Loading...
FIR2021-0011+Scope of work+1.27.2021_7.53.09_AM+2012265FIRE PROTECTION, INC. 17410 Ash Way, Ste 8 Lynnwood, WA 98037 (4251 290-9600 January 26, 2021 City of Edmonds / South County Fire - PLAN REVIEW RE; Demetri's Woodstone Tavern * Building* 101 Main Street, Edmonds, WA 98020 Installation of a Full Coverage Automatic and Manual Fire Alarm System in an Existing Non -Sprinkled Building. The Fire Alarm system will provide Automatic Detection, Manual Activation and Occupant Notification throughout the existing building as per the City of Edmonds & South County Fire's requirements. The Fire Alarm System will monitor the existing CLASS 1 Ansul Kitchen Hood for activation. Scope of work includes: Installation of a new Fully Addressable Fire Alarm Control Panel, (1) Addressable FACP Smoke Detector, (1) Addressable FACP Pull -Station, (13) Addressable Heat Detectors, (1) Addressable Monitor Module, (13) Occupant Notification Devices, (1) AES Radio Communicator, (2) Conventional Relays and (1) FA Document Cabinet. A full pre -test shall be conducted and completed prior to calling the AHJ for acceptance testing. A completed NFPA-72 completion form and AES radio table report will be provided to the AHJ at the time of the fire final acceptance test. Copies of all record documents will be place in the FA Document Cabinet at the FACP. System has been designed per IBC, IFC, NFPA 70 & 72 and your additional requirements. INSTALLATION COMPANY Fire Protection, Inc. 17410 Ash Way Ste 8, Lynnwood, WA 98037 WSCL# FIREPI*021ML UL CERT #608242-002 APPROVED UL MONITORING COMPANY Alarm Center, Inc./FPI 4300 3rd Ave. SE Lacey, WA 800-429-0991 UL CERT #902799-02 AMBIENT TEMPERATURES No area with alarm service equipment shall fall below 40 degrees, common areas shall be at 68 degrees per builder AMBIENT NOISE RANGE All areas serviced by the Fire Alarm Control and notification system will be as listed for per UBC listings, per builder. CONTRACTUAL RESPONSIBLE PARTIES Fire Protection, Inc.: Monitoring, Design, Permits, Installation & System Testing. SEQUENCE OF OPERATIONS All Alarm and Trouble conditions shall enunciate at FACP as well as remote notify UL listed Central Station. Zones of alarm shall cause for all notification circuits to activate, send alarm zone to CS, re -dispatch to Fire and dispatch FPI runner service. Trouble and supervisory signals shall transmit to CS which will dispatch FPI runner service to site, (no notification circuits shall activate.) On site emergency contact personnel shall be notified. Opens, shorts, and ground faults on any zones shall cause for a trouble signal. Should you have any further questions, please feel free to contact me directly. DAVID MOW, SET NICET IV #120904 VP of Operations / Designer of Record