Loading...
BLD2021-0215+ENGINEER RESPONSE LETTER+3.4.2021_5.07.22_PM+2077222BURT ENGINEERING March 4, 2021 City of Edmonds Building Division Edmonds, WA 98020 RE: Replace rotted OSB under siding and deck framing 850 Edmonds St Plan Check BLD2021-0215 Thank you for the careful review of the previous permit drawing submittal. 18530 MERIDIAN AVE N. SHORELINE, WA 98133 The scope of work at the Crawford residence includes replacement of sheathing and siding materials, addressing the waterproofness of the structure, and some minor structural repairs to the deck leading to the north side entry. I have addressed your review comments below. Please feel free to call me directly at 206-779- 6856 to avoid further corrections that can be addressed in that manner. Responses are italicized.• 1. Please clarify as to what extent Burt Engineering will be involved for your project. As the engineer of record for the project, I will provide the plans and details for the sheathing and repairs for the deckframing. 2. Indicate on the plans the Shearibraced wall panels. Provide a detail as to how the braced wall panels are to be constructed. The braced panels are replacing the capacity of the existing TI -11 materials. The sheathing is provided by adding 15132 OSB sheathing. We have provided installation details for the assembly keyed to locations on the floor plans. 3. Please clarify on the plans how the supports are to be fastened, for the walkway and deck repair. To include type, size, location, and material of fasteners for your project. We have provided appropriate details for the repairs. 4. It appears that the rotted framing deck wall(s) are to remain as open framing, as demonstrated on the plans or provide a detail as to the sheathing and cladding being used for the deck framing repair. The details provided clarify the sheathed bracing condition. 5. The cross sections show a North and South repair for your deck framing. Please clarify on the plans the North and South areas of this repair. Details are keyed to the plans showing their respective locations. BkBUR T 18530 MERIDIAN AVE N. SHORELINE, WA 98133 ENGINEERING 6. Please also include calculations/details as to the construction of deck framing rot repair. Please provide any bracing requirements details, that will be needed for this repair. The calculations and details are provided, refer to attached documents. 7. Sheet A-2. Please clarify on the plans the bolting at 2 x 12 member. It appears that this may be a through bolt. The PT 2x12 connection is clarified in the details. 8. It appears that there has been details provided for the rot repair for the North and South deck framing repairs only. Please provide/clarify details on the plans, for the support repairs. There are repairs to both the lateral braces, and to the west end of the deck structure. Refer to plans for locations. Sincerely, BURT ENGINEERING PLLC Cornell E. Burt, P.E. President Cc: File