FIR2021-0108+Fire_Alarm_Battery_Calculations+9.23.2021_12.25.30_PM+2425371IVAPCO RECEIVED COMMERCIAL GEMC FIRE F I R2021-0108 Sep 23 2021 STANDBY DEVELOPMENT SERVICECALC U LATI O N CHART lij CITY OF EDMONDS DEPARTMENT 12V 12V MODULE DESCRIPTION standby Alarm Current Current (mA) Fire Alarm Current Chart GEMC-CONTROL PANEL Control Panel Date: 23-Se -21 Prcject Name: Nyland Apartments -Building 2 Location: Sprinkler Riser Room Prepared By: JD Panel Model #1 FL-FACP-LTE 24V 24V TOTAL TOTAL Standby Alarm QTY STANDBY ALARM Current Current CURRENT CURRENT mA mA (mA) (mA) 96 96 1 96 96 Fire Aux Relay Normally Energized 35 35 GEMC-F8ZCPIM Conventional (8)zone 2-wire fire input module. 120 72 72 # of Zones Used 5 3 24 Devices powered by GEMC-F8ZCPIM AUX PWR Devices powered by GEMC-F8ZCPIM RST PWR GEMC-FK1 LCD Fire Keypad for GEM-C Combo System, Red 110 66 66 GEMC-RECV Commercial Fire Wireless Receiver (Fire Bus Only) 70 42 42 GEMC-EZM8 8 Point Expansion Module 60 36 36 GEMC-FPRINT Printer Module 90 54 54 GEMC-RM3008 Relay Output Module (Fire Bus Only) 22 13 13 # of Relays Normally Energized 12 7 # of Relays Energized on Alarm 12 7 GEMC-NL-MOD Internet Reporting Module 85 51 51 GEMC-RS232 RS232 Adaptor 60 36 36 GEMC-OUT8 PGM Output Module 35 21 21 GEMC-FW-SLC Addressable SLC Fire Module 70 140 FWC-FSLC-SMK Addressable SLC Photo Smoke Detector 0.68 1.40 1 1 1 FWC-FSLC-HEAT Addressable SLC Heat Detector 0.61 0.88 FWC-FSLC-DUCT Addressable SLC Photo Duct Smoke Detector 10.68 0.95 FWC-FSLC-EZM2 Addressable SLC 2 Zone Conv. Input Module 1.05 1.26 1 1 1 FWC-FSLC-EZM1 Addressable SLC Single Input Conv.lnput Module. 0.96 1.16 FWC-FSLC-CZM Addressable SLC Conv Single Module 2.17 1.26 FWC-FSLC-RM2 Addressable SLC Dual Relay Module 0.68 0.70 FWC-FSLC-ISO Addressable SLC Fire Isolation Module 0.47 0.47 FWC-FSLC-SOM1 Addressable SLC Fire Supervised Output Module 1.39 0.28 FWC-FSLC-PULL Addressable SLC Fire Pull Station 0.96 1.14 1 1 1 GEMC-NAC7S Remote NAC Extender. 8 5 5 GEMC-12V2APS-CF Remote Supervised 12VDC Power Supply 8 5 5 GEMC-24VR Add On 24V Regulator NAC A On Board NAC Circuit A N/A 198 1 198 NAC B On Board NAC Circuit B N/A NAC C On Board NAC Circuit C N/A NAC D (set to 24V) On Board NAC Circuit D N/A NAC D (set to 12V) On Board NAC Circuit D N/A Mother Board AUX PWR Mother Board RLY PWR (only if configured for wet operation) FIRE STANDBY CURRENT DRAW 99 mA REQUIRED FIRE STANDBY TIME 24 Hours REQUIRED FIRE STANDBY BATTERY CAPACITY 2.4 AH TOTAL FIRE ALARM CURRENT DRAW 298 mA REQUIRED FIRE ALARM STANDBY TIME 5 Min REQUIRED FIRE ALARM BATTERY CAPACITY 0.0 AH BATTERY DERATING FACTOR TOTAL REQUIRED STANDBY BATTERY CAPACITY 20 % 3.0 AH INSTALLED BATTERY CAPACITY CITY: 2 AH: 7 14.0 AH