FIR2021-0107+Fire_Alarm_Voltage_Calculations+9.23.2021_12.13.16_PM+2425332NAPCO RECEIVED
coMMERCIAL F I R2021-0107 GEMC FIRE Date: 23-Se -21
STANDBY Sep 23 2021 Project Name: N land Apartments - Building 1
CALCULATION CHART DEVELOPMENT SERVICES
In CITY OF EDMONDS Location: I Sprinkler Riser Room
DEPARTMENT Prepared By: JD
Panel Model #: FL-FACP-LTE
12V 12V 24V 24V TOTAL TOTAL
MODULE DESCRIPTION standby Alarm Standby Alarm QTY STANDBY ALARM
Current Current Current Current CURRENT CURRENT
(mA) mA mA (mA) (mA)
Fire Alarm Current Chart
GEMC-CONTROL PANEL Control Panel 96 96 1 96 96
Fire Aux Relay Normally Energized
35
35
GEMC-F8ZCPIM
Conventional (8)zone 2-wire fire input module.
120
72
72
# of Zones Used
5
3
24
Devices powered by GEMC-F8ZCPIM AUX PWR
Devices powered by GEMC-F8ZCPIM RST PWR
GEMC-FK1
LCD Fire Keypad for GEM-C Combo System, Red
110
66
66
GEMC-RECV
Commercial Fire Wireless Receiver (Fire Bus Only)
70
42
42
GEMC-EZM8
8 Point Expansion Module
60
36
36
GEMC-FPRINT
Printer Module
90
54
54
GEMC-RM3008
Relay Output Module (Fire Bus Only)
22
13
13
# of Relays Normally Energized
12
7
# of Relays Energized on Alarm
12
7
GEMC-NL-MOD
Internet Reporting Module
85
51
51
GEMC-RS232
RS232 Adaptor
60
36
36
GEMC-OUT8
PGM Output Module
35
21
21
GEMC-FW-SLC
Addressable SLC Fire Module
70
140
FWC-FSLC-SMK
Addressable SLC Photo Smoke Detector
0.68
1.40
1
1
1
FWC-FSLC-HEAT
Addressable SLC Heat Detector
0.61
0.88
FWC-FSLC-DUCT
Addressable SLC Photo Duct Smoke Detector
10.68
0.95
FWC-FSLC-EZM2
Addressable SLC 2 Zone Conv. Input Module
1.05
1.26
1
1
1
FWC-FSLC-EZM1
Addressable SLC Single Input Conv.lnput Module.
0.96
1.16
FWC-FSLC-CZM
Addressable SLC Conv Single Module
2.17
1.26
FWC-FSLC-RM2
Addressable SLC Dual Relay Module
0.68
0.70
FWC-FSLC-ISO
Addressable SLC Fire Isolation Module
0.47
0.47
FWC-FSLC-SOM1
Addressable SLC Fire Supervised Output Module
1.39
0.28
FWC-FSLC-PULL
Addressable SLC Fire Pull Station
0.96
1.14
1
1
1
GEMC-NAC7S
Remote NAC Extender.
8
5
5
GEMC-12V2APS-CF
Remote Supervised 12VDC Power Supply
8
5
5
GEMC-24VR
Add On 24V Regulator
NAC A
On Board NAC Circuit A
N/A
198
1
198
NAC B
On Board NAC Circuit B
N/A
NAC C
On Board NAC Circuit C
N/A
NAC D (set to 24V)
On Board NAC Circuit D
N/A
NAC D (set to 12V)
On Board NAC Circuit D
N/A
Mother Board AUX PWR
Mother Board RLY PWR
(only if configured for wet operation)
FIRE STANDBY CURRENT DRAW
99 mA
REQUIRED FIRE STANDBY TIME
24 Hours
REQUIRED FIRE STANDBY BATTERY CAPACITY
2.4 AH
TOTAL FIRE ALARM CURRENT DRAW
298 mA
REQUIRED FIRE ALARM STANDBY TIME
5 Min
REQUIRED FIRE ALARM BATTERY CAPACITY
0.0 AH
BATTERY DERATING FACTOR
TOTAL REQUIRED STANDBY BATTERY CAPACITY
20 %
3.0 AH
INSTALLED BATTERY CAPACITY
QTY:
2 AH:
7
14.0 AH