Water Availability CertificateWATER AVAILABILITY
CERTIFICATE
PERMITTING & DEVELOPMENT
ENGINEERING
DIVISION
121 5th Avenue N
P: 425.771.0220
www.edmondswa.aov
ITEMS IN THIS BOX TO BE FILLED IN BY APPLICANT
® Building Permit ❑ Preliminary Plat or PUD
❑ Subdivision ❑ Rezone or Other
Applicant's name: Emerald Place HOA
Proposed Use: Hydrant Flow Test
Location (attach map and legal description if necessary): 400 Walnut St.
Updated on 811412018 Page 1 or2
Permit Number
N/A
Project Name
Emerald Place HOA Hydrant Flow Test
INFORMATION PROVIDED BY WATER AGENCY
1.
N a. Water will be provided by service connection only to an existing 8-inch (size) water
main that is adjacent to the site.
OR
❑ b. Water service will require an improvement to the water system of:
❑ (i). feet of water main to reach the site; and/or
❑ (2). The construction of a distribution system on the site; and/or
❑ (3). Other (describe):
2.
® a. The water system is in conformance with a City approved water comprehensive plan.
OR
❑ b. The water system improvement will require a water comprehensive plan amendment.
(This will cause a delay in permit issuance and approval.)
3.
® a. The proposed project is within the corporate limits of the City, or has been granted Boundary
Review board approval for extension of service outside the City, or is within the City approved
service area of a private water purveyor.
OR
❑ b. Annexation or Boundary Review Board approval will be necessary to provide service.
4.
® a. Water is/or will be available at the rate of flow and duration indicated below at no less than 20 psi
Measured at the nearest fire hydrant 70 feet from the building/property (or as marked on attached map)
Rate of Flow Duration
❑
Less than Soo gpm. (approximately gpm) ❑ Less than one (i) hour
❑
Soo to 999 gpm ❑ One (1) to two (2) hours
❑
1Soo gpm or more N Two (2) hours or more
❑
Flow test of gpm ❑ Other
N
Calculation of 2487 gpm (Commercial building permits require flow test or calculation)
OR
❑ b. Water will system is not capable of providing fire flow.
WATER AGENCY CERTIFICATION
COMMENTS/CONDITIONS: Per model Static Pressure is:L07.6q psi
at i000 cipm, residual pressure is io 2 Psi
at max flow of 2487 gpm, residual pressure is 8g.72 psi
I hereby certify that the above water purveyor information is true. This certification shall be valid for
one year from date of signature.
City of Edmonds Russell Lynch
(Agency Name) Signatory Printed Name
Associate Engineer
(Title) (Signature/Date)
Updated on 811412018 Page 2 of 2