REVIEWED BLD2021-0671+Manufacturer_Specifications_and_Installation_Instructions+5.14.2021_9.29.00_AM+2196968REMNOW MODEL RPB OUTDOOR, POWER VENTED, GAS FIRED PACKAGED DUCT FURNACE / BLOWER UNIT FOR COMMERCIAL/INDUSTRIAL HEATING AND MAKEUP AIR UPROC•$F� wa ANSI Z83.9 & CAN/C. G.A. A. G.A. 14-95 2.8 & 2.6 DESCRIPTION Reznor® RPB Series packaged units are 80% thermal efficient, power -vented, gas -fired forced air furnaces, designed for installation outdoors and used with recirculating and/or makeup air warm air duct systems. These units use either natural or propane gas, as specified, in sizes from 125,000 through 400,000 BTUH gas input. Standard features include a spark -ignited intermittent pilot and a single -stage, 24-volt gas valve. Each unit has all the required limit and safety controls including a venter pressure switch which verifies power vent flow prior to allowing operation of the gas valve. For automatic operation, each unit is wired for field connection to a remote 24-volt thermostat. The RPB Series models have a weatherized galvalume steel cabinet with interlocking joint construction and a full curb cap for mounting on a roof curb or supports. The standard packaged furnace has a horizontal dis- charge air opening. A bottom discharge air opening is available with the addition of a downturn plenum. The blower cabinet has a standard horizontal inlet but is engineered to allow for horizontal and/or bottom air inlet with various optional damper control systems. The air control systems for both return air heating and makeup air are complemented by a selection of gas control options. To obtain the desired CFM, a wide selection of optional motor and drive combinations is available to operate the centrifugal blower. To meet a variety of installation requirements, Model RPB packaged units are available in selected combina- tions equipped with a downturn plenum, an evaporative cooling module, a cooling coil cabinet with DX or chilled water coil, and/or an outside air inlet hood. STANDARD FEATURES • Orifices for natural gas • Aluminized steel heat exchanger (When inlet air temperature is below 40°F or temperature rise is less than 40oF, optional stainless steel heat exchanger is recommended) • 120-volt power supply • 24-volt control transformer • Redundant single -stage combination gas valve (see Note 1) • Intermittent spark pilot • Fan and limit safety controls • Power venter • Reverse air flow limit control • Adjustable belt drive • Motor contactor • Terminal block wiring • Full curb cap base • Horizontal discharge air opening with duct flanges • Horizontal inlet air opening with duct flanges • Left side access to burner and controls (facing airstream) • Insulated, weatherized steel cabinet with interlocking joint construction for outdoor mounting • 1/2" O.D. BX cable (Chicago code) NOTE 1: Regulated combination redundant gas valve consists of combination pilot solenoid valve, electric gas valve, pilot filter, pressure regulator, pilot shut-off, and manual shut-off, all in one body. Gas supply pressure must not exceed 0.5 PSI (8 oz. - 14" W.C.). Minimum inlet pressure for natural gas is 5" W.C. Minimum inlet pressure for propane gas is 11" W.C. NOTE 2: Not certified for residential use. RIEZHOW MODEL RPB (cont'd) OPTIONAL FEATURES - • Unit equipped for propane gas FACTORY INSTALLED • E-3 (409) stainless steel heat exchanger • E-3 (409) stainless steel burners • E-3 (409) stainless steel drip pan • Intermittent spark pilot with flame supervision and timed lockout • 1/4 HP through 3 HP open drip -proof or totally enclosed motors, 5 HP available in open drip -proof motor only (motors meet EISA specifications for efficiency) • 208/1, 230/1, 208/3, 230/3, 460/3, 575/3 alternate supply voltages • Motor starter (optional with motors having internal overload protection) • Burner air shutters (required for units equipped for propane gas) • Two -stage gas control (unit mounted or remote temperature selector) • Electronic modulation (50-100% turndown and 20-100% turndown) • Direct digital control packages for system control • Makeup air controls/dampers • Convenience outlet • Firestat(s) • Freezestat • Filter rack with filters (2" disposable, permanent or pleated) • Evaporative cooling module • 30% O/A inlet hood (adjustable 0-30% dampers) • Downturn plenum cabinet (insulated) • Discharge damper, 2-position, with downturn plenum • Double wall cabinet construction • High ambient burner cutoff • Gas pressure safety switches • Air flow proving switch • Right side controls (facing airstream) OPTIONAL FEATURES - . Full roof curb FIELD INSTALLED • Disconnect switch - UL Listed • Single -stage thermostat • Two -stage thermostat . Electronic 7-day programmable thermostat • Thermostat guard with locking cover • Remote control console • 100% outside air, screened inlet air hood • Vertical flue extension TECHNICAL DATA SIZE 125 150 175 200 225 250 300 350 400 BTUH 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000 Heating Input (kW) (36.6) (44.0) (51.3) (58.6) (65.9) (73.3) (87.9) (102.6) (117.2) Thermal Output BTUH 100,000 120,000 140,000 160,000 180,000 200,000 240,000 280,000 320,000 Capacity(80%)A (kW) (29.3) (35.2) (41.0) (46.9) (52.8) (58.6) (70.3) (82.1) (93.8) Unit Amps (Less motor) 115V 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 Control Amps (24V) 1 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 ANSI - cfm 1,025 - 1,230 1,230 - 1,480 1,440 - 1,725 1,645 - 1,975 1,850 - 2,220 2,055 - 2,465 2,465 - 2,960 2,880 - 3,455 3,290 - 3,950 RPB (m3/hr) (1,835 - 2,202) (2,202 - 2,649) (2,578 - 3,088) (2,945 - 3,536) (3,312 - 3,974) (3,679 - 4,413) (4,413 - 5,299) (5,156 - 6,185) (5,890 - 7,071) ANSI - cfm 1,230 - 3,800 1,480 - 4,700 1,725 - 5,000 1,975 - 5,100 2,220 - 5,150 2,465 - 5,800 2,960 - 6,300 3,455 - 6,800 3,950 - 7,100 Air HRPBa (ma/hr) (2,202 - 6,803) (2,649 - 8,414) (3,088 - 8,951) (3,536 - 9,130) (3,974 - 9,219) (4,413 - 10,383) (,5299 - 11,278) (6,185 - 12,173) (7,071 - 12,710) Volume Range C.G.A. - cfm 1,025 - 1,850 1,230 - 2,220 1,440 - 2,590 1,645 - 2,960 1,850 - 3,330 2,055 - 3,700 2,465 - 4,440 2,880 - 5,185 3,290 - 5,925 RPB (m3/hr) (1,835 - 3,312) (2,202 - 3,974) (2,578 - 4,637) (2,945 - 5,299) (3,312 - 5,961) (3,679 - 6,624) (4,413 - 7,948) (5,156 - 9,282) (5,890 - 10,607) C.G.A. - cfm 1,850 - 3,800 2,220 - 4,700 2,590 - 5,000 2,960 - 5,100 3,330 - 5,150 3,700 - 5,800 4,440 - 6,300 5,185 - 6,800 5,925 - 7,100 HRPBa (ma/hr) (3,312 - 6,803) (3,974 - 8,414) (4,637 - 8,951) (5,299 - 9,130) (5,961 - 9,219) (6,624 - 10,383) (7,948-11,278) (9,282 - 12,173) (10,607 - 12,710) lbs. 482 520 520 534 534 588 588 630 662 Net Weight° (kg) (219) (236) (236) (242) (242) (267) (267) (286) (300) Downturn Plenum lbs. 622 677 677 714 714 817 817 874 930 Ship Weight° kg (282) (307) (307) (324) (324) (371) (371) (396) (422) lbs. 166 177 177 196 196 229 229 253 271 Cabinet Weight° kg (75) (80) (80) (89) (89) (104) (104) (115) (123) Gas connection - Natural' 1/2" 1 1/2" 1/2" 1/2" 1/2" 1 1/2" 3/4" 3/4" 3/4" Filter Size (Filters are optional and available in 2" disposable, permanent or pleated) (2)20x25 (2)16x20 (2)16x25 (2)16x20 (2)16x25 (1)16x20 (1)20x2O (1)16x25 1 20x25 (1)16x20 (1)20x2O (1)16x25 1 20x25 (1)20x2O (3)20x25 (1)20x2O (3)20x25 (3)20x25 (2)16x25 (2)20x20 (1)16x20 (1)16x25 2 20x25 A In the U.S. ratings are for altitudes to 2000 feet. Above 2000 feet derate by orifice change, 4 % for each 1000 feet above sea level. In Canada ratings are for altitudes to 2000 feet. High altitude units (2001 to 4500 ft.) are derated by 10 % of maximum input. e Prefix "H" indicates high CFM units without directional finger baffles. ° Weights shown are for packaged furnace and blower. For weights of accessories, see below. ° Add to base weight of unit. For weights for other options such as the cooling coil cabinet or roof curbs, see those sections. E Gas connection for optional propane is 1/2" for all sizes. Sizes shown are for gas connection to single stage gas valve, NOT gas supply line size. PROJECT SUBMITTAL Quote ID#: 99789 Prepared by: Joe Gately 253-620-8218 jgately@gensco.com Date: 04/07/2021 The attached describes the equipment we propose to furnish for your review and approval. Due to continuous improvement, information in this document is subject to change to reflect current design criteria or corrections of erroneous data. 0 Nortek Global HVAC. LLC. REZNOP° TABLE OF CONTENTS MakeupAir Schedule (Heat)- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- ---------------------------------------------------------------------------- -- -- -- -- -1 RDH 200 2 General Information 2 IncludedOptions- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- - 4 DimensionDrawing --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 7 Technical Data - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -8 Terms And Conditions 9 Warranty------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- 12 Page ii © Nortek Global HVAG, LLG. Makeup Air Schedule (Heat) Supply Fan Exhaust Fan Heating Power Line No. Model -Size / Unit Tag Supply Airflow SCFM Min CA SCFM ESP in we Exhaust Type Exhaust Airflow SCFM ESP in we FuelType Winter Voltage V/IHz FLA A MCA A MOP A put utDs nlMaz p g MBH EAT F LAT F 1 RDH-2001 3000 3000 0.5 Cannot determine 0 0.0 Natural 162.01162.0 10.0 60.0 20811160 8.85 11.06 15.00 N Z O P:Dayton I Q:Untitled I D:RDH-200 Model RDH Series High Efficiency Gas Heating Air Handler . 0 0+• 1 75 — 400 MBH 81 % Thermal Efficiency Model RDH is designed for outdoor installation — rooftop or slab mounting. The RDH is a power - vented heater that is approved for commercial industrial installations in the United States and Canada by ETL Testing Agency. Standard features include the Reznor TCOREO heat exchanger and single burner combustion system, a multi -try direct spark ignition with 100% lockout, pressure switch to verify venter flow, resiliently isolated venter motor, a high temperature limit control, and a centrifugal belt -driven blower capable of up to 3" w.c. of total static pressure. Both the forward curved blower and the blower motor are factory installed on vibration isolation mounts. All published airflow data is supported by AMCA tested and rated airflow performance curves. The energy usage of the system has been designed to meet the current ASHRAE Standard 90.1 (maximum 1.2 bhp per 1000 cfm). Operation is controlled through an integrated circuit board. The circuit board monitors heater operation and has LED diagnostic indicator lights to identify abnormalities in heating control functions. Pi? C us ZlBTEv Intertek CSA 2.6 ANSI Z83.8 REZNOR Standard Features and Benefits • Maximum 70'F temperature rise (optional 120°F). • Circuit breaker protected transformer for 24-volt controls. • High temperature limit control. • Rubber -in -sheer vibration isolation. • L50 bearing rating with a life expectancy of 150,000 hours. • Reverse airflow limit switch. • Airflow pressure switch to verify circulating blower operation on makeup air operations. • Socketed, high quality switching relays to facilitate service. • All service and vent connections from a single side. • Through the cabinet or through the base gas connections. • Engineered heat exchanger condensate management. • Three hinged service doors with heavy duty hardware. • Pre -coat white gloss cabinet finish (all units); 60 gloss minimum and RAL 9001, meets ATSM B117 specification for salt spray for 1,000 hours. • Heavy gauge steel base. • Double wall cabinet with insulation. Field Installed Options • Variable frequency drive (factory -installed is also available). • Thermostats to match analog controls. • Gas pressure regulator. • Smoke detector (in ductwork). • Remote control console and unit monitoring. Fusible and Non -Fused Disconnect Switch (NEMA 3R). • Vent cap. • Vertical Vent Extension Kit. • 16" Insulated Roof Curb. Perimeter roof curb transitions to (C)RGB/RPB roof curbs - for Model RDH replacement of Models (C)RGB/RPB. • Downturn nozzles (25-65o or 50-90°) with directional louvers. Main unit disconnect switch. • M-Series condenser. Page 2 Q Nortek Global HVAG, LLG. P:Dayton I Q:Untitled I D:RDH-200 Factory Installed Options • Stainless steel heat exchanger - 409 or 316 (stainless steel heat exchanger required for 70' - 120'F temperature rise). • Heat exchanger extended warranty - 5-year or 10-year. • Natural gas or propane. • UV germicidal lamps - ultraviolet emitter for neutralization of VOCs and airborne micro-organisms for Improved IAQ - not filtration. (Requires cooling coil cabinet Option AU. Separate 115/1 or 208/1 or 230/1 wiring/breaker and a separate disconnect must be provided.) • Supply voltage - 115/1; 208/1; 230/1; 208/3; 230/3; 460/3; 575/3. • Unit mounted, lockable, non -fused service on/off switch. • Inlet air filters - 2" disposable or permanent; 2" or 4" pleated disposable, arranged in vertical flat bank for ease of service. • Convenience outlet (requires separate power supply). • Controls o Space temperature heating only. • Analog single or two -stage gas valve with room thermostat control (thermostat is available as a shipped -separate accessory or may be field -supplied). o Space or discharge heating/cooling (FX06/07 platform) (optional room command module required for space control). • Digital two -stage heating/three-stage cooling. • Digital electric modulation heating (25% low fire — natural gas, 40% low fire — propane/three-stage cooling, reheat control). • 8:1 modulation heating (12.5% low fire capacity/two-stage cooling). o Discharge Temperature Makeup Air (Heating only). • Analog two -stage with two -stage ductstat or electronic sensor and two -stage valve. o Discharge Temperature Heating/Cooling Makeup Air. • Digital two -stage heating/three-stage cooling. • Digital electronic modulation heating (25% low fire — natural gas, 40% low fire — propane)/two- stage cooling. • 8:1 modulation heating (12.5% low fire capacity)/two-stage cooling (Model RDH size 175 and larger). • Cabinet configuration and construction. • Left or right side controls. • High R-value insulation. • Inlet duct connection flange, or inlet on/off damper with duct flange. REZNOR Mixing box module (double wall). o Three inlet configuration combinations with 100% bottom return air opening and/or 100% outside air rear opening. o Inlet air configuration with 30% outside air opening and 100% return air opening. o Manual, motorized 2 or 3 position, motorized modulating return air or outside air and return air dampers. o Direct -coupled 24VAC damper actuators. o Damper control selections suck as 0-135 ohms resistance potentiometer, building pressure, or 0-10 v control. 0 Bottom return air screen. Double wall downturn plenum cabinet. 0 Shutoff dampers. Blower motor (1/4 to 5 HP) — see pressure drops and blower charts. o Open dripproof, TEFC (motors meet EISA specifications and efficiency). o Adjustable sheave and belt. o Motor contractor; IEC motor starter; or factory -installed variable frequency drive. Cooling coil module with coil. o DX coil (single, 50/50 or 1/3-2/3 circuit, galvanized or stainless casing; copper or aluminum fins (coated or uncoated) — non -ozone depleting R410A refrigerant. o Chilled water coil (3-45 tons; '/4, '/2, 3/4, or full circulating; galvanized or stainless casing; copper or aluminum fins (coated or uncoated). o Stainless steel removable drip pan. DX coil module with dehumidification control. Single, duel and 1/3-2/3 circuit, main DX coil with modulating or standard reheat control. Discharge duct flange. Evaporative cooling module. 0 White pre -painted or 300 series stainless steel cabinet. 0 300 series stainless steel reservoir. 0 Recirculating pump or AquaSaver microcompressor- based, timed water distribution system. 0 Water circulating pump with optional (field installed) fill and drain kit. 0 AquaSaver water metering device with optional (field installed) freeze protection. 0 12" CELdekO or GLASdekO UL 900 Class II noncombustible media. 0 1" or 2" aluminum pre -filter. 0 Water hammer arrestor (field installed) • Firestat • Discharge temperature low limit. • Over/under voltage or phase loss protection. • High ambient limit (burner cutoff). • Gas pressure switches (high, low, or both). Page 3 Q Nortek Global HVAG, LLG. P:Dayton I Q:Untitled I D:RDH-200 REZNORU\ Included Options for RDH-200 AA1 Unit equipped for natural gas heating.Natural gas is a naturally occurring gas mixture consisting primarily of methane and includes varying volumes of alkanes, carbon dioxide, nitrogen, and hydrogen sulfide.1 Therm = 100,000 BTU = 29.3kWh AB1 Burner orifices for elevations 0-2000 Feet AC2 Heat exchanger is manufactured from die -formed halves of 409 E-3 Stainless Steel. Design for improved corrosion resistance over standard heat exchanger material. AG1 Gas controls designed for recirculating air heating application. Furnace has a 24 volt, single stage combination gas valve which includes the electronic on -off valve controlled by a single -stage 24 volt room thermostat, a pressure regulator, a safety pilot valve, and the manual shutoff valve. ©� 0 AJ1 Left side control location facing airstream standard AJ1 AK2 208 Volt, Single Phase, 60 cycle supply voltage. AL6 1 HP 1800 RPM open style blower motor AM9 Fan/drive at 801-850 RPM Page 4 © Nortek Global HVAC, LLC. P:Dayton I Q:Untitled I D:RDH-200 AN2 Motor Contactor AQ2 Horizontal Air Discharge. AR5 Horizontal inlet with duct flanges AUO NO COIL SECTION REZNOR` AW21 Filter Section with an integral filter rack and MERV 8 standard duty 4 inch Pleated Filters. AY3 Double wall cabinet construction, solid liner with insulation BA1 None Wire Nut BC1 Unit Supplied with a Blank cover panel in location for GFI Outlet. No GFI Outlet included. BG7A UNT START REL,24V SIGNL BY OTH Page 5 © Nortek Global HVAC, LLC. P:Dayton I Q:Untitled I D:RDH-200 REZNOR BP1 Unit built with standard gas manifold. This manifold is of black iron piping using NPT specifications. All joints are secured by back bracing to tighten to proper torque specification. The gas train is complete without any gas pressure switches measuring high or low gas pressure. CSO STANDARD BURNER DR2 Adjustable V-Belt Drive Blower MXBO NO MIXING BOX PC4 Rubber vibration isolation limiting motor and blower vibration transmission. SH2 Ship Via LTL crate unit XWO 1 YEAR LIMITED HX WARRANTY ZZO Unit has no cooling provided. Page 6 © Nortek Global HVAG, LLG. MODEL(S) RDH 175 RDH 200 RDH 225 5 1 16 1 402 OPTIONAL WEATHER HOOD 100% OUTSIDE AIR INLET 7196 3911 16 AIR FLOW (MOUNTED 11- HEIGHT) DIRECTION i ROOF CURB -/ 1 J MOUNTING q SURFACE RDH C FLUE OUTLET ®/d o ELECTRICAL CONNECTIONS 263 GA 4 CONNECTION 32 69g (INSIDE CURB CAP) 762 NOTES: 1) UNITS ARE SHOWN WITH LEFT HAND CONTROLS (AJ1). 2) UNITS WITH OPTION AJ2 HAVE GAS AND ELECTRICAL CONNECTIONS/SERVICING ON THE OPPOSITE SIDE. 3 3 3 4 204 4 ,—OPTIONAL 3161 OF OPENING DUCT 1216 FLANGES 3 4 COF 13 DISCHARGE OPENING 2216 O AIR OPENING 3716 II 33 J 9 L 4 6 1715 1 16 4 1 12 3116 (INSIDE CURB CAP) 333 ALL DIMENSIONS ARE IN INCHES P:Dayton I Q:Untitled I D:RDH-200 TECHNICAL DATA REZNOR Model RDH Size 75 1 100 125 1 150 175 1 200 1 225 250 1 300 350 400A Cabinet Size A B C D E Input Heating Capacity" Btuh 75,000 100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000 kw/h 22.0 29.3 36.6 43.9 51.2 58.6 65.9 73.2 87.8 102.5 117.1 Output Heating Capacity Btuh 60,750 81,000 101,250 121,500 141,750 162,000 182,250 202,500 243,000 283,500 324,000 (81 % Thermal Efficiency) kw/h 17.8 23.7 29.6 35.6 41.5 47.4 53.4 59.3 71.2 83.0 94.9 Control Amps (24 volt) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 Full Load Amps (115 volt, less motor) 1.2 1.2 1.2 0.9 0.9 1.7 1.7 1.7 3.0 3.0 3.0 Size inches 10x10 10x10 2 9x7 2 9x7 12x12 12x12 12x12 (2)12x7 2 12x7 (2)12x12 (2)12x12 Min Airflow cfm 469 625 781 938 1094 1250 1406 1563 1875 2188 2500 Heating 3 m3/min 13 18 22 27 31 35 40 44 53 62 71 Max Airflow cfm 1406 1875 2344 2813 3281 3750 4219 4688 5625 6563 7500 Blower Heating m3/min 16 21 27 32 37 42 48 53 64 74 85 Min Airflow cfm 583 583 826 826 917 917 917 1537 1537 1843 1843 Cooling B W //min 1 17 17 23 23 26 26 26 44 44 52 52 Max Airflow cfm 1406 1875 2344 2813 2916 2916 2916 4688 4691 5061 5861 Cooling m3/min 40 53 66 80 83 83 83 133 133 143 166 Gas Natural inches 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 Connection jPropane inches 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 Ship Weight (basic unit Ibs 453 466 586 595 693 719 719 925 940 1,080 1,092 only; add module wts) kg (205) (211) (266) (270) (314) (326) (326) (420) (426) (490) (495) Net Weight (basic unit only; Ibs 355 364 454 463 526 552 552 677 692 793 805 add module wts) c kg (161) (165) (206) (210) (239) (250) (250) (307) (314) (360) (365) Filter (Qty) and Size (Factory -installed filters are optional.) (2) 16x25 (2) 16x25 (2) 20x25 (2) 20x25 (2) 16.16 (2) 16x20 (2) 16x16 (2) 16x20 (2) 16x16 (2) 16x20 (3) 16x16 (3) 16x20 (3) 16x16 (3) 16x20 (1) 16x16 (2) 20x20 3 16x20 (1) 16x16 (2) 20x20 3 16x20 A Does not include motor heat. s The minimum and maximum heating CFM based upon a temperature rise range from 40'F thru 120'F temperature rise. The maximum and minimum cooling CFM is based upon air velocity ranges of 200 FPM thru 500 FPM. The actual CFM may be limited by e.s.p., design conditions, selected options, elevation and other items. Does not include motor weight. Downturn Plenum Weight • Add weight below to unit weight in Technical Data Table. Downturn Plenum Option AQ5 or AQ8 available on Model RDH Only. Model RDH Size 75-100 125-225 250-300 350-400A Downturn Option AQ5 Ibs 140 158 190 206 Plenum Only Bottom Opening kg 63 72 86 93 Net Weight Option AQ8 Ibs 156 176 211 229 Bottom Opening 8r 2 kg 71 80 96 104 Position Damper Corner Weights Size W X Y Z Lbs. 77 69 101 108 75 k 35 31 46 49 Lbs. 79 71 104 110 100 k 36 32 47 50 Lbs. 98 89 129 138 125 k 44 40 59 63 Lbs. 100 90 132 140 150 k 45 41 60 64 Lbs. 114 103 150 160 175 k 52 47 68 73 Lbs. 117 106 154 164 200 k 53 48 70 74 Lbs. 120 108 157 167 225 k 54 49 71 76 Lbs. 147 132 193 205 250 k 67 60 88 93 Lbs. 150 135 197 210 300 (kg.) 68 61 89 95 Lbs. 172 155 1 226 241 350 k 78 70 103 109 Lbs. 174 157 229 244 400A k 79 71 104 111 Airflow TOP VIEW Corner weights are for base unit and include standard controls only. Weights do not include motor, double wall construction, or any optional accessories such as cooling coil cabinet, or mixing box. Page 8 Q Nortek Global HVAG, LLG. U) a) c .U) -0 O L O C: �+- a) cz U E �E C�ONO, Carriers 50YO100 Single-PaCkage Heat Pumr) for YbAr-Round Comfort Plus Outstanding Efficiency Conditioning your home or business for maximum comfort all year long involves not only cooling and de- humidifying indoor air in the summer, but also heating, humidifying and filtering the air in colder months. Carrier's 50YQ heat pump can do it all with a remarkable efficiency that saves energy costs across the board. Built in the Carrier tradition of air conditioning excellence, the 50YQIQ0 Series provides a total package for your comfort needs during all seasons. The 50YQ heat pump is available in 5 sizes, from 24,000 to 48,500 Btuh cooling and from 23,600 to 52,500 Btuh heating. So you can choose the size that's just right for your res den tial/manufactured home or com- mercial building, and enjoy the benefits of comfort plus economy for many years to come. The heat pump achieves its extra- ordinary efficiency because it collects and moves heat from one place to another rather than producing it directly. On the cooling cycle, the unit pumps heat and humidity from inside your home to the outdoors, where they are dispersed. On the reverse cycle, the heat pump recovers heat from outdoors and pumps it inside to warm the indoor air. Even in the coldest weather (there's re- coverable heat in air at temperatures down to absolute zero [-460 F]), the heat pump can collect and concen- trate heat from the outdoor air to keep your home or office cozy. This principle of operation means that the heat pump saves energy whenever you use it. The 50YQ100 has cooling SEER's of 8.5 and higher, and C.O.P.'s for -heating of 2.8, which means that at 47 F the heat pump produces almost 3 times as much energy as it consumes. Depending on the temperature, your Carrier heat pump will be approximately 2 to 3 times more efficient than electric resistance heat. So consider the 50YQ100 single - package heat pump when selecting an air conditioning system for your home or business — it's the ideal unit for a variety of applications. VL Installation without complication The 50YQ100 arrives on the site ready to go. Completely wired, piped and charged at the factory, it installs quickly and easily. Connect electrical power and ductwork - that's all there is to it. An excellent unit for buildings that require crawl space ductwork installation; the 50YQI00 fits right in. it's also ideal for conditioning manu- factured homes, providing ali-season living comfort wherever you are. An operating sensation Time 50YQ100 performs with quiet, dependable efficiency and is certified for residences and commercial build- ings. The key to its operating effective- ness is the fine collection of matched heat pump components — computer designed, quality selected and tested to assure years of reliable operation. s Rugged hermetic compressor — Sealed against air, dirt, and moisture at the factory to assure long life. Internal safeguards protect the motor from costly damage. Crankcase heat- ers prevent refrigerant dilution, pro- mote proper lubrication, even after extended periods of shutdown. Backed by Carrier's 5-year warranty.* e large capacity coils -- With increased coil face area for greater air contact and optimum heat transfer. During warm weather the large 3-row indoor coil cools the air and lowers humidity effectively. The 2-row out- door coil rejects heat to the atmos- phere. Coils reverse roles during cool weather operation. Five-year war- ranty on the outdoor coil.* * Nlultispeed indoor fan — Set the fan for most efficient airflow; fan moves large quantities of air slowly, quietly. Resiliently mounted to mini- mize vibration. Easily removable for servicing. o Quiet outdoor fan — Sweeps air and sound up and away. Vertical dis- charge minimizes noise and protects shrubbery. s AccuRaterT" metering device — Carrier's patented, dual -piston. Accu- Rater device automatically meters the rate of refrigerant flow to meet a wide range of outdoor temperature conditions. Provides precise control' of refrigerant flow for maximum system efficiency. Eliminates reed for check valves and the double flow control devices required on many competitive heat pumps. Included in -line strainers are easy to service. *See your Carrier dealer for complete warranty details. THE HEAT PUMP'S REVERSE CYCLE OPERATING PRINCIPLE 1q,1,6 - W) HEATING CYCLE HEAT REJECTED ROOM AIR F ER ATOR COIL COMPRESSOR COOLING CYCLE HEAT AIR TO ROOM ABSORBED I I -, I EVAPORATOR COIL CONDENSER COIL COMPRESSOR 4 HEAT ABSORBED HEAT REJECTED COIL 2 • *Crankcase beater -- Prevents dilution of Oil by refrigerant during shutdown periods. o Suction line accumulator — Pro tects compressor from refrigerant — — --- floodback. �So 4 Service, with ease and economy The 50YQIOO is engineered to keep service and maintenance to a mini- mum. Components are selected for years of trouble -free operation. Emit 'A panels are readily removed for access to all components. Reduces labor g cost and unit down time. rA%(.­",cEo",:Ssones MODEL ®Time Guard IA device — Prevents PART NO _ DESCRIPTION 50YQ costly compressor damage that could Low -Voltage Control Honeywell Thermostat HH07AT171 and Occur from rapid recycling. Provides 99TZ900401 _ Thermostat Subbase HH93AZ173 —Automatic Changeover a 5-minute delay before compressor 99TZ900411 Low -Voltage Control Honeywell Thermostat HH07AT171 and - restart. Thermostat Subbase HH93AZ175 — Manual Changeover Low Voltage Control White Rodgers Thermostat and All O Service Sent control — Ener- 99TZ90021106 Subbase (Six 38CQ900191) Automatic Changeover Low Voltage Control White Rodgers Thermostat and gizes warning light at indoor thermo- 99TZ90022106 Subbase (Six 38CQ900211) — Manual Changeover $tat If compressor is not operating 38CQ900152 Solid -State Time GuarjZ Control — _ -_- - and service is -required. --4 — Sentry Service Sentry _ All __ _ _ 9 . __ _ __ __ _ - _ -__.. -_ . �► Electric beaters — Single-phase 38RQ900032 � Outdoor Thermostat v 50YM900051 Duct Flange Kit in sizes from 5 kW to 20 kW. Mount 50YM90005106 Duct Flange Kit (Six -Pack) 124-142 in the Indoor air fan compartment. 88EJ10506A00 Electric Heater — 5 kW� _ O Outdoor thermostat package — 88EJ1075CA00 Electnc Heater 7 5 kW _ 124-142 Manually Set Outdoor thermostat 88EJ1100CAOO Electric Heater — 10 kW -- controls heaters so they operate Heater ic c 00 88EJ1150CA-Electric Hear 15 kW 130-142 _._.- _ _ _ _.. .__ _ _ _ . ... only when required for maximum 88EJ0050MA00 Electric Heater 5 kW u 88EJ0075MA00 Electric Heater 7 5 kW _ economy. 88EJ0100MA00 Electric Heater 10 kW - 148 ® Thermostat with subbase (24 v) 88EJ0150MA00 Electric Heater 15 kW — The Carrier line includes several 88EJ0200M400 Electric Heater 20 kW models to choose from. Provides con- _HC95DD121* _ _Start Capacitor —� 124 —_ Venient Selection of cooling, heating, HC95DE088* — Start Capacitors 130,,136 continuous Or automatic fan opera- HC95DE085* —Start Capacitor 142 ____®.__.__..._ _ .. —.- _ — - HC95DE070* Start Capacitor - - _ 148 tFon, manual Or auf02't�atlC C ange ---- _ -- _ -- _ _ —_ __.._ over. Thermostat with supplemental _11N61KB109* mStartRelay — u 12_4 — HN61 HB496* Start Relay - - 130 — eat switchand indicator light F5 HN61H6510* Start Relay_ 136 standard. HN61KB109* Start Relay 142 HN61_K_B075* Start Relay _— 148 38EB660002* Wire Bundle for Start Capacitor and Relay — — All 'Available through Carrier Service Parts Physical data and dimensions OPERATING WT (lb) REFRIGERANT —_ Oper Chg (lb)* Refrig Control COMPRESSOR T- Cylinders Rpm (60-Hz) OUTDOOR FAN Air Discharge Cfm Motor Hp Motor Rpm OUTDOOR COIL Rows... Fins/in. Face Area (sq ft) � INDOOR FAN Air Discharge ARI Cfm Range Cfm Motor Hp Motor Rpm INDOOR COIL Rows... Fins/in. Total Face Area (sq ft) 61MENSI6NS (ft - in) A B Ct LIQUID LINE PRESSURE SWITCH Cutout (psig) Cut -in (psig) DEFROST THERMOSTAT Opens Closes FILTER SIZE$ (in.) Disposable Permanent 320 320 333 375 1 417 - - - - ---�- -- -. --- ---- - - --•---- � - 53 53 53 62 7 3 AccuRaterTM - ----__--- _- _---- - Hermetically Sealed 2 3500 Propeller — Direct Drive Vertical 2500 I 2500 2500 2700 J 3200 1/5 + 1/5 1/4 I '/4 I 1/4 1075 Plate Fin 1 19 1 1 -- 9 17 9 1 -- 917 _ 10 83-- 125 -- 800 700-950 '/5 2 13 405 Centrifugal — Direct Drive, 3 Speed Horizontal 1080 1230 1 1485 850-1200 1000-1350 1367-1708 1/5 1/2 1100/1050/900 Plate Fin 3 13 j 3 13 3 13 405 405 _ 478 4-0'/e 3-61/4 1725 1633-2040 1/2 3 .13 — 5 52 -- 1-1 15/8 _ — 1 2_35/8 2-75A 5 20 • 80 F 27 F __ _-_ --y --- - --- - - -__ I yJ 15x20 _----_ . _ ._ —� 20x25 20x25 15x20(2) 20x20(2) 20x20 _ _ 20x20 — 15x20 20x20 20x25 20x25 15x20(2) *Factory refrigerant charge j Dimension C includes one -in built-in base support channels tRecommended field -supplied filters are one -in thick B A AI11 e CONDUIT CONTROL I V C'_;• WIRING ! e ` CONDUIT. I ; CONTROL > e ' WIRING k C I4 DKO ELECTRIC A l le DIAM KNOCKOUT HEAT ELECTRIC HEAT P' 1114 131. 1 Ie KO DAM KNOCKOUT---- Cf g" LINE DI AM WIRING WIRING'`w� 8 CONN CONN'' ? II I •; [INDOOR AIRFLOW — I -2� E> INDOOR AIRFLOW OUTDOOR AIRFLOW RIGHT SIDE VIEW OUTDOOR AIRFLOW RIGHT SIDE VIEW 50YQ 124-142 50YQ 148 Space required for service on front, rear and left side is 3 ft, 0 inches Space required for service on right side of unit is one ft, 0 inches 4 Submittal Single Packaged Heat Pump 14 SEER Convertible 4WCC4024A1000A Note: "Graphics in this document are for representation only. Actual model may differ in appearance." TAG: Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. January 2015 4WCC4024A-SUB-1 B-EN 4t# Ingersoll Rand Product Specifications MODEL 4WCC4024AI000A RATED Volts/PH/Hz 208-230/1/60 Performance Cooling BTUH (e) 24600 Indoor Airflow (CFM) 758 Power Input (KW) 1.9 EER/SEER (BTU/Watt-Hr.) (b) 12.00 / 14.00 Sound Power Rating [dB(A)] (c) 66.4 PERFORMANCE HEATING (High Temp.) BTUH 22000 Power Input (KW) 1.8 (Low Temp.) BTUH 14300 Power Input (KW) 1.12 HSPF (BTUH/Watt-Hr) 8.0 POWER CONN.—V/Ph/Hz 208-230/1/60 Min. Brch. Cir. Ampacity (d) 19.4 Fuse Size — Max. (amps) 30 Fuse Size — Recmd. (amps) 30 COMPRESSOR SCROLL VOLTS/PH/HZ 208-230/1/60 R.L. Amps— L.R. Amps 12.8/ 58.3 OUTDOOR COIL — TYPE SPINE FIN Rows/F.P.I 2 / 24 Face Area (sq. ft.) 13.32 Tube Size (in.) 3/8 Refrigerant Control EXPANSION VALVE INDOOR COIL — TYPE PLATE FIN Rows/F.P.I 3 / 15 Face Area (sq. ft.) 3.5 Tube Size (in.) 3/8 Refrigeration Control EXPANSION VALVE Drain Conn. Size (in.) 3/4 FEMALE NPT OUTDOOR FAN — TYPE SWEPT DIA. (IN.) 23.4 DRIVE/NO. SPEEDS DIRECT/ 3 CFM @ 0.0 in. w.g. (e) 2550 Motor — H P/ R. P. M 1/ 12 / 850 Volts/Ph/Hz 208-230/1/60 F.L. Amps/L.R Amps .54 / .82 INDOOR FAN — TYPE CONSTANTTORQUE ECM Dia. x Width (in.) 10.62 X 10.68 Drive/No. Speeds DIRECT/ 3 CFM @ 0.0 in. w.g. M SEE FAN PERF TABLE Motor — HP/R.P.M. 1/3 / 1050 Volts/Ph/Hz 208-230/1/60 F.L. Amps 2.8 FILTER / FURNISHED NO Type Recommended THROWAWAY Recmd. Face Area (sq. ft) (9) 2.7 REFRIGERANT R-410 Charge (lbs.) 5.74 CHARGING SPECIFICATIONS Subcooling 16' DIMENSIONS H X D X W Crated (in.) 46 X 45 X 52 WEIGHT Shipping (lbs.) / Net (lbs.) 402 / 328 W Rated in accordance with AHRI Standard 210/240. (b) Rated in accordance with D.O.E. test procedure. (c) Sound Power values are not adjusted for AHRI 270-95 tonal corrections. (d) Calculated in accordance with currently prevailing Nat'l Electrical Code. (e) Standard Air — Dry Coil — Outdoor. (f) Standard Air — Dry Coil — Indoor (9) Filters must be installed in return airstream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05, W.C. 4W CC4024A-SUB-1 B-E N Outline Drawings 25.40 111 Figure 1. 2 — 3 TON MODELS (DUCT 0 4'' [41 118-1/21 19.0 13/41 FEMALE NPT LEFT SIDE 18.03 18.29 123/321 123/321 14.22 [9/161 SECTION Y-Y TYPICAL (8) SIDES OF DOWNFLOW DUCT OPENINGS Note: The view labeled Bottom Side represents the base as viewed looking up from underneath the unit. OUTLET FRONT SIDE BOTTOM SIDE GRAVITY 4WCC4024A—SUB-1 B-EN 3 Outline Drawings Figure 3. 2 — 3 TON MODELS 304.80 1121 (INSIDE) 75.41 12-31/321 RECOMMENDED SERVICE CLEARANCE MM/IN. WITH ECONOMIZER BACK SIDE 304.8 1121 762.0 1301 LEFT SIDE 762.0 1301 914.4 1361 RIGHT SIDE 609.6 1241 - FRONT SIDE 1066.8 [421 - CLEARANCE TO COMBUSTIBLE MATERIAL MM/IN. BOTTOM 0 BACK SIDE 25.4 [11 LEFT SIDE 152.4 [6) RIGHT SIDE 152.4 [61 FRONT SIDE 304.8 1121 TOP 914.4 [361 359.79 [14-5/321 24V ENTRY 288.42 225�68 1II-I,I/321 [8-7/81 117.73 J [ 4 - 5 / 8 1 85.22 [3-11/321 73.46 6-27/321 406.40 1161 (INSIDE) .89 5/81 I.v.Iv 1161 ( I N S I DE ) BOTTOM DUCT OPENINGS \085o' R ENTRY 8 [1-1/81 DIA. KNOCKOUT ER ENTRY 58 11-1/81 DIA. KNOCKOUT 1293 11-3/81 DIA. KNOCKOUT 01 [1-3I/321 DIA. KNOCKOUT [5SINGLE POINT ENTRY OCKOUT RIGHT SIDE 50.01 [ 1 -31 /32D1 DIA. KNOCKOUT 62.71 [2-15/321 DIA. KNOCKOUT 4WCC4024A-SUB-1 B-EN 5 Indoor Fan Performance (230v) Table 1. Horizontal Airflow 4WCC4024A1 EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 WATTS 63 70 77 83 90 95 - - - - - LOW CFM 899 820 755 681 581 505 WATTS 75 83 91 97 104 111 - MEDIUM CFM 959 886 818 756 673 589 - - WATTS - - 119 127 134 142 149 155 HIGH CFM - 940 886 820 748 670 605 Table 2. Down Airflow 4WCC4024A1 EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 COOLING WATTS 63 71 77 83 90 95 - - - - - - LOW CFM 890 811 747 674 575 500 COOLING WATTS 76 84 91 98 105 112 - MED CFM 950 877 810 749 666 583 - - COOLING WATTS - - 119 127 135 143 150 156 - HIGH CFM - - 931 877 812 741 663 599 4WCC4024A-SUB-1 B-EN Supplementary Electric Heater Table 3. BAYHTRV — Supplementary Electric Heaters ELECTRIC RATED HEATER NO KW/STAGE MAX. FUSE CANADA UNIT HEATER VOLT- PHASE AMPS CAPACITY OF. MCA OR HACR ONLY MAX. MODEL MODEL AGE STAGES CKT BKR CKT BKR KW BTUH 1 2 SIZE SIZE 4024-4060 BAYHTRV105 208/240 1 18/21 3.76/5.0 1200 1 3570/ - 23/26 25/30 25/30 17$ 00/ 4024-4060 BAYHTRV108 208/240 1 29/33 6.0/8.0 20500/ 1 6.0/ - 36/41 40/45 40/45 27300 8.0 4024-4060 BAYHTRV110 208/240 1 36/42 7.5/10.0 1 - 45/52 45/60 45/60 34100/ 10.0 4030-4060 BAYHTRV115 208/240 1 54/63 11.27/ 38500/ 2 7.5/ 3.76/ 68/78 70/80 70/80 15.0 1 51200 10.0 5.0 4048-4060 BAYHTRV120 208/240 1 72/83 15.0/ 51200/ 2 7.5/ 7.5/ 90/ 90/110 90/110 20.0 68300 10.0 10.0 104 4060 BAYHTRV125 208/240 1 90/ 18.78/ 64100/ 2 11.26/ 7.5/ 113/ 125/150 125/150 104 25.0 85300 15.0 10.0 130 Table 4. BAYSPEK — Single Power Entry Kit SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION UNIT MODEL SINGLE POWER ENTRY KIT HEATER MODEL MIN CKTAMP MAX OVER -CURRENT DEVICE 4WCC4024A BAYSPEK60 BAYHTRV105 45 50 BAYHTRV108 60 60 BAYSPEK62 BAYHTRV110 71 80 4WCC4024A-SUB-1 B-EN Optional Equipment — Filter Rack Figure 5. BAYFLTR101 Filter Rack (4024-4036) BAYFLTR201 (4042-4060) (Mounts in Filter/Coil Section) Figure 6. BAYACCDOR1A Hinged Filter Access Door (4024-4036) BAYACCD0132A (4042-4060) Replaces Filter/Coil Access Panel Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 4WCC4024A-SUB-1 B-EN Optional Equipment — Filter Rack Optional Equipment — Economizer Table 5. BAYECON101,102A Down Discharge Economizer and Rain Hood (Mounts Over Horizontal Return Air Opening) HVAC Unit Economizer eeeeeeeeee Economizer Unit Application Models rain hood eeeeeeeeeee eeeeeeeeeee BAYECON101A 4024-036 Outside air dampers Return air dampers Required c filter kit, order Mist separately eliminator o BAYECON102A 4042-060 Relief Return damper Duct Roofcurb Table 6. BAYCON200, 201A Horizontal Economizer and Rain Hood / Economizer D, Gaskets (2) Duct E Rain Hood Mixed Air Sensor Economizer Models A B C D E F BAYECON200AA 4024-4036 22" 20" 16-7/8" 15-11/16" 11-11/16" 15" BAYECON201AA 4042-4060 26" 22-21/32" 19" 17-11/16" 14-11/16" 21-3/8" Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 10 4W CC4024A-SUB-1 B-E N Mechanical Specifications General The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. Units shall be certified to UL Standard 1995. All units shall be factory run tested to check cooling operation, fan and blower rotation and control or TXV sequence. Units shall be designed to operate at ambient temperatures between 1151F and 55°F in cooling as manufactured. Cooling performance shall be rated in accordance with AHRI standards. Unit Casing All components shall be mounted in a weather - resistant steel cabinet with an enamel finish. Access panels shall be provided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with fireproof, permanent, odorless fiber material. Knockouts shall be provided for utility and control connections. Drain connections shall be provided to accommodate indoor water runoff. Compressor The compressor shall be hermetically sealed, high efficiency scroll compressors. Internal overcurrent and overtemperature protection, internal pressure relief shall be standard. Other features include centrifugal oil pump, low vibration and noise. Refrigeration System All units shall have refrigerant control. Service pressure tap ports and a refrigerant line filter shall be standard. Evaporator Coil Internally enhanced 3/8" OD seamless copper tubing mechanically bonded to aluminum fins, factory pressure and leak tested at 480 — 650 psig. All units have TXV to control refrigerant flow. Condenser Coil The Spine Fin TM condenser coil shall be continuously wrapped, corrosion resistant all aluminum with minimum brazed joints. This coil is 3/8" OD seamless aluminum tubing glued to a continuous aluminum fin. Coils are lab tested to withstand 2.000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. Indoor Air Fan Constant Torgue, forward -curved, centrifugal wheel in a Composite Vortica ® Blower housing. Motor shall have thermal overload protection and permanently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber mounts. Outdoor Fan One direct -drive, statically and dynamically balanced propeller fan shall be used in a draw -through vertical discharge configuration. Permanently lubricated weather proof motor shall have built-in thermal overload protection. System Controls System controls include condenser fan, evaporator fan and compressor contactors. Accessories Roof Curb The roof curb shall be designed to mate with the unit and provide support and complete weathertight installation when properly installed. Adhesive back polyurethane sealing strips shall be provided to ensure an airtight seal between supply and return openings of the curb and unit. The roof curb design allows field fabricated ductwork to be connected directly to the curb. Curb ships knocked down for field assembly, and includes factory installed wood nailer strips. Electric Heaters Each heater assembly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat modules shall be UL listed. Single Source Power Entry This accessory when used with electric heat accessory shall allow single source power connection to unit and heater combination. Single source power entry kits shall have specific matching heater(s). Kit shall include high voltage terminal blocks, fuse blocks and fuses, cut - to -length interconnecting wiring, and junction box (if required) to provide power sources with fuse protection as required for both the unit and accessory heater. Kit components shall install within the heater cabinet in the heater access section. Single source branch power circuit shall be protected and wired in accordance with local codes. 12 4WCC4024A-SUB-1 B-EN Mechanical Specifications Fully Modulating Economizer This accessory shall be field installed and be composed of the following items: 0-100 % fresh air damper, damper drive motor, fixed dry bulb enthalpy control, and low voltage pigtails for electrical connections. Solid state enthalpy or differential enthalpy control is optional. Economizer operations shall be controlled by the preset position of the enthalpy control. A barometric relief damper shall be standard with the economizer and provide a pressure operated damper that shall be gravity closing and prohibit entrance of outside air on equipment "off" cycle. Economizer requires BAYRLAY004A relay kit to interface the economizer to the heat pump. Manual Outside Air Dampers Rain hood and screen shall be field installed. Suitable for up to 25% outside air. Start Kit Extra compressor starting capacity for single phase equipment. Control Options Standard Indoor Thermostats Two stage heating/cooling or one stage heating/cooling thermostats shall be available in either manual or automatic changeover. Programmable Electronic Night Setting Thermostat Programmable electronic thermostat shall provide heating setback and cooling setup with 7—day programming capability. 1H/1C or 21-1/2C models available. cOTUS ST Intertek The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com. The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. ©2014 Trane AW)4WCC4024A—SUB-IB-EN 15Jan2015 Ingersoll Rand Supersedes 4WCC4024A—SUB-1A-EN (October2014)