FIR2020-0083+Fire_Sprinkler_Plan+9.29.2020_12.02.20_PMwoof screw #18 x 1%"
Hanger No. 19W
Offset Pipe Hanger
r Pipe
Offset Pipe Hanger
wooa �oiap seam or oe�k
x x
J_
ELEVATION
DisreacE a= see1n61E]
Sa pE 09STRiJiC
U-S5 THM /' - 0' (3O1.6mm]
o•
304.fimm 10 1E55 "AN t•-6' (451.2mm]
0•
/•-6'
.s7.2mm ro LE55 THAN 2•-0: 609.bmm
1• (25.4mm
2'-0'
609.6mm 10 LE55 THAN 2'-6' 762.pnm
1' 25.4mm
2'-6'
761.Omm ro LESS THAN X-0' 914.0mm
1' 25.4mm
J'-0-
(914.0mm TO LLSS T1M X-6' 1016.0mm]
3' 763mm]
J'-B•
1016.Omm
TO 1E35 TWW 1'-0' ,1219.2-
3' 76.2m-1
1'-0'
1'219.Omm
TD 1E55 1NAN 1•-6' t37:=
5' 127.Omm]
4•-6•
1371.6mm
TO 1E55 TI/V/ 5•-0' 1524.G m
7' 177.6mm]
s'-o'
ISILOMvn
TO LESS THW V-6' 1676.4mm
7• 177.6mm
'
11,76.4mm
To LESS Tho 6'-0' 1626.6mm
7' 177.Bmm]
6'-0'
11,26.Mun
TO IESS IHW 6'-6' 1961.2mm
9' 226.6mm]
6'-6'
[1981.2-1
TO LESS TAW 7'-0• (2133.6mm]
I1 [279.4mm]
7- 0-
(2133.&m
1 AND GREATER
14[355.6mm]
A C (u-niimm]rn u Tozmm
140FG02
9]2-1Eel 0■►C611119��
Hanger No. 17VV
Pipe Strap
Pipe strap
We Screw#12x1Y.*
f40TG01A
Approved set of plans must be on site at the time of inspection. Failure to provide the approved set may result in a re -inspection fee. System drain(s) required at riser and must drain to the exterior. If riser is above lowest grade, 2nd drain required and signage at riser indicating location. Flow Through systems require signage IAW NFPA
Clothes closets, linen closets and pantries exceeding 24 square feet in area, with the smallest dimension greater the 3' and having wall and ceiling surfaces of gypsum board.
Bathrooms more than 55 square feet in area.
When fuel fired equipment is present on covered decks or porches, at least one quick -response intermediate temperature sprinkler shall be installed above the equipment.
All fuel fired appliances, except attics if above all living areas.
Approved By Fire __DFM175 ", Oa - - -
• GUEST ROOM 1 36SOFT
LIVING
WATERFLOW
INFO
STATIC:
50 PSI
RESIDUAL:
20 PSI
FLOW:
500 GPM
SOURCE: -
RISER DETAIL
011/2" SUPPLY BY OTHERS
0 1 '/ x 1 REDUCER
1" BACKFLOW ASSEMBLY
I, 4) 1" RESIDENTIAL RISER
0 SPARE HEAD BOX
0 8" ELECTRIC BELL
a� N
KITCHEN
T-0 r c
N 1 1
T-6 7'-3
0
PANTR� -�
to
�lCD
Ll
105
2'-3 LAUNDRY
44
12'-0 2'•3 6'-9 �F-0 4
0
HALL +
OPEN TO ABOVE
1 c u 1- - i- - - MUD
7'-0
NIT R PWDR
MAIN FLOOR PLAN
N
1/8" = V-0"
Caution: For areas having
temperature of OOF (-18C) or lower,
an additional batt of insulation
covering the joist and the fire
sprinkler piping should be used. If
this is not done, freeze -ups can
occur in the sprinkler piping.
INSULATION DETAIL
1. CASCADIA FIRE PROTECTION TO DESIGN AND INSTALLA NEW WET FIRE SPRINKLER SYSTEM
BASED ON NFPA#13D - 2016 EDITION AND THE FIRE SPRINKLER MANUFACTURER'S REQUIREMENTS.
DESIGN DENSITY IS .05 GPM WITH TWO FIRE SPRINKLERS FLOWING AND A MAXIMUM SPACING OF 16' x 16'
WITH A MAXIMUM DISTANCE OF 8'-0" FROM WALLS PER MANUFACTURER'S REQUIREMENTS.
2. FIRE SPRINKLERS ARE NOT REQUIRED IN BATHROOMS 55 SQ. FT. OR LESS.
3. FIRE SPRINKLERS ARE NOT REQUIRED IN CLOSETS WHERE NFPA 13D REQUIREMENTS ARE MET.
4. ALL FIRE SPRINKLER PIPE AND FITTINGS SHALL BE LISTED CPVC.
5. BUCKETTESTAND HYDROSTATIC INSPECTION TO BE PERFORMEDAFTER PIPE INSTALLATION.
6. PIPE HANGERS AND SEISMIC BRACING TO BE INSTALLED PER NFPA 13D.
7. AUXILIARY DRAINS TO BE INSTALLED AT LOW POINTS.
8. CASCADIA FIRE PROTECTION IS NOT RESPONSIBLE FOR PAINTING OR WIRING.
9. OWNER IS RESPONSIBLE FOR MAINTAINING TEMPERATURES ABOVE 40 DEGREES TO AVOID FREEZING.
99 ,gip MECJ,
H
1
SF" Divan
I DI
1" CPVC PIPE - SEE INSULATION DETAIL
PROPERTY
FOR HYDI
I
i
I
I
MASTER
BEDROOM
CD C
p, MASTER BATH #q
r
� 1Q2
3 3'p 5'-9 T-6 3'-9
_ rc -
•+
o =�
101
• I
MASTER
CLOSET
UPPER FLOOR PLAN
N
1/8" = 1'-0"
1 SECTION VIEW
% i t r�Hiv
N NTS
O
1 BATH
l
41 SOFT
r
104}4
0 1 I �
GUEST ROOM 2
Driessen Residence
Remote Area: Upper Floor - Hall
CALCULATION DESIGN CRITERIA:
STANDARD NFPA#13D - 2016
OCCUPANCY CLASS Residential
MAX. COVERAGE per HEAD 256 Ft'
DENSITY .05 GPM / Ft' for 2 Sprinklers Ft'
SPRINKLER Tyco Series LFII
ORIFICE 1/2" K= 4.9
WATER FLOW INFORMATION':
STATIC 50 PSI
RESIDUAL 20 PSI
FLOW 500 GPM
AT BASE OF RISER, SYSTEM REQUIRES:
26.02 GPM @ 37.72 PSI
W
R
0
LU
r
a
J
Q
A[ time of Design
FI R2020-0083
RECEIVED
Sep 30 2020
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
overag equired to the following areas:
Casicadia
FIRE PROTECTION
PO BOX 206
PUYALLUP, WA98371
PHONE: (253) 202-3909
WA LICENSE NUMBER #CASCAFP833L2
www.cascadiafirepro.com
r-
O)
N
N
N
CY
tY
W
w
U
U
Z
Z
O
O
w
LL
O
J
�
w_
w_
�
�
O
Lu
Lu
C0
rn
H
co
H
H
Z
=
_
LL
3
z
,U-ten'
to
a
W(O
O
Y
it
Ltd
W
-
-
nI
N
N
J
O
�
�
1
APPROVALS
CITY OF EDMONDS:
OWNER:
ARCHITECT:
GENERAL CONTRACTOR:
OTHER:
REVISIONS
NORTH
SCALE: 1/8" = V-0"
N
0 2 4 8 16
NICETSEAL.
WASHINGTON STATE
CERTIFICATE OF COMPETENCY
FIRE PROTECTION SPRINKLER
SYSTEMS
Ludovico C. Querol
o
1605-0294-C Level
Cascadia Fire Protection, L.L.C.
00
1�
CASCAFP833L2
�
a■
�
C■
ioho
4.1 wwe
Expires
Signature
12131/20
DRIESSEN RESIDENCE
9229 OLYMPIC VIEW DRIVE
EDMONDS, WA98020
PLAN
FIRE PROTECTION PLAN
DRAWN BY. DATE'.
DS 9-28-20
JOB NO. SHEET 1 OF 1
CASCA20-1133 F P-01