APPROVED BLD BLD2021-0728+Plumbing_Plan+5.26.2021_3.58.45_PM+2219084 (2)PLUMBING FIXTURE SCHEDULE:
FIXTURES IN THIS SCHEDULE OR THEIR APPROVED EQUIVALENT ARE PROVIDED BY THE PLUMBING CONTRACTOR. SUBMIT SHOP DRAWINGS ON EACH OF THESE ITEMS. REFER TO
SPECIFICATIONS FOR FURTHER INFORMATION AND INSTALLATION VERIFY ROUGH -IN REQUIREMENTS. REQUIREMENTS WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
Q
INSTALL PER MANUFACTURER'S RECOMMENDATIONS. REFER TO THE ARCHITECTURAL DRAWINGS FOR THE PLUMBING FIXTURE MOUNTING HEIGHTS.
DCV
HD
SK
TMV
TIP
WCO
WHA
SECURE PIPE HANGER
TO STRUCTURE (TYP)
THREADED STEEL
ROD WITH NUT AND
WASHER BOTH SIDES
(TYP).
CLEVIS HANGER,
SHOWN FOR CLARITY.
SIZE HANGER FOR
COLD PIPE OUTSIDE
DIAMETER PLUS
INSULATION
THICKNESS. DO NOT
PENETRATE
INSULATION WITH
HANGER.
PROVIDE A SECTION
OF HIGH DENSITY
INSULATION OR
STYROFOAM BILLETS
AT EACH HANGER OF
COLD INSULATED
PIPE.
PROVIDE SHORT
INSULATION SHIELD
FOR LAPPING
INSULATION JACKET
OVER HIGH DENSITY
INSULATION OR
STYROFOAM BILLETS.
MAINTAIN VAPOR
BARRIER
DUAL CHECK VALVE WITH ATMOSPHERIC PORT: WATTS # SD-3, MEETING ASSE 1022 AND NSF 18,316 STAINLESS STEEL BODY, 3/8" INLET AND OUTLET, ATMOSPHERIC PORT,
AND WYE PATTERN STRAINER. PROVIDE 3/4" INDIRECT DRAIN FROM ATMOSPHERIC PORT AND DISCHARGE TO DRAIN WITH AIR GAP.
HUB DRAIN: PROVIDE A P-TRAP BELOW FINISHED FLOOR AND STUB THE BELL END OF A CAST IRON PIPE 4" ABOVE FINISHED FLOOR. SIZE AS SHOWN ON FLOOR PLAN(S).
SINK (ADA ACCESSIBLE): ELKAY # GECR2521R4, 25" X 21-1/4" X 5-3/8" DEEP, SINGLE COMPARTMENT, SELF -RIMMING, 20 GAUGE TYPE 304 STAINLESS STEEL, FIXTURE WITH 4
HOLE DRILLING FAUCET LEDGE. SET IN BED OF PUTTY.
FAUCET- KOHLER "FORTE" FAUCET # K-10445, 8" SPREAD LEAD FREE FAUCET WITH REVERSIBLE QUARTER TURN WASHERLESS CERAMIC DISC VALVES, HIGH -ARC SWING
SPOUT WITH 7-3/4" REACH, MATCHING FINISH SIDE SPRAY AND NIAGARA N3205N-PC LOW FLOW 0.5GPM NEEDLE SPRAY OUTLET.
TRIM- MCGUIRE # LF2165CC LEAD FREE BRASS WHEEL HANDLE ANGLE STOP VALVES WITH RISERS AND ESCUTCHEONS, MCGUIRE # 151M CUP STRAINER WITH 1-1/2" 17
GAUGE TAILPIECE, MCGUIRE # B8912CF 1-1/2" 17 GAUGE CAST CHROME PLATED BRASS ADJUSTABLE P-TRAP WITH BRASS CLEANOUT AND ESCUTCHEON, PLUMBEREX
"PRO -EXTREME" # X-4222 INSULATION KIT FOR WATER AND WASTE PIPES.
THERMOSTATIC MIXING VALVE: LEONARD # 170-LF, SOLID LEAD FREE BRASS BODY, THERMOSTATIC WAX ELEMENT, CORROSION RESISTANT INTERNAL PARTS, AND
INTEGRAL CHECKS, ASSE 1070 COMPLIANT, CAPABLE OF 2.3 GPM WITH A 10 PSI DIFFERENTIAL AND A MINIMUM FLOW RATE OF 0.25 GPM. SET TEMPERATURE TO 11 OF FOR
DUEL TEMPERATURE LAVATORIES AND HAND SINKS, 10OF FOR SINGLE TEMPERATURE LAVATORIES AND HAND SINKS AND 120F FOR SINKS. MOUNT BELOW THE PLUMBING
FIXTURE WHERE INDICATED ON PLAN(S).
TRAP PRIMER: PRECISION PLUMBING PRODUCTS # PROI-500 "PRIME PRO", CORROSION RESISTANT BRASS BODY, "O" RING SEALS, 1/2" INLET AND OUTLET, AND INTEGRAL
VACUUM BREAKER. INSTALL THE VALVE AT A MINIMUM OF 12" ABOVE FINISHED FLOOR. PROVIDE WITH DISTRIBUTION # DU-2 FOR TWO, # DU-3 FOR THREE, OR # DU-4 FOR
FOUR DRAIN CONNECTIONS.
WALL CLEANOUT: JAY R. SMITH # 4530S, CAST IRON CLEANOUT TEE, COUNTER SUNK PLUG, STAINLESS STEEL ROUND COVER AND SCREW, AND IRON PLUG WITH GASKET
SEAL. REFER TO SPECIFICATIONS FOR INSTALLATION.
WATER HAMMER ARRESTER: PRECISION PLUMBING PRODUCTS, HARD DRAWN COPPER BODY WITH WROUGHT COPPER FITTINGS, PISTON TYPE WITH LUBRICATED EPDM "0"
RING SEALS, MEETING ASSE 1010 OR PDI WH-201. PROVIDE PDI SIZES "A" THROUGH "F" AS SHOWN ON PLANS. PROVIDE SIZE "A" UNLESS SHOWN OTHERWISE ON THE PLANS.
INSULATED PIPE HANGER DETAIL
NO SCALE
REFER TO SPECIFICATIONS FOR INSULATION TYPES,
INSULATION THICKNESSES, HANGER TYPES, HANGER ROD
CONNECTIONS TO STRUCTURE AND HANGER SPACING.
COLD WATER SUPPLY
CONCEALED IN
PARTITION WHERE
SHOWN ON PLAN
PROVIDE BACKFLOW
PREVENTER WITH
STRAINER IF/AS
INDICATED ON FLOOR
PLANS OR REQUIRED
BY LOCAL
AUTHORITIES
PROVIDE DUAL OUTLET
ANGLE STOP VALVE ON
NEARBY SINK WITH ONE
BRANCH TO SINK AND
OTHER TO BEVERAGE
DISPENSER
CLEVIS HANGER,
SHOWN FOR CLARITY.
SIZE HANGER FOR
HOT PIPE OUTSIDE
DIAMETER.
CUT INSULATION TO
FIT AROUND HANGER.
SEALEXPOSED
INSULATION ENDS
WITH JOINT SEALANT
A FOUR FOOT
)F SOFT
TUBING, COILED
KINKS, FROM
I UNIT WATER
FH ADAPTERS
RED, SIZE PER
;TURER'S
NDATIONS
E DISPENSER
TEA, SODA OR
3 SHOWN ON
_E IN
;TOP BEHIND
E DISPENSER
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS
AND EQUIPMENT MANUFACTURER'S INSTALLATION INSTRUCTIONS. AIR GAP ON
INTERNAL WATER FILL DEVICE PROVIDES BACKFLOW PREVENTION. VERIFY IF LOCAL
AUTHORITIES REQUIRE SUPPLEMENTAL PROTECTION.
BEVERAGE DISPENSER WATER
NO SCALE
SINK OR LAVATORY AS
SHOWN ON PLANS
1/2" COLD WATER TO FAUCET(S) AS
SHOWN ON PLANS
1/2" HOT WATER TO FAUCET(S) AS
SHOWN ON PLANS
AUTOMATIC VACUUM
RELIEF VALVE
PROVIDE 12"WIDE x 12"DEEP HEAT
TRAP AT INLET AND OUTLET
(TYPICAL)
PROVIDE DIELECTRIC PIPE UNION
AT TANK CONNECTION FOR
CONNECTION OF DISSIMILAR
METALS (TYPICAL)
INSTALL ASME TEMPERATURE AND
PRESSURE RELIEF VALVE
FURNISHED WITH WATER HEATER
ELECTRIC WATER HEATER,
REFER TO SPECIFICATIONS
AND SCHEDULE
DRAIN VALVE BY WATER
HEATER MANUFACTURER
n
3/4" COLD
WATER
DOWN IN
PARTITION
VENT PIPE
TRAP PRIMER
SHUTOFF VALVE
(TYPICAL)
CHECK VALVE
(TYPICAL)
HARD COPPER DISCHARGE
LINES TO END OVER FUNNEL
DRAIN. AIM DOWN WITH 6"
AIR GAP
2" WASTE PIPE
2" CAST IRON P-TRAP
WITH 2"x3" INCREASER
MOUNT ABOVE FLOOR
2" WASTE PIPE
REFER TO SPECIFICATIONS, SCHEDULES AND NOTES FOR MORE INFORMATION. PIPING
ARRANGEMENT SHOWN IS SCHEMATIC. VERIFY ALL CONNECTION SIZES AND LOCATIONS PER
MANUFACTURERS REQUIREMENTS. ADJUST TO SUIT FIELD CONDITIONS. REFER TO FLOOR PLANS
FOR PIPE SIZES. PROVIDE SEISMIC STRAP OR BRACING IF/AS REQUIRED BY LOCAL AUTHORITIES.
POWER WIRING AND DISCONNECT SWITCH ARE SPECIFIED BY ELECTRICAL.
2 POINT -OF -USE WATER HEATER
NO SCALE
AUTOMATIC TRAP PRIMER
VALVE WITH INTEGRAL
AIR GAP. INSTALL TRAP
PRIMER MINIMUM 12"
ABOVE FLOOR FOR
EVERY 20' OF DISCHARGE
PIPE.
IF TRAP PRIMER IS
INSTALLED IN PARTITION,
PROVIDE ACCESS DOOR
PER SPECIFICATIONS.
PROVIDE DISTRIBUTION
UNIT(S) WHERE MORE
THAN ONE TRAP IS
SERVED BY ONE TRAP
PRIMER VALVE.
PROVIDE FLOOR DRAIN
BODY OR P-TRAP WITH
THREADED TRAP PRIMER
CONNECTION. PROVIDE
SWEAT TO THREADED
ADAPTER. BRAZE JOINT
BELOW FLOOR SLAB ON
GRADE.
CONNECT 1/2" PIPE (WITHOUT
SHUT-OFF VALVE IN BRANCH) TO
TRAP PRIMER INLINE PRIOR TO
FIXTURE SERVED (DO NOT INSTALL
VALVE ON A BYPASS).
INSTALL TRAP PRIMER LINE(S)
DOWNSTREAM OF TRAP PRIMER OR
DISTRIBUTION UNIT USING 1/2" SOFT
COPPER TUBING. INSTALL WITHOUT
KINKS, AND SLOPE CONTINUOUSLY
TOWARDS FLOOR DRAIN. CONCEAL
PIPE(S) IN PARTITION OR CHASE IN
FINISHED AREAS. TRAP PRIMER AND
PIPES MAY BE INSTALLED EXPOSED IN
UNFINISHED, NON-PUBLIC AREAS.
IF PIPE IS BELOW FLOOR SLAB ON
GRADE, PROVIDE 1/2"
ELASTOMERIC INSULATION FROM
PRIMER CONNECTION TO 1"
ABOVE FLOOR SLAB.
PROVIDE TRAP PRIMERS WHERE SHOWN ON FLOOR PLANS, AND WHERE REQUIRED
BY LOCAL AUTHORITIES. PIPING ARRANGEMENT SHOWN IS SCHEMATIC: ADJUST
TO SUIT FIELD CONDITIONS. REFER TO SPECIFICATIONS AND PLUMBING FIXTURE
SCHEDULE FOR MORE INFORMATION. INSTALL TRAP PRIMER VALVE AND
DISTRIBUTION UNIT PER MANUFACTURER'S RECOMMENDATIONS.
TRAP PRIMER IN/OUT WALL
NO SCALE
PLUMBING SYMBOLS
THIS IS A MASTER LEGEND AND NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED. V2.01
STANDARD MOUNTING HEIGHTS
PIPING SYMBOLS
PIPING LINETYPES
REFER TO THE ARCHITECTURAL DRAWINGS FOR PLUMBING FIXTURE MOUNTING HEIGHTS.
® 0 FLOOR SINK (FS), SIZE & TYPE
---CW--- DOMESTIC COLD WATER (CW)
UNO, INSTALL PLUMBING FIXTURES WITH THE MOUNTING HEIGHTS AS LISTED BELOW WITH
FINAL APPROVAL BY THE ARCHITECT.
EM ® FLOOR DRAIN (FD), SIZE & TYPE
---SCW--- SOFTENED COLD WATER (SCW)
LAVATORY OR SINK
(0) ROOF DRAIN (RD), SIZE & TYPE
----HW---- DOMESTIC HOT WATER (HW)
STANDARD HEIGHT 31" FLOOR TO RIM
ADA ACCESSIBLE 34" FLOOR TO RIM
IFI BALL VALVE
-----HWR----- DOMESTIC HOT WATER RECIRC. (HWR)
CHILD HEIGHT 24" FLOOR TO RIM
CONTROL VALVE
140° 140° DOMESTIC HOT WATER (140°)
URINAL
STANDARD HEIGHT 24" FLOOR TO RIM
4 SHUTOFF VALVE
T TRAP PRIMER LINE (T)
ADA ACCESSIBLE 17" FLOOR TO RIM
CHILD HEIGHT 14" FLOOR TO RIM
CHECK VALVE
S SOIL PIPING - ABOVE FLOOR (S)
WATER CLOSET
vt BALANCING VALVE WITH PRESSURE PORTS
-S - SOIL PIPING - BELOW FLOOR (S)
STANDARD HEIGHT 15" FLOOR TO RIM
ADA ACCESSIBLE 17" TO 19" FLOOR TO TOP OF SEAT
f WATER METER
W WASTE PIPING - ABOVE FLOOR (W)
CHILD HEIGHT 10" FLOOR TO RIM
STRAINER
__W__ WASTE PIPING - BELOW FLOOR (W)
WATER COOLER OR DRINKING FOUNTAIN
STANDARD HEIGHT 41" FLOOR TO SPOUT
STRAINER WITH BLOWOFF
GW GREASE WASTE - ABOVE FLOOR (GW)
ADA ACCESSIBLE 36" FLOOR TO SPOUT
CHILD HEIGHT 30" FLOOR TO SPOUT
RELIEF/SAFETY VALVE
- - -GW- - - GREASE WASTE - BELOW FLOOR (GW)
SHOWER VALVES
4 SOLENOID VALVE
CGWV COMBINATION GREASE WASTE AND VENT (CGWV)
STANDARD HEIGHT - MEN 48" FLOOR TO CENTERLINE
Y
STANDARD HEIGHT - WOMEN 42" FLOOR TO CENTERLINE
PRESSURE REDUCING VALVE
-CWV- COMBINATION WASTE AND VENT (CWV)
ADA ACCESSIBLE 38" MIN TO 48" MAX FLOOR TO CENTERLINE
�AGAS PRESSURE REGULATOR
ST STORM DRAIN - ABOVE FLOOR (ST)
SHOWER HEADS
MEN 6'-6" FLOOR TO CENTERLINE
THERMOSTATIC MIXING VALVE
- - -ST- - - STORM DRAIN - BELOW FLOOR (ST)
WOMEN 6'-0" FLOOR TO CENTERLINE
PA
PIPE ANCHOR
OST OVERFLOW STORM DRAIN - ABOVE FLOOR (OST)
TUB VALVES
EJ
STANDARD HEIGHT 32" FLOOR TO CENTERLINE
EXPANSION JOINT
- -VBG- - VENT BELOW GRADE (VBG)
ADA ACCESSIBLE CENTER BETWEEN GRAB BAR AND TUB RIM
BACKFLOW PREVENTER
- -VBF- - VENT BELOW FLOOR (VBF)
CLINIC SERVICE SINKS 30" FLOOR TO RIM
PRESSURE GAUGE
ID INDIRECT DRAIN (ID)
SURGEON'S SCRUB -UP SINKS 35" FLOOR TO FRONT RIM
THERMOMETER
CDH CONDENSATE DRAIN -HIGH EFFICIENCY RTU (CDH)
ICE MAKER OUTLET BOXES 24" FLOOR TO CENTER OF BOX
10 UNION
CD CONDENSATE DRAIN (CD)
WASHING MACHINE OUTLET BOXES 42" FLOOR TO RIM
FLANGE CONNECTION
-ACD- AUXILIARY CONDENSATE DRAIN (ACD)
JANITOR'S SINK FAUCET FITTINGS 42" FLOOR TO CENTERLINE
HOSE BIBB (HB)
SPD SUMP OR SEWAGE PUMP DISCHARGE (SPD)
HOSE BIBBS 36" AFF TO CENTERLINE
IF NONFREEZE WALL HYDRANT (NW)
G NATURAL GAS (G)
NON FREEZE WALL HYDRANTS 18" AFG TO CENTERLINE
n
n MANUAL / AUTOMATIC AIR VENT OR VACUUM RELIEF VALVE
T PRESSURE / VACUUM SWITCH
- - -G- - - NATURAL GAS ON ROOF (G)
MPG MEDIUM PRESSURE NATURAL GAS (MPG)
USE THE DEFAULT MOUNTING HEIGHTS SHOWN ABOVE UNLESS NOTED OTHERWISE IN THE
SPECIFICATIONS OR ELSEWHERE. MOUNTING HEIGHTS LISTED ARE ABOVE FINISHED
FLOOR (AFF) OR ABOVE FINISHED GRADE (AFG). ALL DEVICES SHALL BE INSTALLED IN
CLEANOUT
- -MPG- - MEDIUM PRESSURE NATURAL GAS ON ROOF (MPG)
COMPLIANCE WITH CURRENT ADA AND LOCAL REQUIREMENTS.
CAP
NPW NON POTABLE WATER (NPW)
ANNOTATION
0.1 WALL CLEANOUT (WCO)
LPG LIQUIFIED PETROLEUM GAS (LPG)
OPLUMBING PLAN NOTE CALLOUTO
FLOOR CLEANOUT (FCO)
WS WATER SERVICE (WS)
�O EXTERIOR CLEANOUT (ECO)
FP FIRE PROTECTION (FP)
PLUMBING EQUIPMENT DESIGNATION. (CONTRACTOR FURNISHED AND
1O INSTALLED). REFER TO PLUMBING FIXTURE OR EQUIPMENT
ELBOW UP
PD CONDENSATE PUMP DISCHARGE (PD)
SCHEDULES
� ELBOW DOWN
V VENT PIPING (V)
EQUIPMENT DESIGNATION (OWNER FURNISHED, CONTRACTOR
TEE UP
INSTALLED)
TEE DOWN
CU MECHANICAL EQUIPMENT DESIGNATION (CONTRACTOR PROVIDED
ELBOW UP WITH SHUT-OFF VALVE (SOV)
1 UNO)
� ELBOW DOWN WITH SHUT-OFF VALVE (SOV)
CONNECTION POINT OF NEW WORK TO EXISTING
TEE UP WITH SHUT-OFF VALVE (SOV)
TEE DOWN WITH SHUT-OFF VALVE (SOV)
1 DETAIL REFERENCE UPPER NUMBER INDICATES DETAIL NUMBER
* 4
P1 LOWER NUMBER INDICATES SHEET NUMBER
WATER HAMMER ARRESTER (WHA)
WITH PDI SIZES, (A, B, C, D, & E)
1 SECTION CUT DESIGNATION
RECIRCULATION PUMP
P1
00 P-TRAP
GAS COCK
TRAP PRIMER
ABBREVIATIONS
ADA AMERICANS WITH
MAU MAKE-UP AIR UNIT
DISABILITIES ACT
MAX MAXIMUM
AFF ABOVE FINISHED FLOOR
MBH 1000 BTU PER HOUR
TRAP PRIMER WITH DISTRIBUTION UNIT
AFG ABOVE FINISHED GRADE
MH MANHOLE
AHU AIR HANDLING UNIT
MIN MINIMUM
AP ACCESS PANEL
N/C NORMALLY CLOSED
BAS BUILDING AUTOMATION SYSTEM
N/O NORMALLY OPEN
BFF BELOW FINISHED FLOOR
NIC NOT IN CONTRACT
BFG BELOW FINISHED GRADE
ORD OVERFLOW ROOF DRAIN
BOP BOTTOM OF PIPE
PDI PLUMBING DRAINAGE INSTITUTE
BOS BOTTOM OF STRUCTURE
PH/O PHASE
BTU BRITISH THERMAL UNIT
PRV PRESSURE REDUCING VALVE
CID CONDENSATE PUMP
PVC POLYVINYL CHLORIDE
CPVC CHLORINATED POLYVINYL
RCP REINFORCED CONCRETE PIPE
CHLORIDE
RD ROOF DRAIN
Cu COPPER
RPM REVOLUTIONS PER MINUTE
DI DUCTILE IRON
RTU ROOFTOP UNIT
DIN DOWN
SF SQUARE FEET
DFU DRAINAGE FIXTURE UNIT
SP SUMP PUMP
DS DOWNSPOUT
SS STAINLESS STEEL, SANITARY
(E) EXISTING
SEWER, SOIL STACK
EMS ENERGY MANAGEMENT SYSTEM
TDH TOTAL DYNAMIC HEAD
ETR EXISTING TO REMAIN
TFA TO FLOOR ABOVE
EWC ELECTRIC WATER COOLER
TFB TO FLOOR BELOW
LINETYPE LEGEND
FD FLOOR DRAIN
TYP TYPICAL
FFA FROM FLOOR ABOVE
UL UNDERWRITERS
FFB FROM FLOOR BELOW
LABORATORIES, INC.
THROUGHOUT THE DRAWINGS DIFFERENT LINE -TYPES ARE USED IN COMBINATION WITH
FF FINISHED FLOOR
LINO UNLESS NOTED OTHERWISE
THE SYMBOLS TO INDICATE THE STATUS OF ITEMS AS EXISTING, TO BE DEMOLISHED, TO
FL FLOW LINE
UPS UNINTERRUPTIBLE POWER
BE INCLUDED AS PART OF NEW WORK AND/OR ITEMS WHICH ARE ANTICIPATED TO BE
FLA FULL LOAD AMPS
SUPPLY
PROVIDED IN THE FUTURE. THE STATUS OF ITEMS USING THESE LINETYPES ARE RELATIVE
FLR FLOOR
VCP VITRIFIED CLAY PIPE
TO THE VIEW IN WHICH THEY APPEAR. PHASING SHOWN IN DRAWINGS IS NOT INTENDED
GPM GALLONS PER MINUTE
VFD VARIABLE FREQUENCY DRIVE
TO FULLY DESCRIBE ALL NECESSARY CONSTRUCTION PHASING, WHICH IS DETERMINED BY
HD HEAD, HUB DRAIN
VS VENT STACK
THE CONTRACTOR AS PART OF THEIR RESPONSIBILITIES. ANY SUCH PHASES DESCRIBED
HZ HERTZ
VTR VENT THROUGH ROOF
IN THE CONSTRUCTION DOCUMENTS ARE GENERAL AND ONLY INTENDED TO INDICATE A
IE INVERT ELEVATION
W/ WITH
BROAD ORDER FOR THE SAKE OF DESCRIBING THE PROJECT. THE FOLLOWING LINETYPES
IN WC INCHES OF WATER COLUMN
W/O WITHOUT
MAY BE USED ON ANY DEVICE, EQUIPMENT, NOTE, LINE, SHAPE, ETC.
JB JUNCTION BOX
WC WATER COLUMN
J-BOX JUNCTION BOX
WS WASTE STACK
EXISTING
NEW
KW KILOWATT
WSFU WATER SUPPLY FIXTURE UNIT
WVS WASTE VENT STACK
DEMOLISH ------------------------
FUTURE
ALL WORK SUBJECT
TO FIELD
INSPECTION FOR
CODE COMPLIANCE
FIXTURE
BRANCH
CONNECTION
SCHEDULE
FIXTURE
COLD WATER
HOT WATER
WASTE
VENT
HUB DRAIN
--
--
2"
2"
SINK
1/2"
1/2"
2"
2"
NOTE:
PIPE SIZES SHOWN ARE MINIMUM.
ELECTRIC STORAGE
WATER
HEATER
SCHEDULE
MARK
MANUFACTURER/
MODEL#
AREA
SERVED
TANK SIZE
(GALLONS)
ELECTRICAL DATA
RECOVERY
(GPH)
NOTES
VOLTS
PHASE
KW
EWH
CHRONOMITECMT-2.5
BREAKROOMSINK
2.5
120
1
1.44
9
A
NOTES:
A 68° TEMPERATURE RISE WITH 110°F OPERATING TEMPERATURE.
APPROVED
PLANS MUST BE
GENERAL NOTES
1. PROVIDE A CONSTRUCTION RECORD SET OF "AS -BUILT" DOCUMENTS TO THE
ARCHITECT REFLECTING ANY VARIANCES OF INSTALLED PIPING LOCATIONS OR
EQUIPMENT CONTRARY TO THE CONSTRUCTION DOCUMENTS, REFER TO
SPECIFICATIONS.
2. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF
THE WORK. PRIOR TO SUBMITTING BID, VISIT THE JOB SITE TO OBSERVE THE
EXISTING CONDITIONS OF THE PROJECT. REVIEW THE GENERAL NOTES,
SPECIFICATIONS AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT BE
SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION
DOCUMENTS. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPANCIES PRIOR
TO SUBMISSION OF BID.
3. PROVIDE TO THE ARCHITECT A COPY OF INSPECTION REPORTS AND APPROVAL
CERTIFICATES FROM LOCAL AND STATE INSPECTIONS, REFER TO
SPECIFICATIONS.
4. INSTALLATION SHALL COMPLY WITH LEGALLY CONSTITUTED CODES AND THE
REQUIREMENTS OF AUTHORITIES HAVING.
5. PLANS AND SPECIFICATIONS GOVERN WHERE THEY EXCEED CODE
REQUIREMENTS.
6. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION AND MOUNTING
HEIGHTS OF PLUMBING FIXTURES.
7. DO NOT SCALE FLOOR PLANS FOR EXACT HORIZONTAL LOCATION OF PIPE
ROUTING.
8. INSTALL CONCEALED PIPING TIGHT TO THE STRUCTURE AND AS HIGH AS
POSSIBLE. INSTALL EXPOSED PIPING TIGHT TO THE STRUCTURE, WALL OR
CEILING AND AS HIGH AS POSSIBLE. COORDINATE WITH OTHER TRADES TO
AVOID CONFLICTS.
9. VALVES SHALL BE LINE SIZE UNLESS OTHERWISE NOTED.
10. PIPING IN FINISHED AREAS SHALL BE ROUTED CONCEALED; EXPOSED PIPING,
WHERE NECESSARY, SHALL BE ROUTED AS HIGH AS POSSIBLE AND TIGHT TO
WALLS.
11. INSTALL NO PLASTIC PIPE IN THE CEILING RETURN AIR PLENUM.
12. COORDINATE ALL WORK WITH OTHER TRADES AND CONTRACTORS.
13. COORDINATE PIPING INSTALLATION WITH STRUCTURAL GRADE BEAMS,
FOOTINGS, COLUMN PIERS, ETC. SLEEVE PIPING THROUGH GRADE BEAMS,
FOOTING, ETC. WHERE REQUIRED AND AS NOTED ON PLANS. COORDINATE
SLEEVE INSTALLATIONS WITH THE ARCHITECT, STRUCTURAL ENGINEER,
STRUCTURAL CONTRACTOR AND GENERAL CONTRACTOR BEFORE CONCRETE IS
INSTALLED.
14. CLEAN FAUCET AERATORS AND PIPE STRAINERS PRIOR TO TURNING BUILDING
OVER TO THE OWNER.
15. PROVIDE TRAP PRIMERS WHERE REQUIRED BY LOCAL AUTHORITIES.
16. COORDINATE PIPE ROUTING AWAY FROM ELECTRICAL PANELS. DO NOT INSTALL
PIPING OVER ELECTRICAL PANELS.
17. PAINT ALL EXPOSED GAS AND WATER PIPING USING RUST INHIBITOR PAINT.
PAINT AND COLOR SHALL BE COORDINATED WITH THE ARCHITECT AND / OR
OWNER.
18. COORDINATE ALL ROOF PENETRATIONS WITH OTHER TRADES. MAINTAIN 10,
MINIMUM CLEARANCE FROM ALL AIR INTAKES. MAINTAIN 2' CLEARANCE FROM
ALL OTHER EQUIPMENT.
19. PROVIDE TRANSITION ADAPTER COUPLINGS FOR CONNECTION OF PVC DWV TO
CAST IRON SANITARY, WASTE AND VENT PIPE AT SLAB ON GRADE. SEE DIVISION
22 SPECIFICATION SECTION "SANITARY DRAINAGE AND VENT PIPING AND
20. WATER HAMMER ARRESTORS SHALL BE SIZE "A" UNLESS NOTED OTHERWISE.
21. PROVIDE VERTICAL LIFT SPRING LOADED CHECK VALVES IN HOT AND COLD
WATER SUPPLIES FOR MOP SINK FAUCETS DOWNSTREAM OF SHUTOFF VALVES.
22. VERIFY EXISTING EQUIPMENT TO REMAIN, INCLUDING ACCESSORIES, IS NOT
DAMAGED AND IS IN GOOD WORKING ORDER. REPORT ANY DEFICIENCIES TO
THE ARCHITECT.
23. PROVIDE SIZE AND LENGTH OF HOT WATER FIXTURE SUPPLY PIPE FROM
CIRCULATED HOT WATER BRANCH OR MAIN TO TERMINATION OF HOT WATER
FIXTURE SUPPLY PIPE AT EACH FIXTURE PER 2015 INTERNATIONAL ENERGY
CONSERVATION CODE, TABLE C404.5.1. FOR''/2" HOT WATER FIXTURE SUPPLY
PIPE SIZE TO INDIVIDUAL LAVATORIES, PROVIDE MAXIMUM LENGTH OF TWO
FEET. FOR'/2" HOT WATER FIXTURE SUPPLY PIPE SIZE TO INDIVIDUAL SINKS,
PROVIDE MAXIMUM LENGTH OF 43 FEET. FOR 3/4" HOT WATER FIXTURE SUPPLY
PIPE SIZE TO INDIVIDUAL SINKS, PROVIDE MAXIMUM LENGTH OF 21 FEET.
City Of Edmonds
Building Department
Work PLUMBING
---------------------------------------------------------------------
Address 306 MAIN ST
------------------------------------------------
--------------------------------------------------------------------
Owner BANK OF AMERICA
Approved Date 6 - 9 - 2 0 2 1
Building Official Eri& C4wfer
Permit Number BLD2021-0728
Bankof America'�I
RRP RENOVATION
306 MAIN ST.
EDMONDS, WA 98020
SERIAL NUM./MANH. ID: WA4-115
NRSP VERSION: 2.0
BULLETIN: 04-2019
Gensler
1200 Sixth Avenue
Suite 500
Seattle, WA 98101
United States
Tel 206.654.2100
Fax 206.654.2121
RECEIVED
May 27 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
HENDERSON
ENGINEERS
8345 LENEXA DRIVE, SUITE 300
LENEXA, KS 66214
TEL 913.742.5000 FAX 913.742.5001
WWW.HENDERSONENGINEERS.COM
1950004733
WA. CORPORATE NUMBER: 1754
06/30/20
0 Date Description
04/28/2020 ISSUE FOR PERMIT
Seal I Signature �� M.
56737
Project Name Apr 28 2020
EDMONDS RRP
Project Number
1950004733
Description
PLUMBING GENERAL NOTES, LEGEND
AND SCHEDULES
Scale
AS NOTED
ON JOB SITE
P00000
© 2015 Gensler
O SHEET NOTES
ROOM
113
i
r ❑ O O ❑
❑0 O
PLUMBING WASTE AND VENT PLAN
SCALE: 1 /4"=1'-0"
TO BASEMENT
WASTE AND VENT RISER DIAGRAM
SCALE: NO SCALE
1. CONNECT NEW SANITARY PIPING TO EXISTING
SANITARY PIPING OF EQUAL OR LARGER SIZE BELOW
GRADE ON BASEMENT LEVEL. FIELD VERIFY EXISTING
PIPE SIZE LOCATION AND INVERT ELEVATION PRIOR
TO CONSTRUCTION.
2. VERIFY VTR LOCATION ON ROOF. VTR SHALL BEAT
LEAST 10' AWAY FROM ANY OUTSIDE AIR INTAKE.
3. HATCHED AREA NOT APART OF PLUMBING WORK
SCOPE.
Bank of America'�I
RRP RENOVATION
306 MAIN ST.
EDMONDS, WA 98020
SERIAL NUM./MANH. ID: WA4-115
NRSP VERSION: 2.0
BULLETIN: 04-2019
Gensler
1200 Sixth Avenue Tel 206.654.2100
Suite 500 Fax 206.654.2121
Seattle, WA 98101
United States
RECEIVED
May 27 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
HENDERSON
ENGINEERS
8345 LENEXA DRIVE, SUITE 300
LENEXA, KS 66214
TEL 913.742.5000 FAX 913.742.5001
WWW.HENDERSONENGINEERS.COM
1950004733
WA. CORPORATE NUMBER: 1754
06/30/20
A Date Description
04/28/2020 ISSUE FOR PERMIT
Seal / Signature _�'� M.
56737,
Project Name Apr 28 2020
EDMONDS RRP
Project Number
1950004733
Description
PLUMBING WASTE AND VENT PLAN
Scale
ry
w
J
O
M
Z
H
N
P0101
© 2015 Gensler
(D SHEET NOTES
ROOM
113
r ❑ O O ❑
i
i
l
PLUMBING
i ►'� �. i
3/4" C
1 /2"CW
SK
WHA
J
1. 3/4"CW SUPPLY DOWN TO BASEMENT LEVEL.
CONNECT NEW 3/4"CW SUPPLY TO EXISTING CW
SUPPLY OF EQUAL OR LARGER SIZE LOCATED ABOVE
FINISHED CEILING OR AS CLOSE TO FLOOR DECK AS
NECESSARY. PROVIDE ACCESSIBLE SHUT-OFF VALVE
DOWNSTREAM THE POINT OF CONNECTION. FIELD
VERIFY EXISTING SUPPLY LOCATION AND SIZE PRIOR
TO CONSTRUCTION.
2. ROUTE 1/2" CW PIPING IN WALL AND STUB BELOW
COUNTERTOP WITH SHUT-OFF VALVE FOR
CONNECTION TO QUENCH WATER DISPENSER
STATION BY OTHERS.
3. HATCHED AREA NOT APART OF PLUMBING WORK
SCOPE.
4. INSTALL ELECTRIC WATER HEATER AND
ACCESSORIES IN A MANNER THAT IT WILL NOT
OBSTRUCT ADA CLEARANCES.
W
QUENCH WATER
DISPENSER BY OTHERS
DCV
U
3/4°CW
U WH
TO BASEMENT
TIP LEVEL
Bank of America'�I
RRP RENOVATION
306 MAIN ST.
EDMONDS, WA 98020
SERIAL NUM./MANH. ID: WA4-115
NRSP VERSION: 2.0
BULLETIN: 04-2019
Gensler
1200 Sixth Avenue
Suite 500
Seattle, WA 98101
United States
Tel 206.654.2100
Fax 206.654.2121
RECEIVED
May 27 2021
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
HENDERSON
ENGINEERS
8345 LENEXA DRIVE, SUITE 300
LENEXA, KS 66214
TEL 913.742.5000 FAX 913.742.5001
WWW.HENDERSONENGINEERS.COM
1950004733
WA. CORPORATE NUMBER: 1754
06/30/20
Date Description
04/28/2020 ISSUE FOR PERMIT
Seal / Signature _ � M.
1
56737,
Project Name Apr 28 2020
EDMONDS RRP
Project Number
1950004733
Description
PLUMBING WATER AND GAS PLAN
Scale
AS NOTED
ry
w
0
J
O
M
Z
F-
U)
2 WATER RISER DIAGRAM
SCALE: NO SCALE
P0101
© 2015 Gensler