FIR2021-0028+Fire_Alarm_Battery_Calculations+3.24.2021_10.36.40_AM+2108985EXISTING FACP (SK-5204) BATTERY CALCULATION
SECONDARY POWER SOURCE REQUIREMENTS
STANDBY CURRENT
SECONDARY ALARM
(AMPS)
CURRENT (AMPS)
QTY
PART NO
DESCRIPTION
CURRENT
DRAW
TOTAL (q)
CURRENT
DRAW
TOTAL
PANEL COMPONENTS
(A)
(A)
1
SK-4 MAIN BOARD
FIRE ALARM CONTROL
1 x 0
= 0
1 x 0
= 0
PANEL MAIN BOARD
CIRCUIT
SYMBOL
QTY
PART NO
DESCRIPTION
CURRENT
TOTAL (A)
CURRENT
TOTAL (A)
DRAW (A)
DRAW (A)
Selectable Candela, Low
�0
1
GEC3-24WR
Profile Evacuation
1 x 0
= 0
1 x 0.108
= 0.108
Horn/Strobe, Red 75cd
Selectable Candela, Low
3
GES3-24WR
Profile Evacuation Strobe,
3 x 0
= 0
3 x 0.042
= 0.126
FACP•NAC2
Red 15cd
1
SRK
Strobe 75 ddoor red
1 x 0
= 0
1 x 0.158
= 0.158
WP
�]F
1
SSM24-8
Alarm Bell 8" 24VDC, red
1 x 0
= 0
1 x 0.0535
= 0.0535
0
28
2W-B
2-wire Standard i3
28 x 0.0001
= 0.0028
28 x 0.13
= 3.64
Detector
FACP •Z02
Heat Detector, rate
0
4
302-194
ompensated, 194E 90.2
4 x 0
= 0
4 x 0
= 0
FACP•Z04
0
1
2W-B
2-wire Standard i3
1 x 0.0001
= 0.0001
1 x 0.13
= 0.13
Detector
TOTAL
0.0029
TOTAL
4.2155
TANDBY (A
ALARM (A)
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD
0.0029
x 24
= 0.07 AH
SECONDARY ALARM LOAD
4.2155
x 0.08
= 0.35 AH
STANDBY AND ALARM LOAD SUBTOTAL
0.42 AH
DERATING FACTOR
x 1.2
SECONDARY LOAD REQUIREMENTS (AMP HOURS)
0.51 AH
PROVIDE (2) 12V 7AH BATTERIES Cs� 24VDC
Point -To -Point Voltage Drop Calculation for Panel FACP Circuit NAC2
Starting Calculation Voltage: 20.4v Minimum Operational Voltage: 16v
Total Circuit Current: 0.4455A Total Distance: 390'
Voltage Drop: 0.7v End Of Line Voltage: 19.7v
Percent Drop: 3.43 � Wire GA=#14 AWG Wire Resistance (S2/Ft): 0.00307
Distance measured using drawn segment lengths with 15.00 � additional length calculated
Device Label
Part No.
Description
Device Current
Distance From
Voltage At
Voltage Drop
Voltage Drop
Previous Device
Device
From Source
Percent
Selectable Candela, Low Profile
NAC2.01
GEC3-24WR
Evacuation Horn/Strobe, Red
0.108A
113'
20.09v
0.31v
1.51
75cd
NAC2-02
SRK
Strobe outdoor red 75cd
0.158A
157'
19.77v
0.63v
3.11
NAC2.03
SSM24-8
Alarm Bell 8" 24VDC, red
0.0535A
3'
19.76v
0.64v
3.12
NAC2.04
GES3-24WR
electable Candela, Low Profile
0.042A
39'
19.73v
0.67v
3.27
Evacuation Strobe, Red 15cd
NAC2.05
GES3-24WR
electable Candela, Low Profile
0.042A
50'
19.71v
0.69v
3.39
Evacuation Strobe, Red 15cd
NAC2.06 EOL
GES3-24WR
electable Candela, Low Profile
0.042A
29'
19.7v
0.7v
3.43
Evacuation Strobe, Red 15cd
FIRE PROTECTION INC.
17410 Ash Way, Ste 8
Lynnwood, WA 98037
425-290-9600
FPISEATTLE.COM
NFFVA
000805173
ROY L CATS
�OTC��O
4
�. NFPA`
��
CFPS
#1473
H
HLn
Urn
H
2 U U
rn 0
U � H co
3 a
O wopoo
.0Z wUa
O r- ?H W N a,'
QChLo AN
H O M a O
��A�H W
A AM H k OG+
E+ A O
w H�ww o
�HHw�wHw�w'� Q
A2a�av�aaa c
REVISION RECORD
DATE / DESCRIPTION
DATE: 3/22/21
PROJECT NAME
O
N
� O
� _ 00
oaa
O N
♦"'
ti i
O
N -0
N W
SHEET TITLE
FIRE ALARM
BATTERY & VOLTAGE
DROP CALCULATIONS
SHEET NUMBER
FA 4.0
NEW RPS (FIRESWITCH108) BATTERY CALCULATION
SECONDARY POWER SOURCE REQUIREMENTS
PANEL POWER SUPPLY MAX CURRENT = 10A
TOTAL USED CAPACITY = 4.016A (40.16 %)
STANDBY CURRENT
SECONDARY ALARM
(AMPS)
CURRENT (AMPS)
QTY
PART NO
DESCRIPTION
CURRENT
DRAW (A)
TOTAL A)
(
CURRENT
DRAW (A)
TOTAL
PANEL COMPONENTS
1
FireSwitch108 Main
1 x 0.18
= 0.18
1 x 0.2
= 0.2
Board
CIRCUIT
SYMBOL
QTY
PART NO
DESCRIPTION
CURRENT
TOTAL (A)
CURRENT
TOTAL (A)
DRAW (A)
DRAW (A)
Horn Strobe, 24 VDC,
0
3
GCC24CR
Red, Ceiling 15cd
3 x 0
= 0
3 x 0.143
= 0.429
Horn Strobe, 24 VDC,
RPS-NAC1
0
1
GCC24CR
Red, Ceiling 75cd
1 x 0
= 0
1 x 0.223
= 0.223
GCS Series 24 Volt
6
GCS24CR
Ceiling Mount Selectable
6 x 0
= 0
6 x 0.12
= 0.72
Strobe, Red 15cd
Horn Strobe, 24 VDC,
0
3
GCC24CR
Red, Ceiling 15cd
3 x 0
= 0
3 x 0.143
= 0.429
Horn Strobe, 24 VDC,
0
1
GCC24CR
Red, Ceiling 75cd
1 x 0
= 0
1 x 0.223
= 0.223
RPS-NAC2
GCS Series 24 Volt
3
GCS24CR
Ceiling Mount Selectable
3 x 0
= 0
3 x 0.12
= 0.36
Strobe, Red 15cd
GCS Series 24 Volt
�
1
GCS24CR
Ceiling Mount Selectable
1 x 0
= 0
1 x 0.2
= 0.2
Strobe, Red 75cd
Horn Strobe, 24 VDC,
0
4
GCC24CR
Red, Ceiling 15cd
4 x 0
= 0
4 x 0.143
= 0.572
RPS•NAC3
GCS Series 24 Volt
4
GCS24CR
Ceiling Mount Selectable
4 x 0
= 0
4 x 0.12
= 0.48
Strobe, Red 15cd
TOTAL
0.18
TOTAL
3.836
STANDBY (A
ALARM (A)
REQUIRED STANDBY TIME = 24
HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD
0.18
x 24
= 4.32 AH
SECONDARY ALARM LOAD
3.836
x 0.08
= 0.32 AH
STANDBY AND ALARM LOAD SUBTOTAL
4.64 AH
DERATING FACTOR
x 1.2
SECONDARY LOAD REQUIREMENTS (AMP HOURS)
5.57 AH
PROVIDE (2) 12V 7AH BATTERIES (s� 24VDC
Point -To -Point Voltage Drop Calculation for Panel RPS Circuit NAC1
Starting Calculation Voltage: 20.4v Minimum Operational Voltage: 16v
Total Circuit Current: 1.372A Total Distance: 276'
Voltage Drop: 1.39v End Of Line Voltage: 19.01v
Percent Drop: 6.80 � Wire GA=#14 AWG Wire Resistance (n/Ft): 0.00307
Distance measured using drawn segment lengths with 15.00 � additional length calculated
Device Label
Part No.
Description
Device Current
Distance From
Voltage At
Voltage Drop
Voltage Drop
Previous Device
Device
From Source
Percent
GCS Series 24 Volt Ceiling
NAC1 •01
GCS24CR
Mount Selectable Strobe, Red
0.12A
65'
19.85v
0.55v
2.68
15cd
NAC1 •02
GCC24CR
Horn Strobe, 24 VDC, Red,
Ceiling 15cd
0.143A
,
13
19.76v
0.64v
3.16
NAC1-03
GCC24CR
Horn Strobe, 24 VDC, Red,
0.143A
35'
19.52v
0.88v
4.32
Ceiling 15cd
GCS Series 24 Volt Ceiling
NAC1.04
GCS24CR
Mount Selectable Strobe, Red
0.12A
23'
19.39v
1.01v
4.98
15cd
GCS Series 24 Volt Ceiling
NAC1.05
GCS24CR
Mount Selectable Strobe, Red
0.12A
9'
19.34v
1.06v
5.22
15cd
GCS Series 24 Volt Ceiling
NAC1 -06
GCS24CR
Mount Selectable Strobe, Red
0.12A
25'
19.22v
1.18v
5.76
15cd
NAC1 •07
GCC24CR
Horn Strobe, 24 VDC, Red,
Ceiling 15cd
0.143A
,
19
19.15v
1.25v
6.10
GCS Series 24 Volt Ceiling
NAC1.08
GCS24CR
Mount Selectable Strobe, Red
0.12A
16'
19.11 v
1.29v
6.33
15cd
NAC1 •09
GCC24CR
Horn Strobe, 24 VDC, Red,
Ceiling 75cd
0.223A
32'
19.04v
1.36v
6.66
GCS Series 24 Volt Ceiling
NAC1.10 EOL
GCS24CR
Mount Selectable Strobe, Red
0.12A
40'
19.01v
1.39v
6.80
15cd
Point -To -Point Voltage Drop Calculation for Panel RPS Circuit NAC2
Starting Calculation Voltage: 20.4v Minimum Operational Voltage: 16v
Total Circuit Current: 1.212A Total Distance: 221'
Voltage Drop: 1.09v End Of Line Voltage: 19.31v
Percent Drop: 5.36 � Wire GA=#14 AWG Wire Resistance (n/Ft): 0.00307
Distance measured using drawn segment lengths with 15.00 � additional length calculated
Device Label
Part No.
Description
Device Current
Distance From
Voltage At
Voltage Drop
Voltage Drop
Previous Device
Device
From Source
Percent
GCS Series 24 Volt Ceiling
NAC2.01
GCS24CR
Mount Selectable Strobe, Red
0.12A
73'
19.86v
0.54v
2.67
15cd
GCS Series 24 Volt Ceiling
NAC2.02
GCS24CR
Mount Selectable Strobe, Red
0.12A
12'
19.78v
0.62v
3.05
15cd
GCS Series 24 Volt Ceiling
NAC2.03
GCS24CR
Mount Selectable Strobe, Red
0.12A
12'
19.71v
0.69v
3.39
15cd
NAC2.04
GCC24CR
Horn Strobe, 24 VDC, Red,
Ceiling 15cd
0.143A
,
27
19.57v
0.83v
4.09
NAC2.05
GCC24CR
Horn Strobe, 24 VDC, Red,
Ceiling 15cd
0.143A
19'
19.48v
0.92v
4.49
NAC2.06
GCC24CR
Horn Strobe, 24 VDC, Red,
Ceiling 75cd
0.223A
,
23
19.41v
0.99v
4.87
NAC2.07
GCC24CR
Horn Strobe, 24 VDC, Red,
0.143A
34'
19.34v
1.06v
5.22
Ceiling 15cd
GCS Series 24 Volt Ceiling
NAC2.08 EOL
GCS24CR
Mount Selectable Strobe, Red
0.2A
23'
19.31v
1.09v
5.36
75cd
Point -To -Point Voltage Drop Calculation for Panel RPS Circuit NAC3
Starting Calculation Voltage: 20.4v Minimum Operational Voltage: 16v
Total Circuit Current: 1.052A Total Distance: 319'
Voltage Drop: 1.47v End Of Line Voltage: 18.93v
Percent Drop: 7.22 � Wire GA=#14 AWG Wire Resistance (n/Ft): 0.00307
Distance measured using drawn segment lengths with 15.00 %additional length calculated
Device Label
Part No.
Description
Device Current
Distance From
Voltage At
Voltage Drop
Voltage Drop
Previous Device
Device
From Source
Percent
NAC3.01
GCC24CR
Horn Strobe, 24 VDC, Red,
Ceiling 15cd
0.143A
,
148
19.44v
0.96v
4.68
Horn Strobe, 24 VDC, Red,
NAC3.02
GCC24CR
Ceiling 15cd
0.143A
11'
19.38v
1.02v
4.98
NAC3.03
GCC24CR
Horn Strobe, 24 VDC, Red,
Ceiling 30cd
0.143A
38'
19.21 v
1.19v
5.86
GCS Series 24 Volt Ceiling
NAC3.04
GCS24CR
Mount Selectable Strobe, Red
0.12A
20'
19.13v
1.27v
6.23
15cd
GCS Series 24 Volt Ceiling
NAC3.05
GCS24CR
Mount Selectable Strobe, Red
0.12A
26'
19.05v
1.35v
6.62
30cd
GCS Series 24 Volt Ceiling
NAC3.06
GCS24CR
Mount Selectable Strobe, Red
0.12A
28'
18.98v
1.42v
6.94
15cd
NAC3.07
GCC24CR
Horn Strobe, 24 VDC, Red,
Ceiling 15cd
0.143A
24'
18.95v
1.45v
7.13
GCS Series 24 Volt Ceiling
NAC3.08 EOL
GCS24CR
Mount Selectable Strobe, Red
0.12A
25'
18.93v
1.47v
7.22
30cd