REVIEWED BLD2021-0672+Manufacturer_Specifications_and_Installation_Instructions+5.14.2021_10.26.21_AM+2197171
Direct -Expansion Fan Coil Units Installation, Start -Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS ............... 1 DESCRIPTION AND USAGE ............... 1,2 INSTALLATION ............................2-6 Step 1 — Inspect Equipment ................ 2 Step 2 — Mount Fan Coil ................... 2-4 • FLOOR MOUNTING IN VERTICAL UPFLOW AIRFLOW POSITION • ACCESSORY RETURN AIR PLENUM • FLOOR; WALL OR CEILING MOUNTING IN HORIZONTAL AIRFLOW POSITION • WHEN SUSPENDING UNIT FROM THE CEILING OR WALL • MOUNTING IN DOWNFLOW POSITION • DUCTWORK Step 3 — Connect Ductwork to Unit Supply and Return Air Openings ........... 4,5 • DUCTWORK SPECIFICATIONS • DUCTWORK ACOUSTICAL TREATMENT • RIGHT -SIDE RETURN Step 4 — Connect Refrigerant Liquid • MECHANICAL CONNECTION • SWEAT CONNECTION Step 5 — Make Primary Condensate Drain Line Connection ..................... Step 6 — Make Secondary Condensate Drain Line Connection ..................... ELECTRICAL DATA AND WIRING ......... 5-9 Step 7 — Install a Branch Circuit Disconnect Switch(es) per NEC ............ 5,6 Step 8 — Bring Line Power Leads into Unit ................................... 6 Step 9 — Connect Ground Lead to the Ground Connection in Cooling Control Kit or Electric Heater ............... 6 • THREE -SPEED FAN MOTOR Step 10 — Set Fan Motor Speed ............ 6 Step 11 — Connect Control Power Wiring (24-Volt) with Cooling Control Kit or Electric Heater.. .. ....... 6 • COOLING WIRING CONNECTIONS START-UP ................................. 9 SERVICE AND MAINTENANCE ........... 10-11 SAFETY CONSIDERATIONS Installation and servicing of air conditioning equip- ment can be hazardous due to system pressure and elec- trical components. Only trained and qualified service personnel should install, repair or service air conditioning equipment. Untrained personnel can perform basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air condi- tioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety pre- cautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available for all brazing operations. Before performing service or maintenance operations on system, turn off main power switches in indoor unit and outdoor unit. Turn off accessory heater power switch if applicable. Electrical shock could cause personal injury. IMPORTANT: This unit may include a factory - installed fan coil drip eliminator. The eliminator has been installed especially for high -humidity appli- cation, for vertical installation only. t CAUTION. Do not install eliminator -equipped fan coils in horizontal applications. DESCRIPTION AND USAGE Use standard Models 40AQ in cooling -only, electric heat and heat pump systems. Units consist of a coil (with a vertical condensate pan), a horizontal drain pan, cool- ing controls or electric heaters, 3-speed direct -drive fan/ motor assembly and filter section with cleanable filter — all within an insulated cabinet. Units may be mounted in vertical upflow, downflow or horizontal airflow arrange- ments and are suitable for "attic type" installations. M odels 40AQ — B B (bare box) are identical to stand- ard units except that electric heaters, horizontal drain pan and cooling controls are offered as accessories only. Units may be mounted in vertical upflow or downflow arrangements. Models 40AQ — BU (bare universal) contain stand- ard horizontal drain pan and can be mounted in vertical upflow, downflow and horizontal arrangements. Electric heaters and cooling controls are offered as accessories. Models 40AQ080 and 40AQ120 Fan Units consist of a multi -speed direct -drive blower and per- manent, washable air filter in an insulated casing with access panels. The 40ET900024 evaporator coil is avail- able as an accessory for 40AQ080; the 40ET900036 evaporator coil is available as an accessory for 40AQ120. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 11 14 PC 101 Catalog No.534-025 Printed in U.S.A. Form 40AQ-17SIM Pg 1 12-86 Replaces:40AQ-14SIM Tab 13c 12c For replacement items contact Distributor. Table 1 — Physical Data and Dimensions (See Fig. 1) MODEL 40AQ 018 024,080 1 030 1 036,120 OPERATING WT* (lb) 69 83, 74 1J55 11.7, 114,105 (Kg) 31.4 37.6, 33.6 47.6 FAN Rpm (3-Speed) 950/850/750 Air Discharge Upflow/Horizontal/Downflow Nominal (Cfm) 675 900 1050 1150 1 (L/s) 319 425 495 543 PSC Motor (Hp) 1/$ 1A /3 1/3 (kW) .09 .18 .24 .24 DIMENSIONS Length A (ft-in.) 1-03/16 1-2% 1-5Y4 1-9 (mm) 310 365 438 533 Width B (ft-in.) 1-91/ (mm) 546 Height C (ft-in.) 2-91% 3-23% 3-411/16 3-6 mm 845 975 1034 1067 DUCT INLET D (ft-in.) :25:1 1-01/e 1-21y,6 1-63/a (mm) 308 373 467 E (ft-in.) 1-63/4 _ (mm) 476 DUCT OUTLET (ft-in.) F 0-93/,6 1-01/16 1 1-21$/,6 1-6% (mm) 299 306 379 473 G (in.) 911/16 (mm) 246 CONNECTIONS Suction, ODFt H (mm) 15.87 19.05 Liquid, ODFt d (in.) (mm) 3/8 9.52 Condensate, (in) 3/4 FPT PSC — Permanent Split Capacitor "Weights indicated are for standard units. Bare box 40AQ weights are 59, 78, 96 and 110 lb (26:8, 35.4, 43.5, 49.9 kg) respectively. tSuction line connection is Compatible Fitting, liquid line connection is %-in. SAE flare fitting. Horizontal condensate pan, downflow kit and base, and accessory return air plenum are also available as accessories. All 40AQ units may be used with ductwork; or for free -blow applications when not equipped with electric heaters. Use accessory downflow kit for all downflow applications. Install units in conditioned or uncondi- tioned spaces. All units are tested for installation in unconditioned spaces per ARI standards (80 F [26.7 C] db, 75 F [23.9 C] wb indoor temperature; 80 F [26.7 C] db outdoor temperature). IMPORTANT: When any fan coil is installed over a finished ceiling and/or living area, a secondary condensate pan should be installed under the entire unit (see Step 6). Insulate supply and return air ductwork in uncon- ditioned spaces. Cover insulation with a vapor barrier. Filter Section comes mounted on return air end of fan coil. Filter section includes a reversible filter rack with 5/8-in. (I6-mm)duct connection flange on one side. The filter section is attached to unit either with flanges exposed or turned over so flanges are inside unit. The permanent one -in. (25-mm) filter media pulls out for easy removal and cleaning. Electric Heater — See Table4 and 5 for fan coil/ electric heater combinations. Electric heaters have both heating and cooling controls that include a control circuit transformer, indoor fan relay and low -voltage connection. Cooling Control Kit is a field -installed option re- quired on 40AQ, BB or BU units without electric heater. The kit contains a 60-va transformer, indoor fan relay and low -voltage connections. Cooling control kit is not re- quired when electric heater is used. Heaters are equipped with cooling and heating controls. AccuRater m System Refrigerant Control (by- pass type) is factory installed on 40AQ units. See Table 7 for factory -supplied pistons. Certain combinations of heat pump or condensing unit and fan coil require field replacement of the piston for optimum efficiency. See outdoor unit instructions for required piston. Bypass Type AccuRater Components are shown in Fig. 16. The AccuRater piston has a refrigerant meter- ing hole through it and is field replaceable. INSTALLATION Step 1 — Inspect Equipment — File claim with shipping company if shipment is damaged or incomplete. NOTES: 1. A drain pan extender is taped under the coil unit (exc. on 018 size). For vertical upflow or downflow applications, remove and discard pan. For horizontal application, drain pan extender must be repositioned (024, 030, 036 sizes only) as described in Step 2, hori- zontal airflow position. See Fig. 4. 2. An absorbent pad (Fig. 2) is factory installed over end of suction tube manifold. Pad eliminates condensate drip from end of suction manifold when unit is in horizontal position. Leave pad in position, do not remove.. Step 2 — Mount Fan Coil — Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for ,wiring, piping and servicing unit, Fig. 1. �F g-g (22mm) „(16mm) = �E eKO FOR CONTROL WIRING M'A DUCT CONN. +' FLANGE 11(35 mm) (018, 024) OR 14. (45 mm) (030, 036) KO T.. FOR POWER WIRING C ELECTRIC HEATER AND FAN SECTION ACCESS PANEL HORIZONTAL* CONDENSATE CONN. 40AQ1. 4 FPT PRIMARY / DRAIN CONN. d-LIQUID LINE CONN.\ H-SUCTION LINE CONN.� UPFLOW CONDENSATE CONN. 4'FPT SECONDARY_ DRAIN CONN. 4 FPT PRIMARY DRAIN CONN. 41"FPT SECONDARY DRAIN CONN. ALTERNATE (INTERNAL) /POSITION OF 1,06 mm) FILTER SECTION FLANGESt FILTER SECTION+ MINIMUM SPACE I -9 (530 mm) yFOR SERVICE 'Install accessory condensate pan on 40AQ bare box units to provide horizontal condensate drains. tFllter section may be turned over to provide external duct con- nection flange. Airflow Certified dimension drawings available on request. Fig. 1 — Dimensions and Connections (See Table 1) O Carrier HEATING & COOLING Product Data Comfort' S E R I E S ComfortTM 10 38YKC (60 Hz) 10 SEER Heat Pump Sizes 018 thru 060 The 38YKC Outdoor Sections of Split -System Heat Pumps are designed for quiet, reliable heating during the winter and cooling during the summer. These heat pump systems provide economy of operation through energy conservation. These units provide SEER ratings up to 11.7 and HSPF up to 8.5 when used with components designated by Carrier. They transfer heat from outdoor air during the heating season and, by automatically reversing the refrigerant cycle, remove indoor heat and excess humidity during the cooling season. All models are listed with ARI, UL (U.S. and Canada) and CEC. All models are offered in 208/230v. FEATURES/BENEFITS Compressor — Each compressor is mounted on rubber isolators for additional sound reduction. Continuous operation is approved down to —30°F (-34.4°C) in the heating mode and down to 550F (12.8°C) in the cooling mode. (See heating and cooling performance tables.) Reliable Standard Features — Includes a suction accumulator that minimizes the amount of liquid refrigerant that reaches the compressor; loss of charge protection; crankcase heater on all sizes except 048; and defrost board with time/ temperature defrost function. All units are equipped with a discharge muffler to minimize gas pulsation in heating mode. Defrost Control Board — Incorporates a defrost relay, defrost timer, and low -voltage terminations. Copyright 2004 Carrier Corporation Form 38YKC-7PD The defrost control is a time and temperature initiation/termination control which includes 3 field - selectable time periods of 30, 50, and 90 minutes. WeatherArmorTM III System includes three components: Casing steel is galvanized and coated with a layer of zinc phosphate. A modified polyester powder coating is then applied and baked on, providing each unit with a hard, smooth finish that will last for many years. —All screws on cabinet exterior are coated for a long-lasting, rust - resistant, quality appearance. The coil is protected with an enhanced coil guard. With spacing of 3/8-in. and construction of coated wire, the guard helps protect from inclement weather (hail), vandalism, and incidental damage. Unit Design — All units are equipped with totally enclosed fan motors for greater reliability under rain and snow conditions. The large, wraparound coil uses copper tubes and enhanced sine wave aluminum fins and is designed for optimum heat transfer during heating and cooling. The vertical air discharge carries the sound and air up and away from adjacent patio areas and foliage. Coil can be cleaned with a common garden hose. Model number nomenclature 38YKC 10 SEER Electric Heat Pump Nominal Capacity 018 — 18,000 Btuh 042 — 42,000 Btuh 024 — 24,000 Btuh 048 — 48,000 Btuh 030 — 30,000 Btuh 060 — 60,000 Btuh 036 — 36,000 Btuh 018 External Service Valves — Both service valves are brass, front seating type with sweat connections. Each valve has a service port for ease of checking operating refrigerant pressures. Valves are externally located so refrigerant tube connections can be made quickly and easily. A third service port is located on the service panel for ease of checking operating suction pressure in the heating mode. Warranty — Standard 5-year limited warranty on all parts and a 10-year limited warranty on compressor. 1 1 Packaging Series Electrical 3 — 208/230-1 This heat pump can be part of a Comfort Heat Pump System which can provide higher heating supply air temperatures, as well as up to 30 times more humidity removal in cooling mode. A Comfort Heat Pump System requires the use of a Variable -Speed Fan Coil with C0m ort Thermidistat Control, Comfort Zone II, or Infinity HEAT PUMP SYSTEM Control. OU", ANDA CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI. Physical data G�t.\e� Cor pray/off BSI APPROVALS ISO 9001 Nuimu EN 29001 ® ` ACCBO I7NN BS 5750 PART 1 Of CNNFICAINN \ b ANSVASOC 091 5�9001 #PZg� CERTIFICATE NO. FM 28768 REGISTERED QUALITY SYSTEM. c U(�) L us UNIT SIZE 018-32, 33 024-31,32 030-31,32 036-32, 33 042-32, 33 048-33, 34 060-32, 33 OPERATING WEIGHT (Lb) 139 165 199 215 229 268 293 COMPRESSOR Type Reciprocating Scroll REFRIGERANT R-22 Control Piston Charge (Lb)* 4.13 4.38 5.50 7.13 8.13 8.81 12.38 CONDENSER FAN Air Discharge Vertical Air Qty(CFM) 1500 1900 2400 3100 2900 2900 3100 Motor HP 1/12 1/10 1/8 1/4 1/4 1/4 1/4 Motor RPM (60 Hz) 1100 1100 825 1100 1100 1100 1100 CONDENSER COIL Face Area (Sq Ft) 8.72 10.99 12.17 18.25 12.17 15.21 18.25 Fins per In. 20 25 20 20 20 20 20 Rows 1 1 1 1 2 2 2 Circuits 2 2 3 3 4 5 6 CONNECTION (In. ID) Sweat Vapor 5/8 I 5/8 I 3/4 I 3/4 I 7/8 I 7/8 I 7/8 Liquid 3/8 REFRIGERANT TUBESt (In. OD) Vapor (0-50 Ft Tube Length) 5/8 5/8 3/4 3/4 7/8 7/8 1-1/8 Vapor (Max Diameter for Long -Line Applications) 3/4 3/4 7/8 7/8 1-1/8 1-1/8 1-1/8 Liquid (0-50 Ft Tube Length) 3/8 Liquid (For Long -Line Applications) 3/8 The factory refrigerant charge is for 15 ft of interconnecting tubing. For tubing lengths over 50 ft horizontal or 20 ft vertical differential, consult the Residential Split -System Long -Line Application Guideline for additional refrigerant requirements. t Tube sizes are for runs up to 50 ft. For tube sets between 50 and 175 ft, consult the Residential Split -System Long -Line Application Guideline. NOTE: See unit Installation Instructions for proper installation. METERING DEVICE UNIT SIZE SERIES OUTDOOR PISTON INDOOR PISTON* 018 32,33 43 57 024 31,32 46 65 030 31,32 52 70 036 32,33 1 61 176 042 32,33 63 80 048 33,34 70 86 1 060 32,33 78 98 Piston shipped with outdoor unit and must be installed in approved indoor coil. CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE) UNIT SIZE SERIES REQUIRED SUBCOOLING (°F) 018 32,33 15 024 31,32 15 030 31,32 15 036 32,33 15 042 32,33 15 048 33,34 15 060 32,33 15 RUUD GENERAL DATA-RJKA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJKA- Series A036CK A036CL A036CM A036DK Cooling Performances Irs "PEES Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 37,600 [11] 37,600 [11] EER/SEERz 9.6/10.25 9.6/10.25 9.6/10.25 9.6/10.25 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] 1200/1200 [566/566] ARI Net Cooling Capacity Btu [kW] 36,000 [10.5] 36,000 [10.5] 36,000 [10.5] 36,000 [10.5] Net Sensible Capacity Btu [kW] 26,587 [7.8] 26,587 [7.8] 26,587 [7.8] 26,587 [7.8] Net Latent Capacity Btu [kW] 9413 [2.8] 9413 [2.8] 9413 [2.8] 9413 [2.8] Net System Power kW 3.75 3.75 3.75 3.75 Heating Performance (Heat Pumps) Heating Temp. Btuh [kW] Rating 37,000 [10.8] 37,000 [10.8] 37,000 [10.8] 37,000 [10.8] System Power KW/COP 3.6/3.04 3.6/3.04 3.6/3.04 3.6/3.04 Low Temp. Btuh [kW] Rating 21,600 [6.3] 21,600 [6.3] 21,600 [6.3] 21,600 [6.3] System Power KW/COP 3.2/1.98 3.2/1.98 3.2/1.98 3.2/1.98 HSPF (Btu/Watts-hr) 6.8 6.8 6.8 6.8 Compressor No./Type 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll 1/Copeland Scroll Outdoor Sound Rating (dB)3 83 83 83 83 Outdoor Coil -Fin Type Louvered Louvered Louvered Louvered Tube Type Smooth Smooth Smooth Smooth Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 16.91 [1.57] 16.91 [1.57] 16.91 [1.57] 16.91 [1.57] Rows / FPI [FPcm] 1 / 18 [7] 1 / 18 [7] 1 / 18 [7] 1 / 18 [7] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Indoor Coil -Fin Type Louvered Louvered Louvered Louvered Tube Type Smooth Smooth Smooth Smooth Tube Size in. [mm] 0.3125 [7.9] 0.3125 [7.9] 0.3125 [7.9] 0.3125 [7.9] Face Area sq. ft. [sq. m] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48] 5.16 [0.48] Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] Outdoor Fan -Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [Us] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan -Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254254] 1/10x10 [254x254] Drive Type/No. Speeds Direct/3 Belt/Variable Belt/Variable Direct/3 No. Motors 1 1 1 1 Motor HP 1/2 1/2 3/4 1/2 Motor RPM 1725 1725 1725 1725 Motor Frame Size 48 56 56 48 Filter -Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] (2)1x25x16 [25x635x406] Refrigerant Charge Oz. [g] 99 [2807] 99 [2807] 99 [2807] 99 [2807] Weights Net Weight lbs. [kg] 480 [218] 480 [218] 480 [218] 480 [218] Ship Weight lbs. [kg] 495 [225] 495 [225] 495 [225] 495 [225] See Page 15 for Notes [ ] Designates Metric Conversions 7 U) a) c .U) -0 O L O C: �+- a) cz U E �E C�ONO, Carriers 50YO100 Single-PaCkage Heat Pumr) for YbAr-Round Comfort Plus Outstanding Efficiency Conditioning your home or business for maximum comfort all year long involves not only cooling and de- humidifying indoor air in the summer, but also heating, humidifying and filtering the air in colder months. Carrier's 50YQ heat pump can do it all with a remarkable efficiency that saves energy costs across the board. Built in the Carrier tradition of air conditioning excellence, the 50YQIQ0 Series provides a total package for your comfort needs during all seasons. The 50YQ heat pump is available in 5 sizes, from 24,000 to 48,500 Btuh cooling and from 23,600 to 52,500 Btuh heating. So you can choose the size that's just right for your res den tial/manufactured home or com- mercial building, and enjoy the benefits of comfort plus economy for many years to come. The heat pump achieves its extra- ordinary efficiency because it collects and moves heat from one place to another rather than producing it directly. On the cooling cycle, the unit pumps heat and humidity from inside your home to the outdoors, where they are dispersed. On the reverse cycle, the heat pump recovers heat from outdoors and pumps it inside to warm the indoor air. Even in the coldest weather (there's re- coverable heat in air at temperatures down to absolute zero [-460 F]), the heat pump can collect and concen- trate heat from the outdoor air to keep your home or office cozy. This principle of operation means that the heat pump saves energy whenever you use it. The 50YQ100 has cooling SEER's of 8.5 and higher, and C.O.P.'s for -heating of 2.8, which means that at 47 F the heat pump produces almost 3 times as much energy as it consumes. Depending on the temperature, your Carrier heat pump will be approximately 2 to 3 times more efficient than electric resistance heat. So consider the 50YQ100 single - package heat pump when selecting an air conditioning system for your home or business — it's the ideal unit for a variety of applications. VL Installation without complication The 50YQ100 arrives on the site ready to go. Completely wired, piped and charged at the factory, it installs quickly and easily. Connect electrical power and ductwork - that's all there is to it. An excellent unit for buildings that require crawl space ductwork installation; the 50YQI00 fits right in. it's also ideal for conditioning manu- factured homes, providing ali-season living comfort wherever you are. An operating sensation Time 50YQ100 performs with quiet, dependable efficiency and is certified for residences and commercial build- ings. The key to its operating effective- ness is the fine collection of matched heat pump components — computer designed, quality selected and tested to assure years of reliable operation. s Rugged hermetic compressor — Sealed against air, dirt, and moisture at the factory to assure long life. Internal safeguards protect the motor from costly damage. Crankcase heat- ers prevent refrigerant dilution, pro- mote proper lubrication, even after extended periods of shutdown. Backed by Carrier's 5-year warranty.* e large capacity coils -- With increased coil face area for greater air contact and optimum heat transfer. During warm weather the large 3-row indoor coil cools the air and lowers humidity effectively. The 2-row out- door coil rejects heat to the atmos- phere. Coils reverse roles during cool weather operation. Five-year war- ranty on the outdoor coil.* * Nlultispeed indoor fan — Set the fan for most efficient airflow; fan moves large quantities of air slowly, quietly. Resiliently mounted to mini- mize vibration. Easily removable for servicing. o Quiet outdoor fan — Sweeps air and sound up and away. Vertical dis- charge minimizes noise and protects shrubbery. s AccuRaterT" metering device — Carrier's patented, dual -piston. Accu- Rater device automatically meters the rate of refrigerant flow to meet a wide range of outdoor temperature conditions. Provides precise control' of refrigerant flow for maximum system efficiency. Eliminates reed for check valves and the double flow control devices required on many competitive heat pumps. Included in -line strainers are easy to service. *See your Carrier dealer for complete warranty details. THE HEAT PUMP'S REVERSE CYCLE OPERATING PRINCIPLE 1q,1,6 - W) HEATING CYCLE HEAT REJECTED ROOM AIR F ER ATOR COIL COMPRESSOR COOLING CYCLE HEAT AIR TO ROOM ABSORBED I I -, I EVAPORATOR COIL CONDENSER COIL COMPRESSOR 4 HEAT ABSORBED HEAT REJECTED COIL 2 • *Crankcase beater -- Prevents dilution of Oil by refrigerant during shutdown periods. o Suction line accumulator — Pro tects compressor from refrigerant — — --- floodback. �So 4 Service, with ease and economy The 50YQIOO is engineered to keep service and maintenance to a mini- mum. Components are selected for years of trouble -free operation. Emit 'A panels are readily removed for access to all components. Reduces labor g cost and unit down time. rA%(.",cEo",:Ssones MODEL ®Time Guard IA device — Prevents PART NO _ DESCRIPTION 50YQ costly compressor damage that could Low -Voltage Control Honeywell Thermostat HH07AT171 and Occur from rapid recycling. Provides 99TZ900401 _ Thermostat Subbase HH93AZ173 —Automatic Changeover a 5-minute delay before compressor 99TZ900411 Low -Voltage Control Honeywell Thermostat HH07AT171 and - restart. Thermostat Subbase HH93AZ175 — Manual Changeover Low Voltage Control White Rodgers Thermostat and All O Service Sent control — Ener- 99TZ90021106 Subbase (Six 38CQ900191) Automatic Changeover Low Voltage Control White Rodgers Thermostat and gizes warning light at indoor thermo- 99TZ90022106 Subbase (Six 38CQ900211) — Manual Changeover $tat If compressor is not operating 38CQ900152 Solid -State Time GuarjZ Control — _ -_- - and service is -required. --4 — Sentry Service Sentry _ All __ _ _ 9 . __ _ __ __ _ - _ -__.. -_ . �► Electric beaters — Single-phase 38RQ900032 � Outdoor Thermostat v 50YM900051 Duct Flange Kit in sizes from 5 kW to 20 kW. Mount 50YM90005106 Duct Flange Kit (Six -Pack) 124-142 in the Indoor air fan compartment. 88EJ10506A00 Electric Heater — 5 kW� _ O Outdoor thermostat package — 88EJ1075CA00 Electnc Heater 7 5 kW _ 124-142 Manually Set Outdoor thermostat 88EJ1100CAOO Electric Heater — 10 kW -- controls heaters so they operate Heater ic c 00 88EJ1150CA-Electric Hear 15 kW 130-142 _._.- _ _ _ _.. .__ _ _ _ . ... only when required for maximum 88EJ0050MA00 Electric Heater 5 kW u 88EJ0075MA00 Electric Heater 7 5 kW _ economy. 88EJ0100MA00 Electric Heater 10 kW - 148 ® Thermostat with subbase (24 v) 88EJ0150MA00 Electric Heater 15 kW — The Carrier line includes several 88EJ0200M400 Electric Heater 20 kW models to choose from. Provides con- _HC95DD121* _ _Start Capacitor —� 124 —_ Venient Selection of cooling, heating, HC95DE088* — Start Capacitors 130,,136 continuous Or automatic fan opera- HC95DE085* —Start Capacitor 142 ____®.__.__..._ _ .. —.- _ — - HC95DE070* Start Capacitor - - _ 148 tFon, manual Or auf02't�atlC C ange ---- _ -- _ -- _ _ —_ __.._ over. Thermostat with supplemental _11N61KB109* mStartRelay — u 12_4 — HN61 HB496* Start Relay - - 130 — eat switchand indicator light F5 HN61H6510* Start Relay_ 136 standard. HN61KB109* Start Relay 142 HN61_K_B075* Start Relay _— 148 38EB660002* Wire Bundle for Start Capacitor and Relay — — All 'Available through Carrier Service Parts Physical data and dimensions OPERATING WT (lb) REFRIGERANT —_ Oper Chg (lb)* Refrig Control COMPRESSOR T- Cylinders Rpm (60-Hz) OUTDOOR FAN Air Discharge Cfm Motor Hp Motor Rpm OUTDOOR COIL Rows... Fins/in. Face Area (sq ft) � INDOOR FAN Air Discharge ARI Cfm Range Cfm Motor Hp Motor Rpm INDOOR COIL Rows... Fins/in. Total Face Area (sq ft) 61MENSI6NS (ft - in) A B Ct LIQUID LINE PRESSURE SWITCH Cutout (psig) Cut -in (psig) DEFROST THERMOSTAT Opens Closes FILTER SIZE$ (in.) Disposable Permanent 320 320 333 375 1 417 - - - - ---�- -- -. --- ---- - - --•---- � - 53 53 53 62 7 3 AccuRaterTM - ----__--- _- _---- - Hermetically Sealed 2 3500 Propeller — Direct Drive Vertical 2500 I 2500 2500 2700 J 3200 1/5 + 1/5 1/4 I '/4 I 1/4 1075 Plate Fin 1 19 1 1 -- 9 17 9 1 -- 917 _ 10 83-- 125 -- 800 700-950 '/5 2 13 405 Centrifugal — Direct Drive, 3 Speed Horizontal 1080 1230 1 1485 850-1200 1000-1350 1367-1708 1/5 1/2 1100/1050/900 Plate Fin 3 13 j 3 13 3 13 405 405 _ 478 4-0'/e 3-61/4 1725 1633-2040 1/2 3 .13 — 5 52 -- 1-1 15/8 _ — 1 2_35/8 2-75A 5 20 • 80 F 27 F __ _-_ --y --- - --- - - -__ I yJ 15x20 _----_ . _ ._ —� 20x25 20x25 15x20(2) 20x20(2) 20x20 _ _ 20x20 — 15x20 20x20 20x25 20x25 15x20(2) *Factory refrigerant charge j Dimension C includes one -in built-in base support channels tRecommended field -supplied filters are one -in thick B A AI11 e CONDUIT CONTROL I V C'_;• WIRING ! e ` CONDUIT. I ; CONTROL > e ' WIRING k C I4 DKO ELECTRIC A l le DIAM KNOCKOUT HEAT ELECTRIC HEAT P' 1114 131. 1 Ie KO DAM KNOCKOUT---- Cf g" LINE DI AM WIRING WIRING'`w� 8 CONN CONN'' ? II I •; [INDOOR AIRFLOW — I -2� E> INDOOR AIRFLOW OUTDOOR AIRFLOW RIGHT SIDE VIEW OUTDOOR AIRFLOW RIGHT SIDE VIEW 50YQ 124-142 50YQ 148 Space required for service on front, rear and left side is 3 ft, 0 inches Space required for service on right side of unit is one ft, 0 inches 4 Submittal 2-1/2 Ton Convertible Air Handler TEM4AOB3OS31 SB T Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. January 2018 TEM4A0B30-SUB-1 C-EN 40H Ingersoll Rand Outline Drawing n MINIMUM UNIT CLEARANCE TABLE SERVICE CLEARANCE (RECOMMENDED) SIDES 2" FRONT 21" BACK 0" INLET DUCT I.. OUTLET DUCT N/A NOTE: THIS UNIT IS APPROVED FOR INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL AS STATED ON THE UNIT RATING NAMEPLATE LJ 1,331 7 18. 75 I.12 3.69 38 L 2.15 E F D W PRODUCT DIMENSIONS Air Handler Model A B C D E F H Flow Control Gas Line Braze TEM4AOB3OS31SB 45.02 18.50 1 16.50 16.75 4.68 7.33 18.34 TXV 3/4 All dimensions are in inches TEM4A0B30-SUB-1 C-EN Product Specifications MODEL TEM4AOB3OS31SB RATED VOLTS/PH/HZ 208-230/1/60 RATINGS(a) See O.D. Specifications INDOOR COIL — Type Plate Fin Rows—F.P.I. 3-14 Face Area (sq. ft.) 4.37 Tube Size (in.) 3/8 Refrigerant Control TXV Drain Conn. Size (in.)(b) 3/4 NPT DUCT CONNECTIONS See Outline Drawing INDOOR FAN —Type Centrifugal Diameter -Width (In.) 11 X 8 No. Used 1 Drive - No. Speeds Direct - 3 CFM vs. in. w.g. See Fan Performance Table No. Motors — H.P. 1-1/3 Motor Speed R.P.M. 1075 Volts/Ph/Hz 208-230/1/60 F.L. Amps 2.0 FILTER Filter Furnished? (c) No REFRIGERANT R-410A Ref. Line Connections Brazed Coupling or Conn. Size — in. Gas 3/4 Coupling or Conn. Size — in. Liq. 3/8 DIMENSIONS H x W x D Crated (In.) 46 x 21 x 24 Uncrated 45-1/8 x 18-1/2 x 21-1/8 WEIGHT Shipping (Lbs.) / Net (Lbs.) 116/110 (a) These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data. (b) 3/4" Male Plastic Pipe (Ref: ASTM 1785-76) (0 Remote filter required. Minimum Airflow CFM TEM4AOB3OS31SB Heater Minimum Heat Speed Tap With Heat Without Heat Pump Pump BAYHTR1504BRK, BAYHTR1504LUG, Low Low BAYHTR1505BRK, BAYHTR1505LUG BAYHTR1508BRK, BAYHTR1508LUG, BAYHTR1510BRK, Low Low BAYHTR1510LUG, BAYHTR351OLUG BAYHTR1517BRK Med Low BAYHTR3517LUG High Low TEM4A0B30-SUB-1 C-EN Heater Pressure Drop Table TEM Air Handler Models Airflow CFM Number of Racks Heater Racks 1 2 3 4 Heater Model No. of Racks Air Pressure Drop - Inches W.G. BAYHTR1504 1 1800 0.02 0.04 0.06 0.14 BAYHTR1505 1 1700 0.02 0.04 0.06 0.14 BAYHTR1508 2 1600 0.02 0.04 0.06 0.13 BAYHTR1510 2 1500 0.02 0.04 0.06 0.12 BAYHTR3510 3 1400 0.02 0.04 0.06 0.12 BAYHTR1515 3 1300 0.02 0.04 0.05 0.11 BAYHTR1517 3 1200 0.01 0.04 0.05 0.10 BAYHTR3515 3 1100 0.01 0.03 0.05 0.09 BAYHTR3517 3 1000 0.01 0.03 0.04 0.09 BAYHTR1519 4 900 0.01 0.03 0.04 0.08 BAYHTR1520 4 800 0.01 0.03 BAYHTR1521 4 700 0.01 0.02 BAYHTR1525 4 600 0.01 0.02 TE M4AOB30-SUB-1 C-E N Performance and Electrical Data 1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters. 2. Heater model numbers may have additional suffix digits. Table 1. Air Flow Performance TEM4AOB3OS31SB(a) EXTERNAL STATIC AIRFLOW (in w.g) Speed Taps — 230 VOLTS Speed Taps — 208 VOLTS High Med Low t High Med Low t 0.1 1391 1305 1059 1338 1146 902 0.2 1305 1231 1029 1257 1098 868 0.3 1203 1138 970 1159 1027 817 0.4 1083 1027 884 1044 935 753 0.5 948 899 769 913 823 664 0.6 795 752 626 766 692 0.7 626 587 603 542 1. Values are with wet coil, no filter, and no heaters 2. CFM Correction for dry coil = Add 3% 3. t = Factory setting 0) For the TEM4AOB30S31SA in downflow applications, airflow must not exceed 1200 cfm due to condensate blow off. TEM4A0B30-SUB-1 C-EN Performance and Electrical Data Table 2. Electrical Data TEM4AOB3OS31SB 240 Volt 208 Volt No. of Capacity Heater Minimum Maximum Capacity Heater Minimum Maximum Heater Model No. Circuits/ Phases Amps per Circuit Overload Amps per Circuit Overload kW BTUH Circuit Ampacity Protection kW BTUH Circuit Ampacity Protection No Heater 2.0 * 3 15 2.0 * 3 15 BAYHTR1504BRK 1/1 3.84 13100 16.0 23 25 2.88 9800 13.8 20 20 BAYHTR1504LUG BAYHTR1505BRK 1/1 4.8 16400 20.0 28 30 3.6 12300 17.3 24 25 BAYHTR1505LUG BAYHTR1508BRK 1/1 7.68 26200 32.0 43 45 5.76 19700 27.7 37 40 BAYHTR1508LUG BAYHTR1510BRK 1/1 9.6 32800 40.0 53 60 7.2 24600 34.6 46 50 BAYHTR1510LUG BAYH6RK- Circuitit I ((aa) ) 9.6 32800 40.0 53 60 7.2 24600 34.6 46 50 2/1 BAYHTR1517BRK- 4.8 16400 20.0 25 25 3.6 12300 17.3 22 25 Circuit 2 BAYHTR3510LUG 1/3 9.6 32800 23.1 31 35 7.2 24600 20.0 27 30 BAYHTR3517LUG 1/3 14.4 49200 34.6 45 3050 10.8 36900 30.0 40 40 BAYHTR1517BRK with single circuit 1/1 14.4 49200 60.0 83 90 10.8 36900 51.9 73 80 power source kit BAYSPEKT201A * = Motor Amps (a) MCA and MOP for circuit 1 contains the motor amps TE WAOB30-SU BI C-EN Features and Benefits • Painted metal cabinet with captured foil face insulation • 2% or less air leakage • R-4.2 Insulating Value • Multi -Position UP/Down Flow, Horizontal Left/Right • ALL Aluminum Coil with Enhanced Patented Coil Fin • Electric Heaters with polarized plug connections (sold as accessory) • R-410A Thermal Expansion Valve • ECM Motor (3.5 — 5 Ton Models J • Low Voltage Pigtail Connections • Draw Through Design • Horizontal Drain pan • Single Color • Fused 24V Power • 3 year warranty • 10-year warranty registered • Optional extended warranty available Important_ Condensate management kit is required for all 5 ton air handler models installed in downflow applications. TEWA01330-SUB-1 C-EN 7 4B)Ingersoll Rand® Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands — including Club Caro, Ingersoll Rand@, Thermo King@ and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results. APIngersoll Rand T, THERMO KING 0 TXWE® ingersollrand.com ETA us Intertek Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. TEM4A0B30-SUB-1C-EN 08Jan2018 Supersedes TEM4A0B30-SUB-1B-EN (August2017) ©2014Ingersoll Rand Split System Heat Pump 4TWR403OG1000A Note: "Graphics in this document are for representation only. Actual model may differ in appearance." Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. March 2016 4TWR4030G-SUB-1A-EN 4ffiPingersollRand SERVICE PANEL ELECTRICAL AND REF COMPONENT CLEARANC PER PREVAILING COD TOP DISCHARGE AREA SHOULD BE ABOVE T SFEET) UNRESTRICTED SHOULD BE PLACED VEROOF RUN-OFF WATER DOES 40T POUR DIRECTLY OFROMy�N UNIT, AND ALALL L SURROUND14G SHR BBERtY ON) T�0 S I s. AND OTHER TWO SIDES UNRESTRICTED, ELECTRICAL SERVICE PANEL K 25 11 22,2 (1/8) pIA. HOLE LO9 VOLTAGE 28,6 t1-I/81 DIA, ITH 22,2 (1/8) DIA, HOLE IN4COCN ROL BOX BOTTOM FOR LECTRICAL P0'ER SUPPLY H I F J G LIQUID LINE SERVICE VALVE, CONNECTTIONEMAWITH BR4ZESAE FLARE PRESSURE TAP FITTINGS. K,O, FOR ALTERNATE ELECTRICAL ROUTING GAS LINE I/4 TURN BALL SERVICE VALVE, "D' I,D, FEMALE BRAZED CONNECTION WITH I/4" SAE FLARE PRESSURE TAP FITTING. Model Base A B C D E F G H J K 4TWR4030G 4 741 946 870 3/4 3/8 143 83 206 70 508 (29-1/8) (37-1/4) (34-1/4) (5-5/8) (3-1/4) (8-1/8) (2-3/4) (20) SOUND POWER LEVEL Model A -Weighted Sound Power Level [dB(A) ] Full Octave Sound Power [dB] 63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 4TWR4030G 75 84 73 70 72 73 65 58 50 Note: Rated in accordance with AHRI Standard 270-2008 *For reference only. 2 4TWR4030G-SUB-1A-EN 0 TRANE° Product Specifications OUTDOOR UNIT (a) (b) 4TWR4030GI000A POWER CONNS. — V/PH/HZ (c) 208/230/1/60 MIN. BRCH. CIR. AMPACITY 17 BR. CIR. PROT. RTG. — MAX. (AMPS) 25 COMPRESSOR CLIMATUFF@- SCROLL NO. USED — NO. STAGES 1 — 1 VOLTS/PH/HZ 208/230/1/60 R.L. AMPS (d)— L.R. AMPS 12.8 — 67.8 FACTORY INSTALLED START COMPONENTS (e) NO (Uses BAYKSKT263) INSULATION/SOUND BLANKET NO COMPRESSOR HEAT NO OUTDOOR FAN PROPELLER DIA. (IN.) — NO. USED 27.5 — 1 TYPE DRIVE — NO. SPEEDS DIRECT— 1 CFM @ 0.0IN. W.G. M 3440 NO. MOTORS — HP 1-1/8 MOTOR SPEED R.P.M. 825 VOLTS/PH/HZ 208/230/1/60 F.L. AMPS 0.77 OUTDOOR COIL — TYPE SPINE FIN— ROWS—F.P.I. 1-24 FACE AREA (SQ. FT.) 19.1 TUBE SIZE (IN.) 3/8 REFRIGERANT CONTROL EXPANSION VALVE REFRIGERANT LBS. — R-410A (O.D. UNIT) (g) 6 LBS., 13 OZ FACTORY SUPPLIED YES LINE SIZE — IN. O.D. GAS (h) (1) 3/4 LINE SIZE — IN. O.D. LIQ. 3/8 CHARGING SPECIFICATIONS SUBCOOLING 8°F DIMENSIONS H X W X D CRATED (IN.) 34.4 x 38.7 x 35.1 WEIGHT SHIPPING (LBS.) 248 NET (LBS.) 210 (a) Certified in accordance with the Air -Source Unitary Air -conditioner Equipment certification program, which is based on AHRI standard 210/240. (b) Rated in accordance with AHRI standard 270. M Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses. (d) This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current. (e) No means no start components. Yes means quick start kit components. PTC means positive temperature coefficient starter. Optional kit shown. M Standard Air — Dry Coil — Outdoor (9) This value approximate. For more precise value see unit nameplate. (h) Reference the outdoor unit ship -with literature for refrigerant piping length and lift guidelines. Reference the refrigerant piping software pub # 32-3312-xx or refrigerant piping application guide SS- APG006-xx for long line sets or specialty applications (xx denotes latest revision). 0) Trane outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit and 15 feet of tested connecting lines. If connecting line length exceeds 15 feet, then final refrigerant charge adjustment is necessary. Each additional foot over 15 feet requires 0.6 ozs of refrigerant. See the Installer's Guide for full charging instructions. 4TWR4030G-SUB-1A-EN 0 TRANE Mechanical Specification Options General The Outdoor Units are fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. Casing Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather -resistant powder paint finish on all louvered panels and the fan top panel. The corner panels are prepainted. All panels are subjected to our 1,000 hour salt spray test . The base is made of a CMBP-G30 weatherproof material to resist corrosion. Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and high pressure switch. High and low pressure controls are inherent to the compressor. A factory supplied liquid line drier is standard. Some models may require field installation. Compressor The compressor features internal over temperature, pressure protection and total dipped hermetic motor. Other features include: Centrifugal oil pump and low vibration and noise. Condenser Coil The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. Low Ambient Cooling As manufactured, this system has a cooling capacity to WE The addition of an evaporator defrost control permits operation to 40°F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30°F. Thermostats —Cooling only and heat/cooling (manual and automatic change over). Sub -base to match thermostat and locking thermostat cover. Evaporator Defrost Control — See Low Ambient Cooling. c t1 _ us :ISTED Intertek Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. (�)2016 Trane 4TWR4030G-SUB-1A-EN 01 Mar 2016 AW) Ingersoll Rand.. Supersedes (New) Submittal Split System Heat Pump 4TWR4018G1000A Note: "Graphics in this document are for representation only. Actual model may differ in appearance." Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. March 2016 4TWR4018G-SUB-IA-EN 4ffiPingersollRand SERVICE PANEL ELECTRICAL AND REF COMPONENT CLEARANC PER PREVAILING COD TOP DISCHARGE AREA SHOULD BE ABOVE T SFEET) UNRESTRICTED SHOULD BE PLACED VEROOF RUN-OFF WATER DOES NOT POUR DIRECTLY OFROMy�N UNIT, AND ALALL L SURROUND14G SHR BBERtY ON) T�0 S I s. AND OTHER TWO SIDES UNRESTRICTED, ELECTRICAL SERVICE PANEL K 25 11 22,2 (1/8) pIA. HOLE LO9 VOLTAGE 28,6 t1-I/81 DIA, ITH 22,2 (1/8) DIA, HOLE IN4COCN ROL BOX BOTTOM FOR LECTRICAL P0'ER SUPPLY H I F J G LIQUID LINE SERVICE VALVE, CONNECTTIONEMAWITH BR4ZESAE FLARE PRESSURE TAP FITTINGS. K,O, FOR ALTERNATE ELECTRICAL ROUTING GAS LINE I/4 TURN BALL SERVICE VALVE, "D' I,D, FEMALE BRAZED CONNECTION WITH I/4" SAE FLARE PRESSURE TAP FITTING. Model Base A B C D E F G H J K 4TWR4018G 2 730 724 651 3/4 3/8 127 57 194 38 457 (28-3/4) 28-1/2) (25-5/8) (5) (2-1/4) (7-5/8) (1-1/2) (18) SOUND POWER LEVEL Model A -Weighted Sound Power Level [dB(A) ] Full Octave Sound Power [dB] 63 Hz* 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 4TWR4018G 73 72 66 64 66 71 64 56 47 Note: Rated in accordance with AHRI Standard 270-2008 *For reference only. 2 4TWR4018G-SUB-1 A -EN 0 TRANE° Product Specifications OUTDOOR UNIT (a) (b) 4TWR4018G1000A POWER CONNS. — V/PH/HZ (c) 208/230/1/60 MIN. BRCH. CIR. AMPACITY 12 BR. CIR. PROT. RTG. — MAX. (AMPS) 20 COMPRESSOR CLIMATUFF@- SCROLL NO. USED — NO. STAGES 1 — 1 VOLTS/PH/HZ 208/230/1/60 R.L. AMPS (d)— L.R. AMPS 9 — 56 FACTORY INSTALLED START COMPONENTS (e) YES INSULATION/SOUND BLANKET NO COMPRESSOR HEAT NO OUTDOOR FAN PROPELLER DIA. (IN.) — NO. USED 19.1 — 1 TYPE DRIVE — NO. SPEEDS DIRECT— 1 CFM @ 0.0IN. W.G. M 1880 NO. MOTORS — HP 1 — 1/12 MOTOR SPEED R.P.M. 810 VOLTS/PH/HZ 208/230/1/60 F.L. AMPS 0.54 OUTDOOR COIL — TYPE SPINE FINTM ROWS—F.P.I. 1-24 FACE AREA (SQ. FT.) 11.3 TUBE SIZE (IN.) 3/8 REFRIGERANT CONTROL EXPANSION VALVE REFRIGERANT LBS. — R-410A (O.D. UNIT) (9) 6 LBS., 1 OZ FACTORY SUPPLIED YES LINE SIZE — IN. O.D. GAS (h) (i) 3/4 LINE SIZE — IN. O.D. LIQ. 3/8 CHARGING SPECIFICATIONS SUBCOOLING 10°F DIMENSIONS H X W X D CRATED (IN.) 30.1 x 30 x 26.7 WEIGHT SHIPPING (LBS.) 161 NET (LBS.) 141 (a) Certified in accordance with the Air -Source Unitary Air -conditioner Equipment certification program, which is based on AHRI standard 210/240. (b) Rated in accordance with AHRI standard 270. M Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses. (d) This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current. (e) No means no start components. Yes means quick start kit components. PTC means positive temperature coefficient starter. Optional kit shown. M Standard Air — Dry Coil — Outdoor (9) This value approximate. For more precise value see unit nameplate. (h) Reference the outdoor unit ship -with literature for refrigerant piping length and lift guidelines. Reference the refrigerant piping software pub # 32-3312-xx or refrigerant piping application guide SS- APG006-xx for long line sets or specialty applications (xx denotes latest revision). 0) Trane outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit and 15 feet of tested connecting lines. If connecting line length exceeds 15 feet, then final refrigerant charge adjustment is necessary. Each additional foot over 15 feet requires 0.6 ozs of refrigerant. See the Installer's Guide for full charging instructions. 4TWR4018G-SUB-1A-EN 0 TRANE Mechanical Specification Options General The Outdoor Units are fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. Casing Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather -resistant powder paint finish on all louvered panels and the fan top panel. The corner panels are prepainted. All panels are subjected to our 1,000 hour salt spray test . The base is made of a CMBP-G30 weatherproof material to resist corrosion. Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and high pressure switch. High and low pressure controls are inherent to the compressor. A factory supplied liquid line drier is standard. Some models may require field installation. Compressor The compressor features internal over temperature, pressure protection and total dipped hermetic motor. Other features include: Centrifugal oil pump and low vibration and noise. Condenser Coil The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. Low Ambient Cooling As manufactured, this system has a cooling capacity to WE The addition of an evaporator defrost control permits operation to 40°F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30°F. Thermostats —Cooling only and heat/cooling (manual and automatic change over). Sub -base to match thermostat and locking thermostat cover. Evaporator Defrost Control — See Low Ambient Cooling. c t1 _ us :ISTED Intertek Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. (�)2016 Trane 4TWR4018G-SUB-1A-EN 01 Mar2016 AW) Ingersoll Rand.. Supersedes (New) Submittal 1-1/2 Ton Convertible Air Handler TEM4AOB18S21SB T Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. January 2018 TEM4A0B18-SUB-1 C-EN 40H Ingersoll Rand Outline Drawing n MINIMUM UNIT CLEARANCE TABLE SERVICE CLEARANCE (RECOMMENDED) SIDES 2" FRONT 21" BACK 0" INLET DUCT I.. OUTLET DUCT N/A NOTE: THIS UNIT IS APPROVED FOR INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL AS STATED ON THE UNIT RATING NAMEPLATE LJ 1,331 7 18. 75 I.12 3.69 38 L 2.15 E F D W PRODUCT DIMENSIONS Air Handler Model A B C D E F H Flow Control Gas Line Braze TEM4AOB18S21SB 45.02 18.50 1 16.50 16.75 4.68 7.33 18.34 TXV 3/4 All dimensions are in inches TEM4A0B18-SUB-1 C-EN Product Specifications MODEL TEM4AOB18S21SB RATED VOLTS/PH/HZ 208-230/1/60 RATINGS(a) See O.D. Specifications INDOOR COIL — Type Plate Fin Rows — F. P.I. 3 - 14 Face Area (sq. ft.) 4.37 Tube Size (in.) 3/8 Refrigerant Control TXV Drain Conn. Size (in.)(b) 3/4 NPT DUCT CONNECTIONS See Outline Drawing INDOOR FAN — Type Centrifugal Diameter -Width (In.) 11 X 6 No. Used 1 Drive - No. Speeds Direct - 3 CFM vs. in. w.g. See Fan Performance Table No. Motors — H.P. 1-1/5 Motor Speed R. R M. 1075 Volts/Ph/Hz 208-230/1/60 F.L. Amps 1.2 FILTER Filter Furnished? (c) No REFRIGERANT R-410A Ref. Line Connections Brazed Coupling or Conn. Size —in. Gas 3/4 Coupling or Conn. Size — in. Liq. 3/8 DIMENSIONS H x W x D Crated (In.) 46 x 21 x 24 Uncrated 45-1/8 x 18-1/2 x 21-1/8 WEIGHT Shipping (Lbs.) / Net (Lbs.) 116/110 (a) These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data. (b) 3/4" Male Plastic Pipe (Ref: ASTM 1785-76) (c) Remote filter required. Minimum Airflow CFM TEM4AOB18S21SB Heater Minimum Heat Speed Tap With Heat Without Heat Pump Pump BAYHTR1504BRK, BAYHTR1504LUG, Med Low BAYHTR1505BRK, BAYHTR1505LUG BAYHTR1508BRK, BAYHTR1508LUG, BAYHTR1510BRK, Med Low BAYHTR1510LUG, BAYHTR351OLUG TEM4A0B18-SUB-1 C-EN Heater Pressure Drop Table TEM Air Handler Models Airflow CFM Number of Racks Heater Racks 1 2 3 4 Heater Model No. of Racks Air Pressure Drop - Inches W.G. BAYHTR1504 1 1800 0.02 0.04 0.06 0.14 BAYHTR1505 1 1700 0.02 0.04 0.06 0.14 BAYHTR1508 2 1600 0.02 0.04 0.06 0.13 BAYHTR1510 2 1500 0.02 0.04 0.06 0.12 BAYHTR3510 3 1400 0.02 0.04 0.06 0.12 BAYHTR1515 3 1300 0.02 0.04 0.05 0.11 BAYHTR1517 3 1200 0.01 0.04 0.05 0.10 BAYHTR3515 3 1100 0.01 0.03 0.05 0.09 BAYHTR3517 3 1000 0.01 0.03 0.04 0.09 BAYHTR1519 4 900 0.01 0.03 0.04 0.08 BAYHTR1520 4 800 0.01 0.03 BAYHTR1521 4 700 0.01 0.02 BAYHTR1525 4 600 0.01 0.02 TE M4AOB 18-SUB-1 C-E N Performance and Electrical Data 1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters. 2. Heater model numbers may have additional suffix digits. Table 1. Air Flow Performance TEM4A0B18S21SB EXTERNAL STATIC AIRFLOW (in w.g) Speed Taps - 230 VOLTS Speed Taps - 208 VOLTS High Med Low t High Med Low t 0.1 1094 927 773 1052 849 658 0.2 1032 880 735 990 807 624 0.3 955 818 678 915 750 578 0.4 864 739 601 826 679 518 0.5 759 645 505 723 591 441 0.6 639 534 389 606 490 0.7 505 408 476 374 1. Values are with wet coil, no filter, and no heaters 2. CFM Correction for dry coil = Add 3% 3. t = Factory setting Table 2. Electrical Data TEM4A0B18S21SB 240 Volt 208 Volt No. of Capacity Heater Minimum Maximum Capacity Heater Minimum Maximum Heater Model No. Circuits/ Phases Amps per Circuit Overload Amps per Circuit Overload kW BTUH Circuit Ampacity Protection kW BTUH Circuit Ampacity Protection No Heater 1.2 * 2 15 1.2 * 2 15 BAYHTR1504BRK 1/1 3.84 13100 16.0 22 25 2.88 9800 13.8 19 20 BAYHTR1504LUG BAYHTR1505BRK 1/1 4.80 16400 20.0 27 30 3.60 12300 17.3 23 25 BAYHTR1505LUG BAYHTR1508BRK 1/1 7.68 26200 32.0 42 45 5.76 19700 27.7 36 40 BAYHTR1508LUG BAYHTR1510BRK 1/1 9.60 32800 40.0 52 60 7.20 24600 34.6 45 45 BAYHTR1510LUG BAYHTR3510LUG 1 1/3 1 9.60 32800 23.1 1 30 30 7.20 24600 20.0 26 30 * = Motor Amps TEM4A0B18-SUB-1 C-EN Features and Benefits • Painted metal cabinet with captured foil face insulation • 2% or less air leakage • R-4.2 Insulating Value • Multi -Position UP/Down Flow, Horizontal Left/Right • ALL Aluminum Coil with Enhanced Patented Coil Fin • Electric Heaters with polarized plug connections (sold as accessory) • R-410A Thermal Expansion Valve • ECM Motor (3.5 — 5 Ton Models J • Low Voltage Pigtail Connections • Draw Through Design • Horizontal Drain pan • Single Color • Fused 24V Power • 3 year warranty • 10-year warranty registered • Optional extended warranty available Important_ Condensate management kit is required for all 5 ton air handler models installed in downflow applications. 6 TE WA0B 18-SUB-1 C-E N 4B)Ingersoll Rand® Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands — including Club Caro, Ingersoll Rand@, Thermo King@ and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results. APIngersoll Rand T, THERMO KING 0 TXWE® ingersollrand.com ETA us Intertek Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. TEM4A0B18-SUB-1C-EN 08Jan2018 Supersedes TEM4A0B18-SUB-1B-EN (August2017) ©2014Ingersoll Rand RTU 5-1, 5-275-3 Submittal Single Packaged Heat Pump 14 SEER Convertible 4WCC403OA1000A Note: "Graphics in this document are for representation only. Actual model may differ in appearance." Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and a i,cond it ion in equipment can be hazardous and requires specific knowledge and training, Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment, January2015 4WCC4030A-SUB-1B-EN (t#)Ingersoll Rand Product Specifications MODEL 4WCC4030A1000A RATED Volts/PH/Hz 208-230/1/60 Performance Cooling BTUH W 30400 Indoor Airflow (CFM) 985 Power Input (KW) 2.41 EER/SEER(BTU/Watt-Hr.)(e) 12.00/14.00 Sound Power Rating [dB(A)] (0 70 PERFORMANCE HEATING (High Temp.) BTUH 27200 Power Input (KW) 2.1 (Low Temp.) BTUH 16,700 Power Input (KW) 1.25 HSPF(BTUH/Watt-Hr) 8.0 POWER CONN.—V/Ph/Hz 208-230/1/60 Min. Brch. Cir. Ampacity, (a) 22.6 Fuse Size — Max. (amps) 35 Fuse Size —Recmd.(amps) 35 COMPRESSOR SCROLL VOLTS/PH/HZ 208-230/1/60 R.L. Amps —L.R. Amps 14.1/68.2 OUTDOOR COIL —TYPE SPINE FIN Rows/F.P.I 2 / 24 Face Area (sq. ft.) 13.32 Tube Size (in.) 3/8 Refrigerant Control EXPANSION VALVE INDOORCOIL—TYPE PLATE FIN Rows/F. P.I 4 / 15 Face Area (sq. ft.) 3.5 Tube Size (In.) 3/8 Refrigeration Control EXPANSION VALVE Drain Conn. Size (In.) 3/4 FEMALE NPT OUTDOOR FAN —TYPE SWEPT DIA.(IN.) 23.4 DRIVE/NO. SPEEDS DIRECT/3 CFM @ 0.0In. w.g. (e) 3270 Motor— HP/R.P.M 1 / 6/ 842 Volts/Ph/Hz 208-230 / 1 / 60 F.L. Amps/L.RAmps .65/1.65 INDOORFAN—TYPE CONSTANTTORQUEECM Dia. x Width (In.) 10.62 X 10.68 Drive/No. Speeds DIRECT/ 3 CFM @ 0.0 In. w.g. M SEE FAN PERF TABLE Motor — HP/R.P. M. 1/2 / 1050 Volts/Ph/Hz 208-230/1/60 F.L. Amps 4 FILTER/FURNXSHED NO Type Recommended THROWAWAY Recmd. Face Area (sq. ft) (g) 4.0 REFRIGERANT R-410 Charge (tbs.) 7.2 CHARGING SPECIFICATIONS Subcooling 14' DIMENSIONS H X D X W Crated (in.) 48 X 45 X 52 WEIGHT. Shipping (tbs.)/ Net (tbs.) 4101335 W Rated in accordance with AHRI Standard 210/240. M Rated in accordance with D.O.E. test procedure. W Sound Powervalues are not adjusted for AHRI 270-95 tonal corrections. (^� Calculated in accordance with currently prevailing Nat'l Electrical Cade. (0 Standard Air - Dry Coil — Outdoor. (n Standard Air - Dry Coil — Indoor t91 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent Filters are used size per manufacturer's recommendation with a clean resistance of 0.051, W.C. 4WCC403OA—SUB-1 B-EN Outline Drawings Figure 1. 2 — 3 TON MODELS 101 Nuu 25. 40 111 18. 3 18. 29 [231032] [23I32] I d.t 9I 161 SECTION Y-Y APICAL (6) SIDES of W.YnN DUCT ov[xu65 Note: The view labeled Bottom Side represents the base as viewed looking up from underneath the unit. 4WCC4030A-SUB-1 B-EN M Figure 3. 2 — 3 TON MODELS 304.80 1121 (INSIDE) 75.41 12-31/321 RECOMMENDED SERVICE CLEARANCE WIN. nTH ECONOMIZER BACK SIDE 304.8 1121 762.0 130) LEFT SIDE 362.0 001 914" 1361 RIGHT SIDE 609.6 124) FROM SIDE 1066.8141 CLEARANCE TO COMBUSTIBLE MATERIAL MM/IM. BOTTOM 0 BACK SIDE 25 A (11 LEST SIDE 152.4 16) RIGHT BIDE 152.4 (61 FRONT SIDE 304.E 112) TOP 914.1 (36) 359.79 (14-51321 24V ENTR 288.42 225!68 111-1111321 f8-7/8] 117.73 j [ 4 - 5 / 8 1 85.22 [3-11/321 Outline Drawings 73.46 6-27132) 406.40 (161 (INSIDE) .89 5181 f161 ( INSIDE ) BOTTOM DUCT OPENINGS —POWER58 ENTRY 28.58 [I-I/81 DIA. KNOCKOUT POWER ENTRT 28. 58 (I-I18) DIA. KNOCKOUT 2$. OS 34.93 [1-3/8) DIA. KNOCKOUT $0.01 [1-31/321 DIA. KNOCKOUT 15 I/321 SINGLE POINT ENTRY 34.93 [I-3181 DIA. KNOCKOUT RIGHT SIDE 50.01 [1-31/321 DIA. KNOCKOUT 62.71 [2-15/32) DIA. KNOCKOUT 4WCC403OA-SUB-18-EN Indoor Fan Performance (230v) Tablet. Horizontal Airflow 4WCC4030Al EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 O.5 0.6 0.7 0.8 0.9 1.0 LOW WATTS 119 128 136 145 155 - - - - - - CFM 1065 1012 951 894 829 - - - - - - MEDIUM WATTS 149 157 167 175 186 196 205 - - - - CFM 1150 1102 1046 993 938 877 828 - - - - HIGH WATTS - - 221 230 240 252 263 273 - - - CFM - - 1184 1136 1085 1032 978 934 - - - Table 2. Down Airflow 4 W CC4030Al EXTERNAL STATIC PRESSURE (IN. W G) MOTOR SPEED 0.0 0.1 0.2 1 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 COOLING WATTS 120 128 137 1 145 155 - - - - - - - LOW CFM 1054 1002 942 885 821 - - - - - - COOLING WATTS 149 158 167 176 186 197 206 - - - - - MED CFM 1138 1091 1035 983 928 868 820 - - - - COOLING WATTS - - 222 231 242 253 264 274 - - - - HIGH CFM - - 1173 1124 1074 1022 969 925 - - - 4WCC4030A-SUB-I B-EN Supplementary Electric Heater Table 3. BAYHTRV — Supplementary Electric Heaters ELECTRIC RATED HEATER NO. KW/STAGE MAX. FUSE CANADA UNIT HEATER VOLT- PHASE AMPS CAPACITY OF MCA OR HACR ONLY MAX. MODEL MODEL AGE STAGES CKT BKR CKTBKR KW BTUH 1 2 SIZE SIZE 4024-4060 BAYHTRV105 208/240 1 18/21 3.76/5.0 12800/ 1 3.76/ - 23/26 25/30 25/30 17100 5.0 4024-4060 BAYHTRV108 208/240 1 29/33 6.0/8.0 20500/ 1 6.0/ - 36/41 40/45 40/45 27300 8.0 4024-4060 BAYHTRV110 208/240 1 36/42 7.5/10.0 1 - 45/52 45/60 45/60 34100/ 10.0 4030-4060 BAYHTRVI15 208/240 1 54/63 11.27/ 38500/ 2 7.5/ 3.76/ 66/76 70/80 70/BO 15.0 51200 30.0 5.0 4048-4060 BAYHTRV120 208/240 1 72/83 15.0/ 51200/ 2 7.5/ 7,5/ 90/ g0/110 90/110 20.0 68300 30.0 50.0 104 4060 BAYHTRV125 208/240 1 90/ 18.78/ 64100/ 2 11.26/ 7.5/ 113/ 125/150 125/150 104 25.0 85300 15.0 10.0 130 Table 4. BAYSPEK —Single Power Entry Kit SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION UNIT MODEL SINGLE POWER ENTRY KIT HEATERMODEL MIN CKT AMP MAX OVER -CURRENT DEVICE BAYSPEK60 BAYHTRV105 49 50 4WCC4030A BAYSPEK62 BAYHTRV108 64 70 BAYHTRV110 75 80 BAYSPEK63 BAYHTRV115 101 110 4WCC4030A-SUB-1 B-E N Optional Equipment — Filter Rack Figure 5. BAYFLTR101 Filter Rack (4024-4036) SAYFLTR201(4042-4060) (Mounts in Filter/Coil Section) Figure 6. BAYACCDORIA Hinged Filter Access Door (4024-4036) BAYACCDOR2A (4042-4060) Replaces Fiker/Coil Access Panel Note: The drawings on this page are prepared by the manufacturerin order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer Is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 4W CC4030A-SU B.1 B-EN Optional Equipment — Filter Rack Optional Equipment — Economizer Table 5. BAYECON101,102A Down Discharge Economizer and Rain Hood (Mounts Over Horizontal Return Air Opening) HVAC Unit Economizer Unit Application Models Economizer rain hood BAYECON101A 4024-036 n Outside air dampers Return air dampers f Required filter kit, order Mist separately eliminator '°' \`a� o BAYECON102A 4042-060 Return Relief damper Duct Roofcurb Table 6. BAYCON200, 201A Horizontal Economizer and Rain Hood Economizer A B D C Gaskets (2) Duct E E .-- Rain Hood Mixed Air Sensor Economizer Models A B c D E F BAYECON200AA 4024-4036 22" 20" 16-7/8" 15-11/16" 11-11/16" 15" BAYECON201AA 4042-4060 26" 22-21/32" 19" 17-11/16" 14-11/16" 21-3/8" Note; The drawings on this page are prepared by the manufacturerin order to provide detail regardingiob layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 10 4WCC4030A-SUB-tB-EN Mechanical Specifications General The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. Units shall be certified to UL Standard 1995. All units shall be factory run tested to check cooling operation, fan and blower rotation and control or TXV sequence. Units shall be designed to operate at ambient temperatures between 115OF and 55OF in cooling as manufactured. Cooling performance shall be rated in accordance with AHRI standards. Unit Casing All components shall be mounted in a weather. resistant steel cabinet with an enamel finish. Access panels shall be provided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with fireproof, permanent, odorless fiber material. Knockouts shall be provided for utility and control connections. Drain connections shall be provided to accommodate indoorwater runoff. Compressor The compressor shall be hermetically sealed, high efficiency scroll compressors. Internal overcurrent and over temperature protection, internal pressure relief shall be standard. Other features include centrifugal oil pump, low vibration and noise. Refrigeration System All units shall have refrigerant control. Service pressure tap ports and a refrigerant line filter shall be standard. Evaporator Coil Internally enhanced 3/8" OD seamless coppertubing mechanically bonded to aluminum fins, factory pressure and leak tested at 480 - 650 psig. All units have TXV to control refrigerant flow. Condenser Coil The Spine Fin "" condenser coil shall be continuously wrapped, corrosion resistant all aluminum with minimum brazed joints. This coil is 3/8" OD seamless aluminum tubing glued to a continuous aluminum fin. Coils are lab tested to withstand 2.000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heattransfer. The coil is protected on all four sides by louvered panels. Indoor Air Fan Constant Torgue, forward -curved, centrifugal wheel in a Composite Vortica OO Blower housing. Motor shall have thermal overload protection and permanently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber mounts. Outdoor Fan One direct -drive, statically and dynamically balanced propeller fan shall be used in a draw -through vertical discharge configuration. Permanently lubricated weather proof motor shall have built-in thermal overload protection. System Controls System controls include condenser fan, evaporator fan and compressor contactors. Accessories Roof Curb The roof curb shall be designed to mate with the unit and provide support and complete weathertight installation when properly installed. Adhesive back polyurethane sealing strips shall be provided to ensure an airtight seal between supply and return openings of the curb and unit. The roof curb design allows field fabricated ductwork to be connected directly to the curb. Curb ships knocked down for field assembly, and includes factory installed wood nailer strips. Electric Heaters Each heater assembly shall include power supply fusing if over48 amps, automatic resetting limit switches and heat limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat modules shall be UL listed. Single Source Power Entry This accessory when used with electric heat accessory shall allow single source power connection to unit and heater combination. Single source power entry kits shall have specific matching heater(s). Kit shall include high voltageterminal blocks, fuse blocks and fuses, cut - to -length interconnecting wiring, and junction box (if required) to provide power sources with fuse protection as required for both the unit and accessory heater. Kit components shall install within the heater cabinet in the heater access section. Single source branch powercircuit shall be protected and wired in accordance with local codes. 12 4WCC4030A-S1JB-1 B-EN Fully Modulating Economizer This accessory shall be field installed and be composed of the following items: 0-100 % fresh air damper, damper drive motor, fixed dry bulb enthalpy control, and low voltage pigtails for electrical connections. Solid state enthalpy or differential enthalpy control is optional. Economizer operations shall be controlled by the preset position of the enthalpy control. A barometric relief damper shall be standard with the economizer and provide a pressure operated damper that shall be gravity closing and prohibit entrance of outside air on equipment "off' cycle. Economizer requires BAYRLAY004A relay kitto interface the economizerto the heat pump. Manual Outside Air Dampers Rain hood and screen shall be field installed. Suitable for up to 25% outside air. Mechanical Specifications Start Kit Extra compressor starting capacity for single phase equipment. Control Options Standard Indoor Thermostats Two stage heating/cooling or one stage heating/cooling thermostats shall be available in either manual or automatic changeover. Programmable Electronic Night Setting Thermostat Programmable electronic thermostat shall provide heating setback and cooling setup with 7-day programming capability. 1H/1C or 21-1/2C models available. C ETA US Intertek The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com. The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. ( 2014Trane 4WCC4030A—SUB-1B-EN 15Jan2015 / Supersedes 4WCC4030A—SUB-1A-EN (0ctober2014) AR Ingersoll Rand Submittal Single Packaged Heat Pump 14 SEER Convertible 4WCC4024A1000A Note: "Graphics in this document are for representation only. Actual model may differ in appearance." TAG: Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. January 2015 4WCC4024A-SUB-1 B-EN 4t# Ingersoll Rand Product Specifications MODEL 4WCC4024AI000A RATED Volts/PH/Hz 208-230/1/60 Performance Cooling BTUH (e) 24600 Indoor Airflow (CFM) 758 Power Input (KW) 1.9 EER/SEER (BTU/Watt-Hr.) (b) 12.00 / 14.00 Sound Power Rating [dB(A)] (c) 66.4 PERFORMANCE HEATING (High Temp.) BTUH 22000 Power Input (KW) 1.8 (Low Temp.) BTUH 14300 Power Input (KW) 1.12 HSPF (BTUH/Watt-Hr) 8.0 POWER CONN.—V/Ph/Hz 208-230/1/60 Min. Brch. Cir. Ampacity (d) 19.4 Fuse Size — Max. (amps) 30 Fuse Size — Recmd. (amps) 30 COMPRESSOR SCROLL VOLTS/PH/HZ 208-230/1/60 R.L. Amps— L.R. Amps 12.8/ 58.3 OUTDOOR COIL — TYPE SPINE FIN Rows/F.P.I 2 / 24 Face Area (sq. ft.) 13.32 Tube Size (in.) 3/8 Refrigerant Control EXPANSION VALVE INDOOR COIL — TYPE PLATE FIN Rows/F.P.I 3 / 15 Face Area (sq. ft.) 3.5 Tube Size (in.) 3/8 Refrigeration Control EXPANSION VALVE Drain Conn. Size (in.) 3/4 FEMALE NPT OUTDOOR FAN — TYPE SWEPT DIA. (IN.) 23.4 DRIVE/NO. SPEEDS DIRECT/ 3 CFM @ 0.0 in. w.g. (e) 2550 Motor — H P/ R. P. M 1/ 12 / 850 Volts/Ph/Hz 208-230/1/60 F.L. Amps/L.R Amps .54 / .82 INDOOR FAN — TYPE CONSTANTTORQUE ECM Dia. x Width (in.) 10.62 X 10.68 Drive/No. Speeds DIRECT/ 3 CFM @ 0.0 in. w.g. M SEE FAN PERF TABLE Motor — HP/R.P.M. 1/3 / 1050 Volts/Ph/Hz 208-230/1/60 F.L. Amps 2.8 FILTER / FURNISHED NO Type Recommended THROWAWAY Recmd. Face Area (sq. ft) (9) 2.7 REFRIGERANT R-410 Charge (lbs.) 5.74 CHARGING SPECIFICATIONS Subcooling 16' DIMENSIONS H X D X W Crated (in.) 46 X 45 X 52 WEIGHT Shipping (lbs.) / Net (lbs.) 402 / 328 W Rated in accordance with AHRI Standard 210/240. (b) Rated in accordance with D.O.E. test procedure. (c) Sound Power values are not adjusted for AHRI 270-95 tonal corrections. (d) Calculated in accordance with currently prevailing Nat'l Electrical Code. (e) Standard Air — Dry Coil — Outdoor. (f) Standard Air — Dry Coil — Indoor (9) Filters must be installed in return airstream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05, W.C. 4W CC4024A-SUB-1 B-E N Outline Drawings 25.40 111 Figure 1. 2 — 3 TON MODELS (DUCT 0 4'' [41 118-1/21 19.0 13/41 FEMALE NPT LEFT SIDE 18.03 18.29 123/321 123/321 14.22 [9/161 SECTION Y-Y TYPICAL (8) SIDES OF DOWNFLOW DUCT OPENINGS Note: The view labeled Bottom Side represents the base as viewed looking up from underneath the unit. OUTLET FRONT SIDE BOTTOM SIDE GRAVITY 4WCC4024A—SUB-1 B-EN 3 Outline Drawings Figure 3. 2 — 3 TON MODELS 304.80 1121 (INSIDE) 75.41 12-31/321 RECOMMENDED SERVICE CLEARANCE MM/IN. WITH ECONOMIZER BACK SIDE 304.8 1121 762.0 1301 LEFT SIDE 762.0 1301 914.4 1361 RIGHT SIDE 609.6 1241 - FRONT SIDE 1066.8 [421 - CLEARANCE TO COMBUSTIBLE MATERIAL MM/IN. BOTTOM 0 BACK SIDE 25.4 [11 LEFT SIDE 152.4 [6) RIGHT SIDE 152.4 [61 FRONT SIDE 304.8 1121 TOP 914.4 [361 359.79 [14-5/321 24V ENTRY 288.42 225�68 1II-I,I/321 [8-7/81 117.73 J [ 4 - 5 / 8 1 85.22 [3-11/321 73.46 6-27/321 406.40 1161 (INSIDE) .89 5/81 I.v.Iv 1161 ( I N S I DE ) BOTTOM DUCT OPENINGS \085o' R ENTRY 8 [1-1/81 DIA. KNOCKOUT ER ENTRY 58 11-1/81 DIA. KNOCKOUT 1293 11-3/81 DIA. KNOCKOUT 01 [1-3I/321 DIA. KNOCKOUT [5SINGLE POINT ENTRY OCKOUT RIGHT SIDE 50.01 [ 1 -31 /32D1 DIA. KNOCKOUT 62.71 [2-15/321 DIA. KNOCKOUT 4WCC4024A-SUB-1 B-EN 5 Indoor Fan Performance (230v) Table 1. Horizontal Airflow 4WCC4024A1 EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 WATTS 63 70 77 83 90 95 - - - - - LOW CFM 899 820 755 681 581 505 WATTS 75 83 91 97 104 111 - MEDIUM CFM 959 886 818 756 673 589 - - WATTS - - 119 127 134 142 149 155 HIGH CFM - 940 886 820 748 670 605 Table 2. Down Airflow 4WCC4024A1 EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 COOLING WATTS 63 71 77 83 90 95 - - - - - - LOW CFM 890 811 747 674 575 500 COOLING WATTS 76 84 91 98 105 112 - MED CFM 950 877 810 749 666 583 - - COOLING WATTS - - 119 127 135 143 150 156 - HIGH CFM - - 931 877 812 741 663 599 4WCC4024A-SUB-1 B-EN Supplementary Electric Heater Table 3. BAYHTRV — Supplementary Electric Heaters ELECTRIC RATED HEATER NO KW/STAGE MAX. FUSE CANADA UNIT HEATER VOLT- PHASE AMPS CAPACITY OF. MCA OR HACR ONLY MAX. MODEL MODEL AGE STAGES CKT BKR CKT BKR KW BTUH 1 2 SIZE SIZE 4024-4060 BAYHTRV105 208/240 1 18/21 3.76/5.0 1200 1 3570/ - 23/26 25/30 25/30 17$ 00/ 4024-4060 BAYHTRV108 208/240 1 29/33 6.0/8.0 20500/ 1 6.0/ - 36/41 40/45 40/45 27300 8.0 4024-4060 BAYHTRV110 208/240 1 36/42 7.5/10.0 1 - 45/52 45/60 45/60 34100/ 10.0 4030-4060 BAYHTRV115 208/240 1 54/63 11.27/ 38500/ 2 7.5/ 3.76/ 68/78 70/80 70/80 15.0 1 51200 10.0 5.0 4048-4060 BAYHTRV120 208/240 1 72/83 15.0/ 51200/ 2 7.5/ 7.5/ 90/ 90/110 90/110 20.0 68300 10.0 10.0 104 4060 BAYHTRV125 208/240 1 90/ 18.78/ 64100/ 2 11.26/ 7.5/ 113/ 125/150 125/150 104 25.0 85300 15.0 10.0 130 Table 4. BAYSPEK — Single Power Entry Kit SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION UNIT MODEL SINGLE POWER ENTRY KIT HEATER MODEL MIN CKTAMP MAX OVER -CURRENT DEVICE 4WCC4024A BAYSPEK60 BAYHTRV105 45 50 BAYHTRV108 60 60 BAYSPEK62 BAYHTRV110 71 80 4WCC4024A-SUB-1 B-EN Optional Equipment — Filter Rack Figure 5. BAYFLTR101 Filter Rack (4024-4036) BAYFLTR201 (4042-4060) (Mounts in Filter/Coil Section) Figure 6. BAYACCDOR1A Hinged Filter Access Door (4024-4036) BAYACCD0132A (4042-4060) Replaces Filter/Coil Access Panel Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 4WCC4024A-SUB-1 B-EN Optional Equipment — Filter Rack Optional Equipment — Economizer Table 5. BAYECON101,102A Down Discharge Economizer and Rain Hood (Mounts Over Horizontal Return Air Opening) HVAC Unit Economizer eeeeeeeeee Economizer Unit Application Models rain hood eeeeeeeeeee eeeeeeeeeee BAYECON101A 4024-036 Outside air dampers Return air dampers Required c filter kit, order Mist separately eliminator o BAYECON102A 4042-060 Relief Return damper Duct Roofcurb Table 6. BAYCON200, 201A Horizontal Economizer and Rain Hood / Economizer D, Gaskets (2) Duct E Rain Hood Mixed Air Sensor Economizer Models A B C D E F BAYECON200AA 4024-4036 22" 20" 16-7/8" 15-11/16" 11-11/16" 15" BAYECON201AA 4042-4060 26" 22-21/32" 19" 17-11/16" 14-11/16" 21-3/8" Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 10 4W CC4024A-SUB-1 B-E N Mechanical Specifications General The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. Units shall be certified to UL Standard 1995. All units shall be factory run tested to check cooling operation, fan and blower rotation and control or TXV sequence. Units shall be designed to operate at ambient temperatures between 1151F and 55°F in cooling as manufactured. Cooling performance shall be rated in accordance with AHRI standards. Unit Casing All components shall be mounted in a weather - resistant steel cabinet with an enamel finish. Access panels shall be provided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with fireproof, permanent, odorless fiber material. Knockouts shall be provided for utility and control connections. Drain connections shall be provided to accommodate indoor water runoff. Compressor The compressor shall be hermetically sealed, high efficiency scroll compressors. Internal overcurrent and overtemperature protection, internal pressure relief shall be standard. Other features include centrifugal oil pump, low vibration and noise. Refrigeration System All units shall have refrigerant control. Service pressure tap ports and a refrigerant line filter shall be standard. Evaporator Coil Internally enhanced 3/8" OD seamless copper tubing mechanically bonded to aluminum fins, factory pressure and leak tested at 480 — 650 psig. All units have TXV to control refrigerant flow. Condenser Coil The Spine Fin TM condenser coil shall be continuously wrapped, corrosion resistant all aluminum with minimum brazed joints. This coil is 3/8" OD seamless aluminum tubing glued to a continuous aluminum fin. Coils are lab tested to withstand 2.000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. Indoor Air Fan Constant Torgue, forward -curved, centrifugal wheel in a Composite Vortica ® Blower housing. Motor shall have thermal overload protection and permanently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber mounts. Outdoor Fan One direct -drive, statically and dynamically balanced propeller fan shall be used in a draw -through vertical discharge configuration. Permanently lubricated weather proof motor shall have built-in thermal overload protection. System Controls System controls include condenser fan, evaporator fan and compressor contactors. Accessories Roof Curb The roof curb shall be designed to mate with the unit and provide support and complete weathertight installation when properly installed. Adhesive back polyurethane sealing strips shall be provided to ensure an airtight seal between supply and return openings of the curb and unit. The roof curb design allows field fabricated ductwork to be connected directly to the curb. Curb ships knocked down for field assembly, and includes factory installed wood nailer strips. Electric Heaters Each heater assembly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat modules shall be UL listed. Single Source Power Entry This accessory when used with electric heat accessory shall allow single source power connection to unit and heater combination. Single source power entry kits shall have specific matching heater(s). Kit shall include high voltage terminal blocks, fuse blocks and fuses, cut - to -length interconnecting wiring, and junction box (if required) to provide power sources with fuse protection as required for both the unit and accessory heater. Kit components shall install within the heater cabinet in the heater access section. Single source branch power circuit shall be protected and wired in accordance with local codes. 12 4WCC4024A-SUB-1 B-EN Mechanical Specifications Fully Modulating Economizer This accessory shall be field installed and be composed of the following items: 0-100 % fresh air damper, damper drive motor, fixed dry bulb enthalpy control, and low voltage pigtails for electrical connections. Solid state enthalpy or differential enthalpy control is optional. Economizer operations shall be controlled by the preset position of the enthalpy control. A barometric relief damper shall be standard with the economizer and provide a pressure operated damper that shall be gravity closing and prohibit entrance of outside air on equipment "off" cycle. Economizer requires BAYRLAY004A relay kit to interface the economizer to the heat pump. Manual Outside Air Dampers Rain hood and screen shall be field installed. Suitable for up to 25% outside air. Start Kit Extra compressor starting capacity for single phase equipment. Control Options Standard Indoor Thermostats Two stage heating/cooling or one stage heating/cooling thermostats shall be available in either manual or automatic changeover. Programmable Electronic Night Setting Thermostat Programmable electronic thermostat shall provide heating setback and cooling setup with 7—day programming capability. 1H/1C or 21-1/2C models available. cOTUS ST Intertek The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com. The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. ©2014 Trane AW)4WCC4024A—SUB-IB-EN 15Jan2015 Ingersoll Rand Supersedes 4WCC4024A—SUB-1A-EN (October2014) 0 TRANE0 4WCY4036B-SUB-3 3 Ton Convertible Heat Pump Packaged Units PRODUCT SPECIFICATIONS MODEL 4WCY4036B3000A RATED Volts/PH/Hz 208-230/3/60 Performance Cooling BTUHO 36000 Indoor Airflow (CFM) 1200 Power Input (KW) 3.15 EER/SEER (BTU/Watt-Hr.)© 11.75 / 14.0 Sound Power Rating [dB(A)]OO 69 Performance Heating0 (High Temp.)BTUH 32400 Power Input (KW) 2.4 (Low Temp.) BTUH 24800 Power Input (KW) 2.6 HSPF (BTU / Watt-HQ6 8.0 POWER CONN.—V/Ph/Hz 208-230/3/60 Min. Brch. Cir. Ampacity0 18.4 Fuse Size — Max. (amps) 25 Fuse Size — Recmd. (amps) 25 COMPRESSOR SCROLL Volts/Ph/Hz 208-230/3/60 R.L. Amps — L.R. Amps 10.4 / 73 OUTDOOR COIL — TYPE SPINE -FIN Rows/F.P.I. 2 / 24 Face Area (sq.ft.) 15.49 Tube Size (in.) 3/8 Refrigerant Control EXPANSION VALVE INDOOR COIL — TYPE PLATE FIN Rows/F.P.I. 4 / 15 Face Area (sq.ft.) 3.54 Tube Size (in.) 3/8 Refrigerant Control EXPANSION VALVE Drain Conn. Size (in.) 3/4 FEMALE NPT OUTDOOR FAN —TYPE PROPELLER Dia. (in.) 23.4 Drive/No. Speeds DIRECT / 1 CFM @ 0.0 in. w.g.® 3250 Motor— HP/R.P.M. 1/5 / 830 Volts/Ph/Hz 230/1 /60 F.L. Amps/L.R. Amps 1.1 / 1.9 INDOOR FAN — TYPE CENTRIFUGAL Dia x Width (in.) 10 X 10 Drive/No. Speeds DIRECT / VARIABLE CFM @ 0.0 in. w.g.Os SEE FAN PERFORMANCE TABLE Motor— HP/R.P.M. 1/2 / VARIABLE Volts/Ph/Hz 200-230/1 /60 F.L. Amps/L.R. Amps 4.3 / 4.3 FILTER / FURNISHED NO Type Recommended THROWAWAY Recmd. Face Area (sq. ft.)OO 4.0 REFRIGERANT R41CA Charge (Ibs.) 7.4 DIMENSIONS H X W X L Crated (in.) 47.86 / 44.5 / 52.03 WEIGHT Shipping (lbs.) / Net (lbs.) 468 / 372 4WCY4036B3000A O Certified in accordance with the Unitary Air -Conditioner Equipment certification program, which is based on AHRI Standard 210/240. ® Sound Power values are not adjusted for AHRI 270-95 tonal cor- rections. ® Calculated in accordance with currently prevailing Nat'l Electrical Code. ® Standard Air — Dry Coil — Outdoor. © Standard Air —Wet Coil — Indoor. © Rated in accordance with D.O.E. test procedure. O Filters must be installed in return air system. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendations with clean resistance of 0.05" W.C. 0 2012 Trane Dimensional Data and Weights I 119-5/8j i- I-- 1-- .11 LEFT SIDE 18.03 18.29 123/32] Ll [23/32] 14.22 19/161 SECTION Y-Y TYPICAL (8) SIDES OF DOWNFLOW DUCT OPENINGS NOTE: The view labeled `Bottom Side" represents the Base as viewed looking up from underneath the unit. I VI wl- OUTLET FRONT SIDE M BOTTOM SIDE 1 2 4WCY4024 through 4WCY4036 (1 of 3) Dimensional Data and Weights RECOMMENDED CLEARANCE .COMBUSTIBLE 304.£ [121 ( INSIDE 84.2 [3-. 24V ENTRY 359.79 I } (14-5/321 288.42 225.68 [11-11/32] 18-7/81 117.73 [ 4 - 5 / 8 1 4vv.4v [161 (INSIDE) BOTTOM DUCT OPENINGS POWER ENTRY 28.58 [1-1/8) DIA. KNOCKOUT 180.20 [1-3/321 118.08 POWER ENTRY 28.58 [1-1/8) DIA. KNOCKOUT 34.93 [1-3/81 DIA. KNOCKOUT 150.94 50.01 [1-31/321 DIA. KNOCKOUT [5-15/16] SINGLE POINT ENTRY 34.93 [1-3/81 DIA. KNOCKOUT RIGHT SIDE 62.1 [I-3I/32DIA. KNOCKOUT 62.71 [2-15/321 DIA. KNOCKOUT 4WCY4024 through 4WCY4036 (2 of 3) 406.40 [161 (INSIDE) .i7 CLEARANCE .COMBUSTIBLE 304.£ [121 ( INSIDE 84.2 [3-. 24V ENTRY 359.79 I } (14-5/321 288.42 225.68 [11-11/32] 18-7/81 117.73 [ 4 - 5 / 8 1 4vv.4v [161 (INSIDE) BOTTOM DUCT OPENINGS POWER ENTRY 28.58 [1-1/8) DIA. KNOCKOUT 180.20 [1-3/321 118.08 POWER ENTRY 28.58 [1-1/8) DIA. KNOCKOUT 34.93 [1-3/81 DIA. KNOCKOUT 150.94 50.01 [1-31/321 DIA. KNOCKOUT [5-15/16] SINGLE POINT ENTRY 34.93 [1-3/81 DIA. KNOCKOUT RIGHT SIDE 62.1 [I-3I/32DIA. KNOCKOUT 62.71 [2-15/321 DIA. KNOCKOUT 4WCY4024 through 4WCY4036 (2 of 3) 406.40 [161 (INSIDE) .i7 304.£ [121 ( INSIDE 84.2 [3-. 24V ENTRY 359.79 I } (14-5/321 288.42 225.68 [11-11/32] 18-7/81 117.73 [ 4 - 5 / 8 1 4vv.4v [161 (INSIDE) BOTTOM DUCT OPENINGS POWER ENTRY 28.58 [1-1/8) DIA. KNOCKOUT 180.20 [1-3/321 118.08 POWER ENTRY 28.58 [1-1/8) DIA. KNOCKOUT 34.93 [1-3/81 DIA. KNOCKOUT 150.94 50.01 [1-31/321 DIA. KNOCKOUT [5-15/16] SINGLE POINT ENTRY 34.93 [1-3/81 DIA. KNOCKOUT RIGHT SIDE 62.1 [I-3I/32DIA. KNOCKOUT 62.71 [2-15/321 DIA. KNOCKOUT 4WCY4024 through 4WCY4036 (2 of 3) 406.40 [161 (INSIDE) .i7 Unit Performance Data Indoor Fan Performance 4WCY4O36A Horizontal Airflow 4WCY4036-HOR DIPSWITCH SETTINGS External Static Pressure (in. wg) AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 350 CFM/TON OFF OFF OFF ON Watts 162 173 197 226 256 285 313 343 360 - - CFM 1058 1062 1063 1063 1062 1060 1057 1053 1010 400 CFM/TON' OFF OFF OFF OFF Watts 179 230 265 296 329 366 403 431 436 CFM 1179 1196 1204 1206 1205 1203 1199 1194 1185 450 CFM/TON OFF OFF ON OFF Watts 318 336 365 399 435 469 502 533 - CFM 1390 1376 1370 1366 1361 1354 1349 1351 Down Airflow 4WCY4036-DOWN DIPSWITCH SETTINGS External Static Pressure (in. wg) AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 350 CFM/TON OFF OFF OFF ON Watts 169 182 210 243 273 301 331 370 433 - - CFM 1025 1062 1068 1063 1060 1061 1064 1055 1015 400 CFM/TON` OFF OFF OFF OFF Watts 225 253 283 315 348 381 414 449 484 CFM 1187 1201 1203 1201 1198 1197 1194 1184 1157 450 CFM/TON OFF OFF ON OFF Watts 339 357 390 424 455 483 516 571 - CFM 1391 1377 1377 1375 1366 1352 1344 1360 *Factory Default Setting 4WCY4036 AIRFLOW WITH AUXILIARY HEAT (CFM) SWITCH SETTINGS SELECTION NOMINAL AIRFLOW 7-OFF 8-OFF LOW 1050 CFM 7-ON 8-OFF HIGH 1200 CFM 7-OFF 8-ON HIGH 1200 CFM 7-ON 8-ON HIGH 1200 CFM BAYHTRV305, 308, 310, 315E, Supplementary Electric Heater UNIT MODEL ELECTRIC HEATER MODEL RATED VOLTAGE PHASE AMPS HEATER CAPACITY STAGES KW/STAGE MCA MAX FUSE OR HACR CKT BKR SIZE (4) CANADA ONLY MAX. CKT BKR SIZE (5) KW BTUH 1 2 ^W/TCY4036-060A3 BAYHTRV305E 208/240 3 10/12 3.76/5.0 12800/17100 1 3.76/5.0 13/15 15/15 15/15 ^W/TCY4036-060A3 BAYHTRV308E 208/240 3 17/19 6.0/8.0 20500/27300 1 6.0/8.0 21/24 25/25 25/25 ^W/TCY4036-060A3 BAYHTRV310E 208/240 3 21/24 7.5/10.0 25600/34100 1 7.5/10.0 26/30 30/30 30/30 ^W/TCY4036-060A3 BAYHTRV315E 208/240 3 31/36 11.27/15.0 38500/51200 2 7.5/10.0 3.76/5.0 39/45 40/45 40/45 BAYSPEK61, 64E Single Power Entry Kit SINGLE POWER ENTRY KIT HEATER MODEL UNIT MODEL BAYSPEK061 E BAYHTRV305E 4WCY4036-060A3 BAYHTRV308E 4WCY4036-060A3 BAYHTRV310E 4WCY4036-048A3 BAYSPEK064E BAYHTRV315E 4WCY4036-06OA3 Optional Equipment BAYFLTR101, 201 B, 1 " - 2" Filter Rack (Mounts in Filter/Coil Section) BAYACCDORI A & BAYACCDOR2A Hinged Filter Access Door Replaces Filter/Coil Access Panel The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not respon- sible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. Optional Equipment BAYECON101,102A Down Discharge Economizer and Rain Hood (Mounts Over Horizontal Return Air Opening) HVAC Unit A Economizer eeeeeeeeee rain hood eeeeeeeee�e Outside ai dampers Z. Required c tReturn air filter kit, order ampers separately Mist limi- o . nator Relief damper Return Roofcurb Duct Economizer Unit Application Models A BAYECON101A 4TC*,WC`,YC',DC` 20.125" 018-036 BAYECON102A 4TC' DC' 24.375" *WC",YC`, 042-060 BAYCON200,201A Horizontal Economizer and Rain Hood The drawings on this page are prepared by the manu- facturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manu- facturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. Economiz Duct Economizer A B C D E F BAYECON200AA 22" 20" 16 7/8" 15 11/16 11 11/16 15 BAYECON201AA 26" 22 21/32" 19" 17 11/16 14 11/16 21-3/8 I Mechanical Specifications General The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. All units shall be factory run tested to check cooling operation, fan and blower rotation and control or TXV se- quence. Units shall be designed to operate at ambient temperatures between 115°F and 55°F in cooling as manufactured. Cooling performance shall be rated in ac- cordance with A.H.R.I. standards. Unit Casing All components shall be mounted in a weather -resistant steel cabinet with an enamel finish. Access panels shall be pro- vided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with fireproof, permanent, odorless glass fiber material. Knockouts shall be provided for utility and control connections. Drain connections shall be provided to accommodate indoor water runoff. Compressor The compressor shall be hermetically sealed, high efficiency Climatuff° com- pressors. Internal overcurrent and over temperature protection, internal pressure relief shall be standard. Refrigeration System All units shall have TXV in cooling and TXV in heating. Service pressure tap ports, and a refrigerant line filter dryer shall be stan- dard. Indoor Coil Coils shall be internally finned or smooth bore 3/8" copper tubes mechanically bonded to configured aluminum plate fin as standard. Evaporator coil leak and pressure tested to 200 psig; condenser coil tested to 450 psig. Tirane 6200 Troup Highway Tyler, TX 75707-9010 Condenser Coil — The Spine Fin TMcondenser coil shall be continuously wrapped, corrosion resis- tant all aluminum with minimum brazed joints. This coil is 3/8 inch O.D. seamless aluminum tubing glued to a continuous aluminum fin. Coils are lab tested to withstand 2,000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. Indoor Air Fan — Direct -drive, forward - curved, centrifugal wheel in a Composite Vortica° Blower housing. Motor shall have thermal overload protection. Permanently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber mounts. Condenser Fan — Direct -drive, draw thru propeller type. Weather -proofed permanent split capacitor fan motor shall have built-in thermal overload and per- manently lubricated motor bearings. System Controls System controls include condenser fan, evaporator fan and compressor contac- tors. Accessories Roof Curb —The roof curb shall be de- signed to mate with the unit and provide support and complete weathertight instal- lation when properly installed. Adhesive back polyurethane sealing strips shall be provided to ensure an airtight seal be- tween supply and return openings of the curb and unit. The roof curb design allows field fabricated ductwork to be connected directly to the curb. Curb ships knocked down for field assembly, and includes factory -installed wood nailer strips. Electric Heaters — Each heater assem bly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat mod- ules shall be UL listed. Single Source Power Entry — This ac- cessory when used with electric heat accessory shall allow single source power connection to unit and heater combina- tion. Single source power entry kits shall have specific matching heater(s). Kit shall include high voltage terminal blocks, fuse blocks and fuses, cut -to -length in- terconnecting wiring, and junction box (if required) to provide power sources with fuse protection as required for both the unit and accessory heater. Kit compo- nents shall install within the unit cabinet in the heater access section. Single source branch power circuit shall be protected and wired in accordance with local codes. Fully Modulating Economizer — This accessory shall be field installed and be composed of the following items: 0-100% fresh air damper, damper drive motor, fixed dry bulb enthalpy control, and low voltage wiring plug for electrical connections. Solid state enthalpy or differential enthalpy con- trol is optional. Economizer operations shall be controlled by the preset position of the enthalpy control. A barometic relief damper shall be standard with the econo- mizer and provide a pressure operated damper that shall be gravity closing and prohibit entrance of outside air on equip- ment "off' cycle. Economizer requires BAYRLAY004A relay kit to interface the economizer to the heat pump. Manual Outside Air Dampers — Rain hood and screen shall be field installed. Suitable for up to 25% outside air. Start Kit — Extra compressor starting ca- pacity for single phase equipment. Control Options Standard Indoor Thermostats — Two stage heating/cooling or one stage heat- ing/cooling thermostats shall be available in either manual or automatic changeover. Programmable Electronic Night Set- back Thermostat — Programmable electronic thermostat shall provide heat- ing setback and cooling setup with 7-day, programming capability. 1 H/1 C or 2H/2C models available. COTUS $TE Intertek The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.