by Spears Manufacturing Co. or equivalent. Solvent cements used shall be those referenced in Harvel Plastics, Inc. Installation Instructions (such as Spears FS-5 or equivalent), which meet or exceed the requirements of ASTM F656 and ASTM F493, and shall be approved by the National Sanitation Foundation (NSF) for use with potable water. Socket type joints, sizes 3/4" - 3", shall be made up using the One -Step solvent cement joining method. The solvent cement joining method chosen shall be applied in strict accordance with the appropriate procedures as outlined in Harvel Plastics Installation Instructions. Maintenance: Maintenance shall be in accordance with the Standard for Inspection, Testing, and Maintenance of Water Based Sprinkler Systems as defined by NFPA 25. Harvel Plastics, Inc. • 300 Kuebler Rd., Easton, PA 18040-9290 Tel: 610.252.7355 • Fax: 610.253.4436 • www.harvel.com /71 MARVEL® Product Specifications Harvel° Blazemaster° CPVC Fire Sprinkler Pipe Limitations: • CPVC systems are intended for use at a maximum working pressure of 175 psi and ambient temperature of 150 ° F. • CPVC systems shall employ sprinkler heads having a maximum temperature rating of 2257 F or lower, regardless of type. • CPVC products shall be installed in wet pipe systems only. • Air or compressed gas shall never be used for pressure testing. • CPVC sprinkler systems shall be hydrostatically tested for 2 hours at 200 psi, or 50 psi in excess of the maximum working pressure when the maximum working pressure exceeds 150 psi. Lines shall be slowly filled with water and the air bled from the highest and farthest sprinkler heads before test pressure is applied. • Only Teflon® tape or a thread sealant specifically approved for use with Harvel® CPVC Fire Sprinkler Products shall be used in making threaded connections. • Where freeze protection is required, only glycerin based anti -freeze solutions shall be used and installed in accordance with NFPA 13. Do not use glycol base anti -freeze solutions or contaminated glycerin solutions. • CPVC is not approved for use in combustible concealed spaces where sprinklers are required to protect these areas as defined by NFPA 13, unless certain specific application sprinklers are installed per their listing. Refer to Harvel's current Installation Instructions for additional information. Harvel CPVC Fire Sprinkler Pipe Dimensions SDR 13.5 (ASTM F442) Nominal Size (in.) Average O.D. Min. Wall Average I.D. Nom.Wt. Lbs./Ft. 3/4 1.050 0.078 0.874 0.168 1 1.315 0.097 1.101 0.262 1-1/4 1.660 0.123 1.394 0.418 1-1/2 1.900 0.141 1.598 0.548 2 2.375 0.176 2.003 0.859 2-1/2 2.875 0.213 2.423 1.257 3 3.500 0.259 2.950 1.867 Sample Specification: • CPVC sprinkler piping may be installed in a plenum space adjacent to, but not over, openings in the ceiling such as open ventilation grills, and require the use of schedule 80 fittings for use on 11/2" and larger pipe sizes. Refer to Installation Instructions for additional detail. • Minimum protection when installed "concealed" shall consist of: 3/8" gypsum wallboard or drywall, suspended membrane ceiling panels weighing not less than .35 pounds per square foot, or 1/2" plywood soffits. Minimum protection for NFPA 13R and 13D systems may consist of 1/2" plywood. • Harvel, B1azeMaster, pipe is Listed for use in exposed applications with certain limitations. When installed without protection, "exposed" pipe is to be installed beneath smooth, flat, horizontal ceiling construction. Exposed categories include: standard coverage and residential pendent and sidewall sprinkler applications, light hazard extended coverage and residential sprinkler pendent and sidewall sprinkler applications, use in unfinished basements with exposed solid wood joists, light hazard upright quick response sprinklers, and system risers (in 13R & 13D occupancies). Refer to Harvel's installation instructions for specific sprinkler head temperature ratings and spacing requirements. The product must be installed in strict accordance with NFPA 13, 13D, 13R and Harvel's current CPVC Fire Sprinkler Piping Products Installation Instructions (HFS-3). • Harvel CPVC Fire Sprinkler Products must be installed in accordance with Harvel's current installation instructions (HFS-3). Refer to this document for current listing limitations and installation requirements. ASTM STANDARD D1784 MATERIAL CLASSIFICATION EQUIVALENTS: Cell Classification 23447 = CPVC 'I�Te IV Grade I = CPVC 4120 PIPE SIZES SHOWN ARE MANUFACTURED IN STRICT COMPLIANCE WITH ASTM F442 HrA F i.wk iti daan•cd ip WSW 1 All CPVC fire sprinkler pipe shall be manufactured from a 'Type IV, Grade I Chlorinated Polyvinyl Chloride (CPVC) compound with a Cell Classification of 23447 per ASTM D1784. Pipe shall be manufactured in strict compliance with ASTM F442 to SDR 13.5 dimensions, con- sistently meeting the Quality Assurance test requirements of this standard with regard to material, workmanship, burst pressure, flatten- ing, and extrusion quality. All CPVC fire sprinkler pipe shall be Listed by Underwriters Laboratories for wet pipe systems, and shall carry a rated working pressure of 175 psi @ 150 ° F. All CPVC fire sprinkler pipe shall be installed in accordance with Harvel Plastics, Inc. CPVC Fire Sprinkler Piping Products Installation Instructions. National Fire Protection Association (NFPA) Standards 13, 13D, and 13R must be referenced for design and installation requirements in conjunction with the Installation Instructions. All CPVC fire sprinkler pipe shall be manufactured in the USA by an ISO 9001 certified manufacturer and shall be FM and LPCB approved. All CPVC fire sprin- kler pipe shall be packaged immediately after its manufacture to prevent damage and shall be stored indoors after production, at the manufacturing site, until shipped from factory. This pipe shall bear the logo of the listing agencies, and shall carry the National Sanitation Foundation (NSF) seal of approval for potable water applications. All CPVC fire sprinkler pipe shall be Harvel® B1azeMaster® pipe as manufactured by HARVEL® PLASTICS, INC. F■ Harvel Plastics, Inc. • 300 Kuebler Rd., Easton, PA 18040-9290 Tel: 610.252.7355 • Fax: 610.253.4436 • www.harvel.com El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS The information contained in this publication is based on current information and Product design at the time of publication and is subject to change without notification. Our ongoing commitment to product improvement may result in some variation. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability for particular applications or results to be obtained therefrom. For verification of technical data or additional information not contained herein, please contact Spears° Technical Services Department [West Coast: (818) 364-1611—East Coast: (678) 985-1263]. General Information RECOMMENDATIONS FOR INSTALLERS AND USERS: Plastic piping systems should be ENGINEERED, INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS AND PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the installer and/or user prior to installation of a plastic piping system. All Installation and maintenance personnel should be trained in the proper handling and installation requirements and precautions of plastic piping systems. PRIOR TO ASSEMBLY, all piping system components should be inspected for damage or irregularities. Mating components should be checked to assure that tolerances and engagements are compatible. Do not use any components that appear irregular or do not fit properly. Contact the appropriate manufacturer of the component product in question to determine usability. Consult all applicable codes and regulations for compliance prior to installation. Installation must be made in accordance with Spears° Manufacturing Company FlameGuard° CPVC Fire Sprinkler Piping Products Installation Instructions - FG-3 NOTE — Individual or group instruction in correct solvent welding procedures is available by contacting your local distributor or your servicing Spears° Regional Distribution Center. SOLVENT CEMENT CONNECTIONS — Spears° Manufacturing Company recommends the use of Spears® FS-5 One Step solvent cement for joining Spears° products. Use of solvent cementing products not approved for CPVC fire sprinkler systems, or failure to follow installation instructions will automatically void the warranty. THREADED CONNECTION — Spears° Manufacturing Company recommends the use of Spears° BLUE 75TM Thread Sealant. This product has been tested by Spears' and the sealant manufacturer for compatibility with the Spears' CPVC fire sprinkler products. Consult the sprinkler head manufacturer before using this product. WARNING: OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN THE CPVC OR OTHER FITTING COMPONENTS. Care must be taken to avoid over torquing - generally 1 to 2 turns beyond finger tight is all that is required to make up a threaded connection. Factory testing has indicated 10-25 ft. lbs. of torque is adequate to obtain a leak free seal. GASKET SEALED THREAD CONNECTIONS — This type of connection can only be made with Spears' TorqueSafeTM style Gasket Sealed Female Sprinkler Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER. Tape or paste may impair proper sealing and function. Testing has shown that hand tight until snug is all that is needed to seal this special connection. Dimension Reference G = (LAYING LENGTH) Intersection of center lines to bottom of socket/thread; 90' elbows, M = Outside diameter of socket/thread hub; ± 1/16 inch. tees, crosses; ± 1/32 inch. N = Socket bottom to socket bottom; couplings; ± 1/16 inch. H = Intersection of center lines to face of fitting; 90° elbows tees, crosses; ± 1/32 inch. Q = Width of flats; ±1/16 inch. J = Intersection of center lines to bottom of socket/thread; 45' elbows; ± 1/32 inch W = Height of cap; ± 1/16 inch. L = Overall length of fittings; ± 1/16 inch. CPVC FIRE SPRINKLER PIPE SDR 13.5 (ASTM F 442) Part Number Nominal Size Average O.D. Average I.D. Approx. Weight Lbs.IFt. Inches (mm) Inches (mm) Inches (mm) CP-007 3/4 (19.1) 1.050 (26.7) .874 (22.5) .181 CP-010 1 (25.4) 1.315 (33.4) 1.101 (28.2) .280 CP-012 1-1/4 (31.8) 1.660 (42.2) 1.394 (35.6) .418 CP-015 1-1/2 (38.1) 1.900 (48.3) 1.598 (40.7) .550 CP-020 2 (50.8) 2.375 (60.3) 2.003 (50.9) .872 CP-025 2-1/2 (63.5) 2.875 (73.0) 2.423 (61.5) 1.260 CP-030 3 (76.2) 3.500 (88.9) 2.950 (75.0) 1.900 SPEARS® MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS El TEE Socket x Socket x Socket I 1 I M- — - — -I — �► G H L ---A Part Number Size G H L M Approx. Wt. (Lbs.) 4201-007 3/4 9/16 1-1/2 2-31/32 1-5/16 .11 4201-010 1 13116 1-13116 3-5/8 1-5/8 .20 4201-012 1-1/4 15/32 2-3132 4-7/32 2 .29 4201-015 I 1-1/2 1-5132 I 2-9/16 5-3132 2-11/32 .54 4201-020 2 1-13/32 2-15/16 5-7/8 2-7/8 .86 4201-025 2-1/2 1-23/32 3-1/2 7 3-15/32 1.62 4201-030 3 2-1/16 3-15/16 7-7/8 4-3/16 am REDUCING TEE Socket x Socket x Socket M1 m T1 M - — ' - N12 G1 GH — L Part Number Size G G1 G2 H H1 H2 L M M1 Np Approx. V\A. (Lbs.) 4201-102 3/4x3/4x1 3/4 25/32 3/4 1-11/16 1-13/16 1-11/16 3-318 1-5/16 1-21/32 1-5/16 .13 4201-125 1x3/4x3/4 21/32 13116 5/8 1-25/32 1-13/16 1-5/8 3-13132 1-17/32 1-5/16 1-5/16 .15 4201-126 1x33/4x1 314 1-7/8 1-3132 1 1-27/32 2-31/32 1 1-31/32 3-13/16 1 1-23/32 1-23132 1-13/32 .26 4201-131 1x1x3/4 21/32 13116 21/32 1-25/32 1-13/16 1-25132 3-9/16 1-5/8 1-5/16 1-5/8 .16 4201-157 1-1/4x1x3/4 11/16 1-1/32 11/16 1-15/16 2-1/32 1-13116 3-25/32 2-3132 1-13/32 1-23/32 .32 4201-158 1-1/4x1x1 27/32 29/32 25/32 2-1/16 2-1/32 1-29/32 3-15/16 1-31/32 1-5/8 1-5/8 .24 4201-159 1-1/4x1x1-1/4 31/32 31/32 31/32 2-7/32 2-7/32 2-3/32 4-11/32 2-3132 1 2-3132 1-23/32 .35 4201-167 1-1/4x1-1/4x3/4 21/32 1 21/32 1-29132 2 1-29/32 3-13/16 2 1-5/16 2 .22 4201-168 1-1/41-1/41 13116 31/32 13/16 2-1/16 2-3132 2-1/16 4-1/8 1-31/32 1-21/32 2 .24 4201-169 1-1/4x1-1/4x1-1/2 1-1/8 15116 1-1/8 2-3/8 2-11/32 2-3/8 4-3/4 2-3132 2-11/32 2-3/32 .51 4201-201 1-1/2x1-1/4x3/4 11/16 1 1/4 2-1/16 2 1-15/16 4 2-5/16 1-318 2-1/16 .41 4201-202 1-1/2x1-1/4x1 27/32 1-1/32 1 2-7/32 2-5/32 2-1/4 4-15/32 2-5/16 1-11/16 2-1/16 .42 4201-210 1-1/2x1-1/2x3/4 23132 1-1/16 23/32 2-3/32 2-1/32 2-3132 4-3116 2-5116 1-318 2-5116 .37 4201-211 1-1/2x1-1/2x1 13/16 1-3/16 13/16 2-3/16 2-1/4 2-3116 4-3/8 2-11/32 1-23/32 2-11/32 .41 4201-212 1-1/2x1-1/2x1-1/4 1 1-1/8 1 2-3/8 2-11/32 2-3/8 4-13116 2-11/32 2-3/32 2-11/32 .48 4201-213 1-1/2x1-1/2x2 1-5/16 1-1/8 1-5/16 2-11/16 2-21/32 2-11/16 5-3/8 2-11/32 2-27/32 2-11/32 1 .72 MADE IN THE U.S.A. El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS REDUCING TEE (continued) Socket x Socket x Socket f m T NT2 1 I G1 I-D! h � GH -H2-G2 - -L- Part Number Sze G G1 G2 H 1-11 H2 L M M1 MQ Approx. V\A. (Lbs.) 4201-248 2X2x314 11/16 1-13/32 11/16 2-7/32 2-7/16 2-7/32 4-7/16 2-27/32 1-3/8 2-27/32 .52 4201-249 2x20 27/32 1-7/16 27/32 2-11/32 2-9/16 2-11/32 4-23/32 2-7/8 1-3/4 12-7/8 .57 4201-250 2x20-1/4 I 1 1-11/32 1 1 2-17/32 1 2-19/32 2-17/32 r,3/32 2-27/32 2-3/32 2-27/32 .63 4201-251 2x20-1/2 1-7/32 1-13/32 1-7/32 2-11/16 2-25/32 2-11/16 5-3/8 2-27/32 2-11/32 2-27/32 .85 4201-289 2-1/2x2-1/2x1 29/32 25/32 29/32 2-21/32 1-29/32 2-21/32 5-5/16 3-1/2 1-23132 3-1/2 1.03 4201-290 2-1/22-1/2x1-1/4 1-3/32 1-23G2 1-3/32 2-27/32 2-31/32 2-27/32 5-21/32 3-17/32 2-3132 3-17/32 1.13 4201-291 2-1/2x2-1/2x1-1/2 1-3/16 1/2 1-3116 2-15/16 1-7/8 1 2-15/16 5-7/8 3-15/32 2-11/32 3-15132 1.26 4201-292 2-102-102 1-13132 1-5/8 1 1-13/32 3-3/16 1 3-1/8 3-3/16 6-11/32 3-1/2 3-7/8 3-1/2 1.34 4201-335 3x3x1 7/8 1-15/16 7/8 2-3/4 3-1/16 2-3/4 5-15/32 4-3/16 1-23/32 4-3/16 1.26 4201-336* 3x3x1-1/4 1-3/8 1-3/4 1-3/8 3-5/16 3-1/2 3-5/16 6-5/8 4-1/8 2-7/8 4-1/8 1.94 4201-337 3x3x1-1/2 1-5/32 2-1/16 1-5/32 3-1/32 3-7/16 3-1/32 6-3/32 4-3116 2-3/8 4-3/16 1.46 4201-338 3x3x2 1-7/16 1-13/16 1-7/16 3-5/16 3-5/16 1 3-5116 6-19/32 4-3/16 2-7/8 4-3/16 1.69 4201-339 &W-1/2 1-3/4 1-31/32 1 1-3/4 3-5/8 1 3-23/32 1 3-5/8 1 7-1/4 4-3/16 3-17/32 4-3/16 211 Branch Outlet Sized with Bushing TorqueSafeTM SPRINKLER HEAD TEE Gasket Sealed Brass Mn Thread Insert Style G1 f Socket x Socket x Gasket FI PT I H1 1Mth Elastomer Seal - Use NO Thread Sealant f M -- t — G2 L Part Number Size G G1 G2 H 1-11 H2 L M M1 W Approx. Wt. (Lbs.) 4202-101 G 3/4x3/4x1/2 7/16 1-3116 7/16 1-7/16 1-7/16 1-17/32 2-29/32 1-3/8 1-3/8 1-3/8 .22 4202-124 G 1x3/4x1/2 7/16 1-11/32 9/16 1-9/16 1-11/16 1-9/16 3-1/8 1-11/16 1-3/8 1-3/8 .26 4202-130G 1x1x1/2 7/16 1-11/32 7/16 1-9/16 1-11/16 1-9/16 3-1/8 1-23/32 1-3/8 1-23/32 .28 4202-166G 1-1/4x1-1/4x1/2 7/16 1-5/8 7/16 1-11/16 1-15/16 1-11/16 3-3/8 2-1/16 1-3/8 2-1/16 .34 4202-209 G 1-1/2x1-1/2x1/2 1/2 1-13116 1/2 1-7/8 2-3/32 1-7/8 3-3/4 2-11/32 1 1-3/8 1 2-11/32 .41 4202-247 G 2x2x1/2 1/2 2-1/16 1/2 2 2-11/32 2 1 4-1/32 2-27/32 1 1-3/8 1 2-27/32 .54 Not intended to convey or dispense water for human consumption through drinking or cooking SPEARS' MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS r] SM WLER HEAD TEE Brass Thread Insert Style Socket x Socket x Fipt M1 I G1 H1 M G G2 f H— H2 � L � Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. VWt. (Lbs.) 4202-101 3/4x3/4x1/2 7/16 1-5/32 7/16 1-7/16 1-17/32 1-7/16 2-29/32 1-3/8 1-7/32 1-3/8 .27 4202-124 1x3/4x1/2 7/16 1-11/32 9/16 1-9/16 1-11/16 1-9/16 3-1/8 1-11/16 1-3/8 1-3/8 .26 4202-130 1x1x1/2 7/16 1-7/32 7/16 1-9/16 1-25/32 1-9/16 3-1/8 1-3/4 1-3/16 1-3/4 .26 4202-010 1x1x1 11/16 1-3/32 11/16 1-13/16 1-29/32 1-13/16 3-19/32 1-23/32 1-23/32 1-23/32 .37 4202-156 1-1/4x1x1/2 7/16 1-15/32 9/16 1-11/16 2-1/32 1-11/16 3-3/8 2-3/32 1-7/32 1-3/4 .30 4202-166 1-1/4x1-1/4x1/2 7/16 1-1/2 7/16 1-11/16 2-1/16 1-11/16 3-13/32 2-3/32 1-3/16 2-3/32 .32 4202-199 1-1/2x1-1/4x1/2 1/2 1-5/8 9/16 1-7/8 2-3/16 1-13/16 3-11/16 2-5/16 1-7/32 2-1/16 .37 4202-209 1-1/2x1-1/2x1/2 1/2 1-23/32 1/2 1-7/8 2-3/32 1-7/8 3-314 2-5/16 1-17/32 2-5/16 .45 4202-237 2x1-1/2x1/2 1/2 1-7/8 17/32 2 2-7/16 1-29/32 1 3-15/16 1 2-27/32 1 1-7/32 1 2-5/16 .48 4202-247 2x2x1/2 1/2 1-31/32 1/2 2 2-3/8 2 1 4-1/32 1 2-27/32 1 1-17/32 1 2-27/32 .58 Not intended to conveyor dispense water for human consumption through drinking or cooking SMN KLER HEAD TEE Special Reinforced R asti c Thread Style Socket x Socket x SR Fipt M1—I G1 r T jM - -t- - �I — L G H H2 L H1 Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. VWt. (Lbs.) 4202-101SR 3/4x3/4x1/2 19/32 314 19/32 1-19/32 1-7/16 1-19/32 3-7/32 1-13132 1-3116 1-13132 .16 4202-124SR 1x3/4x1/2 7/16 29/32 9/16 1-19/32 1-5/8 1-9/16 3-5/32 1-23132 1-3/16 1-17/32 .19 4202-130SR 1x1x1/2 7/16 29/32 7/16 1-9/16 1-5/8 1-9/16 3-1/8 1-23132 1-3116 1-23132 .20 4202-010SR 1x1x1 21/32 3/4 21/32 1-25/32 1-5/8 1-25/32 3-19/32 1-23132 1-11/16 1-23/32 .26 4202-156SR 1-1/4x1x1/2 15/32 1-5/32 19/32 1-23132 1-7/8 1-23/32 3-13/32 2-3132 1-3116 1-23/32 .26 4202-166SR 1-1/4x1-1/4x1/2 7/16 1-1/8 7/16 1-11/16 1-27/32 1-11/16 3-3/8 2-3/32 1-3/16 2-3/32 .26 4202-168SR 1-1 /4x1 -1 /4x1 27/32 1-1/32 27/32 2-3/32 1-29/32 2-3/32 4-7/32 2-3132 1-11/16 2-3/32 .34 4202-199SR 1-1/2x1-1/4x1/2 9/16 1-9/32 1 17/32 1-15/16 2 1-25132 1 3-23/32 2-11/32 1-3/16 2-3132 .33 4202-209SR I 1-1/2x1-1/2x1/2 1/2 1-1/4 1/2 1-7/8 1-31/32 1-7/8 3-3/4 2-11/32 1-3116 2-11/32 I .35 4202-211SR 1-1/2x1-1/2x1 27/32 1-7/32 27/32 2-7/32 2-1/8 2-7/32 4-15/32 2-11/32 1-23/32 2-11/32 .44 4202-237SR 2x1-1/2x1/2 23132 1-9/16 3/8 2-7/32 2-9/32 1-3/4 3-31/32 2-7/8 1-3116 2-11/32 .45 4202-247SR 2x2x1/2 1/2 31/32 1/2 2 1-11/16 19/32 4 2-7/8 1-3116 2-7/8 .48 4202-287SR 2-1/2>2-1/2x1/2 17/32 1-3/4 17/32 2-9/32 2-1/2 2-9/32 4-19/32 3-1/2 1-7/32 3-1/2 .78 MADE IN THE U.S.A El FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS TORQUESAFETM SPRINKLER HEAD TEE Gasket Sealed Brass Thread Insert Style Socket x Gasket FI PT x Socket V\ith Elastomer Seal - Use NO Thread Sealant �� G1 H1 — 4-- w IM L H L Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. W. (Lbs.) 4203-122G 1x1/2x1 19/32 13/16 1-13/32 1 1-19/32 1-27M 1-3/4 3-11M 1-5/8 I 1-5/8 11-3/8 .25 Not intended to conveyor dispense water for human consumption through drinking or cooking SPRINKLER HEAD TEE Brass Thread Insert Style Socket x Fipt x Socket �N�I G1 1 t H1 M — + - M2 jG2 H H2 L Part Number Size G G1 G2 H H1 H2 L M M1 W Approx. V\h. (Lbs.) 4203-122 1x1/2x1 23/32 3/4 1-1/4 1 1-5/8 1-5/8 1-15/16 3-1/2 1-23/32 1-23/32 1-3/16 .25 Not intended to convey or dispensewater for human consumption through drinking or cooking SPRINKLER HEAD TEE Speci al Rei nforced R anti c Thread Styl e Socket x SR Fi pt x Socket G1 t _ w L Part Number Sze G G1 G2 H H1 H2 I L M M1 W Approx. W. (Lbs.) 4203-122SR 1x1/2xl 27/32 23/32 1-/32 1-23M 1-5/8 1-25/32 3-13/32 1-314 1-3/4 1-3/16 .21 5 SPEARS' WNUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS El STREET TEE Spigot x Socket x Sockets PIPE nv O.D. H1 G1 G2 H H2- L Part Number Sze G G1 G2 H H1 H2 L M1 W Approx. Wt. (Lbs.) 4244-007 314 13/16 27/32 27/32 1-13116 1-7/8 1-7/8 3-5/8 1-13/32 1-13132 .16 4244-010 1 1-5/32 1-1/32 1-1/32 2-1/8 1-29/32 1-29/32 4-3/16 1-3/4 1-3/4 .27 4244-012 1 1-1/4 1 1-1/4 1 1 1 1 1 2-7/16 1 2-9/32 1 2-9/32 1 4-27/32 1 2-3M 2-3f32 .42 4244-015 1-1/2 1-13/16 1-1/8 1-1/8 2-7/8 2-9/16 2-9/16 5-11/32 2-11M 2-11/32 .56 4244-M 2 1-23/32 1-7/16 1-13M 3-1/4 2-15/16 2-15/16 6-5�32 2-7/8 2-7/8 .84 W ELBOW Socket x Socket qr M� Part Number I Size G I H M Approx. Wt. (Lbs.) 420E-007 3/4 9/16 1-1/2 1-5/16 .07 420E-010 I 1 I 314 1-5/8 I 1-5/8 .11 4206-012 I 1-1/4 I 7/8 2-5132 I 2 I .21 4206-015 I 1-1/2 I 1-5/32 2-17/32 I 2-3/8 I .41 4206-M 2 1-13/32 2-29/32 2-7/8 .45 420E.025 2-1/2 1-5/8 3-7/16 3-7/16 1.17 420E-030 3 I 1-29/32 3-23(32 I 4-3(16 I 1.80 SIDE OUTLET ELBOW Socket x Socket x Socket E M I t—' H Part Number Size G I H I M Approx. W. (Lbs.) 4213-007 314 27/32 1-19/32 1-5/16 I .09 4213-010 1 13(16 1-7/8 1-5/8 I .18 MADE IN THE U.S.A El FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS REDUCING 9T ELBOW Socket x Socket H1 G1— G 1 - M1 H M —I Part Number Size G G1 I H H1 M M1 Approx. VWt. (Lbs.) 4206-131 1x3/4 25/32 11/16 1-25/32 1-25M 1-19/32 1-5/16 .11 TorqueSafeTM W SPRINKLER HEAD ELBOW Gasket Sealed Brass Thread Insert Style Socket x Gasket FI PT With Elastomer Seal - Use NO Thread Sealant H1 GI— GLj12 Mi H Part Number I size G G1 I H I H1 I M M1 I Approx. Wt. (Lbs.) 4207-101 G 3/4x1/2 9/16 1-7/32 1-13/32 1-17/32 1-13/32 1-3/8 .19 4207-130G 1x1/2 15/32 1-13/32 1-9/16 1-11/16 1-23(32 1-3/8 .23 4207-166G 1-1/41/2 15/32 1-19/32 1-15/16 1-11/16 2-3(32 1-3/8 .25 Not intended to convey or dispense water for human consumption through drinking or cooking SPRINKLER HEAD 900 ELB01N Brass Thread Insert Style Socket x Fipt H1� G1 G — M1 H I I~ M Part Number I Size G I G1 I H I H1 I M I M1 I Approx. Wt. (Lbs.) 4207-101 I 3/41/2 7/16 1-5/32 I 1-23/32 I 1-17/32 1-13/32 1-17/32 I .25 4207-130 1 x 1 /2 15/32 1-5/8 1-9/16 1-11 /16 1-23/32 1-17/32 .28 4207-131 1x3/4 17M 1-1/4 1-21/32 2 1-23/32 1-3/8 I .25 4207-166 1-1 /4x1 /2 15/32 I 1-17/32 1-11 /16 I 1-15/16 I 2-3(32 11-17/32 I .33 Not intended to conveyor dispense water for human consumption through drinking or cooking 7 SPEARS' WNUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS El SPRINKLER HEAD 900 ELBOW Sped al Rei nforced R asti c Thread Styl e Socket x SR Fipt H1�G1 G M1 IH L I— M,I Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101SR 3/4x1/2 11/32 I 13/16 1-15/32 I 1-1/2 1-13132 1-3/16 .14 4207-130SR 1x1/2 7/16 7/8 1-9/16 1-5/8 1-23/32 1-3/8 .20 4207-131SR 1x3/4 1/2 7/8 1-5/8 1-9/16 1-23/32 1-3/8 .16 4207-166SR 1-1/4x1/2 13/32 1-1/32 1-21/32 1-23/32 2-3/32 1-7/32 .19 W STREET ELBOW Spigot x Socket G1 H1-j G Mi I H I. ►� PIPE O.D. Part Number Sze G G1 H H1 M1 Approx. W. (Lbs.) 4209-007 3/4 I 29132 19132 1-15/16 1-11/16 1-13132 .12 4209-010 1 I 1-9/32 23132 2-13/32 1-27/32 I 1-3/4 .21 4209-012 1-1/4 1-9/16 27/32 2-13/16 2-3/32 2-3/32 .32 4209-015 1-1/2 1-15M 1-3/16 2-27/32 2-9/16 1 2-11/32 .42 4209-020 2 1-23/32 1-3/8 3-7/32 2-15/16 2-27/32 .65 MADE IN THE U.S.A El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 22-1/Z ELBOW Socket x Socket J 1 i I. MCI Part Number Size H I J M Approx. Wt. (Lbs.) 4216-007 3/4 1-3/16 7/32 1-13/32 .09 4216-010 I 1 I 1-3/8 I 9/32 I 1-25/32 I .14 4216-012 1-1/4 I 1-1/2 I 5/16 2-3/32 .20 4216-015 1-1/2 1-7/16 I 13/32 I 1-3/8 .19 4216-020 2 1-7/8 3/8 2-27/32 .43 4216-030 3 2-3/8 1/2 4-5/32 1.00 22-1/Z STREET ELBOW Spigot x Socket 1� H1 M1 H �I f� -►k PIPE O.D. Part Number Size H H1 J J1 M1 Approx. V\A. (Lbs.) 4242-007 3/4 1-1/4 1-1/2 1/4 1/2 1-0/8 .08 4242-010 I 1 1-7/16 I 1-11/32 I 5/16 7/32 1-23r32 .14 4242-012 1-1/4 1-9/16 I 1-25/32 17/32 11/16 2-1/16 .21 4242-015 1-1/2 1-13/32 I 1-23/32 1/2 11/32 I 2-11/32 .28 4242-020 2 1-29/32 2-1/8 7/32 518 2-7/8 .42 4242-025 2-1/2 2-1/8 2-1/4 13M 1/2 3-1/2 .68 4242-030 3 2-13/32 2-13M 9116 17/32 4-5/32 .99 SPEARS' MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS El 45° ELBOW Socket x Socket I H I 1= M;I Part Number Sze H J M Approx. Wt. (Lbs.) 4217-007 314 1-5/16 5/16 1-5/16 .07 4217-010 1 1-13/32 3/8 1-5/8 .11 4217-012 1-1/4 1-5/8 3/8 2-5/32 .21 4217-015 1-1/2 1-27/32 15/32 2-11/32 .32 4217-M 2 2-1/8 21/32 2-7/8 .48 4217-025 2-1/2 2-17/32 3/4 3-1/2 .88 4217-030 3 2-29/32 29/32 45/32 1.17 453 STREET ELBOW Spigot x Socket J� H1 A H� !. ►I PIPE O.D. Part Number Sze H H1 J J1 M1 Approx. V\k. (Lbs.) 4227-010 1 I 1-1/2 1,516 I 1/2 114 1-5/8 .10 4227-012 1-1/4 1-25/32 1-9/16 9/16 11132 1-31/32 .15 4227-015 1-1/2 2-1/32 2-1/8 19/32 25132 2-11/32 .29 4227-020 2 2-5116 1-15116 25M 13/32 2-7/8 .44 MADE IN THE U.S.A 10 El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS CROSS Socket x Socket x Socket x Socket G1, II M L1 H1 Imo► H �L� Part Number Size G G1 H H1 L L1 M Approx. Wt. (Lbs.) 4220-007 3/4 5/8 I 5/8 1-21/32 1-21/32 3-5/16 3-5/16 I 1-13132 .22 4220-010 1 3/4 3/4 1-5/8 1-5/8 3-1/4 3-1/4 1-23132 .20 4220-012 1-1/4 1-1/8 1-1/8 2-3/8 2-3/8 4-3/4 4-3/4 2-3/32 .63 4220-015 1-1/2 1-7/32 1-7/32 2-5/8 2-5/8 5-7/32 5-7/32 2-318 .80 4220-020 2 1-1/2 1-1/2 3 3 6 6 3 1.43 4220-025 2-1/2 1-11/16 1-11/16 3-7/16 3-7/16 6-7/8 6-7/8 3-17/32 216 4220-030 3 2-3/32 2-3132 3-31/32 3-31/32 7-15/16 7-15/16 4-7/16 3.37 REDUCI I G CROSS Socket x Socket x Socket x Socket ��►rM1 H1 I —T— L1 i G1 I H L P8rt Number Size G G1 H H1 L L1 M M1 Approx. W. (Lbs.) 4220-131 1x3/4 23132 518 1-5/8 1-5/8 3-1/4 3-1/4 1-7/8 1-1/2 .31 4220-167 1-1/404 1-1/16 23/32 2-1/16 1-31/32 4-3/32 3-31/32 2-1/16 1-13132 .35 4220-210 1-1/2x3/4 11/16 1-5/32 2-3/32 2-3116 4-3/16 4-11/32 2-3/8 1-13/32 .42 4220-248 204 11/16 1-7/16 2-7/32 2-7/16 4-13/32 4-7/8 2-29/32 1-13/32 .56 4220-289 2-12d 29/32 1-3/4 2-11/16 2-7/8 5-11/32 5-3/4 3-1/2 1-3/4 .98 11 SPEARS° MANUFACTURING CONPAW FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS El COUPLING Socket x Socket L I — M � Part Number Size L M N Approx. W. (Lbs.) 4229-007 I 3/4 2-1/8 1-5/16 I 3/16 I .05 4229-010 I 1 2-3/16 1-5/8 I 332 I .08 4229-012 1-1/4 2-19/32 2 3(32 .13 4229-015 1-1/2 2-7/8 2-11/32 3/32 .22 4229-020 2 3-1/8 2-7/8 1/8 .33 4229-025 2-1/2 3-11/16 3-15132 3/16 .48 4229-030 I 3 4 43/16 1/4 I .89 REDUCER COUPLING Socket x Socket M M1 L Part Number Sze L M M1 N Approx. V\A. (Lbs.) 4229-131 1x3/4 2-318 1-23/32 1-13/32 7/32 .10 4229-167 I 1-1/43/4 2-19/32 I 2-3/32 1-5/8 I 11/32 .17 4229-168 1-1/4x1 2-11/16 2-3/32 1-23/32 5/16 .18 4229-210 1-lrb04 2-13/16 2-11/32 1-13/32 15/32 .19 4229-211 I 1-1/2x1 2-7/8 I 2-11M 1-15/16 I 3/8 .24 4229-212 I 1-1/2x1-1/4 2-13/16 I 2-13/32 2-1/8 I 5/32 .23 4229-248 I Z04 3-3116 I 2-7/8 1-7/16 I 23/32 .32 4229-249 2x1 3-1/8 2-7/8 1-23/32 1/2 .31 4229-250 2x1-1/4 3-3/16 2-7/8 2-1/8 17/32 .33 4229-251 2x1-1/2 3-3/16 2-27/32 2-11/32 9/32 .31 4229-291 2-1/2x1-1/2 3-23/32 3-15/32 2-11/32 21M .51 4229-292 I 2-1/DQ 3-21M I 3-1/2 2-7/8 I 13132 .52 MADE IN THE U.S.A. 12 FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS GROOVED COUPLING ADAPTER Groove x Socket PIPE M1 O.D.;N 1 L Part Number Size L M1 N Approx. W. (Lbs.) 4233-012 1-1/4 3-518 2-3/32 2-11/32 .72 4233-015 I 1-1/2 I 3-3/4 I 2-11M I 2-11M I .83 42331M I 2 I 3-27M I 2-27M I 2-11M I 1.27 4233-025 I 2-1/2 I 4-3/ 16 I 3-15/32 I 2-7/ 16 I 2 02 4233-090 3 4-5/16 4-1/8 1-7/16 2-76 FEMALE ADAPTER Brass Thread Insert Style Socket x Fipt M M1 L 1 N .► �L Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-007 3/4 2 1-13M 1-3/8 5/16 .23 4235-010 I 1 2-3/16 1-3/4 I 1-11/16 11/32 I .25 4235-012 I 1-1/4 2-318 2-3/32 I 2-1/16 11/32 I .36 4235-015 I 1-1/2 2-9/16 2-3/8 I 2-7/16 11/32 I .47 4235-020 2 2-25/32 2-27/32 3-3/16 7/16 1.05 Not intended to convey or dispense water for human consumption through drinking or cooking 13 SPEARS' MWNUFACTURING COMPANY HANGERS AND SEISMIC BRACING Fig. 24 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe** Double Fastener Strap Side Mounted (Cooper B-Line B3183) Size Range: 3/4" (20mm) thru 2" (50mm) CPVC pipe Material: Pre -Galvanized Steel Function: Intended to perform as a hanger to support CPVC piping used in automatic fire sprinkler systems. Can be installed on the top or on the bottom of a beam. Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL) to support fire sprinkler piping. May be installed in wood using fasteners supplied with product, or into minimum 20 gauge (0.912mm) steel using (2) 1/4" x 1" tek type screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Features: Fig. 24 incorporates features which protect the pipe and ease installation. The flared edge design protects the CPVC pipe from �F any rough surface. Easily attaches to the building structure using the two UL Listed hex head self threading screws' furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No pre -drilling of a pilot hole in wood is required. Finish: Pre -Galvanized' Order By: Figure number and pipe size' l.. " Hardened hex head self threading screw is furnished with the 3a-" product and is the minimum fastener size acceptable. "" With reduced spacing, consult factory. (DTOLCC- c &u s LISTED 24-3/4 CPVC 3/4" (20) 25/16" (58.7) 15/32" (27.8) 13/16" (30.2) Max. Hanger Spacing00 51/2 (1.67) Fastener 5/16" Hex (7.9) Approx. 9 (4.1) 24-1 ill (25) 25/8" (66.7) 15/16" (33.3) 13/16" (30.2) 6 (1.83) 5/16" (7.9) 9 (4.1) 24-11/4 11/4" (32) 3" (76.2) 11/2" (38.1) 13/16" (30.2) 61/2 (1.98) 5/16" (7.9) 11 (5.0) 24-11/2 11/2" (40) 31/4" (82.5) 15/8" (42.3) 13/16" (30.2) 7 (2.13) 5/16" (7.9) 12 (5.4) 24-2 2" (50) 311/16" (93.7) 1 127/32" (43.6) 1 13/16" 1 (30.2) 8 1 (2.44) 1 5/16" (7.9) 1 15 (6.8) Fig. 25 - Surge Restrainer Size Range: — One size fits 3/4" (20mm) thru 2" (40mm) pipe. Material: — Pre -Galvanized Steel Function: — Designed to be used in conjunction with Fig. 200 band hangers to restrict the upward movement of piping as it occurs during sprinkler head activation or earthquake type activity. The surge restrainer is easily and efficiently installed by snapping into a locking position on the band hanger. This product is intended to satisfy the requirements as indicated in the National Fire Protection Association NFPA 13, 2010 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain either steel pipe or CPVC plastic Pipe. Approvals: — Underwriters Laboratories Listed only when used with band hanger Fig. 200, in the USA (UL) and Canada (cUL). Finish: Pre -Galvanized Order By: Figure number and band hanger, size from 3/4" (20mm) thru 2" (40mm). Patent #5,344,108 j� LISTED All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. COOPER B-Line Fig. 28 - "Stand -Off" Hanger & Restrainer for CPVC Plastic Pipe & IPS Steel Pipe ** Size Range: — 3/4" (20mm) through 2" (50mm) Material: — Steel, Pre -Galvanized Function: — Designed to be used as a hanger and restrainer for CPVC piping where the "stand-off" design will ease installation by eliminating the need for wood blocking. Features: • Flared edge design protects CPVC pipe from any rough or abrasive surfaces. • Unique twist and lock design holds pipe firmly in place and allows retrofit type of installation. • The "Stand -Off" design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting surface orientation. • Attaches easily to wood structure with two hex head self -threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16" (7.9mm) extension socket eliminating impact tool damage to pipe. • Attaches easily to steel, minimum 18 gauge (1.024mm) with (2) 1/4" x 1 " tek type self drilling tapping screws. • UL Listed as a hanger and a restrainer for fire sprinkler piping. Approvals: — Underwriters Laboratory Listed in the USA (UL) and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fasteners supplied with product, or into minimum 18 gauge steel using (2) 1/4" x 1 " tek type screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satisfies the UL vertical restraint requirement where needed. UL Listed as a hanger and vertical restraint when installed on 3/8" (9 5mm) composite wood material. Use two Fig. 27B Speed Nuts when used as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper installed screw when used as a hanger only. Order by: — Figure number and pipe size. Pat. # 7,455,268, Pat. # 7,832,248 ** With reduced spacing, consult factory. Fig. 27B n (1) Required High 3 Side of Hanger H Application Hanger Application Fig. 27B (2) Required Li Hanger and Restraint Application 28-3/4 Pipe 3/4" Size (20) A 31/32" (77.0) B 2" (50.8) 31/2" C (88.9) Max Hanger Spacingii 51/2 (1.67) Approx. 18 (8.1) 28-1 ill (25) 35/16" (84.1) 23/16" (55.6) 31/2" (88.9) 6 (1.83) 21 (9.5) 28-11/4 11/4" (32) 35/8" (92.1) 23/8" (60.3) 31/2" (88.9) 61/2 (1.98) 23 (10.4) 28-11/2 11/2" (40) 4" (101.6) 21/2" (63.5) 31/2" (88.9) 7 (2.13) 31 (14.0) 28-2 1 2" (50) 1 41/2" (114.3) 1 211/16" (68.3) 1 35/8" (92.1) 1 8 (2.44) 1 34 (15.4) &TOLCC- c LISTED All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. PW COOPER B-Line Fig. 28M - Offset Hanger & Restrainer for CPVC Plastic Pipe and IPS Steel Pipe ** Size Range: 3/4" (20mm) thru 2" (32mm) Material: Steel, Pre -Galvanized Function: Designed to be used as a hanger and restrainer for CPVC piping or steel piping where the "stand-off' design will ease installation by eliminating the need for wood blocking. Features: • Flared edge design protects CPVC pipe from any rough or abrasive surfaces • Unique snap -on design holds pipe firmly in place and allows retrofit type of installation • The "Stand -Off" design eliminates the need for wood block extension • Can be installed on horizontal or vertical piping regardless of mounting surface orientation • Attaches easily to wood structure with two hex head self -threading screws furnished with product • Installs easily using rechargeable electrical driver with 5/15" (7.gmm) extension socket eliminating impact tool damage to pipe • Attaches easily to steel, minimum 18 gauge (1.024mm) with (2) 1/4" x 1" tek type self drilling tapping screws • cULus Listed as a hanger and a restrainer for fire sprinkler piping Installation Note: When installed in wood structural members and threads from the #10 x 1 " screws are exposed, use Fig. 27B speed nut to secure Approvals: Underwriters Laboratory Listed in the USA (UL) and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fasteners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28M satisfies the UL vertical restraint requirements where needed. Order By: Figure number and pipe size Patent #7,744,042 With reduced spacing, consult factory. L ,q a °V Restraint * Required per NFPA 13 for CPVC plastic pipe (DTCLCC- C&US LISTED FRequir 'I (2) Required � Hanger and Restraint Application Fig. 27B (1) Required High Side of Hanger Detail A Hanger Application All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. a E R U a 'a PW COOPER B-Line MISCELLANEOUS MATERIALS CP� POTTER The Symbol of Protection VSR-SG VANE TYPE WATERFLOW FOR CPVC PIPE ALARM SWITCH WITH RETARD AND GLUE -IN UNION Specifications subject to change without notice. Stock Number: 1144460 Optional: Cover Tamper Switch Kit, stock no. 0090148 Replaceable Components: Retard/Switch Assembly, stock no. 1029030 CAUTION Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating switch to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times. General Information The Model VSR-SG is a vane type waterflow switch for use on wet sprinkler systems using CPVC plastic fittings (manufactured by Tyco, Nibco, Victaulic, Ipex, and Spears Manufacturing Company) that use 1 ", 1 '/4", 1 '/2", or 2" pipe sizes. It is equipped with a union to accommodate installation in confined spaces. The VSR-SG contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the switch. The flow condition must exist for a period of time necessary to overcome the selected retard period. Enclosure The VSR-SG switches and retard switch are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch. Installation (see Fig. 1, 3, and 5) These switches may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The switch should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or A CAUTION Do not trim the paddle. Failure to follow these instructions may prevent the switch from operating and will void the warranty. UL, CUL and CSFM Listed, CE Marked Service Pressure: Up to 175 PSI (12,07 BAR) Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) - UL Maximum Surge: 18 FPS (5.5 m/s) Contact Ratings: Two sets of SPDT (Form C) 10.0Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min. at 24VDC Conduit Entrances: Two openings provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: • NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. • Temperature Range: 407 -1207, (4.5°C - 49°C) - UL Service Use: British Standard B59251 Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious iniury or death could result. within 24" (60 cm) of a valve or drain. The unit has a 1" male fitting for gluing into a CPVC plastic tee. NOTE: Do not leave cover off for an extended period of time. Loosen the union nut and separate the 1" male fitting from the VSR-SG. Glue the 1" male fitting into the TEE following the TEE manufacturer's instructions for preparation and gluing of CPVC piping systems. (Note: The 1" male fitting must bottom out on the stop of the TEE for proper operation of the VSR-SG. See Fig. 1.) Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SG to the V male fitting. Select the proper paddle for the pipe size and type of TEE used. See Fig. 3 for instructions on how to change paddle. Verify that the o-ring is properly positioned in its groove. Hand tighten the nut on the union after orienting the switch in the appropriate direction to detect waterflow as shown in Fig. 5 & Fig. 7. The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand. A CAUTION Do not over -tighten the union nut, hand tighten only. Use of a wrench may damage the union nut. PotterElectric Signal Company, LLC • St. Louis, MO • Cust Service: 866-572-3005 • Tech Support: 866-956-0988 /Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG. #5401205 - REV H PAGE 1 OF 4 01/12 VSR-SG VANE TYPE WATERFLOW (DPOTTER FOR CPVC PIPE ALARM SWITCH WITH REARD The Symbol of Protection AND GLUE -IN UNION Testing The frequency of inspection and testing for the Model VSR-SG and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). A method of testing the VSR-SG must be provided. The valve used for testing shall be easily reached and shall produce a minimum flow of 10 GPM to activate the switch. The discharge orifice shall be equal to the smallest sprinkler used in the system. I Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Fig. 1 Glue the 1 " male fitting into the TEE following the TEE manufacturer's instructions for preparation and gluing of CPVC piping systems. Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SG to the V male fitting. 9" (MINIMUM CLEARANCE REQUIRED FOR 7" MALE FITTING INSTALLATION OR MUST BOTTOM OUT REMOVAL OF DEVICE) ON STOP NO BUSHINGS, L INSERTS OR DWG. #1062-1 ADAPTERS ARE PERMITTED Fig. 3 DIRECTION OF WATERFLOW VVV TO DWG. #1063-3 Important: 11 paddles are furnished with each unit to accommodate the various sizes and manufacturers of TEES. The paddles have raised lettering that show the pipe size and the TEE manufacturer they are to be used with. The proper paddle must be used. The paddle must be properly attached (see Fig. 3) and the screw that holds the paddle must be securely tightened. Fig. 2 Break out thin section of cover when wiring both switches from one conduit entrance. 1h ( Fig. 4 Typical Electrical Connections Notes: 1. The Model VSR-SG has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. 2. For supervised circuits, see "Switch Terminal Connections" drawing and warning note (Fig. 6). CONNECTOR NEUTRAL FROM BREAKER NEUTRAL FROM BELL 1 BREAKER JLINE FROM BREAKER BOIL (End Of Line Resistor) NOTE: When connecting to a LIL Listed control panel, use the panel's resistor value for circuit supervision. PRINTED IN USA MFG. 95401205 - REV H PAGE 2 OF 4 01/12 Fig. 6 Switch Terminal Connections Clamping Plate Terminal INGOOINO 00TGOINe An uninsulatcd section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. Do not strip wire beyond 3/8" of length or expose an uninsulated conductor beyond the edge of the terminal block. When using stranded wire, capture all strands under the clamping plate. VSR-SG CPPOTTERVANE TYPE WATERFLOW FOR CPVC PIPE ALARM SWITCH WITH RETARD The Symbol of Protection AND GLUE -IN UNION Fig. 5 Retard Adjustment The delay can be adjusted by rotating the retard adjustment knob from 0 to the max setting (60- 90 seconds). The time delay should be set at the minimum required to prevent false alarms. OPTIONAL COVER TAMPER SWITCH Do not leave cover fffor extended period of ties, RETARD ADJUSTMENT KNOB Flowing water activates switch in orie direction only. i•) MOUNT SO ARROW ON BASE POINTS IN DIRECTION OF WATERFLOW V MALE FITTING ON ALL SIZES U.54A L.OFTHE TEE MAYBE 1", 1 `%a"' 1 x", or 2" Fig. 7 Mounting Dimensions -Orientation PIPE ' PLASTIC PADDLE Fig. 8 GREEN GROUND DWG# 1205-15 PRINTED IN USA MFG. #5401205 - REV H 01/12 PAGE 3 OF 4 VSR-SG @POTTER VANE TYPE WATERFLOW FOR CPVC PIPE ALARM SWITCH WITH RETARD The Symbol of Protection AND GLUE -IN UNION Maintenance Inspect the waterflow switch monthly. If leaks are found, replace the waterflow switch. The VSR-SG waterflow switch should provide years of trouble -free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock #1029030 (see Fig. 9). There is no maintenance required, only periodic testing and inspection. Retard/Switch Assembly Replacement (See Fig. 9) I The Retard/Switch Assembly is field -replaceable without draining the system or removing the waterflow switch from the pipe 1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 2. Disconnect the power source for local bell (if applicable). 3. Identify and remove all wires from the waterflow switch. 4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws. 5. Remove the retard assembly by lifting it straight up over the tripstem. 6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 7. Re -install the (2) original mounting screws. 8. Reconnect all wires. Perform a flow test and place the system back in service. Fig. 9 (2) ORIGINAL MOUNTING REMOVE (2) ORIGINAL MOUNTING BREAK OUTTHIN SECTION OFCOVER SCREWS SCREWS HOLDING RETARD/SWITCH WHEN WIRING BOTH SWITCHES AS TO BASE FROM ONE CONDUIT ENTRANCE. q RETARD/SWITCHASSEMBLY----\ DO NOT REMOVE (2) RETARD HOUSING SCREWS Removal of Waterflow Switch (2) LOCATING (2) LOCATING PI BOSSES IN BASE BASE G# 1190-2 • To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector, then disconnect wiring. • Loosen nuts and seperate unit from the glued -in fittings • Gently lift the unit far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector. • Lift detector clear of pipe. PRINTED IN USA MFG. 95401205 - REV H PAGE 4 OF 4 01/12