FIR2021-0072+Fire_Alarm_Equipment_Specification_Sheets+7.14.2021_9.39.32_AM+2299403
r(., "q .� 4 Froula Alarm Systems, Inc. 861 Industry Drive ♦ Tukwila WA 98188-3411 Phone: 206-575-1962 ♦ Fax: 206-575-8168 July 13, 2021 Fire Alarm System Submittals For Dr. Christie Lee Tenant Improvement 10032 Edmonds Way Suite Retail #2 Edmonds, Washington 98020 ram„ Froula Alarm Systems, Inc. 861 Industry Drive ♦ Tukwila WA 98188-3411 Phone: 206-575-1962 ♦ Fax: 206-575-8168 Dr. Christie Lee Tenant Improvement July 13, 2021 Table of Contents Fire Alarm System Manufacturer Model No. Description Potter IPA-4000 Addressable Fire Alarm Control Panel - EXISTING Potter PSN-64 Intelligent Booster Power Supply Potter CS-24W Multi -Candela Ceiling Mount Strobe Potter CHS-24W Multi -Candela Ceiling Mount Horn/Strobe Interstate BSL1075 12V 7.2AH Battery Coleman 81802 18-2 FPLP Wire Coleman 81804 18-4 FPLP Wire Coleman 81402 14-2 FPLP Wire (E)POTTER The Symbol of Protection Features • 4,064 addresses available on this analog addressable system • Additional system capacity achieved via multi -point SLC modules • 1500 software zones • NFPA 72 Compliant Smoke Sensitivity Test Built -In • System Operates as Class A or Class B for SLC, P-Link and NACs • 10 Amp Power Supply, Expandable to 315 amps • 6 NACS, Regulated, Rated at 3 Amps each, expandable to 192 • 4 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each, ideal for manual release and abort • Strobe Synchronization and System Wide Sync for Potter/AMSECO®, Gentex®, Cooper Wheelock® and System Sensor® strobes • Dedicated Alarm, Supervisory and Trouble Relays • 4,000 Event History Buffer • Cabinet will house up to 18 AH batteries • Optional two line DACT with UD-2000 that can report General, Zone or Point Information • Built in IP communicator • Ethernet Port for Programming and Network Connectivity • E-Mail System Status, Reports and Event Information • Product includes 5 year warranty • UUKL Listed for Smoke Control Description The IPA4000 is an expandable analog/addressable releasing fire alarm system with a total system capacity of 4,064 addresses. Additional capacity on the system is achieved using multi -point SLC modules The control panel utilizes the exclusive Potter protocol that includes a complete line of sensors and modules. The system is expandable with a total of thirty-one additional addressable Signaling Line Circuits (SLC) each with a maximum of 127 devices. Each SLC may be comprised of any combination of smoke sensor, heat detectors or modules and allows for a total of 50 ohms of impedance and may use any wire compliant with the National Electrical Code (NEC). The IPA-4000 has a 10 Amp power supply with six Notification Appliance Circuits (NACs) and four Input/Output (1/0) circuits. The NACs are rated at 3 Amps each and the I/Os are rated at 1 Amp each. Each output is regulated and power limited. In addition, each output is uniquely programmable and may be configured for steady signal, strobe synchronization, constant power, door holder power, or releasing. The strobe synchronization includes Potter/AMSECO, Gentex, System Sensor and Cooper/Wheelock and with the exclusive Quadrasync each output may have a unique brand and all strobes will flash together. The I/Os are designed for inputs such as manual release stations and abort switches that will not require polling and react nearly instantaneously. The IPA4000 is listed for releasing of fire suppression systems. The software allows cross zones, counting zones, and timers for suppression. The system is capable of multiple release outputs across multiple hazards. In addition, the PSN-1000 may be used to extend releasing capability. The NACs may be expanded using the PSN-1000 series intelligent power supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional input circuits and the IPA4000 will support up to 31 power supplies. The system will synchronize the strobes system wide. In addition, the PSN- 1000E has space to allow the installation of up to six PAD100-SLCE SLC loop expansion cards. The cards mount on a stacker bracket that allows access to all SLC circuit connections. IPA-4000 Fire Alarm Control Panel FM APPROVED Technical Specifications ge LISTED Dimensions 18 "/16"W x 27 s/16"H x 4 7/16"D AC Mains 5.0 Amps @ 120 VAC 50/60 HZ 3.0 Amps @ 240 VAC 50/60 HZ Enclosure 16 gauge cold rolled steel with removable locked door with Lexan viewing window Standby Current-130 mA Alarm Current-220 mA • 10 Amps power for NACs, I/O, and P-Link Battey 3 Amps per NAC, regulated • 1 Amp per I/O circuit, regulated • Battery Charger range 8-55 Ah • Battery Charger voltage 27.3 VDC • P-Link maximum current of 1 Amp Temperature and 320 to 1200 (0°C to 49°C) with a maximum Humidity Range humidity of 93% non -condensing. NFPA 12, 12A, 13, 15, 16, 17, 17A, 70, 72, 750, and 2001 ANSI/UL 864 - Local (L), Remote Sta- tion (RS), Central Station (CS), Propriety (PPU), Auxiliary (AUX).Type of Service: Standards Automatic (A), Manual (M), Water flow (WF) Sprinkler Supervisory (SS) Type of Signaling: Digital Alarm Communicator (DAC), March Time (March), Non Coded (NC), Reverse Polarity (Rev Pol), Other Technologies (OT) IBC 2000, 2003, 2006, 2009, 2012 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830102 - REV G • 1/20 PAGE 1 OF 4 (E)POTTER The Symbol of Protection IPA-4000 Fire Alarm Control Panel SLC Loop Accessories The control panel may be connected with up to 4,064 addressable devices or modules in any combination. The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. SLC Loop Devices Device Description PAD 100-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. PAD 100-PHD Combination Analog Photo Electric Smoke/Heat Detector — a smoke detector with a listed obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135' Fahrenheit heat detector. PAD100-HD Analog Fixed Temperature Heat Detector that is selectable from 135' F to 185°F. PAD 100-DUCTR Addressable Duct Smoke Detector with Form C Relay. PAD100-DUCT Addressable Duct Smoke Detector. PAD 100-6B 6" round base that is mounted to an electrical box and wired for connection of one of the above sensors. PAD100-413 4" round base that may be mounted to an electrical box and wired for connection to the above sensors. PAD100-I13 Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop. PAD100-RB Addressable Relay Base that contains one relay controlled by the SLC. Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC. PAD100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local, group and all call. PAD100-CD Addressable CO gas detector. PAD 100-DD Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure. PAD100-LFSB Addressable Low Frequency Sounder Base that contains an addressable sounder module that may be configured for local, group and all call. The LFSB complies with the Low Frequency Signal Requirements (520 Hz) PAD100-SPKB Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from 1/8W to 4W. Modules Device Description PAD100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure. PAD100-PSSA Single Action Addressable Pull Station. PAD 100-PSDA Dual Action Addressable Pull Station. PAD100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4" square electrical box. PAD 100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. PAD 100-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. Also provides two contact inputs. PAD 100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel. PAD 100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system. PAD 100-IM Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. PAD100-RM Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. PAD 100-LED Module provides a single addressable LED that is controlled by the control panel. PAD 100-SM Speaker Module provides switching for two audio channels. PAD 100-LEDK Addressable LED and key switch that mounts in a single gang box. PAD 100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised. PAD100-OR0I One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830102 - REV G • 1/20 PAGE 2 OF 4 (E)POTTER The Symbol of Protection SLC Features The Potter protocol is a digital protocol with a proven design for reliability and noise immunity. The system does not require special cable or conductors for connection of the Signaling Line Circuit as long as the cable is compliant with NFPA 70 and NFPA 72. The system allows for Class A or Class B installations as well as "T-Taps."Each loop is capable of 127 points, with a max wiring distance of 10,000 ft. Sensor Features The sensors through the fire alarm control panel provide a real time status as to the condition of the system. The smoke detector sensitivity, heat detector temperature level and drift compensation are all programmable options. The system also allows for a day/night mode where the panel automatically adjusts the sensitivity depending on the time of day. To assist in the reduction of false alarms, the smoke detectors also have a maintenance warning that sends a trouble signal when a detector is dirty to the point that it can no longer maintain the programmed sensitivity. User Interface The fire alarm control panel has a 4 x 40 LCD display to provide information to the system status. The keypad has navigation keys to allow manipulation of the Menu on board the panel. The panel is shipped standard with the following LEDs: • AC Power - Green • Alarm - Red • Earth Fault - Amber • Supervisory - Amber • Silenced - Amber • Trouble - Amber • Pre -Release - Amber • Release - Red The common buttons include a Silence, Reset, Acknowledge, and Drill. All of the buttons are accessible once the locked door is opened. P-Link The IPA-4000 has a proprietary communication protocol that communicates through a RS-485 connection to field devices. Up to 64 devices may be connected to a single P-Link connection. The P-Link includes the communication terminals and regulated 24 VDC connection for the field devices. The field devices may be any of the following: PAD100-SLCE-Analog/Addressable loop expansion module (maximum of 31 per IPA-4000) IPA-4000 Fire Alarm Control Panel RA-6075R — 2 x 16 LCD annunciator with a key pad in a locked metal enclosure. RA-6500R(F) — 4 x 40 LCD annunciator with a key pad in a locked metal enclosure. Flush mount version available. LED-16(F) — 16 LED annunciator with common indicators in a locked metal enclosure. Flush mount version available. PSN-1000(E) — 10 amp, remote intelligent power supply with 6 NACs, 2 Inputs and a P-Link repeater. This panel is listed in conjunction with the IPA-4000 as releasing circuits. CA-6500 — Class A convertor that converts the SLC, NACs and P-Link connection UD-2000 — UL listed, Dual line telephone alarm communicator DRV 50 — LED driver expander, used to connect up to 50 LEDs in a graphic display FCB-1000 — Fire communication bridge, provides remote mounting of the Ethernet connection FIB-1000 — Fiber interface module, used to extend P-Link to multi - mode fiber (2 required) RLY 5 — Relay module, provides 5 form C relay contacts rated at 3.0 amps 24VDC/125AC SPG-1000 — Serial parallel gateway, allows for the connection to a serial or parallel printer The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the stacker bracket or ordered with the optional rack mount enclosure. MC-1000 Multi -Connect allows up to sixty-three IPA series panels to share a single reporting technology. IDC-6 — Initiating device circuit provides 6 programmable inputs AE-2 — Two card expansion cabinet AE-8 — Eight card expansion cabinet AE-14 — Fourteen card expansion cabinet Ethernet/I.P. Connection The IPA-4000 is shipped standard with an Ethernet connection. This connection is the programming port and may be connected to a building Wide Area Network (WAN) or Local Area Network (LAN). Once connected to the Internet, the panel may be selectively programmed to e-mail alarm conditions, trouble conditions, supervisory conditions, test, Event History and detector status. An e-mail may be sent to the panel and the panel will e-mail the event history, detector status, configuration file or server status to an authorized E-mail account. In addition, reminders may be set to send an e-mail for service, testing or other conditions. In addition, the Ethernet connection is UL listed as an IP communicator. The IP communicator is listed to report to the UL listed Sur -Gard III IP receiver. The IP communicator replaces the traditional less reliable alarm communicator transmitter that utilized telephone lines. The IP communicator is an active method of connection and communication to the monitoring station. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830102 - REV G • 1/20 PAGE 3 OF 4 (E)POTTER The Symbol of Protection Dimensions 18.91 " 17.60" TOP o ° O Oo 0 0 0 0 N LEFT SIDE BOTTOM Ordering Information Model Description Stock No. IPA-4000 Fire Alarm Releasing Control Panel 3992717 Replacement Board IPA-4000 3992740 IPA-4000 Fire Alarm Control Panel 4.41" 3.75" DEPTH SIDE Compatible Releasing Devices Note: For releasing applications please order the Potter EOLD (3005012) for circuits connected to a releasing solenoid or actuator. Brand Description Skinner 73218BN4UNLVNOCI12CZ 73212BN4TNLVN0C322C2 Victaulic 753-E Series Mini Max MX123 & MX200 w/ 8876677 & 889323 Viking 11591, 11601, 11602, 13843, & 13844 TLX PA0036 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830102 - REV G • 1/20 PAGE 4 OF 4 CP� POTTER The Symbol of Protection patent pending C uL US LISTED S2930 7315-0328:0189 Product includes a 5 year warranty Dimenions: 16 1/8"W x 16 3/4"H x 3 1/2"D Stock Number: 3006436 PSN-64 Red Enclosure 3006437 PSN-106 Red Enclosure 3006446 PSN-106 Black Enclosure PSN SERIES POWER SUPPLY UL, cUL, CSFM Listed • PSN-64 has 6 amps regulated with 4 Outputs • PSN-106 has 10 amps regulated with 6 Outputs • Outputs Rated at 3 amps maximum each • May be configured as up to three class "A" Style "Z" notification circuits • 3 amp, 24 VDC programmable output power • Supervised Battery Charger: 27.3 @ I (supports 7-55 AH batteries) • Easy to install cabinet with leveling mounts and key lock • Wiring knockouts provided on sides and top of cabinet • Two Trouble Relays (5A at 30VDC) General System Trouble (programmable for AC delay) Low AC Trouble with optional delay settings • Diagnostic LED's Status LED's for Active NAC and NAC trouble conditions Status LED's for Earth Fault(Amber),AC (Green), Battery Fault (Amber) • Trouble Memory feature captures troubles which have previously restored • Synchronized notification appliance circuits Potter/AMSECO®, Wheelock®, Gentex®, System Sensor® • Configurable output circuits (DIP switch sets options for each circuit) • 15 mA at 8-33 VDC input trigger • Reference EOL allows 2K — 27K EOL value to be used • Quadrasync provides panel wide synchronization of same or multiple brands • PassThru mode allows the Outputs to match the Input Signal Electrical Specs: • 120/240 VAC 50-60 Hz input • 5.1 Amps @ 120 VAC or 2.5 Amps @ 240 VAC • Battery Standby Current 75 mA • Alarm Standby Current 75 mA (no external load) Terminals support 12 - 18 AWG wire. Description The PSN series of notification power supplies offers reliable notification Sensor® strobe devices. Each output can be configured the same sync power with unprecedented versatility. The power supplies offer either protocol or set independently. 6 or 10 amps of continuous power through 4 or 6 outputs respectively. In addition, the panel has an input PassThru mode allows the outputs Each output is rated at 3 amps and it may be used continuously without to follow the input signal and sync up the input flash. The panel will any derating. recognize the type of input being supplied and pass this through to the The power supply operates on either 120 VAC or 220 VAC power input and has a regulated 24 VDC output. In addition, the panel can charge up to 55 AH batteries and leads the industry in housing up to 18 AH batteries. The cabinet is constructed out of 18 gauge cold rolled steel and has a durable red powder coat finish. In addition, a key lock is provided for securing the door. Ample electrical knockouts are provided on the sides and the top, allowing the installer options for running wires and maintaining the correct separations. The power supply offers an industry leading Quadrasync function that allows formultiple strobe circuits of different brands to be synchronized to flash at the same time. The panel can have four different brands each connected to its own circuit and all of the strobes flash together. Each output can independently be configured to provide one of outputs with the same pattern. This input pass through can be selected on each output independently. The power supply contains simple dipswitch programming and LED indications providing the installer indications of the operation and the ability to correct any faults. A Trouble Memory is provided to allow an installer to review past troubles and make the necessary repairs. Each output has an LED to pin point the exact circuit where a problem may have occurred. Relays are provided for monitoring the general system and AC failure. Each output and be independently configured for various applications and installations. Each output can be independently configured for Class A or Class B operation, constant power, ANSI Temporal Code 3, Single, Multiple or Combo Inputs or Door Holder Power. four synchronizations or steady power. This provides unequivocal flexibility in new and retrofit installations. The panel can be configured to synchronize Potter/AMSECO®, Gentex®, Wheelock® and System Potter Electric Signal Co., LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support: 866-956-1211 • Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MKT. #8910013 - REV D PAGE 1 OF 2 1/18 CP� POTTER The Symbol of Protection PSN-106 Wiring Diagram PSN SERIES POWER SUPPLY N 120/240 VAC GND FAULT o Jumper Position DETECT ENABLE ON o o c OFF 120VAC 50Hz-60Hz 240VAC 50Hz-60Hz Black Connect to separate White unswitched AC circuit Ground ar LBD s stutus NACI NAC2 NAC3 NAC4 NAC5 NAC6 DCPWR ®®® aaaBBaaa aaaaaaae El 0 eases SI H N 9Z FuseV 0 COMM• Elo eases 52 ,o �❑ p � �� o eases 53 0 AM O eases sa Factory Installed Interconnect. 0 AC Power ❑ ❑ ❑ ❑ ❑ ❑ o aaaae S5 Low Battery 0 Cona rn ❑ ❑ ❑ ❑ ❑ ❑ 0 eases Sfi 8 ❑ seas ������ Bulk Options ❑ ❑�❑ El rim O O NAC NAC2 NAC3 NAC4 NA 5 NACb CP REP 1 EJ2 LAI NCCO\ MNO NCCOMNOZ!Batty+e _OCommon relays areBattery OPtional E.O.L. non -power limited. O Ref ce E.O.L. E.O.L. DC Power Trigger — + + Battery connection (non -power limited). Use two (2)12V batteries connected in series. The contractor shall supply and install the Potter PSN power supply. The power supply shall operate on either 120 or 240 VAC input. The panel shall be capable of continuous load power without any degradation to the main supply or the distribution board. The cabinet shall be capable of housing up to 18 AH batteries and the panel shall be capable of charging up to 55 AH batteries in an external cabinet. The panel shall have dip switches for simplistic configuration of the system and LEDs to provide visual indication to the installer of the status of the system. The dip switches shall allow forAC power delay selection, Class A/B operation per output, Door Holder Power options, constant auxiliary power, trigger input type, ANSI Code 3 Temporal Code, Pass Thru (input tracking), Potter/AMSECO® sync, Gentex® Sync, System Sensor® Sync or Wheelock® sync. The LEDs shall provide indication of communication between the power supply and distribution circuit Note: PSN-64 and PSN-106 draw 15 mA when polarity reverses and the power supply is triggered. There is no current draw in Standby Mode. assemblies. The LEDs shall have distinct flash patterns to provide further indication of the troubles present. The panel shall have selectable Trouble Memory to provide the installer an indication that a past trouble existed on a circuit for diagnostic purposes. Each output of the power supply shall be capable of 3 amps of continuous power without degradation over time. The power supply shall provide for multiple circuits of strobe appliances. The power supply shall synchronize the flashes of any of the above listed strobe appliances on a per circuit basis. Up to four different strobe circuits may be connected and all of the strobes shall flash in unison as required by UL 864. In addition to this Quadrasync feature, the panel shall allow any of the four above mentioned sync patterns as an input and pass this signal through and synchronize the outputs to match the input flash pattern. PRINTED IN USA MKT. #8910013 - REV D PAGE 2 OF 2 1/18 c POTTER The Symbol of Protection YL LISTED S3247 Product includes a 5 year warranty Description The Potter CS/CHS Series is a ceiling mount strobe or horn/strobe combination that offers dependable audible and visual alarms and the lowest current consumption. The CS/CHS offers tamperproof field selectable candela options of 15, 30, 75, 95, 115 and 150 candela. The CHS horn offers a continuous or synchable temporal three in 2400Hz and mechanical tone. All tones are easy for the professional to change in the field by using switches. The models are shipped from the factory in the temporal three alarm mode. The CS Series has a very minimal operating current and has a minimum flash rate of 1Hz regardless of input voltage. CS/CHS SELECTABLE CANDELA CEiLiNg mou NT Features • Nominal voltage 24 VDC • Tamperproof field selectable candela options 15, 30, 75, 95, 115, & 150 • Super -Slide® Bracket - Ease of Supervision Testing • Checkmate® - Instant Voltage Verification • Synchronize strobe and/or horn with Gentex AVSM Control Module • Prewire entire system, install mounting bracket, then install signals • Documented lower installation and operating costs • Input Terminals 12 to 18 AWG • Switch Selection for High or Low dBA • Switch Selection for 2400Hz or mechanical Tone • Switch Selection for Continuous or Temporal 3 • Tamperproof re-entrant grill • Surface mount with the CLNGBB (Ceiling Surface Mount Back Box) • Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions) • Faceplate available in red or off-white Operating Temperature: • 32°F to 120°F (0°C to 49°C). The CS Series is not listed for outdoor use. Unit Dimensions • 6" (15.24 cm) x 2.6" (6.604 cm) The Ceiling Mount Series comes standard with the 4" mounting plate which incorporates the popular Super -Slide® feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The CS/CHS also features the patented Checkmate® - Instant Voltage Verification feature which allows the installer to check the voltage drop draw without removing the signal. The CS Series appliances are ANSI/UL 464 and ANSUUL 1971 listed for use with fire protective systems. PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 •TechSupport: 866-956-0988 • Canada888-882-1833 •www.pottersignal.com PRINTED IN USA MFG. #8830051 -REV A PAGE 1 OF 4 06/13 CF POTTER The Symbol of Protection Mounting Super -Slide® 2. Insert Locking Screw 1. Slide Onto Bracket Checkmate® Instant Voltage V DO NOT PAINT o o O lJ Z C ��6 0 � ®lSfn94C��§ W The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations. NOTICE: CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES. CS/CHS SELECTABLE CANDELA CEi Li Ng mou NT 3. Snap Cover Over Assembly Switch Locations FAF' Switch positions 1 and 2 in the down position to select isolated horn and strobe power inputs. Switch 3 selects between temporal or non - temporal tone. Up is temporal. Switch 4 selects between mechanical or high frequency tone. Up is mechanical. Switch 5 selects between high or low dBA. Up is high dBA. PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 •TechSupport: 866-956-0988 • Canada888-882-1833 •www.pottersignal.com PRINTED IN USA MFG. #8830051 -REV A PAGE 2 OF 4 06/13 CS/CHS CP� POTTER SELECTABLE CANDELA The Symbol of Protection CEiLiNg mou NT CS Series 24 Volt Ceiling Mount Selectable Strobe Model Number Part Number Nominal Voltage Candela CS-24R 4890020 24 VDC 15, 30, 75, 95, 115, 150 CS-24W 4890021 24 VDC 15, 30, 75, 95, 115, 150 CS-24PR 4890022 24 VDC 15, 30, 75, 95,115, 150 CS-24PW 4890023 1 24 VDC 15, 30, 75, 95, 115, 150 CHS Series 24 Volt Ceiling Mount Selectable Horn/Strobe Model Number Part Number Nominal Voltage Candela Reverberant dBA @ 10 ft. per ANSI/UL 464 In Anechoic Room dBA @ 10 ft. CHS-24R 4890040 24 VDC 15, 30, 75, 95, 115, 150 81-86 90 CHS-24W 4890041 24 VDC 15, 30, 75, 95, 115, 150 81-86 I 90 CHS-24PR 4890042 24 VDC 15, 30, 75, 95, 115, 150 1 81-86 I 90 CHS-24PW 4890043 24 VDC 15, 30, 75, 95, 115, 150 1 81-86 1 90 Model Designations: C = Ceiling Mount S = Strobe HS = Horn/Strobe R = Red Faceplate W = White Faceplate All units are available in plain (no lettering). Plain units are non -returnable. CS24 Product Strobe Current Ratings (mA) Candela 15 cd 30 cd 75 cd 95 cd 115 cd 150 cd 24 VDC (16-33 Volts) 24 VDC 72 mA 101 mA 167 mA 200 mA 214 mA 286 mA UL Maxl 120 mA 120 mA 200 mA 220 mA 290 mA 1 321 mA CHS24 Product Horn Decibel and Current Ratings (mA) Horn Mode Minimum dBA @ 10 ft. per ANSWL 464 (HIGH) Minimum dBA @ 10 ft. per ANSI/UL 464 (LOW) Regulated 24 VDC Max. Operating @ High Setting (mA) Temp 3 2400Hz 83 75 23 Temp 3 Mechanical I 81 I 73* I 22 Continuous 240011z I 86 I 78 I 23 Continuous Mechanical 84 76 22 NOTES: • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. • For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual. • Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products. • Operating the horn in this mode at this voltage will result in not meeting the minimum ANSWL 464 reverberant sound level required for public mode fire protection service.These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode). • RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33VDC for 24VDC units). For strobes the UL max current is usually at the minimum listed voltage (16VDC for 24VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual. PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -Tech Support: 866-956-0988 • Canada888-882-1833 •www.pottersignal.com PRINTED IN USA MFG. #8830051 -REV A PAGE 3 OF 4 06/13 CP� POTTER The Symbol of Protection Ar CS/CHS SELECTABLE CANDELA CEi Li Ng mou NT The visible and audible/visible signal shall be Gentex model GCS or GCC or approved equal and shall be listed by Underwriters Laboratories Inc. per ANSI/UL 1971 for the GCS and ANSI/UL 464 for the GCC. The notification appliance shall also be listed with the California State Fire Marshal (CSFM). The notification appliance (combination audible/visible units and audible units only) shall produce a peak sound output of 90dBA or greater as measured at 24VDC in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The appliance shall have an operating current of 72mA or less at 24VDC for the 15 candela strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox with the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power. The appliance shall be capable of test supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box. Conventional CS/CHS Series Wiring Diagrams UL Listed Control Signal Panel S+ S+ S- H+ H- Supervised 0 0 Signal Circuit n UL Listed Control Signal Panel S+ S+ S- H+ H- Supervised B Signal Circuit END LINE \ f RESISTOR Signal I I Signal END OF LINE RESISTOR END OF LINE RESISTOR NOTES: • All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn. • FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936. PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -Tech Support: 866-956-0988 •Canada888-882-1833 •www.pottersignal.com PRINTED IN USA MFG. #8830051 -REV A PAGE 4 OF 4 06/13 Sealed Lead -Acid Batteries .ice 4 �=Z Gt-df \dta:p 20 Ff F#e (0.36 P) 7.2 Ph 1.75 v/ c@25° C 10 Ft F#e (0.65 Al 6.5 Ph 1.70v/c 5FtF#e(1.14P) 5.7Ph 1.55 V c 1 Ff Fite (4.1 P) 4.1 Ph Boc Fd- Cdl Ghrge\dtagv(ardat) Fot 13.5--13.8 225-230 Cyde 14.414.7 240-245 Dahxge Grret Amps (5 s n-rb ffEDd no 80 D,cdwge C Ta t Arps (nudffunutinct.$) 50 Nbc. Gage Cwret 216 A Ap3u(Fnd Gage Gxrat (225 v/ c F1cet) 0.014 (14 rrP) PgaUc Frd Gage Garet (245 v/ cCyde) 0.07 (70 mil Tarrird Type TypeA/ (Gcptia-d) 5Jf o 9mTths@21°C cwe Nkeid P88- c3W cr Back netodwgT,inftn„faluirgpow!ipa AcrrrrajdvWvAhcUnchm "liar gtui isftmWad3l PM 5pedficetion 9ieet BS-1 075 (PC1270) Tedinid qDedfications Nt7rird \dtagp 12V Wdrd Goty 7.2 Ph (20 �t Fite) Cirrffijcns Leigh 150 rrm Vie 64.5 rrm Fight: 95 rrm Taal FboTermnd: 101 mn u;t: mn( 0.50) 0 0 Actual VVAtage / Ampere C anadty at Various Cisdwge Tim rv(lt rpr CNI na ` W lff,dta:p Tffe 5 Mn 10 n in 15 n in 30 rrin 45 rrin 60 rrin 1.75 v/ c VV 45.4 30.77 23.28 129 10.31 8.07 25°C A 25.94 17.58 13.3 7.37 5.89 4.61 1.67 V c VV 47.76 31.4 23.9 13.09 10.04 8.07 2.'i C A 28.6 18.8 14.31 7.84 6.01 4.83 1.60 V c VV 49.28 31.52 24.0 13.3 9.3 7.79 2YC A 30.8 19.7 15.0 8.31 5.81 497 i n t e r s t a t e b a t t e r i e s. c o m © Ute-Aate Bite y _I�5encf ATaica, I m o2i ai vas COLEMANCABLEL Rap��R_ 4C4_1 Toll -Free (800) 323-9355 Wiring The World Fax: (847) 689-1192 PRODUCT DATA SHEET PART NUMBER: 81802 DESCRIPTION: 18/2 SOLID FPLP FT6 CABLE CONSTRUCTION: This cable consists of two bare copper insulated conductors and an overall jacket. APPROVALS: UL Standard 1424, NEC Article 760. APPLICATION: Fire Alarm Power Limited Circuit Cable Used in Plenum Applications Construction Parameters: Cable Cross -Section Conductor Stranding Insulation Material Insulation Thickness Insulated Conductor Diameter Number of Conductors Lay Length Jacket Material Jacket Thickness Overall Cable Diameter Approximate Cable Weight Flame Rating Electrical Properties: 18 AWG Bare Copper Solid Polymer Alloy 0.006" Nom. 0.052" Nom. 2 1.75" Nom. Low Smoke PVC 0.016" Nom. 0.136" Nom. 17.4 Lbs/1 M' Nom. UL 910 Steiner Tunnel Smoke and Flame Test Temperature Rating -20oC to 75oC Operating Voltage 300 V RMS Max. Capacitance Between Conductors @ 1 KHz 50 pF/ft Nom. Capacitance Between Conductors to Shield @ 1 KHz ----- DC Resistance per Conductor @ 200C 6.32 Ohms/1 M' Nom. Insulation Colors Black Red Jacket Color Red (Other colors available for minimum order) Legend (Surface Ink Print) E100315 " 18 AWG 2/C (UL) TYPE FPLP 75C -- C(UL) TYPE CMP FT6 On special orders, the customer will accept all factory lengths and +1-10 percent of total order requested. The jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of information contained herein or otherwise. This specification is proprietary intellectual property of Coleman Cable. Any information contained herein shall not be disclosed to any party without written consent of Coleman Cable. Customer Name_ Customer Approval Specification Issue Date: January 19, 2001 1-800-323-9355 (Phone) Designed By: PEP 1-847-689-1192 (Fax) 81802 © 2000 Coleman Cable Systems, Inc. Z< COLEMANCABLE Toll -Free (800) 323-9355 Wirinq The World PRODUCT DATA SHEET PART NUMBER: 81804 DESCRIPTION: 18/4 SOLID FPLP FT6 CABLE CONSTRUCTION: This cable consists of four bare copper insulated conductors and an overall jacket. APPROVALS: UL Standard 1424, NEC Article 760. APPLICATION: Fire Alarm Power Limited Circuit Cable Used in Plenum Applications Construction Parameters: Conductor Stranding Insulation Material Insulation Thickness Insulated Conductor Diameter Number of Conductors Lay Length Jacket Material Jacket Thickness Overall Cable Diameter Approximate Cable Weight Flame Rating Electrical Properties: 18 AWG Bare Copper Solid Polymer Alloy 0.006" Nom. 0.052" Nom. 4 Parallel Low Smoke PVC 0.016" Nom. 0.158" Nom. 29.1 Lbs/1 M' Nom. UL 910 Steiner Tunnel Smoke and Flame Test Temperature Rating -200C to 750C Operating Voltage 300 V RMS Max. Capacitance Between Conductors @ 1 KHz 53 pF/ft Nom. Capacitance Between Conductors to Shield @ 1 KHz ----- DC Resistance per Conductor @ 200C 6.32 Ohms/1 M' Nom. Insulation Colors Black Red Green Yellow Jacket Color Red (Other colors available for minimum order) Fax: (847) 689-1192 Cable Cross -Section Legend (Surface Ink Print) E100315 * 18 AWG 4/C (UL) TYPE FPLP 75C -- C(UL) TYPE CMP FT6 On special orders, the customer will accept all factory lengths and +1-10 percent of total order requested. The jacket is sequentially footmarked. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of information contained herein or otherwise. This specification is proprietary intellectual property of Coleman Cable. Any information contained herein shall not be disclosed to any party without written consent of Coleman Cable. Customer Name Date Signed Customer Approval Specification Issue Date: January 19, 2001 1-800-323-9355 (Phone) Designed By: PEP 1-847-689-1192 (Fax) 81804 © 2001 Coleman Cable Systems, Inc. :p F-apdWR ON ! COLEMANCABLE Toll -Free (800) 323-9355 Wiring The World Fax: (847) 689-1192 PRODUCT DATA SHEET PART NUMBER: 81402 DESCRIPTION: 14/2 SOLID FPLP METRO CABLE CONSTRUCTION: This cable consists of two bare copper insulated conductors and an overall jacket. APPROVALS: UL Standard 1424, NEC Article 760. APPLICATION: Fire Alarm Power Limited Circuit Cable Used in Plenum Applications Construction Parameters: Conductor Stranding Insulation Material Insulation Thickness Insulated Conductor Diameter Number of Conductors Lay Length Jacket Material Jacket Thickness Overall Cable Diameter Approximate Cable Weight Flame Rating Electrical & Enviromental Properties: Temperature Rating Operating Voltage Capacitance Between Conductors @ 1 KHz Capacitance Between Conductors to Shield @ 1 KHz Inductance DC Resistance per Conductor @ 200C Insulation Colors Jacket Color Legend (Surface Ink Print) 14 AWG Bare Copper Solid Polymer Alloy 0.009" Nom. 0.082" Nom. 2 1.75" Nom. Low Smoke PVC 0.020" Nom. 0.204" Nom. 37.4 Lbs/1 M' Nom. UL 910 Steiner Tunnel Smoke and Flame Test -20oC to 75oC 300 V RMS Max. 54 pF/ft Nom. 0.07 uH/ft Nom. 2.54 Ohms/1 M' Nom. Black Red Red (Other colors available for minimum order) El00315' 14 AWG 2/C (UL) TYPE FPLP 75C Cable Cross -Section On special orders, the customer will accept all factory lengths and +/-10 percent of total order requested. The information presented here is, to the best of our knowledge, is true and accurate. However, since conditions of use are beyond our control, all recommendations or suggestions are presented without guarantee or responsibility on our part. We disclaim all liability in connection with the use of information contained herein or otherwise. This specification is proprietary intellectual property of Coleman Cable. Any information contained herein shall not be disclosed to any party without written consent of Coleman Cable. Customer Name Date Signed Customer Approval Specification Issue Date: August 13, 2001 1-800-323-9355 (Phone) Designed By: PEP 1-847-689-1192 (Fax) 81402 © 2000 Coleman Cable Systems, Inc.