Loading...
SI REPORT Distinctive Dentistry-3314-9.7.21(Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medgasservices.io (425) 894 5918 Dental Gas Line Verification Report Date: September 9th, 2021 Job Number: 3314 Contractor: Local Plumbing S Construction Date(s) and Time(s) of Testing: September 9th, 2021- 0600 hrs. Facility: Distinctive Dentistry 22815 Edmonds Way Edmonds, WA 98020 Scope of Work: New Medical Gases, Dental Air and Vacuum Our firm certifies that the verifier named in the report is properly trained and certified to perform the activities required. All testing and measurement equipment are properly calibrated and maintained. As a representative of Medical Gas Services, LLC, the verifier named in this report has conducted testing and verification of medical gas piping systems and related equipment to certify the following on the above date. General Findings: A. Medical Gases are in compliance with NFPA 99(2012ed): Category 3, Dental - "NOT FOR ANESTHESIA" B. No crossed lines were found in Medical Gases in the tested areas on the day of testing. C. Medical Gases meet minimum concentrations. D. Medical Gases are at normal pressure. E. Dental Air is at normal pressure. F. Dental Vacuum is at normal level. G. Medical Gas and Dental system components in area tested are in compliance with NFPA 99 (2012ed). Category 3, Dental. H. City of Edmonds: Permit # 27033600102706 I. Attachments: Worksheets Note: Existing Equipment and Systems NFPA 99(2012ed)1153.14 - An existing Category 3 system that is not in strict compliance with the provisions of this standard shall be permitted to be continued in use as long as the authority havingiunsdiction has determined that such use does not constitute a distinct hazard to life. 3314-9.7.21-VR Pg.1 of 4 (Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medsasservices.io (425) 894 5918 II. Medical Gases A. Oxygen: 1. Static line pressure: 52 psig. 2. Oxygen concentration at outlet: 97.8% 3. Dynamic outlet free flow at outlet: >3.5 scfm B. Nitrous Oxide: 1. Static line pressure: 50 psig. 2. Nitrous Oxide concentration at outlet: >99% 3. Dynamic outlet free flow at outlet: >3.5 scfm III. Dental Air and Vacuum: A. Dental Air: 1. Static line pressure: 105 psig. 2. Oxygen concentration at outlet: 20.7 % B. Dental Vacuum: 1. Static line vacuum: 15 "HqV. IV. Particulate Line Test: PASS V. Odor: PASS VI. Outlet: A. Outlet Style: DISS VII. Manifold / Alarm: A. Manifold: 1. Brand: Belmed 2. Model Number: N/A 3. Serial Number: N/A B. Alarm: 1. Brand: Belmed 2. Model Number: N/A 3. Serial Number: N/A 3314-9.7.21-VR Pg. 2 of 4 (Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medgasservices.io (425) 894 5918 VIII. Dental Equipment: A. Dental Air: 1. System air components in compliance with NFPA 99(2012ed) 2. Brand: TechWest 3. Model Number: ACOR202 4. Serial Number:11018 5. Configuration: Duplex 6. Horsepower: 1.5 hp 7. Intake: Outside 8. Pump: Oil Less B. Dental Vacuum: 1. System vacuum components in compliance with NFPA 99(2012ed) 2. Brand: TechWest 3. Model Number: VPD252 4. Serial Number: VPD2-7337 5. Configuration: Simplex 6. Horsepower: 1 hp 7. Vented to outside. C. Amalgam Separator: 1. Brand: Solmetex 2. Model Number: NXT-HG5-001 3. Serial Number: NXT69890 X. Cylinder Storage: A. Location: Inside B. Ventilation: Natural C. Cooling Sprinkler: Yes D. Door labeled: Yes E. 1 Hour Rated: Yes F. Cylinders Secured: Yes 3314-9.7.21-VR Pg. 3 of 4 (Medical Gas Services 918 S Horton St, Suite 917 Seattle, WA 98134 medsasservices.io (425) 894 5918 XI. Brazier: Jose Villagrana A. Brazier Number: VILLAJ`849PO B. Plumbing Contractor: Local Plumbing S Construction XII. Comments: A. Dental vacuum drain is sealed into floor XIII. Recommended Corrections: A. Install an open drain or confirm a sealed drain is acceptable with authority having jurisdiction Tested By: Alexander Christensen - Medical Gas Technician Review By: Matthew Wachsmuth - ASSE 6030 Verifier r 3314-9.7.21-VR Pg. 4 of 4 /fMedical Gas Services 918 S Horton St, Suite 917 Seattle. WA 98134 medsasservices.io (425) 894 5918 Category 3 Verification Check List Reference NFPA 99(2012ed) Job #: 3314 Facility: Distinctive Dentistry Tested By: AC Test Date: 9.7.21 Facility: ® New ❑ Existing Type of Facility: ® Dental ❑ Medical ❑ Veterinary ❑ Lab ❑ Other: Medical Gases ❑ NO N E Oxygen Line: ® New ❑ Existing Nitrous Oxide Line: ® New ❑ Existing ❑ NONE Line Pressure: 52psi Concentration: 97.8% Line Pressure: 50 psi Concentration: >99 % Flow Test: >8 SCFH ( >_3.5 scfm ) ® Pass ❑ Fail Flow Test: >8 SCFH ( >_3.5 scfm ) ® Pass ❑ Fail Particulate Test: ® Pass ❑ Fail Particulate Test: ® Pass ❑ Fail Odor: ® Pass (None) ❑ Fail, Odor: ® Pass (None) ❑ Fail, Crossed Lines: ❑ Yes ® No Outlet Brand: N/A Quick Connect Style: DISS Location of Outlets: Cabinets Cylinder Storaqe ❑ NONE Tank Room: ® New ❑ Existing Location: ® Inside ❑ Remote Door Labeled: ® Yes ❑ No Individually Secured: ® Yes ❑ No Cooling Sprinkler: ® Yes ❑ No 1 Hour Rated: ® Yes ❑ No Separate from Mechanical Equipment: ® Yes ❑ No Electrical Switches/Outlets 5' above floor: ® Yes ❑ No Volume Connected or Stored: ® (3000 ft3 ❑ >3000 ft3 Number of Cylinders Connected: 1 OX x 1 N20 Ventilation: ® Natural ❑ N/A Ventilation: ❑ Mechanical ® N/A 2 Openings 1' of Floor & Ceiling: ® Yes ❑ No ❑ N/A Exhaust Fan Runs Continuously: ❑ Yes ❑ No ® N/A Minimum 72 in' Free Area: ® Yes ❑ No ❑ N/A Draws Air from within 1' of Floor: ❑ Yes ❑ No ® N/A Vented directly to outside: ® Yes ❑ No ❑ N/A Fan Connected to Essential Power: ❑ Yes ❑ No ® N/A Manifold ❑ NONE Manifold: ® New ❑ Existing Piping Labeled: ® Yes ❑ No Brand: Belmed Flex Hoses < 5': ® Yes ❑ No / Rigid Copper ® Yes ❑ N/A Model #: N/A Check Valve DL of Regulator: ® Yes ❑ No Serial #: N/A Relief Valve 50% Above Norman Line Pres: ® Yes ❑ No Alarm/ Warninq System ❑ NONE ❑ NOT REQUIRED Alarm: ® New ❑ Existing ❑ None Non -Cancellable Visual Alarm: ® Yes ❑ No Brand: Belmed Cancellable Audible Alarm: ® Yes ❑ No Model #: N/A HI / LO Line Pressure Alarm: ® Yes ❑ No Serial #: N/A Reserve In Use Alarm / Change Over: ® Yes ❑ No 3314-9.7.21 Pg.1 of 2 /fMedical Gas Services 918 S Horton St, Suite 917 Seattle. WA 98134 medsasservices.io (425) 894 5918 Category 3 Verification Check List Reference NFPA 99(2012ed) =mergency Shutoff/Zone Valve ❑ NONE Valve: ❑ New ❑ Existing ® None - Not Required Brand: 3 Part Valve: ❑ Yes ❑ No With Down Line Gauges: ❑ Yes ❑ No Sensor Location: ❑ UL ❑ DL Labeled: Dental Equipment ❑ Not Tested Dental Air System: E New ❑ Existing ❑ NONE Dental Vacuum System: E New ❑ Existing ❑ NONE Brand: TechWest Brand: TechWest Model #: ACOR202 Model #: VPD252 Serial #: 11018 Serial #: VPD2-7337 Conf: ❑ Simplex ® Duplex ❑ Triplex ❑ Quad Conf: ® Simplex ❑ Duplex ❑ Triplex ❑ Quad Compressor Type: Oil Less Pump Type: Oil. Less Compressor On: 80 psi Compressor Off: 110 psi Vac Level: 15 "H9V Horsepower: 1 hp. Line Pressure: 105 psi Particulate: ® Pass ❑ Fail Drain: ® Sealed ❑ Open ® Floor ❑ Wall Concentration: 20.7 % Horsepower: 1.5 hp. Flexible Connectors: Z Yes ❑ No Receiver: Z Yes ❑ No Drain: Z Manual ❑ Auto Air / Water Separator: Z Yes ❑ No Moisture Indicator: ® Yes ❑ No Exhausted to Outside: ® Yes ❑ No Dryer: ® Yes ❑ No Type: Desiccant Location of Discharge: Roof Intake: Z Outside ❑ Inside (other) ❑ Inside (same) Piping: Z Hard Copper Z Schedule 40 PVC Amalgam Separator ® New ❑ Existing ❑ Not Required ❑ None Brand: Solmetex Model #: NXT-HG5-001 Serial #: NXT69890 Comments: 3314-9.7.21 Pg. 2 of 2