FIR2021-0028+NARRATIVE+3.24.2021_10.37.05_AM+2108991FIRE PROTECTION, INC. PO BON 12642 MILL CREEK, WA 98082 14251 290-9600 OR 1-800-681-1125 FAX 14251353-4546 March 24, 2021 Attn: City of Edmonds Fire Prevention RE; Parts & Smarts Fire Alarm T.I Please find enclosed the Fire Alarm Tenant Improvement Design A Part/Smarts Fire Alarm Tenant Improvement per the City of Edmond's requirements. The main floor of the existing non -sprinkled building is undergoing a tenant improvement. This is a Parts/Smarts project, FPI will provide a code compliant design, fire alarm permit/submittals, new fire alarm equipment, system pre -testing and final acceptance testing. Evergreen Power Systems Inc will provide the electrical permit and electrical installation as shown. The main floor of the existing building will be brought up to current code per Edmonds Municipal Code 19.25.035. Additional Detection and Occupant Notification will be installed in areas lacking proper coverage, all exiting devices to remain unless noted. The existing FACP (SK-5204) is located in the electrical room on the lower floor. Edmonds Municipal Code as it relates to fire amendments: 19.25.035 Fire protection systems: C. Fire Alarms and Detection Systems. In addition to the requirements of Section 907.2, an approved, monitored automatic fire alarm system shall be installed and maintained throughout all buildings, structures, floors, and suites described in this section. If conflicts exist between the IFC and this section, this section shall prevail. Fire alarm systems shall be installed per NFPA 72 and SCF's fire alarm standard. Partial area fire alarm systems are prohibited except where approved by the fire code official. 1. In existing buildings, structures or suites having an existing fire alarm system that does not protect all areas, when the building, structure, or suite undergoes an alteration, repair, modification, or similar improvement requiring a building permit, unprotected areas shall be provided with protection as approved by the fire code official. 6. In building or suite provided with a fire alarm system, fire detection system, or supervised sprinkler system, but lacks adequate occupant notification appliances, audio/visual devices shall be installed as required by NFPA 72 and SCF's fire alarm standard. The system has been designed per NFPA 72, IBC, IFC, NEC and your current codes & standards. A full pre -test and NFPA form shall be conducted and completed prior to calling the AHJ for acceptance testing. INSTALLATION COMPANY Fire Protection, Inc. 17410 Ash Way, Ste8 Lynnwood, WA 98032 WSCL# FIREPI*021ML UL CERT #608242-002 PROJECT LOCATION TR International 22817 102dn PL W Edmonds, WA 98020 CONTRACTUAL RESPONSIBLE PARTIES. Fire Protection, Inc.: Design, Permitting, Equipment, & Testing Evergreen Power Systems Inc: Electrical & Equipment Installation. AMBIENT TEMPERATURES No area with alarm service equipment shall fall below 40 degrees, common areas shall be at 68 degrees per builder SEQUENCE OF OPERATIONS All Alarm and Trouble conditions shall enunciate at FACP as well as remote notify listed Central Station. Zones of alarm shall cause for all notification circuits to activate and send an alarm zone to CS and re - dispatch to Fire Service. Trouble and supervisory signals shall transmit to CS, (no notification circuits shall activate.) Opens on any zones shall cause for a trouble signal. Should you have any further questions, please feel free to contact me directly. David Mow, SET NICET IV #120904 L&I # MOW*DDE957M6/MOW**D*983RF V.P. of Operations/Designer of Record