BLD2021-0102+Structural_Calculations+1.26.2021_12.13.50_PM+2010357smartlink
Mr. John Evans
Smartlink, LLC
11410 Northeast 122nd Way
Kirkland, WA 98034
(415) 265-8200
Date: December 22, 2020
Subject: Rooftop Structural Analysis Report
AT&T Designation:
Site USID: 20533-A
Site FA: 10092667
Site Name: PUGET DRIVE
Turf Vendor Number: SN61
I�
MORRISON HERSHFIELD
Morrison Hershfield
1455 Lincoln Parkway, Suite 500
Atlanta, GA 30346
(770) 379-8500
Site Address: 1414 9th Avenue North, Edmonds, Snohomish County, WA 98020
Site Coordinates: Latitude: 47' 49' 18.29" N, Longitude: 122' 21' 57.86" W
Tower Description: 46.3± ft — Building w/ Screen Wall
Mount Description: Antenna Pipe Mount
Morrison Hershfield Project Number: SML-055 / 2000479
Dear Mr. Evans,
Morrison Hershfield is pleased to submit this "Rooftop Structural Analysis Report" to determine the structural
integrity of existing antenna mounting system for the existing and proposed antenna and equipment on the
above -mentioned supporting structure.
This analysis has been performed in accordance with the 2015 International Building Code based upon an
ultimate 3-second gust wind speed of 110 mph. Applicable Standard references and design criteria are listed in
Section 2 - Analysis Criteria.
Our analysis demonstrates that the existing and proposed mounts and building structure ARE in conformance
with the requirements of the above noted standards under the effects of loading described.
Summary of Results
Mount Components
40.4%
Sufficient
*Building Structure (Gravity)
<5%
Sufficient
**Building Structure (Lateral)
<10%
Sufficient
*2015 IEBC Section 1103.2, Exception 1
**2015 IEBC Section 1103.3, Exception 2
We at Morrison Hershfield appreciate the opportunity of providing our continuing professional services to you
and Smartlink, LLC. If you have any questions or need further assistance on this or any other projects, please
give us a call.
Respectfully submitted by:
Morrison Hershfield
G. Lance Cooke, P.E. (WA License No. 42237)
Senior Engineer
Morrison Hershfield
Rooftop Structural Analysis Report
Project Number. SML-055 / 2000479
December 22, 2020
Page 2
1.0 INTRODUCTION
This is a 46.3± ft building with screen wall constructed of structural steel & masonry. Existing and proposed
antennas and equipment are to be installed at a mount elevation of 43.2 ft & 42.4 ft in sector A & B, mounted to
the existing chimney walls and at a mount elevation of 43.2 ft in sector C inside the screen wall.
2.0 ANALYSIS CRITERIA
The following design parameters have been used in our analysis:
Design Standard: 2015 International Building Code
ASCE 7-10, Minimum Design Loads for Building and Other Structures
AISC 325-15, Manual of Steel Construction
ACI 318-14, Building Code Requirements for Structural Concrete
Design Wind Speed: 110 mph (Ultimate 3-sec gust) with no radial ice
Risk Category: II
Exposure Category: C
Topographic Factor, Kt: 1.0
Seismic Ss: 1.278
Seismic Si: 0.501
The structural analysis was based on the following documentation:
Table 1 — Documentation
Document
Description
Source
Structural Calculations
Cornerstone Engineering, Inc.,
Client
j Proect No: 09-69015, dated 04/20/2009
Structural Calculations
Morrison Hershfield,
MH
j Proect No: 8100200.00, dated 06/14/2011
As -Built Construction Drawings
Camp+ Associates,
Client
Job No. SN61, dated 02/16/2016
Mount Analysis Report
Morrison Hershfield,
j
MH
Proect No. GED-356R1 / 7170287, dated 08/31/2017
Design Review Form
Smartlink, LLC,
Client
Site ID: SN61, dated 12/09/2020
RF Data Sheet
AT&T,
Client
RFDS Name: STTLWASN61, dated 12/04/2020
m0
Rooftop Structural Analysis Report
Project Number. SML-055 / 2000479
December 22, 2020
Page 3
3.0 ANALYSIS LOADING
The existing and proposed antennas, transmission lines and other equipment considered in this analysis were
provided by the client and are noted in Table 2.
Table 2 — Antenna Loads
Mount C.L
ft
Antenna
C.L ft
Antenna Description
Location
Note
PROPOSED
43.2
(Sector
A & C)
42.4
(Sector B)
43.2
(Sector
A & C)
42.4
(Sector B)
(2) Cellmax CMA-UBTMLBMLBHH/6516/16/21/21 Panel
1300/2200
1
(1) Kathrein 800372965 Panel
20°
(3) Nokia AIRSCALE RRH 4T4R B5 160W RRH
-
(3) Kathrein 78211288 Combiner
(3) Site Pro 1 #SP250 Wall Mount
EXISTING
43.2
(Sector
&
A &C)
(Sector B)
43.2
(Sector
A&C)
42.4
(Sector B)
(3) Kathrein 80010864 Panel
200/1300/2200
2
(3) Lucent B25 RRH4X30-4R RRH
-
(3) Lucent B66A RRH4X45-4R RRH
(3) Nokia Flexi RRH 4T4R B14 160W FRBI RRH
(3) Lucent RRH2X40W-07-L RRH
(3) Lucent RRH4X25-WCS-4R RRH
(6) Kathrein 78211287 Combiner
(3) Raycap FC12-PC6-10E J-Box
(9) Raycap DC2-48-60-0-9E J-Box
(3) Kathrein 80010991 Panel
20°/130°/220°
3
Note: Any discrepancies in loading from this listing should be brought to Morrison Hershfield's attention; results of this
assessment cannot be used if the loading is different.
1. Proposed antennas and equipment.
2. Existing antennas and equipment to remain.
3. Existing antenna and equipment to be removed and have not been considered in this analysis.
m0
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 4
4.0 ANALYSIS PROCEDURE
RISA-3D (version 18.0.1), a commercially available analysis software package, was used to create a three-
dimensional model of the antenna mounting system and calculate member stresses for various loading cases.
Wind and seismic loading on equipment for various loading cases were determined in accordance with
ASCE 7-10. Select output from the analysis is included in the report.
5.0 ASSUMPTIONS
1) The building, foundation, and antenna supporting mounts were constructed according to applicable
code.
2) The building and antenna supporting mounting system have been maintained according to construction
document and manufacturer's specifications.
3) The building and its components, including antenna supporting mounts have not been compromised.
4) The analysis of the existing building and its foundation is outside of the scope of this report and has not
been performed.
5) The analysis will be required to be revised if the existing conditions in the field differ from those shown in
the above -referenced documents or assumed in this analysis. No allowance was made for any
damaged, missing, or rusted members.
6) Steel grades have been assumed as follows, unless noted otherwise:
Channel, Solid Round, Angle, Plate ASTM A36 (GR 36)
HSS (Rectangular) ASTM 500 (GR B-46)
HSS (Round) ASTM 500 (GR B-42)
Pipe ASTM A53 (GR 35)
Connection Bolts ASTM A325
U-Bolts ASTM A307
Unistrut — P1000 ASTM A570 (GR 33)
7) The existing connection details are taken from the structural calculations completed by Cornerstone
Engineering, Inc., Project No: 09-69015, dated 04/20/2009, and the mount geometry details are
assumed based on photos, dated 02/11/2016, and is considered to be correct.
8) The existing and proposed loading for AT&T are taken from their RF Data Sheet, RFDS Name:
STTLWASN61, dated 12/04/2020, and from the design review form by Smartlink, LLC, Site ID: SN61,
dated 12/09/2020, and is considered to be correct.
This analysis may be affected if any assumptions are not valid or have been made in error. Morrison Hershfield
should be notified to determine the effect on the structural integrity of the antenna mounting system.
m•
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 5
6.0 SUMMARY OF RESULTS
The following tables summarize the location and utilized percentage of available capacity for each component of
the mount. With consideration to the appropriate safety factors, 100% represents the full capacity of the
component. Percentages below 100% indicate available capacity and conformance of the component.
Percentages between 100% and 105% indicate an acceptable capacity. Percentages above 105% indicate an
overstressed situation requiring structural modification to ensure conformance with the applicable codes and
standards.
Based on our analysis results, the existing and proposed mounts ARE within capacity to support the loads
under the current loading scenario.
Table 3 — Component Stresses vs. Capacity (Antenna Pipe Mount)
Notes Component Critical Mount % Capacity Pass / Fail
Member Centerline (ft)
1 Mast Pipe M7 43.2 20.2 Pass
1 Connection Check - 43.2 40.4 Pass
Structure Rating (max from all components) = 40.4%
Notes:
1) See additional documentation in "Additional Calculations" for calculations supporting the % capacity consumed.
7.0 RECOMMENDATIONS
The existing and proposed mounts and building have sufficient capacity to support the proposed loading
configuration. No modifications are required at this time.
ATTACHMENTS: Mount Analysis Input & Output, Building Analysis Input & Output, Additional Calculations,
Mount Assembly Drawings and RF Data Sheet
m•
MOUNT ANALYSIS IPUT & OUTPUT
Morrison Hershfield
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 7
ALPHA, BETA & GAMMA LOADING SECTORS
AL.k
Alpha
Gamma
Beta
m•
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 8
WIND LOAD CALCULATIONS ON APPURTENANCES
Code: I International Building Code 2015
Occupancy:
0 ccu pan cy Grou p = B Business 99,
Risk Category & ImpiDrtance Factors:
Risk Categary Category II : All bldgs and other structures except those listed in Categories I, III, & IV
Wind Loads - Other Structures: ASCE 7- 10 Ultimate 'Wind Pressures
V�ind Factor = 1.00
Gust Effect Factor (G) = 0.85 Ultimate Wind Speed= 110 mph
Kzt ' 1.00 Exposure = C
1. AT&T Proposed (1) Cellmax CMA-UBTMLBMLBHH/6516/16/21/21 Panel;
(72.4"x27.2"x7.7", Wt. = 85.0 Ibs), Total (2)
Front
A. Solid Freestanding
Walls & Solid Signs
(& open signs
With less than 30% open)
sJh =
0.1-
Case A & D
Gist to sign tap (h)
43.2 ft
BJs =
0.38
C, =
1.95
Height (s)
&C ft
LrJs =
0.00
F = qz G Cf As =
43,9 As
Width (D)
2.3 ft
Kz =
1.061
As =
1'.- sf
Wall Return (Lr)
qz=
27.9 psf
F =
001 Ibs
Directionality (Kd)
0.85
1 ASCE7 Load Combinations Use(
Side
A. Solid Freestanding
Nulls & Solid Signs
(& open signs
With less than 30%
cpen�
sJh=
0.1Li
CaseA&G
Gist to sign top (h)
43.2 ft
BJs =
0.11
C. =
1.90
Height (s)
6.0 ft
LrJs =
0.00
F = qz G Cf As =
45,0 As
Width CR)
0.6 ft
Kz =
1.061
As =
'. ? s f
Wall Return (Lr) =
qz =
27.9 psf
F =
174 Ibs
Directionality (Kd)
0.85
ASCE7 Load Combinations Use(
2. AT&T Proposed (1) Kathrein 800372965 Panel; (78.7"x14.9"x6.5", Wt. = 79.0 Ibs), Total (1)
Front
A. Solid Freestandina Malls & Solid Signs ii& or)en signs with less than 30% men
Dist to sign tap (h)
Height (s)
W dth (5)
Wall Return (Lr) _
Directionality (Kd)
sih =
0.15
4a.2 ft
Bis =
0.19
6.6 ft
Lr1s =
0.00
1.2 ft
Kz =
1.061
z =
27.9 psf
0.85
ASCE7 Load Combinations Use( v
Case A& D
C. =
1.86
F=qzG CfAs =
44.0 As
As
8.1 sf
F =
359 Ibs
m0
Rooftop Structural Analysis Report
Project Number. SML-055 / 2000479
December 22, 2020
Page 9
Side
A. Solid Freestanding Walls & Solid Signs (& open signs With less than 30% open)
sfh =
0.15
Case A & B
Dist to sign tap (h)
43.2 ft
Bfs =
0.08
C. =
1.92
Height (s)
6.6 ft
Lrfs =
0.00
F = vz C Cf As =
45.5 As
Withh (B)
0.5 ft
Kz =
1.061
As
3.6 sf
Wall Return (Lr)
CIZ =
27.9 psf
F =
162 Ibs
Cirectionality (Kd..
0.85
1 ASCE7 Load Combinations Usec
3. AT&T Existing (1) Kathrein 80010864 Panel; (55.2"x14.8"x6.7", Wt. = 55.1 Ibs), Total (3)
Front
A. Solid Freestanding Walls & Solid Signs (& open signs With less than 30% openX
sA=
0.11
Case A&B
Dist tD sign tap (h)
4k.2 ft
Bfs =
0.2
CC, =
1.35
Height (s)
4.6 ft
Lrfs =
0.00
F = qZ G Cf As =
43.9 As
Width (B)
1.2 ft
Kz =
1.061
As =
5.7 sf
Wall Return (Lr)
qz =
27.9 psf
F =
249 Ibs
Directionality (Kd)
0-851
ASCE7 Load Combinations Use(,v
Side
A. Solid Freestanding Walls & Solid Signs (& open signs With less than 30% open
sfh=
0.11
Case A&B
Dist to sign top (h)
4k'�.2 ft
Bfs =
0.12
C. =
1.99
Height (s)
4.6 ft
Lrfs =
0.00
F = qz u Cf As =
44.8 As
Width (B)
0.6 ft
Kz =
1.061
A4 =
2.µ sf
Wall Return (Lr) _
=
27.9 psf
F =
115 Ibs
Directionality (Kd..
0.85
ASCE7 Load Combinations Usec
4. AT&T Proposed (1) Nokia AIRSCALE RRH 4T4R B5 160W RRH;
(13.3"x11.6"x6.5", Wt. = 36.8 Ibs), Total (3)
Front
A. Solid Freestanding Malls & Solid Signs (& open signs With less than 30% open
sfh =
0.03
Case A & B
Dist to sign to-p (h)
43.2 ft
Bfs =
0.87
C. = 1.91
Height (s)
1.1 ft
Lrfs =
0.00
F = qz - Cf As = 43.0 As
Width (B)
1.0 ft
Kz =
1.061
As 1.1 4f
Wall Return (Lr)
CIZ =
27.9 psf
F = 46 Ibs
Dlrecctlo n ality (Kd)
0.85
ASCE7 Load Combinations Use( -v
Side
A. Solid Freestandina
Malls & Solid Signs M
cnen signs with less th-an 30% ooeni
Dist tD sign tap (h)
Height (s)
Width (B)
Wall Return (Lr) _
Directionality (Kd)
-qh =
G.aa
43.2 ft
Bfs =
0.49
1.1 ft
Lrfs =
0.00
0.5 ft
Kz =
1.061
z =
27.9 psf
0.85
ASCE7 Load Combinations Usec
Case A & B
C, =
1.85
F = qz G Cf As =
43.9 As
As =
0.6 sf
F =
26 Ibs
m0
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 10
5. AT&T Existing (1) Lucent B25 RRH4X30-4R RRH; (21.4"x12.0"x7.2", Wt. = 51.0 Ibs), Total (3)
Front
A. Solid Freestanding Walls & Solid Signs (& open signs With less than 30% op"n�
sih = 0.0-
Case A & B
Gist to- sigq top (h)
43.2 ft
Bis = O. E�
C, =
1.3-
Height (s)
1.9 ft
Lris = 0.00
F = qz G Cf As =
43.8 As
Width (B)
1.0 ft
Kz = 1.061
As =
1. � sf
Wall Return (Lr)
q z = 27.9 psf
F =
7tt Ibs
Directionality (Kd)
O.OE
ASCE7 Load Combinations Use( -1
Side
A. Solid Freestanding Walls & Solid Signs (& open signs With less than 30% op"n�
sih =
0.04
Case A & B
Gist to sign top (h) 43.2 ft
Bis =
0.34
C. =
1.3E
Height (s) 1.8 ft
Lris =
0.00
F = qz G Cf As =
43.9 As
1,Vidth (B) 0.6 ft
Kz =
1.061
As =
1.1 sf
IoVa II Retu rn (Lr) =
qz =
27.9 psf
F =
47 Ibs
Directionality (Kd) G.85 FASCE7 Load Combinations Use( -I
6. AT&T Existing (1) Lucent B66A RRH4X45-4R RRH; (25.8"x11.8"x7.2", Wt. = 56.8 Ibs), Total (3)
Front
A. Solid Freestandina Walls & Solid Signs M ooen signs with less than 30% ooen
sih = 0.0E
Case A & B
Dist to sign tap (h f
-'.2 ft
Bis = 0.-�
C. =
1.8E
Height (s)
2.2 ft
Lris = 0.00
F = qz G Cf As =
43.9 As
Width (B)
1.0 ft
Kz = 1.M1
As
2.1 sf
Wall Return (Lrf
Ctz = 27.9 psf
F =
93 Ibs
Directionality (Kd)
G-135
LASCE7 Load Combinations Used
Side
A. Solid Freestanding Walls & Solid Signs (& open signs With less than 30% op"n�
sih = 0.0E
Case A & B
Dist to sign top (h)
43.2 ft Bis = 0.29
C. = 1. SE
Height (s)
2.2 ft Lris = 0.00
F = qz G Cf As = 43.9 As
Width (B f
0.6 ft Kz = 1.0 1
As 1." sf
Wall Return (Lr) =
qz = 27.9 psf
F = 57 lbs
Directionality (Kd)
9.$5 ASCE7 Load Combinations Used
7. AT&T Existing (1) Nokia Flexi RRH 4T4R B14 160W FRBI RRH;
(23.0"x13.0"x7.9", Wt. = 55.1 Ibs), Total (3)
Front
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% op"n�
Dist to sign top (hf
Height (s)
Width (B f
Wall Return (Lr) =
Directionality (Kd f
sih = 0.04
13.2 ft Bis = O.E7
1.9 ft Lris = 0.00
1.1 ft Kz = 1.061
z = 27.9 psf
ASCE7 Load Combinations Used
Case A & B
C. =
1.3-
F = qz G Cf As =
43.8 As
As =
2.1 sf
F =
51 ICs
Rooftop Structural Analysis Report
Project Number. SML-055 / 2000479
December 22, 2020
Page 11
Side
A. Solid Freestanding Walls & Solid Signs (& open signs With less than 30% open
sJh =
0.04
Case.A a B
Dist to sign top (h)
43.2 ft
Ells =
0.34
Height (s)
1.19 ft
Lrls =
0.09
F = qz f = 43.0 As
Width (B)
0.7 ft
Kz =
1.061
As = =f
Wall Return (Lr)
qz =
27.9 psf
F = It
Blrectlonality (Kd'
0.85
ASCE7 Load Combinations Use( -
8. AT&T Existing (1) Lucent RRH2X40W-07-11- RRH; (19.3"x10.6"x9.7", Wt. = 52.4 Ibs), Total (3)
Front
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% open
Soh =
C.4-i
Case A & B
Dist tk sign tap (h)
43.2 ft
Bls =
C. =
G =
1.35
Height (s)
1.6 ft
Lrls =
0.00
F = qz G Cf As =
43.8 As
tiiltidth (B)
0.-D ft
Kz =
1.061
As =
1.4 sf
Wall Return (Lr)
qz =
27.9 psf
F =
62 Ibis
Directionality (Kd)
0.85
1 ASCE7 Load Combinations Use( -
Side
A. Solid Freestanding Nulls & Solid Signs (& open signs with less than 301� open)
sdh =
0.04
Case A & B
Dist to sign top (h)
43.2 ft
Bfs =
0.50
C. =
1.85
Height (s)
1.6 ft
Lrls =
0.00
F = qz G CfAs =
43.9 As
Width (B)
0.8 ft
Kz =
1.061
As =
1.3 sf
Wall Return (Lr)
qz =
27.9 psf
F =
57 Ibs
Directionality (Kd:-
0.35
ASCE7 Load Combinations Use(
9. AT&T Existing (1) Lucent RRH4X25-WCS-4R RRH; (34.7"x13.2"x11.3", Wt. = 91.0 Ibs), Total (3)
Front
A. Solid Freestanding Walls & Solid Signs (& open signs With less than 30°4 open
sih =
" "'
Case A & B
Dist to sign tap (h)
43.2 ft
Bfs =
0.38
G =
135
Height (s)
2.9 ft
Lrls =
0.09
F = qz U -,'f As =
43.9 As
Width (5)
1.1 ft
Kz =
1.061
As =
3.2 sf
Wall Return (Lr)
ciz =
27.9 psf
F =
140 Ibis
Directionality (Kd)
4.85
ASCE7 Load Combinations Use( -v
Side
A. Solid Freestanding Walls & Solid Signs (& open signs With less than 30% open)
Dist to sign tap (h)
Height (s)
Width (B)
Nall Return (Lr) _
Directionality (Kd)
srh =
0.07
43.2 ft
Bds =
0.33
2.9 ft
Lrfs =
0.90
0.9 ft
Kz =
1.061
CIZ _
27.9 psf
0.$5
ASCE7 Load Combinations Use( �
Case A & B
G =
1.35
F = qz G Cf As =
43.9 As
As =
2.7 sf
F =
129 Ibis
m0
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 12
10. AT&T Proposed (1) Kathrein 78211288 Combiner; (6.7"x6.0"x6.6", Wt. = 11.0 Ibs), Total (3)
Front
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% opgn]
sih =
0.01
Case A & B
Dist to sign top (h) 43.2 ft
Bis =
0.90
C. =
1.31
Height (s) 0.6 ft
Lris =
0.00
F = qz G Cf As =
43.0 As
Width (B) 0.5 ft
Kz =
1.061
As =
0.3 sf
Wall Return (Lr) =
gz =
27.9 psf
F =
12 Ibs
Directionality (Kd) 935 [ASCE7 Load Combinations Usec- I
Side
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% open)
sth =
0.01
Case A & B
Gist to sign tap (h)
43.2 ft
Bfs =
0.99
C. =
1.90
Height (s)
0.6 ft
Lris=
0.00
F = gz G Cf As =
42.8 As
'Nidth (8)
0.6 ft
Kz =
1.061
As =
u.' sf
'-Nall Return (Lr)
qz=
27.E psf
F =
1 a Ibs
Directionality (Kd)
0.85
ASCE7 Load Combinations Use( v
11. AT&T Existing (1) Kathrein 78211287 Combiner; (6.7"x6.0"x3.2", Wt. = 5.5 Ibs), Total (6)
Front
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% open)
sih =
0.01
Case A & B
Dist to sign top (h) 43.2 ft
Bis =
0.90
C, =
1.91
Height (s) 0.6 ft
Lrls =
0.00
F = gz G Cf As =
43.0 As
Width (B) 0.5 ft
Kz =
1.061
As 3
u.' sf
Wall Return (Lr} =
qz =
27.9 psf
F =
12 Ibs
Directionality, (Kd) 0.35 [ASCE7 Load Combinations Use(
Side
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% open)
sft
0.01
Case A & B
Gist to sign tap (h)
43.2 ft
Bfs=
0.-18
G =
1.8F
Height (s)
0.6 ft
Lris=
0.00
F = qz G Cf As =
43.9 As
VOCIth (B)
0.3 ft
Ka =
1.061
As =
-1 sf
)Nall Return (Lr)
qz=
27.9 psf
F =
7 Ibs
Directionality (Kd)
0.85
1 ASCE7 Load Combinations Use( -
12. AT&T Existing (1) Raycap FC12-PC6-10E J-Box; (15.5"x16.2"x6.6", Wt. = 20.4 Ibs), Total (3)
Front
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% op"n�
Dist to sign top (h;
Height (s)
Width (B)
Wall Return (Lr) _
Directionality (Kd)
slh = 0.05
='.2 ft Bis = 1.05
1.a ft Lris = 0.00
1.4 ft Kz = 1.061
ctz = 27.9 psf
9-85 ASCE7 Load Combinations Use( -w
Case A & B
CJ
= 1.90
F=gz -CfAs
= 42.7As
As
= 1.7 sf
F
= 75 Ibs
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 13
Side
A. Solid Freestanding Malls & Solid Signs (& open signs with less than 30% open)
s1h =
0.0 3
Case A & B
Dist to sign tap (h) 43.2 ft
B/s =
0.43
G = 1.95
Height (a) 1.3 ft
Lr/s =
0.00
F = qz G Cf As = 43.9 As
Width (B) 0.6 ft
Kz =
1.061
As = U.' sf
Nall Return (Lri =
qz =
27.9 psf
F = 31 Ihs
Directionality (Kd) OAKS EASCE7 Load Combinations Use(
13. AT&T Existing (1) Raycap DC2-48-60-0-9E J-Box; (10.8"x10.4"x6.3", Wt. = 16.0 Ibs), Total (9)
Front
A. Solid Freestanding Nulls & Solid Signs (& open signs with less than 30% open)
sih =
0.02
Case A & B
Dist to sign top (h) 443.2 ft
B/s =
0.96
G =
1.90
Height (s) 0.9 ft
Lr/s =
0.00
F = qz G Cf As =
42.8 As
Width (By 0.9 ft
Kz =
1.061
As =
C.3 sf
Wall Return (Lr) =
qz =
27.9 psf
F =
33 Ihs
Directionality (Kd) O.KS ASCE7 Load Combinations Use(
Side
A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% open)
sth = 0.02
Case A & B
Dist to sign tap (h)
443.2 ft
B;fs= 0.
G =
1.94
Height (s)
0.9 ft
Lrfs = 0.00
F = qz G Cf As =
43.7 As
Width (B)
0.5 ft
Kz = 1.061
As =
u.` sf
Nall Return (Lr)
CIZ = 27.9 psf
F =
21 Ihs
Directionality (Kd)
O.KS
1 ASCE7Load Combinations Use( - I
WIND LOAD CALCULATIONS ON MOUNT MEMBERS
1. P2.0 STD Mast Pipe WF = (30.9)*(2.375/12) = 6.1 Ibs/ft
B. Open Sions & Lattice Frameworks (openings 30% or more of gross areal
Height to centroid afAf (a}' 4a.2 f. Kz = 1.061
Base pressure (qz) = 27.9 psf
'Xidth (zero if round) -0.0 ft
Diameter (zero if recc 0.2 ft D(gz)".E = 1.0E
Percent of open area I = 0.1
to grass area 90.0% G = 1.3
Directionality (Kd) 0.95 ASCE7 Load Combinations Used
F=q, G G1%, = 30.9 Af
Solid Area: A sf
F = 0 Ibs
m0
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 14
SEISMIC LOAD CALCULATIONS ON APPURTENANCES
Code: International Building Code 2015
Occupancy:
Occupancy Group = Business
Risk Category & Importance Factors:
Risk Category Category II: All bldgs and other structures except those listed in Categories I, III, & IV
Seismic Loads: IBC 2015 Strength Level Forces
Risk Category : II
Importance Factor (I) : 1.00
Site Class'. D class a
Ss (0.2 sec) = 127.00
S1 (1.0 sec) = ` c.1 ; '.':
Fa = 1.000 Sms = 1.273 S_---- = ME2 Design Category = D
Fir = 1.E00 Sm1 = 0.7E2 S_., = 0.E01 Design Category = D
MECH AND ELEC COMPONENTS SEISMIC COEFFICIENTS
l.lech or Electrical Component : Other mechanical or electrical components. -I
Importance Factor (Ip} : Ip = 1.5 Life safety component required to function after an earthquake (e.g. fire protection sprinklers T
Component Amplification Factor (ad = 1 h= 46.3 feet J
Camp Response Modification Factor (Rk) = 1.5 z =q �µ.3 feet z1h = 1.00
Fp = 0.4a,SdslpWp(1+2zlhYRp = 1.022 Wp
not greater than Fp = 1.15SclslpWp = 2.0,45 Wp
but not less than Fp = 0.3Sclslpft = MZ3 Wp use Fp = 1.022 Vdp
1. AT&T Proposed (1) Cellmax CMA-UBTMLBMLBHH/6516/16/21/21 Panel;
(72.4"x27.2"x7X', Wt. = 85.0 Ibs), Total (2)
Seismic Load, FP = 1.022 WP = 1.022 x 85.0 = 86.9 Ibs
2. AT&T Proposed (1) Kathrein 800372965 Panel; (78X'x14.9"x6.5", Wt. = 79.0 Ibs), Total (1)
Seismic Load, FP = 1.022 WP = 1.022 x 79.0 = 80.7 Ibs
3. AT&T Existing (1) Kathrein 80010864 Panel; (55.2"x14.8"x6X', Wt. = 55.1 Ibs), Total (3)
Seismic Load, FP = 1.022 WP = 1.022 x 55.1 = 56.3 Ibs
4. AT&T Proposed (1) Nokia AIRSCALE RRH 4T4R B5 160W RRH;
(13.3"x11.6"x6.5", Wt. = 36.8 Ibs), Total (3)
Seismic Load, FP = 1.022 WP = 1.022 x 36.8 = 37.6 Ibs
m0
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 15
5. AT&T Existing (1) Lucent B25 RRH4X30-4R RRH; (21.4"x12.0"x7.2", Wt. = 51.0 Ibs), Total (3)
Seismic Load, FP = 1.022 WP = 1.022 x 51.0 = 52.1 Ibs
6. AT&T Existing (1) Lucent B66A RRH4X45-4R RRH; (25.8"x11.8"x7.2", Wt. = 56.8 Ibs), Total (3)
Seismic Load, FP = 1.022 WP = 1.022 x 56.8 = 58.0 Ibs
7. AT&T Existing (1) Nokia Flexi RRH 4T4R B14 160W FRBI RRH;
(23.0"x13.0"x7.9", Wt. = 55.1 Ibs), Total (3)
Seismic Load, FP = 1.022 WP = 1.022 x 55.1 = 56.3 Ibs
8. AT&T Existing (1) Lucent RRH2X40W-07-L RRH; (19.3"x10.6"x9.7", Wt. = 52.4 Ibs), Total (3)
Seismic Load, FP = 1.022 WP = 1.022 x 52.4 = 53.6 Ibs
9. AT&T Existing (1) Lucent RRH4X25-WCS-4R RRH; (34.7"x13.2"x11.3", Wt. = 91.0 Ibs), Total (3)
Seismic Load, FP = 1.022 WP = 1.022 x 91.0 = 93.0 Ibs
10. AT&T Proposed (1) Kathrein 78211288 Combiner; (6.7"x6.0"x6.6", Wt. = 11.0 Ibs), Total (3)
Seismic Load, FP = 1.022 WP = 1.022 x 11.0 = 11.2 Ibs
11. AT&T Existing (1) Kathrein 78211287 Combiner; (6.7"x6.0"x3.2", Wt. = 5.5 Ibs), Total (6)
Seismic Load, FP = 1.022 WP = 1.022 x 5.5 = 5.6 Ibs
12. AT&T Existing (1) Raycap FC12-PC6-10E J-Box; (15.5"x16.2"x6.6", Wt. = 20.4 Ibs), Total (3)
Seismic Load, FP = 1.022 WP = 1.022 x 20.4 = 20.8 Ibs
13. AT&T Existing (1) Raycap DC2-48-60-0-9E J-Box; (10.8"x10.4"x6.3", Wt. = 16.0 Ibs), Total (9)
Seismic Load, FP = 1.022 WP = 1.022 x 16.0 = 16.4 Ibs
m•
Y
ZAX
Beta Sector
Envelope Only Solution
Morrison Hershfield
VG
SML-055 / 2000479
Existing Mast pipes mounted
using unsitruts in Position 2 in
Alpha & Beta sectors are now
moved to brick chimney using
SP250 mounting system and
connected using HY-200
20533-A/ PUGET DRIVE
Alpha Sector
SK-1
Dec 21, 2020
Antenna Pipe Mounts.r3d
Y
N14
z x
N N1
N19
3
�75
jlrpf-
9
rN N4 N55
?6
�0
N2 N39
N 17
N20 N60
8 LJ 43
�6 �5
�3
N8
N13 N38
0
�8
N42
N59
87
N48
Envelope Only Solution N' l
Morrison Hershfield 20533-A/ PUGET DRIVE SK-2
VG Dec 21, 2020
SML-055 / 2000479 Antenna Pipe Mounts.r3d
Y
Z � X
Z
S �
?S
a
w 2
3
�9
1
�r2 err
Co
�rO
Co
�24
Envelope Only =olution
Morrison Hershfield 20533-A/ PUGET DRIVE SK-3
VG Dec 21, 2020
SML-055 / 2000479 Antenna Pipe Mounts.r3d
Y
Z � X
Im
N
O 0
Im
� N
� � O
m
N m
o IN
O
m
I �
N
O m
m
m I
� N
m O
m �
IN m
p IN
O
Envelope Only Solution
Morrison Hershfield 20533-A/ PUGET DRIVE SK-4
VG Dec 21, 2020
SML-055 / 2000479 Antenna Pipe Mounts.r3d
Y
z x -42.5 Ib
-2 .5 lb
IX
-22 lb -42.5 lb
IF
-42.51b -27.5lb IF -2 .5lb
-22 lb
IF
-42 5 lb -27.5 lb
IF
Loads: BLC 1, DL
Envelope Only Solution
Morrison Hershfield 20533-A/ PUGET DRIVE SK-5
VG Dec 21, 2020
SML-055 / 2000479 Antenna Pipe Mounts.r3d
Y
-6.1 Iblft
z�x
-6.1 Iblft
87lb 11b1ft
5m.5 1b -5.1lb/ft
-6.1 Iblft
lb
-6.1 Ib/ft
-87 lb 1 Ib/ft
-57.5lb
U-51211.5lb -6.1 IbIft
-300.5 lb
RA
lb
57.5 lb
-87 lb
Loads: BLC 2, WIND X
Envelope Only Solution
Morrison Hershfield
20533-A/ PUGET DRIVE
SK-6
VG
Dec 21, 2020
SML-055 / 2000479
Antenna Pipe Mounts.r3d
Y
-6.1 Iblft
z�x
-6.1 Iblft
87lb 6. Iblft
1 lb -6.1 Iblft
o
o
-6.1 Ib/ft
o
lb
-6.1 Iblft
00.5lb 6. Ib/ft
o
125lb 1 lb 6.1 Iblft
87 lb
lb
125 lb
IX
00.5 lb
Loads: BLC 3, WIND Z
Envelope Only Solution
Morrison Hershfield 20533-A/ PUGET DRIVE SK-7
VG Dec 21, 2020
SML-055 / 2000479 Antenna Pipe Mounts.r3d
Y
Z�X
4.5b
-28_ lb
IX
-5.6 lb
4 .5
-28.2 lb -28. lb
-4 .5 lb
-5.6 lb
-282 lb
.5 I
Loads: BLC 4, SESIMIC X
Envelope Only Solution
Morrison Hershfield 20533-A/ PUGET DRIVE SK-9
VG Dec 21, 2020
SML-055 / 2000479 Antenna Pipe Mounts.r3d
Y
Z�X
-43.5
-28IX
-5.
-43.5 I
-28. -28.
-43.5 I IX X
-5_
-28 _
-43.5 I
Loads: BLC 5. SEISMIC Z
Envelope Only Solution
Morrison Hershfield 20533-A/ PUGET DRIVE SK-10
VG Dec 21, 2020
SML-055 / 2000479 Antenna Pipe Mounts.r3d
Company Morrison Hershfield 12/21/2020
1RISA
Designer : VG hPM
Job Number Checked
SML-055 / 2000479 Checkee d By: SWS
'], � I �„ �; _,[, ,r Model Name : 20533-A / PUGET DRIVE
Model Settings
Solution
Members
Number of Reported Sections
5
Number of Internal Sections
100
Member Area Load Mesh Size in2
144
Consider Shear Deformation
Yes
Consider Torsional Warping
Yes
Wall Panels
Approximate Mesh Size in
12
Transfer Forces Between Intersecting Wood Walls
Yes
Increase Wood Wall Nailing Capacity for Wind Loads
Yes
Include P-Delta for Walls
Yes
Optimize Masonry and Wood Walls
Yes
Maximum Number of Iterations
3
Processor Core Utilization
Single
No
Multiple (Optimum)
Yes
I
Maximum
No
Axis
Vertical Global Axis
Global Axis corresponding to vertical direction Y
Convert Existing Data Yes
Default Member Orientation
Default Global Plane for z-axis Xz
Plate Axis
Plate Local Axis Orientation Nodal
Codes
Hot Rolled Steel
AISC 15th 360-16 : LRFD
Stiffness Adjustment
Yes Iterative
Notional Annex
None
Connections
None
Cold Formed Steel
None
Stiffness Adjustment
Yes Iterative
Wood
None
Temperature
< 100F
Concrete
None
Masonry
None
Aluminum
None
Structure Type
Building
Stiffness Adjustment
Yes Iterative
Stainless
None
Stiffness Adjustment
Yes Iterative
Concrete
Compression Stress Block
Rectangular Stress Block
Analyze using Cracked Sections
Yes
Leave room for horizontal rebar splices 2*d barspacing)
No
List forces which were ignored for design in the Detail Report
Yes
Rebar
Column Min Steel 1
RISA-3D Version 19 [Antenna Pipe Mounts.r3d ] Page 1
Company Morrison Hershfield 12/21/2020
1RISA
Designer : VG hPM
Job Number Checked
SML-055 / 2000479 Checkee d By: SWS
a M . I c:��.��r, �� Model Name : 20533-A / PUGET DRIVE
Model Settings (Continued)
Column Max Steel
8
Rebar Material Spec
ASTM A615
I
Warn if beam -column framing arrangement is not understood
No
Number of Shear Regions 14
Reaion 2 & 3 SDacina Increase Increment (in) 14
Seismic
RISA-3D Seismic Load Options
Code
ASCE 7-10
Risk Category
I or II
Drift Cat
Other
Base Elevation ft
Include the weight of the structure in base shear calcs
Yes
Site Parameters
S,
0.501
SD,
0.501
SDS
0.852
TL sec
6
Structure Characteristics
T Z sec
T X sec
C,X
0.02
C,Ex . Z
0.75
C,Ex . X
0.75
RZ
3
RX
3
Olz
2
O2 x
2
CIZ
4
C,x
4
Z
1
X
1
RISA-3D Version 19 [Antenna Pipe Mounts.r3d ] Page 2
Company Morrison Hershfield 12/21/2020
11RISA6
Checked
Designer VG hPM
Job Number SML-055 / 2000479 Checkee d By: SWS
ANEMETSCHEK COMPANY Model Name : 20533-A /PUGET DRIVE
Hot Rolled Steel Properties
Label E ksi G ksi Nu Therm. Coeff. ley°F-' Density k/ft3 Yield ksi Ry Fu ksi Rt
1 A53 Gr.B 29000 11154 0.3 0.65 1 0.49 1 35 1.6 1 60 1 1.2
Hot Rolled Steel Section Sets
Label Shape Type Design List Material Design Rule Area [in 2] I [in']Izz [in']J in4
1 Mast Pipe PIPE 2.0 Column Pipe A53 Gr.6 Typical 1.02 0.627 0.627 1.25
Hot Rolled Steel Design Parameters
I ahPl Shane I Pnnth rinl I rmmn ton rinl Function
1 M1
Mast Pie
48
Lbyy
Lateral
2 M2
Mast Pie
72
Lbyy
Lateral
3 M3
Mast Pie
96
Lbyy
Lateral
4 M4
Mast Pie
48
Lbyy
Lateral
5 M5
Mast Pie
48
Lbyy
Lateral
6 M6
Mast Pie
72
Lbyy
Lateral
7 M7
Mast Pie
96
Lbyy
Lateral
8 M8
Mast Pie
48
Lbyy
Lateral
Node Boundary Conditions
NnrlP I ahPl X rlh/inl Y rlh/inl 7 rlh/inl
1
N25
Reaction
Reaction
Reaction
2
N26
Reaction
Reaction
Reaction
3
N27
Reaction
Reaction
Reaction
4
N28
Reaction
Reaction
Reaction
5
N29
Reaction
Reaction
Reaction
6
N30
Reaction
Reaction
Reaction
7
N31
Reaction
Reaction
Reaction
8
N32
Reaction
Reaction
Reaction
9
N33
Reaction
Reaction
Reaction
10
N34
Reaction
Reaction
Reaction
11
N35
Reaction
Reaction
Reaction
12
N36
Reaction
Reaction
Reaction
13
N40
Reaction
Reaction
Reaction
14
N46
Reaction
Reaction
Reaction
15
N52
Reaction
Reaction
Reaction
16
N63
Reaction
Reaction
Reaction
17
N65
Reaction
Reaction
Reaction
18
N66
Reaction
Reaction
Reaction
19
N67
Reaction
Reaction
Reaction
20
N68
Reaction
Reaction
Reaction
21
N69
Reaction
Reaction
Reaction
22
N70
Reaction
Reaction
Reaction
23
N71
Reaction
Reaction
Reaction
24
N72
Reaction
Reaction
Reaction
Basic Load Cases
BLC Descrintion Cateoory Y Gravity Point Distributed
1 DL
DL
-1
12
2 WIND X
WLX
10
8
3 WIND Z
WLZ
12
8
4 SESIMIC X
ELX
12
5 SEISMIC Z
ELZ
12
Load Combinations
Solve PDelta BLC Factor BLC Factor BLC Factor BLC Factor BLC Factor
2 1 IBC 16-2 (a) I Yes I Y I DL 1 1.2 I LL 1 1.6 I LLS I 1.6
RISA-31D Version 19 [Antenna Pipe Mounts.r3d ] Page 3
Company Morrison Hershfield 12/21/2020
11RISA6
Checked
Designer VG hPM
Job Number SML-055 / 2000479 Checkee d By: SWS
ANEMETSCHEK COMPANY Model Name : 20533-A /PUGET DRIVE
Load Combinations (Continued)
Dt-scrintinn Snlvp PDt-Itn RI C Factnr RI C Factnr RI C Factnr RI C Factnr RI C Factnr
3
IBC 16-3 b a
Yes
Y
DL
1.2
WLX
0.5
4
IBC 16-3 b b
Yes
Y
DL
1.2
WLZ
0.5
5
IBC 16-3 b c
Yes
Y
DL
1.2
WLX
-0.5
6
IBC 16-3 b d
Yes
Y
DL
1.2
WLZ
-0.5
7
IBC 16-4 a a
Yes
Y
DL
1.2
WLX
1
LL
0.5
ILLS
1
8
IBC 16-4 a b
Yes
Y
DL
1.2
WLZ
1
LL
0.5
ILLS
1
9
IBC 16-4 a c
Yes
Y
DL
1.2
WLX
-1
LL
0.5
ILLS
1
10
IBC 16-4 a d
Yes
Y
DL
1.2
WLZ
-1
LL
0.5
ILLS
1
11
IBC 16-6 a
Yes
Y
DL
0.9
WLX
1
12
IBC 16-6 b
Yes
Y
DL
0.9
WLZ
1
13
IBC 16-6 c
Yes
Y
DL
0.9
WLX
-1
14
IBC 16-6 d
Yes
Y
DL
0.9
WLZ
-1
15
IBC 16-5 a
Yes
Y
DL
1.2
Sds*DL
0.2
ELX
1
LL
0.5
ILLS
1
16
IBC 16-5 b
Yes
Y
DL
1.2
Sds*DL
0.2
ELZ
1
LL
0.5
ILLS
1
17
IBC 16-5 c
Yes
Y
DL
1.2
Sds*DL
0.2
ELX
-1
LL
0.5
ILLS
1
18
IBC 16-5 d
Yes
Y
DL
1.2
Sc1s*DL
0.2
ELZ
-1
LL
0.5
ILLS
1
19
IBC 16-7 a
Yes
Y
DL
0.9
Sds*D
-0.2
ELX
1
20
IBC 16-7 b
Yes
Y
DL
0.9
Sds*D
-0.2
ELZ
1
21
IBC 16-7 c
Yes
Y
DL
0.9
Sds*D
-0.2
ELX
-1
22
IBC 16-7 d
Yes
Y
DL
0.9
Sds*D
-0.2
ELZ
-1
23
IBC 16-5 os-a
Yes
Y
DL
1.2
Sds*DL
0.2
Om*ELX
1
LL
0.5
ILLS
1
24
IBC 16-5 os-b
Yes
Y
DL
1.2
Sds*DL
0.2
Om*ELZ
1
LL
0.5
ILLS
1
25
IBC 16-5 os-c
Yes
Y
DL
1.2
Sds*DL
0.2
Om*EL
-1
LL
0.5
ILLS
1
26
IBC 16-5 os-d
Yes
Y
DL
1.2
Sc1s*DL
0.2
Om*ELZ
-1
LL
0.5
ILLS
1
27
IBC 16-7 os-a
Yes
Y
DL
0.9
Sds*D
-0.2
Om*ELX
1
28
IBC 16-7 os-b
Yes
Y
DL
0.9
Sds*D
-0.2
Om*ELZ
1
29
IBC 16-7 os-c
Yes
Y
DL
0.9
Sds*D
-0.2
Om*EL
-1
30
IBC 16-7 os-d
Yes
Y
DL
0.9
Sds*D
-0.2
Om*ELZ
-1
31
IBC 16-5 a
Yes
Y
DL
1.2
Sds*DL
0.2
ELX
1
LL
0.5
ILLS
1
32
IBC 16-5 b
Yes
Y
DL
1.2
Sds*DL
0.2
ELZ
1
LL
0.5
ILLS
1
33
IBC 16-5 c
Yes
Y
DL
1.2
Sds*DL
0.2
ELX
-1
LL
0.5
ILLS
1
34
IBC 16-5 d
Yes
Y
DL
1.2
Sc1s*DL
0.2
ELZ
-1
LL
0.5
ILLS
1
35
IBC 16-7 a
Yes
Y
DL
0.9
Sds*D
-0.2
ELX
1
36
IBC 16-7 b
Yes
Y
DL
0.9
Sds*D
-0.2
ELZ
1
37
IBC 16-7 c
Yes
Y
DL
0.9
Sds*D
-0.2
ELX
-1
38
IBC 16-7 d
Yes
Y
DL
0.9
Sds*D
-0.2
ELZ
-1
Envelope Node Reactions
NndB I ahel X rlhl LC Y flhl LC 7 FIN r C MX rk-in] I C MY rk-inl L C M7 rk-in] I C
1
N25
max
88.424
7
276.265
9
133.374
13
0
38
0
38
0
38
2
min
-18.424
9
-221.174
11
-158.43
7
0
1
0
1
0
1
3
N26
max
69.581
11
55.663
7
248.325
9
0
38
0
38
0
38
4
min
-69.581
13
-16.586
13
-223.293
11
0
1
0
1
0
1
5
N27
max
56.335
7
434.512
9
108.958
13
0
38
0
38
0
38
6
min
-56.335
9
-375.242
11
-117.622
7
0
1
0
1
0
1
7
N28
max
161.815
11
764.062
7
328.58
9
0
38
0
38
0
38
8
min
-161.815
13
-704.923
13
-319.916
11
0
1
0
1
0
1
9
N29
max
6.863
7
21.305
9
11.707
13
0
38
0
38
0
38
10
min
-6.863
9
-3.147
11
-16.416
7
0
1
0
1
0
1
11
N30
max
11.337
11
21.883
7
25.366
9
0
38
0
38
0
38
12
min
-11.337
13
-2.364
13
-20.657
11
0
1
0
1
0
1
13
N31
max
18.424
7
276.265
7
133.374
11
0
38
0
38
0
38
14
min
-18.424
9
-221.174
13
-158.43
9
0
1
0
1
0
1
15
N32
max
69.581
11
55.663
9
248.325
7
0
38
0
38
0
38
16
min
-69.581
13
-16.586
11
-223.293
13
0
1
0
1
0
1
17
N33
max
56.335
7
434.512
7
108.958
11
0
38
0
38
0
38
18
min
-56.335
9
-375.242
13
-117.622
9
0
1
0
1
0
1
19
N34
max
161.815
11
764.062
9
328.58
7
0
38
0
38
0
38
RISA-31D Version 19 [Antenna Pipe Mounts.r3d ] Page 4
Company Morrison Hershfield 12/21/2020
11RISA6
Checked
Designer VG hPM
Job Number SML-055 / 2000479 Checkee d By: SWS
ANEMETSCHEK COMPANY Model Name : 20533-A /PUGET DRIVE
Envelope Node Reactions (Continued)
Nndt- I ahPI X rlhl I C Y flhl I C 7 FIN I (; MX fk-inl I C MY fk-inl I C M7 rk-inl I C
20
min
-161.815
13
-704.923
11
-319.916
13
0
1
0
1
0
1
21
N35
max
6.863
7
21.305
7
11.707
11
0
38
0
38
0
38
22
min
-6.863
9
-3.147
13
-16.416
9
0
1
0
1
0
1
23
N36
max
11.337
11
21.883
9
25.366
7
0
38
0
38
0
38
24
min
-11.337
13
-2.364
11
-20.657
13
0
1
0
1
0
1
25
N40
max
69.581
11
55.663
7
248.325
9
0
38
0
38
0
38
26
min
-69.581
13
-16.586
13
-223.293
11
0
1
0
1
0
1
27
N46
max
18.424
7
276.265
7
133.374
11
0
38
0
38
0
38
28
min
-18.424
9
-221.174
13
-158.43
9
0
1
0
1
0
1
29
N52
max
11.337
11
21.883
9
25.366
7
0
38
0
38
0
38
30
min
-11.337
13
-2.364
11
-20.657
13
0
1
0
1
0
1
31
N63
max
6.863
7
21.305
9
11.707
13
0
38
0
38
0
38
32
min
-6.863
9
-3.147
11
-16.416
7
0
1
0
1
0
1
33
N65
max
18.424
7
276.265
9
133.374
13
0
38
0
38
0
38
34
min
-18.424
9
-221.174
11
-158.43
7
0
1
0
1
0
1
35
N66
max
56.335
7
498.512
8
178.576
12
0
38
0
38
0
38
36
min
-56.335
9
-439.154
14
-187.227
10
0
1
0
1
0
1
37
N67
max
55.065
11
498.385
10
147.556
8
0
38
0
38
0
38
38
min
-55.065
13
-439.278
12
-138.917
14
0
1
0
1
0
1
39
N68
max
11.337
11
21.883
7
25.366
9
0
38
0
38
0
38
40
min
-11.337
13
-2.364
13
-20.657
11
0
1
0
1
0
1
41
N69
max
69.581
11
55.663
9
248.325
7
0
38
0
38
0
38
42
min
-69.581
13
-16.586
11
-223.293
13
0
1
0
1
0
1
43
N70
max
56.335
7
498.512
8
178.576
12
0
38
0
38
0
38
44
min
-56.335
9
-439.154
14
-187.227
10
0
1
0
1
0
1
45
N71
max
55.065
11
498.385
10
147.556
8
0
38
0
38
0
38
46
min
-55.065
13
-439.278
12
-138.917
14
0
1
0
1
0
1
47
N72
max
6.863
7
21.305
7
11.707
11
0
38
0
38
0
38
48
min
-6.863
9
-3.147
13
-16.416
9
0
1
0
1
0
1
49
Totals:
max
1083.9
11
667.403
1
1595.4
12
50
min
-1083.9
13
347.812
22
-1595.4
10
Envelope AISC 15TH (360-16): LRFD Member Steel Code Checks
MPmhPr Shane Cndp ChPcki ncfinl I C Shaar ChPcki ncfinll C:nhi*Pnr flhlnhi*Pnt flhlnhi*Mn v-v fk-inlnhi*Mn 7-7 fk-inl Ch Fnn
1 M 1
PIPE 2.0
0.055
36
12
0.029
41
9
26521.424
32130
22.459
22.459
1
H 1-1 b
2 M2
PIPE 2.0
0.139
36
10
0.015
36
1420866.733
32130
22.459
22.459
1
H1-1b
3 M3
PIPE 2.0
0.102
71
9
0.032
71
1314916.096
32130
22.459
22.459
2.072H1-lb
4 M4
PIPE 2.0
0.006
39
8
0.003
39
1026521.424
32130
22.459
22.459
1
H1-1b
5 M5
PIPE 2.0
0.055
36
12
0.029
41
9
26521.424
32130
22.459
22.459
1
H1-1b
6 M6
PIPE 2.0
0.139
36
10
0.015
36
1420866.733
32130
22.459
22.459
1
H1-1b
7 M7
PIPE 2.0
0.202
30
14
0.033
30
1014916.096
32130
22.459
22.459
1
H1-1b
8 M8
PIPE 2.0
0.006
39
8
0.003
39
1026521.424
32130
22.459
22.459
1
H1-1b
RISA-31D Version 19 [Antenna Pipe Mounts.r3d ] Page 5
Y Code Check
(Env)
z x No Calc
> 1.0
.90-1.0
_ .75-.90
.50-.75
0.-.50
0
0
0
0
0
0
0
0
0
rn
0
0
0
N O
O
A
Member Code Checks Displayed (Enveloped)
Envelope Only Solution
Morrison Hershfield 20533-A/ PUGET DRIVE SK-11
VG Dec 21, 2020
SML-055 / 2000479 Antenna Pipe Mounts.r3d
Y Shear Check
(Env)
z x No Calc
> 1.0
.90-1.0
_ .75-.90
.50-.75
= 0.-.50
0
0
w
0
0
0
0
0 0
W O
O
O
W
O
O
O
O
O O
W O
Member Shear Checks Displayed (Enveloped)
Envelope Only Solution
Morrison Hershfield 20533-A/ PUGET DRIVE SK-12
VG Dec 21, 2020
SML-055 / 2000479 Antenna Pipe Mounts.r3d
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 22, 2020
Page 16
BOLT CONNECTION CHECK
LC
I Node Label
X Ibs
Y Ibs
Z Ibs
MX [kip —in
MY [kip —in
MZ [kip-inj [kip—in
Shear
Tension
1.0 DL + 0.14 Sds`DL + 0.7 Om"ELX
N31
6.243
164.459
56.665
0
0
0
164.6
0.0
0.6 DL - 0.14 Sds`DL + 0.7 Om`ELX
N26
33.245
33.149
-108.515
0
0
0
46.9
-108.5
existing are (2) 1/2" dia. Hilti HIT threaded rod w/ Hilti HY20 anchoring system w/ 3" embedment used for
connecting the pipe mounts.
HIT HY 20 Allowable Loads for Threaded HIT- I Inserts in Hollow Concrete Block,
Lightweight Concrete Block, Brick with Holes, Clay Tile'-2
Hff Short 2" (51 mmp Embedment
HIT Standard 3.3M" (86mm) Embedment?
LM or NIIW Hallow Conar sts Block
Brick with Hales
Clay Tllc
Anchor
Type
Anchof �r
arn
In (mm)
Tendon
Shear
Tension
Shear
Tendon
Shear
lb (kM
lb (kM
Ib {kN)
lb (kN}
lb (kl*
Ib (kN)
No. 14 Screw
240
510
300
530
85
150
(6.4)
(1-1)
-3j
(1.3)
(2.4)
;0-4j
(0-7)
5J16
400
780
585
750
1T5
220
HIT •Ilnsert
(7.9)
(1-13)
p-5i
(2.6)
(3.3)
{0-8)
(1-0)
Anchor
318
400
1425
1160
1380
185
435
(9.5)
(1-8)
{6."si
(5-2)
(6.1)
{0-8)
(1-9)
11.2
400
1800
1160
1635
185
500
(12-7)
{1-B}
1:8-01
(5-2)
(7.3)
p-s3
(2-2)—
I Based on using a safety factor of 6 for tension anci 4 for shear-
2 Due to wide strength variatlons encounkcred in masonry, these values should be considered as g ulide values-
3 #14 screw Installed at 2" emt�ed mcnt in brick with holes and clay tl Ia.
Allowable Shear = 1635 Ibs
Allowable Tension = 1160 Ibs
Shear Capacity = 164.6/1635 = 10.1% [OK!]
Tension Capacity = 108.5/1160 = 9.4% [OK!]
IV 0
Rooftop Structural Analysis Report
Project Number. SML-055 / 2000479
December 22, 2020
Page 17
gih"l
k Ib6
Y hrl
Z �
M7t ki -in
MY ki in
MZ ki -in
Tension
1.0 DL + 0.14 5ds'DL + (.7 Om'ELX N27
05
•212.158
•65.51#3
i;
Q
l
214.3
•Fi5. }
1.0 01L+ 0.14 9deDL +0.70m'ELX N93
10.45
275.2$5
5�.M
C.
is
1
277.0
0-D
Assuming the proposed are (2) 1/2" dia. Hilti HIT A307 threaded rod w/ Hilti HIT-HY 200 anchoring system
w/ 4.5" embedment used for connecting the pipe mounts.
Table 101 - H I I t I H17-HY 200 allowable adhesive I)ond Ioads for threadeed rods and relnforoing bars
In the top of grout -filled concrete masonry walls'.2.2.4.E.`
Shear load lb ftN)l
Load parallel to
Load perpendicular
Nominal anchor
Effective
Edge
Minimum =rd
diameter or rebar
embedment
distance
distance
Tension
edgeof masonry
taedge of ma onry+
size
in- (mm)
in. ( FW1,
in- (mm)
lb 0"
wall
wall
1 3/4
685
T75
285
4 At2
(44)
{3.4)
(3-4)
(1.3)
1/2"
(114)
4
880
1,156
480
(102)
P-9)
(5.1)
(2-1)
1 3J4
830
890
315
5 -5/B
(44)
8
(3.7)
(4-0)
(1.4)
5/8
(143)
(203)
4
980
1,315
625
(102)
(4-4)
(5-8)
(2.8)
4-1/2
770
605
235
T4
(1 14)
1 314
r44j
(3.4)
(2-7)
0 M
5 -5r'8
795
720
295
T5
(143)
Ci.5)
(3.2)
(1-a)
Table 102 - HIM HIT•HY 200 allowable tension and shear values for threaded rods based) on steel strengthIAO
Tension I QM)
Shear lb (MN
Anchor
ISO 896
ASTM
ASTM
ISo S98
ASTM
ASTM
diameter
clays
ASTM
ASTM
A193
F593 GW
class
ASTM
ASTM
A193
F-593 CW
in-
58
A36
A307
E17
(315/30.4)
HIT-V(-R)
5.8
A36
A307
B7
(316/304)
HIT-(7(-R)
2,640
2,115
2,185
4,555
3,645
3,430
1,360
1,090
1,125
2,345
1,675
1,770
Wa
(11.7)
(9-4)
(9-7)
(20.3)
(162)
(1 5.3)
(6-0)
(4.8)
(5-0)
(10.4)
i8.3)
(7.9)
4,700
3,755
3,885
8,100
6,480
6,100
2,420
1,935
2,000
4,170
3,335
3,145
1/2
(20.9)
(16.7)
(17-3)
(36.0)
(28.8)
(27.1)
(10A
(8.6)
(8-9)
(18,5)
(14.8)
(14-0)
7,340
5,870
6,075
12,655
10,125
9,535
3,780
3r025
3,130
6,520
5,215
4,915
5f8
(32.6)
(26.1)
(27A)
(56-3)
(45.0)
(42.4)
(16-3)
(13-5)
(13.9)
(29-0)
(232)
(21-9)
10,570
8,455
8,75o
18,225
12,390
13,735
5,445
4,355
4,505
%390
6X5
7,075
3/4
(47.0)
(37-6)
€ o-%
(61-1)
(55.1)
(61.1)
(242)
(19-4)
(20-0)
(41-8)
(28-4)
(31-5)
Allowable Shear = 685 Ibs
Allowable Tension = 775 Ibs
Shear Capacity = 277/685 = 40.4% [OK!]
Tension Capacity = 65.5/775 = 8.5% [OK!]
MA 94
BUILDING ANALYSIS INPUT & OUTPUT
Morrison Hershfield
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 21, 2020
Page 19
BUILDING ELEVATION
ro nr�r nu. mwxa
r�orKi. � a
V ro%Y IXr
Diu
ov 1a1�36'4r .� * 1el
(q auP/Pw[c
•WX ML �xMlp/.tlNR
[aw�i1 attM[ Mfn
cou,'R o
WWm ak lfx wt
rorW
`'. ¢:11-
�eam�s�wu�e %rmmsf
"J,
i`�r'w`xsc1°"ian`v rnw'
YCTM Y
—I�.rsi vw¢.en[xx�
f xrtx m i.
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 21, 2020
Page 20
GRAVITY LOAD CONSIDERATION (BUILDING):
The proposed equipment load is less than 400-Ib. By inspection, the lightweight antenna gravity loads are
adequately supported by the existing building. The increase in gravity loads does not affect the demand capacity
ratio of the building. By inspection, the equipment swap does not increase any additional gravity load on the
building. Therefore, gravity loads are adequately supported by the existing building and gravity loads are not
increased by more than 5%.
The existing and proposed loads are insignificant when compared to the heavy existing building
components supporting them. Therefore, the existing structural supporting elements and foundations
are deemed adequate in accordance with section 1103.2 exception 1.
LATERAL LOAD CONSIDERATION (BUILDING):
WIND LOAD CALCULATIONS (BUILDING):
Code: International Building Code 2015
Occupancy:
Occupancy Group = B Business
Risk Category & Importance Factors:
Risk Categ a ry Category II : All bldgs and other structures except those listed in Categories I, III, & IV
Wind Loads - Other Structures: ASCE 7- 10
'-,' ind Factor = 1.00
Gust Effect Factor (G) ' 0.8E Ultimate Wind Speed= 110 mph
Kzt = 1.00 Exposure = C
Ultimate Wind Pressures
m0
Rooftop Structural Analysis Report
Project Number. SML-055 / 2000479
December 21, 2020
Page 21
Wind Loads - MVVFR3 h--cw aAmrisa s,il&ngs) t f� a buil&ngs
Ka = Kh Cease 1) = 1.03
Base pressure Cqh) 28.3 Psf
G Cpi = -0.1 �_
Wind Pressure Coefficients
Edge Strip (a) = 4.8 ft
End Zone (2a) = 9.6 ft
Zone 2 lengrth = 24.0 ft
CA SE A
CASE B
= 0 deg
Surface
GC f
wl-GC i
w?+GC i
GC f
wl-GC i
w1+GC i
1
GAG
Q.58
9.22
-9.45
-Q.27
2
-0.69
-0. 51
-13.37
-0.69
-0. 51
-0. #'
3
-9.37
-0.19
-4.55
-9.37
-4.19
-4.55
4
-0.29
-0.11
-13.47
-0.45
-(1.27
-0.63
5
9.49
0.58
0.22
6
-9.29
-0.11
-4.47
1 E
0.61
4.79
0. ; 3
-0.43
-0. 30
-4.66
2E
-1.47
-9.39
-1.2E
-1.47
-0.89
-1.25
3E
-0.53
-0.35
-0.71
-9.53
-0.35
-4.71
4E
-9.43
-9.25
-0.t�1
13.43
-0.30
-G.66
5E
-13.61
0.79
0.43
6E
-13.43
-0.25
-4.61
Ultimate Wind Surface Pressures (psf)
1
16.4 6.2
-7.7 -1 7.9
2
-14.5 -24.7
-14.5 -24.7
3
-5.4 -15.6
-5.4 -15.6
4
-3.1 -13.3
-7.7 -17.9
5
16.4 6.2
6
-3.1 -13.3
1 E
22.4 12.2
-9.5 -13.7
2E
-25.2 -35.4
-25.2 -35.4
3E
-9.9 -20.1
-9.9 -24.1
4E
-7.1 -17.3
-3.5 -13.7
5E
22.4 12.2
6E
-7.1 -17.3
Parapet
'r'dnd-,%,ard parapet = 0.0 psf CGCpn = +1.5)
Leeward parapet = 0.0 psf CGCpn =-1.0)
Horizontal MWFRS Simale Diaahraam Pressures tosf
Transverse direction (normal to Lj
Interior Zone: Wall
19.6 psf
Roof
-9.1 psf **
End Zone: Wall
29.5 psf
Roof
-15.3 psf **
Longitudinal direction (parall-lto L)
Interior Zone: Nall 19.6 psf
End Zone: Wall 29.5 psf
** NOTE: Total horiz farce shall not be less than that determined
by neglecting raaf farces (except far MWFRS moment frames).
The code requires the MWFRS be designed for a min ultimate
farce Df 16 psf multiplied by the wall area plus an 3 psf force
applied tatheverticaIprojection of thereof.
Windward roof
Dverhangs= 19.3 psf (upward) addtD
windward roof pressure
OVEF NU M WPfl;wJ%FpR04P
LHQ44�kFL RDI F
JJ L J L J l l I 1
4EF17_JtiL
� gJi
TRANSVERSE ELEVATION
vr��mw,wsanc.�
tn�
JI 11 1 J L i l l
MEkSIGx4
LOHGT,CVV WAT- ELE VA UCfK
I�
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 21, 2020
Page 22
Wind Forces on Building Structure
Wind force on End Zone = 2x4.8 ft x 46.6 ft x 29.5 psf
= 13197.1 lbs.
Wind force on Interior Zone = 175.4 ft x 46.6 ft x 19.6 psf
= 160203.3 lbs.
Wind Force Antenna Mount
= 3500 lbs
Total Wind Force (Building)
= 176900.4 lbs.
Lateral Wind Load Cmmnarisnns-
= 13.2 kips
= 160.2 kips
= 3.5 kips (approx.)
= 176.9 kips
Loading
Original
Additional
Total
Net Increase
Remark
[Lbs.]
[Lbs.]
[Lbs.]
!/.]
Lateral (Shear)
173400.4
3500
176900.4
1.9
OK
The total additional lateral loading is at less than 10% of the original design loads on the building lateral
force resisting system. In accordance with the section 1103.3 of the 2015 International Existing Building
code, a full analysis of the existing building is not required.
SEISMIC ANALYSIS
Seismic Loads: IBC 2015
Risk Category : II
Importance Factor (I) : 1.44
Site Cla ss : C Class D
Ss (0.2 sec) = 12 7. 90 %
S1 (1.0 sec) = E0.10 °leg
Fa = 1.000 Sms =
1.279
Fv = 1 =rr Sm1 =
0.752
DESIGN COEFFICIENTS AND FACTORS
Response Modification Coefficient (R) = 3
Over -Strength Factor (!2o'y = 3
Deflection Amplification Factor (Cd} = 3
S,= = 0.952
S:-1 = 0.501
Seismic Load Effect (E) = Eh +1-Ev =
p a= +1- 0.2Sa= D
Special Seismic Load Effect (Emy = Emh +1- Ev =
Qo a= +1- 0.2Sa= D
PERMITTED ANALYTICAL PROCEDURES
Simplified Analysis - Use Equivalent Lateral Force Analysis
Equivalent La#eral-Force Analy,
- Permitted
Building period coef. (C-:, =
0.020
Approx fundamental period C-a; =
CTh
User calculated fundamental period C-; =
Long Period-ransitionPeriod C-L.. =
ASCE7map=
Seismic response coef. (Cs; =
S_._VR =
need not exceed Cs =
ShcIIRT=
but not less than Cs =
0.044Sdsl =
USE Cs =
J
= 0.3E2
S_1 = 0.E01
Strength Level Forces
Design Category = D
Design Category = D
= 1.3ae +1- 0.170C Qe = horizontal seismic force
= 3ae+1- 0.170C C = dead load
Equivalent Lateral -Force Analysis
Cu = 1.4
0.35E sec x= 0.7E -max = Cu-a = 0.497
sec Use - = 0.3EE
0.294
0.470
0.037
0.2 3-'
Design Base Shear V = 0.23z'l �
m•
Rooftop Structural Analysis Report
Project Number: SML-055 / 2000479
December 21, 2020
Page 23
Total Building Weight, W = = 355200 Ibs (approximately)
Design Base Shear, V = 0.284 W = 0.284*355200 = 100877 Ibs
MECH AND ELEO COMPONENTS SEISMIC COEFFICIENTS
Mech or Electrical Component : Other mechanical or electrical components. IV
Importance Factor (Ip) : 1p = 1.5 Life safety component required to function after an earthquake (e.g. fire protection sprinklers IV
Component amplification Factor (ad = 1 h=` 46.a feet
Comp Response Modification Factor (Rp) = 1.5 z ` ��.? feet zfh = 1.00
Fp = 0.4a,SdslWNp(1+2zlhYRp = 1.022 Wp
not greater than Fp = 1.6Sdslpb'dp = 2.045 VVp
but not less than Fp = 0.EiSds1plo7p = MzEi V1tp
Weight of the tower & equipment, Wp
Seismic Force, Fp = 1.022*Wp = 1.022*3000
Lateral Seismic Lnad Cmmnarisnns'
use Fp = 1.022 'Np
= 3000 Ibs (approximately)
= 3066 Ibs
Loading
Original
Additional
Total
Net Increase
Remark
[Lbs.]
[Lbs.]
[Lbs.]
1/]
Lateral (Shear)
100877
3066
103943
2.9
OK
The total additional lateral loading is at less than 10% of the original design loads on the building lateral
force resisting system. In accordance with the section 1103.3 of the 2015 International Existing Building
code, a full analysis of the existing building is not required..
m0
MOUNT ASSEMBLY DRAWINGS
Morrison Hershfield
2
3 X2
4 X2
5 X2
MOLTING PIPE
ORDERED SEPARATELY
I� �I
PARTS LIST
PART NO.
PART DESCRIPTION
LENGTH
UNIT WT.
NET WT.
X-S250
WALL MOUNT BRACKET
6.46
12.91
X-UB1212
1/2" X 2-1/2" X 4.1/2" X 2" U-BOLT (HDG.)
0.63
1.25
G12FW
1/2" HDG USS FLATWASHER
0.03
0.14
G12LW
1/2" HDG LOCKWASHER
0.01
0.06
G12NUT
1/2" HDG HEAVY 2H HEX NUT
0.07
0.29
TOTAL WT. #
13.84
TOLERANCE NOTES
DESCRIPTION
Locations:
TOLERANCES ON DIMENSIONS, UNLESS OTHERWISE NOTED ARE:
CANTILEVER
Engineering
New York, NV
Atlanta, GA
SAWED, SHEARED AND GAS CUT EDGES(± 0.030J
WALL
�j(�J
Support Team:
Los Angeles, CA
DRILLED AND GAS CUT HOLES (±0.030) - NO CONING OF HOLES
MOUNT
1-888-753-7446
Plymouth, IN
Salem, OR
LASER CUT EDGES AND HOLES ±a 010" - NO CONING OF HOLES
( )
AvalmonSY�M
Dallas, TX
BENDS ARE! 1/2 DEGREE
ALL OTHER MACHINING (±0.030 f
CPD NO. DRAWN BY ENG. APPROVAL
PART NO.
ALL OTHER ASSEMBLY(± 0.060)
CEK 10/7/2010
SP250
02
PROPRIETRRYNOre:
,WINGUSAGE CHECKED BY 1 DWG. NO. -n
CUSTOMER BMC 10/7/2010 SP250
ADDITIONAL CALCULATIONS
Morrison Hershfield
SCE
AMERICAN SOCIETY OF CIVIL ENGINEERS
Address:
No Address at This
Location
Wind
ASCE 7 Hazards Report
Standard: ASCE/SEI 7-10 Elevation: 102.03 ft (NAVD 88)
Risk Category: II Latitude: 47.821748
Soil Class: D - Stiff Soil Longitude:-122.366071
IIIII 'll
Z.d
�
II�V-
II,
F' I f E •:III •.I I
_I�a ._—. iSh line I•IiI• � .....,.il
}I F�Ik
Results:
Wind Speed:
110 Vmph
10-year MRI
72 Vmph
25-year MRI
79 Vmph
50-year MRI
85 Vmph
100-year MRI
91 Vmph
Data Source:
ASCE/SEI 7-10, Fig. 26.5-1A and Figs. CC-1—CC-4, incorporating errata of
March 12, 2014
Date Accessed:
Sat Dec 19 2020
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear
interpolation between contours.
Wind speeds are interpolated in accordance with the 7-10 Standard. Wind speeds
correspond to approximately
a 7% probability of exceedance in 50 years (annual exceedance probability =
0.00143, MRI = 700 years).
Site is not in a hurricane -prone region as defined in ASCE/SEI 7-10 Section 26.2.
Mountainous terrain, gorges,
ocean promontories, and special wind regions should be examined for unusual wind
conditions.
https://asce7hazardtool.onIine/ Page 1 of 3 Sat Dec 19 2020
-ASCE®
AMERICAN SOCIETY OF CIVIL ENGINEERS
Seismic
Site Soil Class:
D - Stiff Soil
Results:
Ss :
1.278
SDs
0.852
S,
0.501
SDI
0.501
Fa
1
TL
6
Fv
1.5
PGA:
0.52
SMs
1.278
PGA M :
0.52
SM,
0.752
FPCA
1
le :
1
Seismic Design Category D
14 MCER Response Spectrum 09 Design Response Spectrum
1-2 i 0_7
1-0 0.•
•
i Ofi
(H 0.5
0-B 0.4
0.3
0.4
0.2
0-2 0.1
fl i)_[:::_
0 2 3 - - 6 7 0 - -
Sa (g) vs T(s) Sa (g) vs T(s)
Data Accessed: Sat Dec 19 2020
Date Source: USGS Seismic Design Maps based on ASCE/SEI 7-10, incorporating
Supplement 1 and errata of March 31, 2013, and ASCE/SEI 7-10 Table 1.5-2.
Additional data for site -specific ground motion procedures in accordance with
ASCE/SEI 7-10 Ch. 21 are available from USGS.
https://asce7hazardtool.online/ Page 2 of 3 Sat Dec 19 2020
-ASCE®
AMERICAN SOCIUY OF CIVIL ENGINEERS
Ice
Results:
Ice Thickness:
Concurrent Temperature
Gust Speed:
Data Source:
Date Accessed:
0.25 in.
25 F
30 mph
Standard ASCE/SEI 7-10, Figs. 10-2 through 10-8
Sat Dec 19 2020
Ice thicknesses on structures in exposed locations at elevations higher than the surrounding terrain and in valleys
and gorges may exceed the mapped values.
Values provided are equivalent radial ice thicknesses due to freezing rain with concurrent 3-second gust speeds,
for a 50-year mean recurrence interval, and temperatures concurrent with ice thicknesses due to freezing rain.
Thicknesses for ice accretions caused by other sources shall be obtained from local meteorological studies. Ice
thicknesses in exposed locations at elevations higher than the surrounding terrain and in valleys and gorges may
exceed the mapped values.
The ASCE 7 Hazard Tool is provided for your convenience, for informational purposes only, and is provided "as is" and without warranties of
any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers;
or has been extrapolated from maps incorporated in the ASCE 7 standard. While ASCE has made every effort to use data obtained from
reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability,
currency, or quality of any data provided herein. Any third -party links provided by this Tool should not be construed as an endorsement,
affiliation, relationship, or sponsorship of such third -party content by or from ASCE.
ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent
professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such
professionals in interpreting and applying the contents of this Tool or the ASCE 7 standard.
In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors,
employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential
damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by
law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data
provided by the ASCE 7 Hazard Tool.
https://asce7hazardtool.online/ Page 3 of 3 Sat Dec 19 2020
DESIGN REVIEW FORM
Morrison Hershfield
A B C O F F G H I T 1 K L I M I N O P
1
S rn<3 rt ( 111 1#. Design Review
3
PACE Jt
Parent/Child
FA g
ORACLE PTN g
Site Number
Site Name
POE Static
Spectrum
RRH Type
4
MRWOR046539
Parent
10092667
3801AOT6F5
SN61
Puget Drive
Active
850 mhz 5G
AirScale RRH 4T4R B5
5
6
7
8
9
10
11
12
Scoping call notes: (for reference
only and not to be used for
entitlement or
design)
v3 (12/04/2020): Alpha & Beta: Swap out 17/19 antenna with 6' 8-port cellmax antenna for 5G. Gamma: Swap out 17/19 antenna with 6' 12-port slim Kathrein antenna for 5G. Diplex
L7 & 5G 850. Make sure that there is at
least 3' separation between antennas. Need two 472949A (UNI SFP 7 for Nokia Radios) per MB radio if not yet installed. Swap out existing BBU SFP Type from 5 to 7.
V02:06/24/20:5G NR Radio Final RFDS.
Note :- HORIZONTAL SEPARATION from ANOTHER ANTENNA to be 3 FT & FIN RRH needs to have 2ft of clearance from antennas and other RRHs.Make sure to place/move all RRH
behind the Antennas.
14
Construction Manager:
Alex Hinton
Land Use Specialist:
15
Leasing Specialist:
Project Manager:
IJohn Evans
16
17
Project Summary
18
Installing 850 mhz 5G to Existing (3) Sector AT&T Rofftop Site. Removing (3) Kathrein 80010864 Antennas in Position (2) Alpha, Beta, Gamma. Installing (2) Cellmax CMA-UBTMLBMLBHH-6516-16-21-21 Antennas in
Position (2) Alpha, Beta Sectors. Installing (1) Kathrein 800372965 Antenna in Gamma Sector within existing FRP Shroud. Relocating Antenna Posiiton (2) on Alpha Sector to South side of existign Chimney Stack to prevent
Skewing. New Mounting methed required for proposed antennas in Alpha, Beta Sectors. Installing (3) 78211288 Kathrein Diplexers for 700/850 on proposed antennas. Installing (3) AirScale RRH 4T4R B5 160W AHCA
RRH's (1) Per Sector mounted on rooftop. Removing Existing 24V Power Plant Cabinet. Installing (1) (N) Netsure 512 -48V Outdoor Power Cabinet. Reinstalling Breakers for All existing equipment. Removing Existing Battery
Cabinet With (20) Marathon M12V155FT Batteries. Installing (1) (N) Outdoor-48V Battery Cabinet With (16) M12V180 batteries. Installing (3) 25 AMP Breakers for (N) B5 RRH's. Installing (1) 5G upgrade kit in existing
FLX16 Cabinet. Installing (1) Thermal HEX door on existign FLX16 Purcell cabinet. Per the DC Trunk Calculator Dated 11/18/2020 no upconverters are needed. Installing (1) DC12-48-60-0-25E Outdoor Raycap at equipment
pad for Proposed B5 RRH's. Migrate Existing DC Cabling from DC2/DC12RM unit to (N) DC12 Outdoor Unit.
20
Tower Type:
Rooftop
Existing Mount type:
Stand off
No
Red Center:
43.2' - 42.4'
Tower Notes:
21
Equipment Type:
Indoor
Proposed Mount type:
TBD
Bird on Site:
Tip Height:
Relocating Alpha Sector Pos. (2) Mount to South Side Of Chimney
Stack. Find New Anchor Bolt Solution for Proposed Antennas
Mounted To Chimney
22
Site type:
Colo
Mount Swap:
No
FAA Height:
23
Number of Sectors:
3
Mount MOD:
Yes
Previous SA:
24
Tower Owner:
Manlift/Crane & Size:
No
Previous MA:
25
26
CIVIL SOW:
Removing Existing 24V Power Plant Cabinet. Installing (1) (N) Netsure 512 -48V Outdoor Power Cabinet. Reinstalling Breakers for All existing equipment. Removing Existing Battery Cabinet With (20)
Marathon M12V155FT Batteries. Installing (1) (N) Outdoor-48V Battery Cabinet With (16) M12V180 batteries. Installing (3) 25 AMP Breakers for (N) B5 RRH's. Installing (1) 5G upgrade kit in existing
FLX16 Cabinet. Installing (1) Thermal HEX door on existign FLX16 Purcell cabinet. Per the DC Trunk Calculator Dated 11/18/2020 no upconverters are needed. Installing (1) DC12-48-60-0-25E Outdoor
Raycap at equipment pad for Proposed B5 RRH's. Migrate Existing DC Cabling from DC2/DC12RM unit to (N) DC12 Outdoor Unit.
27
28
RF SOW:
Installing 850 mhz 5G to Existing (3) Sector AT&T Roffop Site. Removing (3) Kathrein 80010864 Antennas in Position (2) Alpha, Beta, Gamma. Installing (2) Cellmax CMA-UBTMLBMLBHH-6516-16-21-
21 Antennas in Position (2) Alpha, Beta Sectors. Installing (1) Kathrein 800372965 Antenna in Gamma Sector within existing FRP Shroud. Relocating Antenna Posiiton (2) on Alpha Sector to South side
of existign Chimney Stack to prevent Skewing. New Mounting methed required for proposed antennas in Alpha, Beta Sectors. Installing (3) 78211288 Kathrein Diplexers for 700/850 on proposed
antennas. Installing (3) AirScale RRH 4T4R B5 160W AHCA RRH's (1) Per Sector mounted on rooftop.
29
30
Tower or Mount
MOD Required:
(include
responsible party)
Relocate Antenna mounts in Position (2) Alpha, Beta Sectors. They are currently mounted to Uni-Strut which is no longer AT&T approved. Create Anchor Bolt solution into existing Brick Chimney.
31
32
Existing Antennas
Proposed Antennas
Final Antennas
33
Type
City
Sectors
Type
City
I Sectors
Type
City
Sectors
34
80010991
3
ABS
CMA-UBTMLBMLBHH-6516-16-21-21
2
A B
CMA-UBTMLBMLBHH-6516-16-21-21
2
A B C
35
80010864
3
ABC
800372965
1
C
800372965
1
A B
36
180010864
3
A B C
37
38
39
Existing Diplexers
Proposed Diplexers
Final Diplexers
40
Type
I City
Sectors
Type
City
Sectors
Type
I City
Sectors
41
782 11287
6
ABC
782 11288
3
ABC
782 11287
6
A B C
42
78211288
3
A B C
43
44
45
46
47
Existing TMAs
Proposed TMAs
Final TMAs
48
Type
City
Sectors
Type
City
I Sectors
Type
City
Sectors
49
50
51
52
53
54
55
1 1 Existing RRHs
Proposed RRHs
Final RRHs
56
1 Type
Qty
Location
Type
Qty
I Location
Type
City
Location
57
Flexi RRH 4T4R B14160W
3
Tower
AirScale RRH 4T4R B5
3
Tower
Flexi RRH 4T4R B14160W
3
Tower
58
RRH2X40W_7L
3
Tower
RRH2X40W 7L
3
Tower
59
B25 RRH4X30-4R
3
Tower
B25 RRH4X30-4R
3
Tower
60
B66A RRH4X45-4R
3
Tower
B66A RRH4X45-4R
3
Tower
61
RRH4x25-WCS-4R
3
Tower
RRH4x25-WCS-4R
3
Tower
62
lAirScale RRH 4T4R B5
3
Tower
B C D E F I G 1 11 1 I J K L I M I N 1 0 P
63
64
Existing Combiners
Proposed Combiners
Final Combiners
65
Type
City
Sectors
Type
Qty
Sectors
Type
city
Sectors
66
67
68
Existing Filters
Proposed Filters
Final Filters
69
Type
Qty
Sectors
Type
City
Sectors
Type
city
Sectors
70
71
72
Existing Coax
Proposed Coax
Final Coax
73
Type
City
Type
City
Type
City
74
N/A
N/A
75
76
Existing RET Cables
Proposed RET Cables
Final RET Cables
77
Type
City
Type
City
Type
Qt y
78
ATCB-BOl-050
3
ATCB-BOl-050
3
79
80
Existing Fiber Trunks
Proposed Fiber Trunks
Final Fiber Trunks
RI
Type
Qty
Type
City
Type
City
82
RFFT-24SM-001-50M
3
RFFT-245M-001-SOM
3
83
84
Existing Power Trunks
Proposed Power Trunks
Final Power Trunks
85
Type
Qty
Type
Qty
Type
Qty
86
P W RT-608-5
6
P W RT-608-5
6
87
88
Existing DC/Fiber Distribution Rooftops & Watertanks
Proposed DC/Fiber Distribution Rooftops & Watertanks
Final DC/Fiber Distribution Rooftops & Watertanks
89
Type
Qty
Type
City
Type
City
90
FC12-PC6-10E
3
FC12-PC6-10E
3
91
DC2-48-60-0-9E
9
DC2-48-60-0-9E
9
92
Existing Equipment Level Surge
Proposed Equipment Level Surge
Final Equipment Level Surge
93
Type
Ty
Type
Qty
Type
City
94
DC6-48-60-RM(1st Generation)
1
DC12-48-60-0-25E
1
DC12-48-60-0-25E
1
95
DC12-48-60-RM
1
DC12-48-60-RM
1
96
Existing Antenna Level Surge
Proposed Antenna
Level Surge
Final Antenna Level Surge
97
Type
City
Type
City
Type
City
98
99
100
101
POWER SOW:
Removing Existing 24V Power Plant Cabinet. Installing (1) (N) Netsure 512 -48V Outdoor Power Cabinet. Reinstalling Breakers for All existing equipment. Removing Existing Battery Cabinet With
(20) Marathon M12V155FT Batteries. Installing (1) (N) Outdoor-48V Battery Cabinet With (16) M12V180 batteries. Installing (3) 25 AMP Breakers for (N) BS RRH's. Installing (1) SG upgrade kit in
existing FLX16 Cabinet. Installing (1) Thermal HEX door on existign FLX16 Purcell cabinet. Per the DC Trunk Calculator Dated 11/18/2020 no upconverters are needed.lnstalling (1) DC12-48-60-0-25E
Outdoor Raycap at equipment pad for Proposed B5 RRH's. Migrate Existing DC Cabling from DC2/DC12RM unit to (N) DC12 Outdoor Unit.
102
Existing Power Plant
Proposed Power Plant
Final Power Plant
103
Type
Voltage
Type
Voltage
Type
Voltage
104
24v TE43
24
NetSure 512
48
NetSure 512
48
105
106
Existing Rectifier
Proposed Rectifier
Final Rectifier
107
Type
City
Typei
City
Type
City
108
Cordex 24v/3.lkw
5
48v/2.0kw
10
48v/2.O1,w
10
109
110
Existing Converter
Proposed Converter
Final Converter
III
Type
City
Type
City
Type
City
112
Cordex CXDF 24-48/2kw
5
48v/1.5kw
2
48v/1.5kw
2
113
114
Existing Battery String
Proposed Battery String
Final Battery String
115
Type
City
BBU4 Y inet
Type
City
BBU Cabinet City
Type
Oty
BBU Cabinet City
116
M155
10
1
M12V180
4
1
M12V180
4
1
117
ESTIMATED BATTERY RESERVE TIME:
118
Existing Generator
Proposed Generator
Final Generator
TType
City
Type
City
Type
City
120
N/A
N/A
N/A
21
122
All aspects of the project(s) covered within this document both Parent Childs must be installed per ATT standards.
123