SPECIAL INSPECTIONS COMBINEDWELDING OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7181143.0009 Service Date: 12/07/18 Report Date: 12/12/18 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Client Project HWA GeoSciences Inc City of Edmonds Five Corners Reservoir Attn: Steven Greene 8519 Bowdoin Way 21312 30th Drive SE Edmonds, WA Ste 110 Bothell, WA 98021 Project No.: M7181143 Permit No.: BLD20171768 Weather: Sunny Samples: N/A Inspected fit -up, backing, groove angle, and root openings for welding back the access plate previously removed at the 1.5M gallon water tank. Inspection was per welding requirements outlined in RFI #9. The fit -up for the horizontal weld at top and vertical welds at each side of the plate were found to be in accordance with RFI #9 and AWS D-1.1 Welding Code. Preliminary Item. The bevel for the bottom horizontal weld where the plate is double thickness (reinforcing the access hatch) was not made deep enough. Requested further preparation of bevel to provide full depth bevel down to the backing plate as required for a single bevel groove weld with backing pre -qualified weld in AWS D- 1.1 Welding Code. Arranged for further inspection to review above correction. PRELIMINARY INSPECTION Pending review of above -noted correction. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Thomas Cain Reported to: HWA Geosciences Contractor: HWA Geosciences Report Distribution: (1) HWA GeoSciences Inc, Steven (1) City of Edmonds WA, Leif Bjorback Greene (1) Mayes Testing Engineers, Inc, (1) Redside Construction LLC, Andrew Todd Wirtz Evans Reviewed By: �r-�� Robert Gardner Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 10-16-13, Rev.10 Page 1 of 1 WELDING OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7181143.0010 Service Date: 12/10/18 Report Date: 12/17/18 20225 Cedar Vallev Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Client Project HWA GeoSciences Inc City of Edmonds Five Corners Reservoir Attn: Steven Greene 8519 Bowdoin Way 21312 30th Drive SE Edmonds, WA Ste 110 Bothell, WA 98021 Project No.: M7181143 Permit No.: BLD2017-1768 Weather: Sunny Samples: N/A Inspected fit -up, backing, groove angle, and root openings for welding back the access plate previously removed at the 1.5M gallon water tank. Inspection was per welding requirements outlined in RFI #9. Returned to site to re -inspect complete joint penetration (CJP) weld fit -up for the access plate re -installation bottom horizontal weld where the plate is double thickness reinforced at the access hatch. The fit -up for this weld location was found to be in accordance with RFI #9 and AWS D-1.1 Welding Code. Also, inspected work in progress on initial root weld passes and backing plate welds. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Thomas Cain Reported to: HWA Geosciences Contractor: HWA Geosciences Report Distribution: (1) HWA GeoSciences Inc, Steven (1) City of Edmonds WA, Leif Bjorback Greene (1) Mayes Testing Engineers, Inc, (1) Redside Construction LLC, Andrew Todd Wirtz Evans Reviewed By: �r-�� Robert Gardner Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 10-16-13, Rev.10 Page 1 of 1 WELDING OBSERVATION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7181143.0011 Service Date: 12/13/18 Report Date: 12/17/18 Client HWA GeoSciences Inc Attn: Steven Greene 21312 30th Drive SE Ste 110 Bothell. WA 98021 Permit No.: BLD2017-1768 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project City of Edmonds Five Corners Reservoir 8519 Bowdoin Way Edmonds, WA Project No. Weather: M7181143 Clouds Visually inspected conditions of tank closure plate on 1.5-million-gallon tank prior to ultrasonic examination of complete joint penetration (CJP) welds scheduled for 12/14/18. Contractor was instructed to grind paint 4" on both sides of weld for UT testing. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Carl Reynolds Reported to: HWA Geosciences Contractor: HWA Geosciences Report Distribution: (1) HWA GeoSciences Inc, Steven (1) City of Edmonds WA, Leif Bjorback Greene (1) Mayes Testing Engineers, Inc, (1) Redside Construction LLC, Andrew Todd Wirtz Evans Reviewed By: �r-�� Robert Gardner Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 10-16-13, Rev.10 Page 1 of 1 STRUCTURAL STEEL OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7181143.0013 Service Date: 02/08/19 Report Date: 02/15/19 Client HWA GeoSciences Inc Attn: Steven Greene 21312 30th Drive SE Ste 110 Bothell. WA 98021 Permit No.: BLD20171768 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project City of Edmonds Five Corners Reservoir 8519 Bowdoin Way Edmonds, WA Project No. Weather: M7181143 Cloudy On site for inspection of welds on 3-million-gallon water storage tank handrail connection at top of tank, per detail D on S-5, and a total of (4) painters lugs per detail 2 on M-3. Found welds visually acceptable per AWS D1.1 acceptance criteria. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: David Schmutzler Reported to: HWA Geosciences Contractor: HWA Geosciences Report Distribution: (1) HWA GeoSciences Inc, Steven (1) City of Edmonds WA, Leif Bjorback Greene (1) Mayes Testing Engineers, Inc, (1) Redside Construction LLC, Andrew Todd Wirtz Evans Reviewed By: �r-�� Robert Gardner Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 10-16-13, Rev.10 Page 1 of 1 STRUCTURAL STEEL OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7181143.0014 Service Date: 03/22/19 Report Date: 03/27/19 Client HWA GeoSciences Inc Attn: Steven Greene 21312 30th Drive SE Ste 110 Bothell. WA 98021 Permit No.: BLD20171768 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project City of Edmonds Five Corners Reservoir 8519 Bowdoin Way Edmonds, WA Project No. Weather: M7181143 Clear On site for structural steel welding inspection in accordance with AWS D1.1 specifications. Inspected 3.0 MG tank at the following locations: 1) Internal support brackets per 3/CP-1 drawing, (6) brackets total acceptable. 2) Pipe support brackets, internal welds per 2/M-2 drawing for pipe overflow. 3) External pipe support brackets and pipe welds per 1/M-2 drawing. Brackets started near roof top to bottom drain. 4) 10" floor drain cover plate. 5) 6" sample port pipe inside has approximately 1" of weld missing at flange to pipe connection at the 5- o'clock position. Welder is aware of re -work. 6) 6" sample port pipe outside has doubler plates and pipe welds found acceptable. Verified stainless steel bolts have been installed at internal pipe support brackets per 2/M-2 drawing as required. Item 4 is Preliminary pending verification of completed work. PRELIMINARY INSPECTION Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Mark Vassallo Reported to: HWA Geosciences Contractor: HWA Geosciences Report Distribution: (1) HWA GeoSciences Inc, Steven (1) City of Edmonds WA, Leif Bjorback Greene (1) Mayes Testing Engineers, Inc, (1) Redside Construction LLC, Andrew Todd Wirtz Evans Reviewed By: (dee-, Michael S. Dolder, PE Senior Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 10-16-13, Rev.10 Page 1 of 1 STRUCTURAL STEEL OBSERVATIONS REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7181143.0014 Service Date: 03/22/19 Report Date: 03/29/19 Revision 1 - Incorrect item number Client HWA GeoSciences Inc Attn: Steven Greene 21312 30th Drive SE Ste 110 Bothell. WA 98021 Permit No.: BLD20171768 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project City of Edmonds Five Corners Reservoir 8519 Bowdoin Way Edmonds, WA Project No. Weather: M7181143 Clear On site for structural steel welding inspection in accordance with AWS D1.1 specifications. Inspected 3.0 MG tank at the following locations: 1) Internal support brackets per 3/CP-1 drawing, (6) brackets total acceptable. 2) Pipe support brackets, internal welds per 2/M-2 drawing for pipe overflow. 3) External pipe support brackets and pipe welds per 1/M-2 drawing. Brackets started near roof top to bottom drain. 4) 10" floor drain cover plate. 5) 6" sample port pipe inside has approximately 1" of weld missing at flange to pipe connection at the 5- o'clock position. Welder is aware of re -work. 6) 6" sample port pipe outside has doubler plates and pipe welds found acceptable. Verified stainless steel bolts have been installed at internal pipe support brackets per 2/M-2 drawing as required. Item 5 is preliminary pending verification of completed work. PRELIMINARY INSPECTION Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Mark Vassallo Reported to: HWA Geosciences Contractor: HWA Geosciences Report Distribution: (1) HWA GeoSciences Inc, Steven (1) City of Edmonds WA, Leif Bjorback Greene (1) Mayes Testing Engineers, Inc, (1) Redside Construction LLC, Andrew Reviewed By Todd Wirtz Evans Terry Deroor Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 10-16-13, Rev.10 Page 1 of 1 NDE: ULTRASONIC TESTING INSPECTION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7181143.0016 Service Date: 04/16/19 Report Date: 04/22/19 Client HWA GeoSciences Inc Attn: Steven Greene 21312 30th Drive SE Ste 110 Bothell. WA 98021 Permit No.: BLD20171768 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project City of Edmonds Five Corners Reservoir 8519 Bowdoin Way Edmonds, WA Project No. Weather: M7181143 Clouds Performed ultrasonic examination (UT) of complete joint penetration (CJP) welds on 3-million-gallon tank panel. Welding was completed by WABO certified welders and conformed to AWS D1.1 visual and UT acceptance criteria and contract documents. See attached UT report for additional information. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Carl Reynolds Reported to: HWA Geosciences Contractor: HWA Geosciences Report Distribution: (1) HWA GeoSciences Inc, Steven (1) City of Edmonds WA, Leif Bjorback Greene (1) Mayes Testing Engineers, Inc, (1) Redside Construction LLC, Andrew Reviewed By Todd Wirtz Evans Terry Deroor Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 10-16-13, Rev.10 Page 1 of 1 AYE TESTINGEYOGAfEGMLAIC. 20225 Cedar Valley Road, Suite 110 P 425.742.9360 Lynnwood, WA 98036 F 425.745.1737 10029 S. Tacoma Way,Suite E-2 P 253.584.3720 Tacoma, WA 98499 F 253.584.3707 7911 NE 33rd Drive, Suite 190 P 503.281.7515 Portland, OR 97211 F 503.281.7579 Specification: AWS D1.1 Project No. Project UT Equipment: Long. Transducer: Model USM GO+ Freq.: 2.25 Serial No. GOPLS15070215 Size: 1" Page 1 of Ultrasonic Examination Report M7181143 Date: 4/16/19 Citv of Edmonds Five Corners Reservoir Weld Process ❑ SMAW Shear Transducer: Freq.: 2.25 Size: .625x.625 1 ❑� FCAW ❑ GMAW ❑ SAW Calibration Block: ❑� IIW ❑ DSC Other: Location Weld L Q E 7 O •<6 u N IF Decibels Discontinuity G CD Q m W Remarks 01 C Q L V 7 Vl ' J O _ M V = a d J V L y N b d i J O R 7 C r Q c rn <6 LY C 0 V 2 � d Sound Path Length Depth Distance X Y Top UP 70 68 X Bottom UP 70 68 X Left UP 70 68 X Right UP 70 68 X Inspector: C. Revnolds Level: MTE 1521-2C, Rev 1, 9/16/09 NDE: ULTRASONIC TESTING INSPECTION REPORT MAYES TESTING ENGINEERS nlrerracan cmernxv Report Number: M7181143.0012 Service Date: 12/14/18 Report Date: 12/20/18 Client HWA GeoSciences Inc Attn: Steven Greene 21312 30th Drive SE Ste 110 Bothell. WA 98021 Permit No.: BLD20171768 Samples: N/A 20225 Cedar Valley Rd Ste 110 Lynnwood, WA 98036-6365 425-742-9360 Project City of Edmonds Five Corners Reservoir 8519 Bowdoin Way Edmonds, WA Project No. Weather: M7181143 Overcast On site for ultrasonic testing (UT) of complete penetration welds in accordance with AWS D1.1 specifications. Inspected a 9'x12' insert plate on a 1.5-million-gallon water tank. Insert located at the NE side of the tank. Also inspected a flange cover plate for a 2' manhole located at the NW side of the tank. Both welds found acceptable to Code. See attached UT Report for data. To the best of our knowledge, the items inspected today are in conformance with approved plans and specifications. Services: Special Inspections / Materials Testing Mayes/Terracon Rep.: Mark Vassallo Reported to: HWA Geosciences Contractor: HWA Geosciences Report Distribution: (1) HWA GeoSciences Inc, Steven (1) City of Edmonds WA, Leif Bjorback Greene (1) Mayes Testing Engineers, Inc, (1) Redside Construction LLC, Andrew Todd Wirtz Evans Reviewed By: �r-�� Robert Gardner Senior Project Field Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CT0001, 10-16-13, Rev.10 Page 1 of 1 MAYES TESTING ENGINEERS Page 1 of 1 �1rm,�,r�wa my Ultrasonic Examination Report 20225 Cedar Valley Road, Suite P 425.742.9360 110 Lynnwood, WA 98036 F 425.745.1737 10029 S. Tacoma Way,Suite E-2 P 253.584.3720 Project No. M7181143 Date: 12/14/18 Tacoma, WA 98499 F 253.584.3707 Project City of Edmonds Five Corners Reservoir 7911 NE 33rd Drive, Suite 190 P 503.281.7515 Portland, OR 97211 F 503.281.7579 Specification: AWS D1.1 UT Equipment: Transducer: Model USMGO+ Freq.: 2.25 Serial No. GOPLS13120023 Size: 5/8x5/8 Weld Process ❑ SMAW Method: ❑ Long 0 Shear Other: 0 FCAW ❑ GMAW ❑ SAW Calibration Block: 0 IIW ❑ DSC Other: Location Weld E 7 Z O lC S O1 Q N Decibels Discontinuity Q a V Remarks > J O a > J G1 b d > J c O 0 w Q c rn f0 tY C O 'O d Sound I Path Length Depth Distance X Y CP 70 67 X 9'x12' Insert CID 70 67 X 2' Manhole Cover Inspector: Mark Vassallo Level: MTE 1521-2C, Rev 1, 9/16/09