Preliminary TAB_10.25.18Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-01(info) AREA: ORCHESTRA 123 Unit Data Unit Manufacturer D-AIRTECH Unit Model Number D-AHU 2 Unit Serial Number D-18-002 AHU-01(info)/SF Filter Bank Filter Type Pleated Filter Quantity - Size 1 1 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 1 Filter Dimensions - Size 2 12x24x4 Filter Quantity - Size 3 1 Filter Dimensions - Size 3 12x24x2 Filter Quantity - Size 4 1 Filter Dimensions - Size 4 24x24x2 Test Data Total Design Flow 1500 CFM CA Design Flow 900 CFM AHU-01(info) Supply Outlet Summary Tested By: Dwight Hammack Date: 9/24/2018 Motor Data AHU-01(info)/Supply Fan Motor HP 1-1.08 HP Motor Phase 3 Motor Hertz 60 Hz Test Pressures SF Design External SP 1.6 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 ORCHESTRA Flowhood C 101, 1.0 225 123 Outlet-02 ORCHESTRA Flowhood C 12" 1.0 225 123 Outlet-03 ORCHESTRA Flowhood C 101, 1.0 175 123 Outlet-04 ORCHESTRA Flowhood C 101, 1.0 175 123 Outlet-05 ORCHESTRA Flowhood C 101, 1.0 175 123 Outlet-06 ORCHESTRA Flowhood C 101, 1.0 175 123 Outlet-07 ORCHESTRA Flowhood C 101, 1.0 175 123 Outlet-08 ORCHESTRA Flowhood C 10" 1.0 175 123 Totals: - 1500 0 0 0 Neudorfer Engineers, Inc. Page 1 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-02(info) AREA: BAND 121 Unit Data Unit Manufacturer D-AIRTECH Unit Model Number D-AHU 2 Unit Serial Number D-18-003 AHU-02(info)/SF Filter Bank Filter Type Pleated Filter Quantity - Size 1 1 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 1 Filter Dimensions - Size 2 12x24x4 Filter Quantity - Size 3 1 Filter Dimensions - Size 3 12x24x2 Filter Quantity - Size 4 1 Filter Dimensions - Size 4 24x24x2 Test Data Total Design Flow 1500 CFM OA Design Flow 900 CFM AHU-02(info) Supply Outlet Summary Tested By: Dwight Hammack Date: 9/24/2018 Motor Data AHU-02(info)/Supply Fan Motor HP 1-1.08 HP Motor Phase 3 Motor Hertz 60 Hz Test Pressures SF Design External SP 1.6 in. we System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 BAND 121 Flowhood C 101, 1.0 225 Outlet-02 BAND 121 Flowhood C 101, 1.0 225 Outlet-03 BAND 121 Flowhood C 101, 1.0 175 Outlet-04 BAND 121 Flowhood C 101, 1.0 175 Outlet-05 BAND 121 Flowhood C 101, 1.0 175 Outlet-06 BAND 121 Flowhood C 101, 1.0 175 Outlet-07 BAND 121 Flowhood C 101, 1.0 175 Outlet-08 BAND 121 Flowhood C 101, 1.0 175 Totals: - - - - - 1500 0 0 0 - Neudorfer Engineers, Inc. Page 2 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-03(info) AREA: KITCHEN 117 Unit Data Unit Manufacturer D-AIRTECH Unit Model Number D-AHU 2 Unit Serial Number D-18-004 Unit Discharge Top Horizontal AHU-03(info)/SF Filter Bank Filter Type Pleated Filter Quantity - Size 1 1 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 1 Filter Dimensions - Size 2 12x24x4 Filter Quantity - Size 3 1 Filter Dimensions - Size 3 24x24x2 Filter Quantity - Size 4 1 Filter Dimensions - Size 4 12x24x2 Test Data Total Design Flow 1500 CFM Total Actual Flow 1565 CFM OA Design Flow 780 CFM RA Design Flow 1500 CFM EA Design Flow 1500 CFM EA Actual Flow 1493 CFM AHU-03(info) Supply Outlet Summary Tested By: Dwight Hammack Date: 10/24/2018 Motor Data AHU-03(info)/Return/Relief fan Motor HP 1-0.665 HP Motor Phase 3 Motor Hertz 60 Hz AHU-03(info)/Supoly Fan Motor HP 1.1.08 HP Motor Phase 3 Motor Hertz 60 Hz Test Pressures SF Design External SP 1.6 in. we RF Design External SP 1.5 in. we System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 KITCHEN 117 Flowhood A 101, 1.0 300 269 312 104 (1) Outlet-02 KITCHEN 117 Flowhood A 101, 1.0 300 263 305 102 Outlet-03 KITCHEN 117 Flowhood A 101, 1.0 300 278 324 108 Outlet-04 KITCHEN 117 Flowhood A 101, 1.0 300 271 314 105 Outlet-05 KITCHEN 117 Flowhood A 10" 1.0 300 267 310 103 Totals: - - - - I - 1 1500 1348 1565 104 - AHU-03(info) Return Inlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Inlet-01 KITCHEN Flowhood RG 24x24 1.0 1500 1387 1493 100 Totals: - - 1500 1387 1493 100 Neudorfer Engineers, Inc. Page 3 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-04(info) AREA: MUSIC 122 Unit Data Unit Manufacturer D-AIRTECH Unit Model Number D-AHU 2 Unit Serial Number D-18-005 AHU-04(info)/SF Filter Bank Filter Type Pleated Filter Quantity - Size 1 1 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 1 Filter Dimensions - Size 2 12x24x4 Filter Quantity - Size 3 1 Filter Dimensions - Size 3 12x24x2 Filter Quantity - Size 4 1 Filter Dimensions - Size 4 24x24x2 Test Data Total Design Flow 1800 CFM OA Design Flow 1080 CFM AHU-04(info) Supply Outlet Summary Tested By: Dwight Hammack Date: 9/24/2018 Motor Data AHU-04(info)/Supply Fan Motor HP 1-1.22 HP Motor Phase 3 Motor Hertz 60 Hz Test Pressures SF Design External SP 1.6 in. we System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 MUSIC 122 Flowhood C 12" 1.0 360 Outlet-02 MUSIC 122 Flowhood C 12" 1.0 360 Outlet-03 MUSIC 122 Flowhood C 12" 1.0 360 Outlet-04 MUSIC 122 Flowhood C 12" 1.0 360 Outlet-05 MUSIC 122 Flowhood C 12" 1.0 360 Totals: - - - I - 1 1800 0 0 1 0 AHU-04(info) Return Inlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Inlet-01 MUSIC Flowhood 1.0 Totals: - - 0 0 1 0 1 0 Neudorfer Engineers, Inc. Page 4 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-05(info) AREA: COMMONS 115/SERVERY 115A Unit Data Unit Manufacturer D-AIRTECH Unit Model Number D-AHU 6 Unit Serial Number D-18-006 Fan Rotation Counterclockwise AHU-05(info)/SF Filter Bank Filter Type Pleated Filter Quantity - Size 1 4 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 4 Filter Dimensions - Size 2 24x24x2 Filter Quantity - Size 3 2 Filter Dimensions - Size 3 12x24x2 Filter Quantity - Size 4 2 Filter Dimensions - Size 4 12x24x4 Test Data Total Design Flow 5800 CFM CA Design Flow 3480 CFM Tested By: Dwight Hammack Date: 9/24/2018 Motor Data AHU-05(info)/Supply Fan Drive Type Direct Drive Motor Manufacturer Rosenberg Motor HP (2)4.42 HP Motor RPM 2636 RPM Motor Rated Volts 480 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps (2)4.4 Amps Test Pressures SF Design External SP 1.8 in. we Neudorfer Engineers, Inc. Page 5 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: AHU-05(info) Supply Outlet Summary System/Unit Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 Flowhood C 101, 1.0 210 Outlet-02 Flowhood C 101, 1.0 210 Outlet-03 Flowhood C 101, 1.0 210 Outlet-04 Flowhood C 101, 1.0 210 Outlet-05 Flowhood C 101, 1.0 210 Outlet-06 Flowhood C 101, 1.0 210 Outlet-07 Flowhood C 101, 1.0 210 Outlet-08 Flowhood K 101, 1.0 180 Outlet-09 Flowhood K 101, 1.0 180 Outlet-10 Flowhood K 101, 1.0 180 Outlet-11 Flowhood K 101, 1.0 180 Outlet-12 Flowhood K 101, 1.0 180 Outlet-13 Flowhood K 101, 1.0 180 Outlet-14 Flowhood K 101, 1.0 180 Outlet-15 Flowhood K 101, 1.0 180 Outlet-16 Flowhood K 101, 1.0 180 Outlet-17 Flowhood K 101, 1.0 180 Outlet-18 Flowhood K 101, 1.0 180 Outlet-19 Flowhood K 101, 1.0 180 Outlet-20 Flowhood K 101, 1.0 185 Outlet-21 Flowhood K 101, 1.0 185 Outlet-22 Flowhood K 101, 1.0 180 Outlet-23 Flowhood K 101, 1.0 180 Outlet-24 Flowhood K 101, 1.0 180 Outlet-25 Flowhood K 101, 1.0 180 Outlet-26 Flowhood K 101, 1.0 180 Outlet-27 Flowhood K 101, 1.0 180 Outlet-28 Flowhood K 10" 1.0 180 Outlet-29 Flowhood K 101, 1.0 180 Outlet-30 Flowhood K 101, 1.0 180 Outlet-31 Flowhood K 101, 1.0 180 - - 5800 0 0 0 - Neudorfer Engineers, Inc. Page 6 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-06(info) AREA: HALLWAY COMMONS 100C Unit Data Unit Manufacturer D-AIRTECH Unit Model Number D-AHU 2 Unit Serial Number D-18-007 Fan Rotation Counterclockwise AHU-06(info)/SF Filter Bank Filter Type Pleated Filter Quantity - Size 1 1 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 1 Filter Dimensions - Size 2 12x24x4 Filter Quantity - Size 3 1 Filter Dimensions - Size 3 12x24x2 Filter Quantity - Size 4 1 Filter Dimensions - Size 4 24x24x2 Test Data Total Design Flow 1900 CFM CA Design Flow 1140 CFM Tested By: Dwight Hammack Date: 9/24/2018 Motor Data AHU-06(info)/Supply Fan Drive Type Direct Drive Motor Manufacturer Rosenberg Motor HP 2.3 HP Motor RPM 2202 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 2.3 Amps Test Pressures SF Design External SP 1.8 in. we Neudorfer Engineers, Inc. Page 7 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: AHU-06(info) Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 HALLWAY Flowhood K 10" 1.0 190 COMMONS 100C Outlet-02 HALLWAY Flowhood K 10" 1.0 190 COMMONS 100C Outlet-03 HALLWAY Flowhood K 10" 1.0 190 COMMONS 100C Outlet-04 HALLWAY Flowhood K 101, 1.0 190 COMMONS 100C Outlet-05 HALLWAY Flowhood K 101, 1.0 190 COMMONS 100C Outlet-06 HALLWAY Flowhood K 101, 1.0 190 COMMONS 100C Outlet-07 HALLWAY Flowhood K 101, 1.0 190 COMMONS 100C Outlet-08 HALLWAY Flowhood K 101, 1.0 190 COMMONS 100C Outlet-09 HALLWAY Flowhood K 101, 1.0 190 COMMONS 100C Outlet-10 HALLWAY Flowhood K 101, 1.0 190 COMMONS 100C Totals: - - - - 1900 0 1 0 0 AHU-06(info) Return Inlet Summary System/Unit Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Readin Final % Remarks Inlet-01 Flowhood E 24X24 1.0 950 Inlet-02 Flowhood E 24X24 1.0 950 - - - 1900 0 0 0 Neudorfer Engineers, Inc. Page 8 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-07(info) AREA: GYMNASIUM 107 Unit Data Unit Manufacturer D-AIRTECH Unit Model Number D-AHU 12 Unit Serial Number D-18-008 AHU-07(info)/SF Filter Bank Filter Type Pleated Filter Quantity - Size 1 6 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 6 Filter Dimensions - Size 2 24x24x2 Filter Quantity - Size 3 3 Filter Dimensions - Size 3 12x24x2 Filter Quantity - Size 4 3 Filter Dimensions - Size 4 12x24x4 Test Data Total Design Flow 11400 CFM OA Design Flow 6840 CFM AHU-07(info) Supply Outlet Summary Tested By: Dwight Hammack Date: 9/24/2018 Motor Data AHU-07(info)/Supply Fan Motor HP (4)4.42 HP Motor RPM 2671 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps (4)4.4 Amps Test Pressures SF Design External SP 2.1 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 GYMNASIM C 32" 1.0 5700 107 (DUCT Outlet-02 GYMNASIM C 32" 1.0 5700 107 (DUCT Totals: - - - - - 11400 1 0 0 0 - Neudorfer Engineers, Inc. Page 9 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info) AREA: ADMIN WING Unit Data Unit Manufacturer D-AIRTECH Unit Model Number D-AHU-12 Unit Serial Number D-18-009 Unit Discharge Top Vertical Fan Rotation Counterclockwise AHU-08(info)/SF Filter Bank Filter Manufacturer Flanders Filter Type Pleated Filter Quantity - Size 1 6 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 12x24x2 Filter Quantity - Size 3 6 Filter Dimensions - Size 3 24x24x4 Filter Quantity - Size 4 3 Filter Dimensions - Size 4 12x24x4 Test Data Total Design Flow 11095 CFM CA Design Flow 6660 CFM RA Design Flow 11095 CFM Tested By: Dwight Hammack Date: 8/9/2018 Motor Data AHU-08(info)/RA/EF Drive Type Direct Drive Motor Manufacturer Rosenberg Motor HP 4.83x2 HP Motor RPM 1600 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 4.6x2 Amps AHU-08(info)/Supoly Fan Drive Type Direct Drive Motor Manufacturer Rosenberg Motor HP 4.42x4 HP Motor RPM 2789 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 4.4x4 Amps Test Pressures SF Design External SP 2.5 in. we RF Design External SP 1.8 in. we Neudorfer Engineers, Inc. Page 10 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: AHU-08(info) Return Inlet Summary System/Unit Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Readin Final % Remarks Inlet-01 Flowhood E 24X12 1.0 360 Inlet-02 Flowhood E 24X24 1.0 930 Inlet-03 Flowhood E 24X24 1.0 730 Inlet-04 Flowhood E 24X12 1.0 355 Inlet-05 Flowhood E 24X24 1.0 500 Inlet-06 Flowhood E 24X12 1.0 295 Inlet-07 Flowhood 1.0 210 Inlet-08 Flowhood E 24X12 1.0 210 Inlet-09 Flowhood E 24X12 1.0 325 Inlet-10 Flowhood E 24X12 1.0 325 Inlet-11 Flowhood E 24X12 1.0 50 Inlet-12 Flowhood E 24X12 1.0 285 Inlet-13 Flowhood E 24X12 1.0 110 Inlet-14 Flowhood E 24X12 1.0 260 Inlet-15 Flowhood E 24X12 1.0 330 Inlet-16 Flowhood E 24X12 1.0 165 Inlet-17 Flowhood E 24X24 1.0 1110 Inlet-18 Flowhood E 24X12 1.0 155 Inlet-19 Flowhood E 24X24 1.0 700 Inlet-20 Flowhood E 24X24 1.0 700 Inlet-21 Flowhood E 24X24 1.0 450 Inlet-22 Flowhood E 24X12 1.0 150 Inlet-23 Flowhood E 24X12 1.0 150 Inlet-24 Flowhood E 24X12 1.0 135 Inlet-25 Flowhood E 24X12 1.0 420 - - 9410 0 0 0 SYSTEM/UNIT: AHU-08(info)/VAV-146 AREA: DEN 104 Unit Data Manufacturer Price Model Number SDV5 Cooling Inlet Size 14 inches AHU-08(info)/VAV-146 Supply Outlet Summary Tested By: Dwight Hammack Date: 9/27/2018 Air Test Data Clg Max Des. Primary Flow 1260 CFM Clg Min Des. Primary Flow 380 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 DEN Flowhood A 12" 1.0 315 Outlet-02 DEN Flowhood A 12" 1.0 315 Outlet-03 DEN Flowhood A 12" 1.0 315 Outlet-04 DEN Flowhood A 12" 1.0 315 Totals: I - - I - - 1260 0 1 0 0 Neudorfer Engineers, Inc. Page 11 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-147 AREA: COUNSELOR 103 Unit Data Manufacturer Price Model Number SDV5 VAV Address 22 Application # 2021 Cooling Inlet Size 5 inches Cooling K Factor 351.00 Tested By: Dwight Hammack Date: 9/27/2018 Air Test Data Clg Max Des. Primary Flow 155 CFM Clg Min Des. Primary Flow 45 CFM Clg Max Act. Primary Flow 160 CFM Clg Min Act. Primary Flow 45 CFM Log: I AHU-08(info)NAV-147 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-147 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 COUNSELOR Flowhood A 8" 1.0 155 205 160 103 1 1 (1) Totals: - - - 155 205 160 103 1 - SYSTEM/UNIT: AHU-08(info)/VAV-148 AREA: SMALL GROUP 102A Unit Data Manufacturer Price Model Number SDV5 VAV Address 20 Application # 2021 Cooling Inlet Size 5 inches Cooling K Factor 324.00 Tested By: Dwight Hammack Date: 9/26/2018 Air Test Data Clg Max Des. Primary Flow 165 CFM Clg Min Des. Primary Flow 50 CFM Clg Max Act. Primary Flow 170 CFM Clg Min Act. Primary Flow 50 CFM Log: I AHU-08(info)NAV-148 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-148 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 SMALL Flowhood A 8" 1.0 165 205 170 103 (1) GROUP Totals: - - - 165 205 170 103 Neudorfer Engineers, Inc. Page 12 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-149 AREA: SMALL GROUP 102B Unit Data Manufacturer Price Model Number SDV5 VAV Address 19 Application # 2021 Cooling Inlet Size 7 inches Cooling K Factor 478.00 Tested By: Dwight Hammack Date: 9/27/2018 Air Test Data Clg Max Des. Primary Flow 330 CFM Clg Min Des. Primary Flow 100 CFM Clg Max Act. Primary Flow 340 CFM Clg Min Act. Primary Flow 100 CFM Log: I AHU-08(info)NAV-149 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-149 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 SMALL Flowhood A 12" 1.0 330 205 340 103 (1) GROUP Totals: - - - 330 205 340 103 - SYSTEM/UNIT: AHU-08(info)/VAV-150 AREA: LEARENING SUPPORT 102 Unit Data Manufacturer Price Model Number SDV5 VAV Address 18 Application # 2021 Cooling Inlet Size 14 inches Cooling K Factor 2050.00 Tested By: Dwight Hammack Date: 9/26/2018 Air Test Data Clg Max Des. Primary Flow 1400 CFM Clg Min Des. Primary Flow 420 CFM Clg Max Act. Primary Flow 1415 CFM Clg Min Act. Primary Flow 420 CFM Log: I AHU-08(info)NAV-150 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-150 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 LEARNING Flowhood A 12" 1.0 350 305 350 100 SUPPORT Outlet-02 LEARNING Flowhood A 12" 1.0 350 280 345 99 SUPPORT Outlet-03 LEARNING Flowhood A 12" 1.0 350 290 360 103 SUPPORT Outlet-04 LEARNING Flowhood A 12" 1.0 350 210 360 103 (1) SUPPORT Totals: - 1400 1085 1415 101 - Neudorfer Engineers, Inc. Page 13 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-151 AREA: LOBBY 100A Unit Data Manufacturer NAILOR Cooling Inlet Size 9 inches AHU-08(info)/VAV-151 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 450 CFM Clg Min Des. Primary Flow 135 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LOBBY Flowhood K 10" 1.0 225 Outlet-02 LOBBY Flowhood K 112" 1.0 225 Totals: - - - - 450 0 0 0 SYSTEM/UNIT: AHU-08(info)/VAV-152 AREA: RECEPTION OFFICE 101 Unit Data Manufacturer Price Model Number SDV5 VAV Address 15 Application # 2021 Cooling Inlet Size 14 inches Cooling K Factor 2241.00 Tested By: Dwight Hammack Date: 9/26/2018 Air Test Data Clg Max Des. Primary Flow 1230 CFM Clg Min Des. Primary Flow 370 CFM Clg Max Act. Primary Flow 1215 CFM Clg Min Act. Primary Flow 370 CFM Log: I AHU-08(info)NAV-152 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-152 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 RECEPTION Flowhood A 10" 1.0 305 210 310 102 (1) OFFICE Outlet-02 RECEPTION Flowhood A 101, 1.0 310 240 305 98 OFFICE Outlet-03 RECEPTION Flowhood A 101, 1.0 305 210 300 98 OFFICE Outlet-04 RECEPTION Flowhood A 10" 1.0 310 235 300 97 OFFICE Totals: - - - - - 1230 895 1215 99 - Neudorfer Engineers, Inc. Page 14 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-153 AREA: CONFERENCE 101A Unit Data Manufacturer Price Model Number SDV5 VAV Address 16 Application # 2021 Cooling Inlet Size 8 inches Cooling K Factor 451.00 Tested By: Dwight Hammack Date: 9/27/2018 Air Test Data Clg Max Des. Primary Flow 360 CFM Clg Min Des. Primary Flow 110 CFM Clg Max Act. Primary Flow 345 CFM Clg Min Act. Primary Flow 110 CFM Log: I AHU-08(info)NAV-153 9/26/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-153 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 CONFERFENC Flowhood A 12" 1.0 360 265 345 96 (1) E Totals: - - - 360 265 345 96 - SYSTEM/UNIT: AHU-08(info)/VAV-154 AREA: HEALTH CLINIC 101B Unit Data Manufacturer Price Model Number SDV5 VAV Address 14 Application # 2021 Cooling Inlet Size 7 inches Cooling K Factor 438.00 Tested By: Dwight Hammack Date: 9/26/2018 Air Test Data Clg Max Des. Primary Flow 300 CFM Clg Min Des. Primary Flow 90 CFM Clg Max Act. Primary Flow 310 CFM Clg Min Act. Primary Flow 90 CFM Log: I AHU-08(info)NAV-154 9/26/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-154 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 HEALTH Flowhood A 10" 1.0 300 260 310 103 (1) CLINIC Totals: - - - 300 260 310 103 - Neudorfer Engineers, Inc. Page 15 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-155 AREA: COT ROOM 101 D Unit Data Manufacturer Price Model Number SDV5 VAV Address 13 Application # 2021 Cooling Inlet Size 8 inches Cooling K Factor 650.00 Tested By: Dwight Hammack Date: 10/1 /2018 Air Test Data Clg Max Des. Primary Flow 400 CFM Clg Min Des. Primary Flow 350 CFM Clg Max Act. Primary Flow 400 CFM Clg Min Act. Primary Flow 350 CFM Log: I AHU-08(info)NAV-155 10/1/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-155 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Readin Final Remarks Outlet-01 COT ROOM Flowhood A 12" 1.0 400 260 1 400 100 (1) Totals: - - - - 400 260 1 400 100 SYSTEM/UNIT: AHU-08(info)/VAV-156 AREA: OFFICE MGR 101C Unit Data Manufacturer Price Model Number SDV5 VAV Address 12 Application # 2021 Cooling Inlet Size 7 inches Cooling K Factor 468.00 Tested By: Dwight Hammack Date: 9/27/2018 Air Test Data Clg Max Des. Primary Flow 310 CFM Clg Min Des. Primary Flow 95 CFM Clg Max Act. Primary Flow 310 CFM Clg Min Act. Primary Flow 95 CFM Log: I AHU-08(info)NAV-156 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-156 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK I Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 OFFICE MGR Flowhood A 10" 1 1.0 310 195 310 100 (1) Totals: - - - I - - 310 195 310 100 - Neudorfer Engineers, Inc. Page 16 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-157 AREA: DEAN/RECORD STG 101 E/101 K Unit Data Manufacturer Price Model Number SDV5 VAV Address 11 Application # 2021 Cooling Inlet Size 10 inches Cooling K Factor 1048.00 Tested By: Dwight Hammack Date: 9/27/2018 Air Test Data Clg Max Des. Primary Flow 670 CFM Clg Min Des. Primary Flow 210 CFM Clg Max Act. Primary Flow 680 CFM Clg Min Act. Primary Flow 210 CFM Log: I AHU-08(info)NAV-157 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-157 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 DEN/RECORD Flowhood A 12" 1.0 350 275 360 103 (1) STG Outlet-02 DEN/RECORD Flowhood A 12" 1.0 320 250 320 100 STG Totals: - - - 670 1 525 1 680 1 101 SYSTEM/UNIT: AHU-08(info)/VAV-158 AREA: DHH OFFICES 101 N/101 L Unit Data Manufacturer Price Model Number SDV5 VAV Address 10 Application # 2021 Cooling Inlet Size 9 inches Cooling K Factor 674.00 Tested By: Dwight Hammack Date: 9/27/2018 Air Test Data Clg Max Des. Primary Flow 470 CFM Clg Min Des. Primary Flow 140 CFM Clg Max Act. Primary Flow 460 CFM Clg Min Act. Primary Flow 140 CFM Log: I AHU-08(info)NAV-158 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-158 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 DHH OFFICE Flowhood A 12" 1.0 235 145 230 98 Outlet-02 DHH OFFICE Flowhood A 12" 1.0 235 120 230 98 (1) Totals: - - 470 265 460 98 - Neudorfer Engineers, Inc. Page 17 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-159 AREA: AP OFFICE/DHH RECEPT 101R/101Q Unit Data Manufacturer Price Model Number SDV5 VAV Address 9 Application # 2021 Cooling Inlet Size 10 inches Cooling K Factor 1179.00 Tested By: Dwight Hammack Date: 9/27/2018 Air Test Data Clg Max Des. Primary Flow 675 CFM Clg Min Des. Primary Flow 300 CFM Clg Max Act. Primary Flow 645 CFM Clg Min Act. Primary Flow 300 CFM Log: I AHU-08(info)NAV-159 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-159 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 AP Flowhood A 12" 1.0 355 330 330 93 OFFICE/DHH RECPT Outlet-02 AP Flowhood A 10" 1.0 320 225 315 98 (1) OFFICE/DHH RECPT Totals: - - - - - 675 1 555 1 645 1 96 SYSTEM/UNIT: AHU-08(info)/VAV-160 AREA: P OFFICE 101S Unit Data Manufacturer Price Model Number SDV5 VAV Address 8 Application # 2021 Cooling Inlet Size 8 inches Cooling K Factor 467.00 Tested By: Dwight Hammack Date: 9/27/2018 Air Test Data Clg Max Des. Primary Flow 360 CFM Clg Min Des. Primary Flow 110 CFM Clg Max Act. Primary Flow 365 CFM Clg Min Act. Primary Flow 110 CFM Log: I AHU-08(info)NAV-160 9/27/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-160 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readinq Final Readin Final % Remarks Outlet-01 P OFFICE Flowhood A 12" 1.0 360 170 365 101 (1) Totals: - - 360 170 365 101 - Neudorfer Engineers, Inc. Page 18 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-161 AREA: WORK ROOM 101 M Unit Data Manufacturer Price Model Number SDV5 VAV Address 5 Application # 2021 Cooling Inlet Size 7 inches Cooling K Factor 479.00 Tested By: Dwight Hammack Date: 10/1/2018 Air Test Data Clg Max Des. Primary Flow 300 CFM Clg Min Des. Primary Flow 90 CFM Clg Max Act. Primary Flow 305 CFM Clg Min Act. Primary Flow 90 CFM Log: I AHU-08(info)NAV-161 10/1/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-161 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Readin Final Remarks Outlet-01 WORKROOM Flowhood A 10" 1.0 300 200 305 102 (1) Totals: - - - - 300 200 305 102 SYSTEM/UNIT: AHU-08(info)/VAV-162 AREA: STAFF OFFICE 101 P Unit Data Manufacturer Price Model Number SDV5 VAV Address 7 Application # 2021 Cooling Inlet Size 10 inches Cooling K Factor 1116.00 Tested By: Dwight Hammack Date: 10/1/2018 Air Test Data Clg Max Des. Primary Flow 650 CFM Clg Min Des. Primary Flow 400 CFM Clg Max Act. Primary Flow 655 CFM Clg Min Act. Primary Flow 400 CFM Log: I AHU-08(info)NAV-162 10/1/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-162 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 STAFF Flowhood A 12" 1.0 325 250 335 103 LOUNGE Outlet-02 STAFF Flowhood A 12" 1.0 325 240 320 98 (1) LOUNGE Totals: - 650 1 490 1 655 1 101 1 - Neudorfer Engineers, Inc. Page 19 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-163 AREA: PROF DEVELOPEMENT 101T Unit Data Manufacturer Price Model Number SDV5 Cooling Inlet Size 12 inches AHU-08(info)/VAV-163 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/1 /2018 Air Test Data Clg Max Des. Primary Flow 730 CFM Clg Min Des. Primary Flow 220 CFM Clg Min Act. Primary Flow 220 CFM System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 PROF Flowhood A 12" 1.0 365 DEVELOPMEN T Outlet-02 PROF Flowhood A 12" 1.0 365 DEVELOPMEN T Totals: - - - - - 730 0 1 0 0 SYSTEM/UNIT: AHU-08(info)/VAV-164 AREA: SLP 108 Unit Data Manufacturer Price Model Number SDV5 VAV Address 23 Application # 2021 Cooling Inlet Size 5 inches Cooling K Factor 390.00 Tested By: Dwight Hammack Date: 10/1 /2018 Air Test Data Clg Max Des. Primary Flow 150 CFM Clg Min Des. Primary Flow 45 CFM Clg Max Act. Primary Flow 145 CFM Clg Min Act. Primary Flow 45 CFM Log: I AHU-08(info)/VAV-164 10/1/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-164 Supply Outlet Summary System/Unit Area Served Type of Readin Outlet T e Size LxW / D AK Design Velocit Design Value Prelim Readin Final Final Final Remarks Outlet-01 SLP Flowhood A 8" 1.0 150 185 145 97 (1) Totals: - - 150 185 145 97 Neudorfer Engineers, Inc. Page 20 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-165 AREA: DHH PYCH/COUNS 109 Unit Data Manufacturer Price Model Number SDV5 VAV Address 24 Application # 2021 Cooling Inlet Size 5 inches Cooling K Factor 343.00 Tested By: Dwight Hammack Date: 10/1/2018 Air Test Data Clg Max Des. Primary Flow 145 CFM Clg Min Des. Primary Flow 45 CFM Clg Max Act. Primary Flow 155 CFM Clg Min Act. Primary Flow 45 CFM Log: I AHU-08(info)NAV-165 10/1/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-165 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 DHH Flowhood A 8" 1.0 145 205 155 107 (1) PYSCH/COUN S Totals: - - - - - 145 205 155 107 - SYSTEM/UNIT: AHU-08(info)/VAV-166 AREA: AUDIO/DHH SLP 110 Unit Data Manufacturer Price Model Number SDV5 VAV Address 25 Application # 2021 Cooling Inlet Size 5 inches Cooling K Factor 329.00 Tested By: Dwight Hammack Date: 10/1/2018 Air Test Data Clg Max Des. Primary Flow 135 CFM Clg Min Des. Primary Flow 40 CFM Clg Max Act. Primary Flow 140 CFM Clg Min Act. Primary Flow 40 CFM Log: I AHU-08(info)NAV-166 10/1/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-166 Supply Outlet Summary System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 AUDIO/DHH Flowhood A 8" 1.0 135 150 140 104 (1) SLP Totals: - - - - - 135 150 140 104 - Neudorfer Engineers, Inc. Page 21 of 93 Air Handling Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: AHU-08(info)/VAV-167 AREA: OT/PT 122 Unit Data Manufacturer Price Model Number SDV5 VAV Address 26 Application # 2021 Cooling Inlet Size 8 inches Cooling K Factor 650.00 Tested By: Dwight Hammack Date: 10/1 /2018 Air Test Data Clg Max Des. Primary Flow 420 CFM Clg Min Des. Primary Flow 125 CFM Clg Max Act. Primary Flow 445 CFM Clg Min Act. Primary Flow 125 CFM Log: I AHU-08(info)NAV-167 10/1/2018 Dwight Hammack (1) The volume damper is full open. AHU-08(info)/VAV-167 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 OT/PT Flowhood A 8" 1.0 210 130 225 107 (1) Outlet-02 OT/PT Flowhood A 8" 1.0 210 155 220 105 Totals: - - - - - 420 285 445 106 - Neudorfer Engineers, Inc. Page 22 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: EF-01 AREA: TYPE II KITCHEN HOOD Unit Data Fan Manufacturer Cook Fan Model Number 150 ACRUH Fan Serial Number 033SH28555 Fan Rotation Counterclockwise Fan Discharge Vertical Drive Type DIRECT Fan Speed 48% Test Data Total Design Flow 788 CFM Total Actual Flow 835 CFM Fan RPM Design 1593 RPM Fan RPM Actual 957 RPM Motor Volts T1-T2 120 Volts Motor Amps T1 1.00 Amps EF-01 Exhaust Inlet Summary Tested By: Dwight Hammack Date: 10/5/2018 Motor Data Motor Manufacturer US Motors Motor HP 1/2 HP Motor RPM 300-1800 RPM Motor Rated Volts 120/208-240 Volts Motor Phase 1 Motor Hertz 60 Hz Motor Full Load Amps 6.2/3.8-3.5 Amps Test Pressures Fan Suction SP -0.05 in. we Fan Discharge SP 0.00 in. we Design Total SP 1.30 in. we Actual Total SP 0.05 in. we System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim ReadingReadin Final Final % Remarks Inlet-01 KITCHEN Flowhood KITCHE 14" Rd 1.0 788 1590 835 106 N HOOD Totals: - - - 788 1590 835 106 Neudorfer Engineers, Inc. Page 23 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: EF-02 AREA: DISHWASSHER Unit Data Fan Manufacturer Cook Fan Model Number 101 ACRU Fan Serial Number 033SH28555 Fan Rotation Counterclockwise Fan Discharge Vertical Drive Type DIRECT Fan Speed Medium Test Data Total Design Flow 525 CFM Total Actual Flow 550 CFM Fan RPM Design 1419 RPM Fan RPM Actual 1031 RPM Motor Volts T1-T2 120 Volts Motor Amps T1 0.50 Amps EF-02 Exhaust Inlet Summary Tested By: Dwight Hammack Date: 10/5/2018 Motor Data Motor Manufacturer Cook Motor HP 1/4 HP Motor RPM 350-1725 RPM Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor Full Load Amps 3.40 Amps Test Pressures Fan Suction SP -0.21 in. we Fan Discharge SP 0.00 in. we Design Total SP 0.75 in. we Actual Total SP 0.21 in. we System/Unit Area Served Type of Readin Outlet T e Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Inlet-01 DISHWASHER Flowhood Duct 10" Rd 1.0 525 895 550 105 Totals: - - 525 1 895 550 105 SYSTEM/UNIT: EF-03 AREA: CUST/RECEIVING 126 Unit Data Fan Manufacturer GREENHECK Fan Model Number SQ-95-VG Drive Type DIRECT Test Data Total Design Flow 500 CFM Fan RPM Design 1594 RPM EF-03 Exhaust Inlet Summary Motor Data Motor HP 1/6 HP Motor Phase 1 Motor Hertz 60 Hz Test Pressures Design Total SP 0.50 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value Readin Readin Inlet-01 CUST/RECEIVI Flowhood 1.0 500 NG Totals: - - - 500 0 0 0 Neudorfer Engineers, Inc. Page 24 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: EF-04 AREA: ACTIVITIES TOILET 116 Unit Data Fan Manufacturer Cook Fan Model Number 135 SQN Fan Serial Number 033SH28555 Fan Rotation Counterclockwise Fan Discharge Vertical Drive Type DIRECT Fan Speed 67% Test Data Total Design Flow 1550 CFM Total Actual Flow 1675 CFM Fan RPM Design 1577 RPM Fan RPM Actual 1208 RPM Motor Volts T1-T2 120 Volts Motor Amps T1 3.30 Amps Log: Tested By: Dwight Hammack Date: 10/24/2018 Motor Data Motor Manufacturer US Motors Motor HP 3/4 HP Motor Phase 1 Motor Hertz 60 Hz Test Pressures Design Total SP 1.00 in. we EF-04 10/5/2018 Dwight Hammack (2) The volume damper is full closed. EF-04 10/5/2018 Dwight Hammack (1) The volume damper is full open. EF-04 10/5/2018 Dwight Hammack Statics Neudorfer Engineers, Inc. Page 25 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 EF-04 Exhaust Inlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value ReadingReadin Inlet-01` ACTIVITIES Flowhood E 12X12 1.0 150 60 157 105 (1) TOILET Inlet-02 ACTIVITIES Flowhood E 12X12 1.0 150 65 162 108 TOILET Inlet-03 ACTIVITIES Flowhood E 12X12 1.0 100 95 95 95 TOILET Inlet-04 ACTIVITIES Flowhood E 12X12 1.0 75 110 71 95 TOILET Inlet-05" ACTIVITIES Flowhood E 12X12 1.0 75 115 81 108 (2) TOILET Inlet-06 ACTIVITIES Flowhood E 12X12 1.0 75 145 70 93 TOILET Inlet-07 ACTIVITIES Flowhood E 12X12 1.0 75 220 82 109 (2) TOILET Inlet-08 ACTIVITIES Flowhood E 12X12 1.0 75 105 71 95 TOILET Inlet-09 ACTIVITIES Flowhood E 12X12 1.0 75 130 81 108 (2) TOILET Inlet-10 ACTIVITIES Flowhood E 12X12 1.0 75 160 107 143 (2) TOILET Inlet-11 ACTIVITIES Flowhood E 12X12 1.0 75 160 75 100 (2) TOILET Inlet-12 ACTIVITIES Flowhood E 12X12 1.0 75 130 78 104 TOILET Inlet-13 ACTIVITIES Flowhood E 12X12 1.0 75 135 83 111 (2) TOILET Inlet-14 ACTIVITIES Flowhood E 12X12 1.0 75 180 117 156 (2) TOILET Inlet-15 ACTIVITIES Flowhood E 12X12 1.0 75 145 71 95 TOILET Inlet-16 ACTIVITIES Flowhood E 12X12 1.0 75 120 81 108 TOILET Inlet-17 ACTIVITIES Flowhood E 12X12 1.0 75 120 71 95 (2) TOILET Inlet-18 ACTIVITIES Flowhood E 12X12 1.0 100 115 95 95 TOILET Totals: - - 1550 2310 1648 106 - Log: EF-04/Inlet-01 10/2/2018 Xuan Nguyen (1) The volume damper with Young's regulator is full open. EF-04/Inlet-05 10/3/2018 Xuan Nguyen (2) The volume damper with Young's regulator is full closed (Typical). Neudorfer Engineers, Inc. Page 26 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: EF-05 AREA: LC (M SCI) 136 Unit Data Fan Manufacturer Cook Fan Model Number 135 ACRU Fan Serial Number 033SH28555 Fan Rotation Counterclockwise Fan Discharge Vertical Drive Type DIRECT Fan Speed 61 % Test Data Total Design Flow 1200 CFM Total Actual Flow 1210 CFM Fan RPM Design 1191 RPM Fan RPM Actual 786 RPM Motor Volts T1-T2 120 Volts Motor Amps T1 1.10 Amps EF-05 Exhaust Inlet Summary Tested By: Dwight Hammack Date: 10/5/2018 Motor Data Motor Manufacturer US Motors Motor HP 1/2 HP Motor RPM 300-1800 RPM Motor Rated Volts 120-208/240 Volts Motor Phase 1 Motor Hertz 60 Hz Motor Full Load Amps 6.2/3.8-3.5 Amps Test Pressures Fan Suction SP -0.17 in. we Fan Discharge SP 0.00 in. we Design Total SP 0.60 in. we Actual Total SP 0.17 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value ReadingReadin Inlet-01 LC (M SCI) Velgrid E 24X24 2.8 1200 1855 1210 101 136 Totals: - 1200 1855 1210 101 Neudorfer Engineers, Inc. Page 27 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: EF-06(info) AREA: FUME HOOD EXH Unit Data Fan Manufacturer Cook Fan Model Number 150 ACRUH Fan Serial Number 033SH28555 Fan Rotation Counterclockwise Fan Discharge Vertical Drive Type DIRECT Fan Speed 46% Test Data Total Design Flow 580 CFM Fan RPM Design 1389 RPM Fan RPM Actual 882 RPM EF-06(info) Exhaust Inlet Summary Tested By: Xuan Nguyen Date: 10/3/2018 Motor Data Motor Manufacturer US Motors Motor HP 1/2 HP Motor RPM 300-1800 RPM Motor Rated Volts 120-208/240 Volts Motor Phase 1 Motor Hertz 60 Hz Motor Full Load Amps 6.2/3.8-3.5 Amps Test Pressures Design Total SP 1.20 in. we System/Unit Area Served Type of Readin Outlet Type Size LxW / D AK Design VelocityValue Design Prelim Readin Final Readin Final % Remarks Inlet-01 FUME HOOD Pitot Tube HOOD 38x19.5 5.15 1 580 1340 Totals: - 1 580 1340 1 0 1 0 1 - SYSTEM/UNIT: EF-07 AREA: BOILER/MECH 125 Unit Data Fan Manufacturer Cook Fan Model Number 120-SQM-120-VG Fan Serial Number 033SH28555-8601 Fan Rotation Clockwise Drive Type DIRECT Fan Speed 55 Test Data Total Design Flow 1000 CFM Total Actual Flow 1005 CFM Fan RPM Actual 1034 RPM Motor Amps T1 1.10 Amps EF-07 Exhaust Inlet Summary Tested By: Alex Lebedev Date: 10/22/2018 Motor Data Motor Manufacturer Cook Motor HP 1/2 HP Motor RPM 1418 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Test Pressures Fan Suction SP -0.07 in. we Fan Discharge SP 0.09 in. we Design Total SP 0.60 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value Readin Readin Inlet-01 BOILER/MECH Velgrid EG 14x14 1.36 1000 1679 1005 101 125 Totals: - - 1000 1679 1005 101 Neudorfer Engineers, Inc. Page 28 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: EF-08(info) AREA: ELECTRICAL 126 Unit Data Fan Manufacturer Cook Fan Model Number 120 ACE Fan Serial Number 033SH44823 Fan Rotation Counterclockwise Fan Discharge Vertical Drive Type DIRECT Test Data Total Design Flow 800 CFM Fan RPM Design 1500 RPM EF-08(info) Exhaust Inlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Tested By: Dwight Hammack Date: 9/24/2018 Motor Data Motor Manufacturer US Motors Motor HP 1/2 HP Motor RPM 300-1800 RPM Motor Rated Volts 120-208/240 Volts Motor Phase 1 Motor Hertz 60 Hz Motor Full Load Amps 6.2/3.8-3.5 Amps Test Pressures Design Total SP 0.60 in. we System/Unit Area Served Type of Readin Outlet T e Size LxW / D AK Design Velocit Design Value Prelim Readin Final Readin Final % Remarks Inlet-01 ELEC 128 Flowhood 1.0 800 Totals: 800 1 0 1 0 1 0 1 - SYSTEM/UNIT: EF-09 AREA: KILN Unit Data Fan Manufacturer ENVIROVENT 2 Fan Model Number ENVIROVENT 2 Drive Type DIRECT Test Data Total Design Flow 140 CFM EF-09 Exhaust Inlet Summary Motor Data Motor HP 14 AMPS HP Motor Phase 1 Motor Hertz 60 Hz System/Unit Area Served Type of Readin Outlet T e Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Inlet-01 KILN Flowhood 1.0 140 Totals: - - 140 1 0 0 0 Neudorfer Engineers, Inc. Page 29 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: EF-10 AREA: TOILET 113A Unit Data Fan Manufacturer GREENHECK Fan Model Number SQ-97-VG Drive Type DIRECT Test Data Total Design Flow 150 CFM Fan RPM Design 1501 RPM EF-10 Exhaust Inlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor HP 1/4 HP Motor Phase 1 Motor Hertz 60 Hz Test Pressures Design Total SP 0.60 in. we System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Inlet-01 TOILET 113A Flowhood E 12X12 1.0 150 Totals: - 150 0 0 0 Neudorfer Engineers, Inc. Page 30 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: EF-11 AREA: NORTH ADMIN TLTS/HEALTH ROOM Unit Data Fan Manufacturer Cook Fan Model Number 150 ACE Fan Serial Number 033SH28555 00/0011601 Fan Rotation Counterclockwise Fan Discharge Vertical Drive Type DIRECT Fan Speed 57% Test Data Total Design Flow 1550 CFM Total Actual Flow 1525 CFM Fan RPM Design 1242 RPM Fan RPM Actual 1148 RPM Motor Volts T1-T2 120 Volts Motor Amps T1 1.10 Amps EF-11 Exhaust Inlet Summary Tested By: Dwight Hammack Date: 10/24/2018 Motor Data Motor Manufacturer US Motors Motor HP 1 HP Motor RPM 300-1800 RPM Motor Rated Volts 120-208/240 Volts Motor Phase 1 Motor Hertz 60 Hz Motor Full Load Amps 12.4/8.1-7.2 Amps Test Pressures Fan Suction SP -0.17 in. we Fan Discharge SP 0.00 in. we Design Total SP 1.00 in. we Actual Total SP 0.17 in. we System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readin Final Readin Final % Remarks Inlet-01 NORTH ADMIN TLTS Flowhood E 24X12 1.0 400 280 385 96 Inlet-02 Flowhood E 24X12 1.0 100 90 100 100 Inlet-03 Flowhood E 12X12 1.0 150 110 155 103 Inlet-04" Flowhood E 12X12 1.0 150 40 150 100 (1) Inlet-05 Velgrid R 18X12 1.05 200 525 190 95 Inlet-06 Flowhood E 24X12 1.0 200 360 210 105 Inlet-07 Flowhood E 12X12 1.0 150 120 140 93 Inlet-08 Flowhood E 24X12 1.0 200 210 195 98 Totals: I - I - I - I - I - 1550 1735 1 1525 98 - Log: I EF-11 /Inlet-04 10/3/2018 Xuan Nguyen (1) The volume damper with Young's regulator is full open. Neudorfer Engineers, Inc. Page 31 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: EF-12 AREA: SOUTH ADMIN Unit Data Fan Manufacturer GREENHECK Fan Model Number G-098-VG Drive Type DIRECT Test Data Total Design Flow 450 CFM Fan RPM Design 1383 RPM EF-12 Exhaust Inlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor HP 1/4 HP Motor Phase 1 Motor Hertz 60 Hz Test Pressures Design Total SP 0.60 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value Readin Readin Inlet-01` SOUTH ADMIN Flowhood E 12X12 1.0 150 TLTS Inlet-02" SOUTH ADMIN Flowhood E 12X12 1.0 150 TLTS Inlet-03 SOUTH ADMIN Flowhood E 12X12 1.0 150 TLTS Totals: - - 450 1 0 0 0 - Log: EF-12/Inlet-01 10/3/2018 Xuan Nguyen The grille/register/diffuser is not installed. EF-12/Inlet-02 10/3/2018 Xuan Nguyen The grille/register/diffuser is not installed. SYSTEM/UNIT: EF-13 AREA: MECH 304 CUST CLOSET Unit Data Fan Manufacturer GREENHECK Fan Model Number G-097-VG Drive Type DIRECT Test Data Total Design Flow 150 CFM Fan RPM Design 1324 RPM EF-13 Exhaust Inlet Summary Motor Data Motor HP 1/4 HP Motor Phase 1 Motor Hertz 60 Hz Test Pressures Design Total SP 0.60 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value ReadingReadin Inlet-01 304 CUST Flowhood E 24x12 1.0 150 CLOSET Totals: - - - 150 0 0 0 Neudorfer Engineers, Inc. Page 32 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: EF-14 AREA: MECH 504 CUST CLOSET Unit Data Fan Manufacturer GREENHECK Fan Model Number G-097-VG Drive Type DIRECT Test Data Total Design Flow 150 CFM Fan RPM Design 1324 RPM EF-14 Exhaust Inlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor HP 1/4 HP Motor Phase 1 Motor Hertz 60 Hz Test Pressures Design Total SP 0.60 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value ReadingReadin Inlet-01 MECH 504 Flowhood E 24x12 1.0 150 CUST CLOSET Totals: - - - - - 150 0 0 0 SYSTEM/UNIT: EF-15 AREA: MECH 206 CUST CLOSET Unit Data Fan Manufacturer GREENHECK Fan Model Number G-097-VG Drive Type DIRECT Test Data Total Design Flow 150 CFM Fan RPM Design 1324 RPM EF-15 Exhaust Inlet Summary Motor Data Motor HP 1/4 HP Motor Phase 1 Motor Hertz 60 Hz Test Pressures Design Total SP 0.60 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value ReadingReadin Inlet-01 MECH 206 Flowhood E 24X12 1.0 150 CUST CLOSET Totals: - 150 0 0 0 Neudorfer Engineers, Inc. Page 33 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: EF-16 AREA: MECH 406 CUST CLOSET Unit Data Fan Manufacturer GREENHECK Fan Model Number G-097-VG Drive Type DIRECT Test Data Total Design Flow 150 CFM Fan RPM Design 1324 RPM EF-16 Exhaust Inlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor HP 1/4 HP Motor Phase 1 Motor Hertz 60 Hz Test Pressures Design Total SP 0.60 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value ReadingReadin Inlet-01 MECH 406 Flowhood E 24X12 1.0 150 CUST CLOSET Totals: - - - - - 150 0 0 0 SYSTEM/UNIT: EF-17 AREA: MECH 605 CUST CLOSET Unit Data Fan Manufacturer GREENHECK Fan Model Number G-097-VG Drive Type DIRECT Test Data Total Design Flow 150 CFM Fan RPM Design 1324 RPM EF-17 Exhaust Inlet Summary Motor Data Motor HP 1/4 HP Motor Phase 1 Motor Hertz 60 Hz Test Pressures Design Total SP 0.60 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value ReadingReadin Inlet-01 MECH 605 Flowhood E 24X12 1.0 150 CUST CLOSET Totals: - 150 0 0 0 Neudorfer Engineers, Inc. Page 34 of 93 Fan Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: EF-18 Info AREA: STAFF LOUNGE 101 P HOOD Unit Data Fan Manufacturer Cook Fan Model Number 101 ACE Fan Serial Number 033SH28555 00/0014201 Fan Rotation Counterclockwise Fan Discharge Vertical Drive Type DIRECT Test Data Total Design Flow 400 CFM Fan RPM Design 1437 RPM EF-18 Info Exhaust Inlet Summary Tested By: Xuan Nguyen Date: 10/3/2018 Motor Data Motor Manufacturer Cook Motor HP 1/4 HP Motor RPM 300-1725 RPM Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor Full Load Amps 3.40 Amps Test Pressures Design Total SP 0.60 in. we System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final % Remarks Reading Type LxW / D Velocity Value ReadingReadin Inlet-01" MECH 406 Flowhood HOOD 1.0 400 CUST CLOSET Totals: - 400 0 0 0 Log: EF-18 Info/Inlet-01 10/3/2018 Xuan Nguyen The ductwork is incomplete due to range hood is not installed. Neudorfer Engineers, Inc. Page 35 of 93 Fan Coil PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: FCU-01 AREA: PRACTICE Unit Data Unit Manufacturer NAILOR Unit Model Number D35FHE Unit Serial Number 589771-1.01 Drive Type Direct Drive Fan Speed 50% Test Data Total Design Flow 600 CFM Total Actual Flow 576 CFM RA Design Flow 310 CFM RA Actual Flow 293 CFM OA Design Flow 290 CFM OA Actual Flow 283 CFM RA Damper Position 67 OA Damper Position 33 Motor Volts T1-T2 207 Volts Motor Amps T1 0.90 Amps Log: DATE: 10/25/2018 CONTACT: AUTHOR: Tested By: Dwight Hammack Date: 10/24/2018 Motor Data Motor HP 1/4 Motor Rated Volts 208 Motor Phase 1 Motor Hertz 60 Motor FL Amps 2.2 Test Pressures Fan Suction SP -0.10 " W.C. Fan Discharge SP 0.05 " W.C. Design External SP 0.35 " W.C. Actual External SP 0.15 " W.C. Filter Data Filter Type Pleated Filter Qty - S1 1 Filter Size - S1 16x20x2 FCU-01 10/24/2018 Dwight Hammack OSA was set by subtracting return air from the supply air. FCU-01 10/24/2018 Dwight Hammack (1) The volume damper is full open. FCU-01 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 PRACTICE Flowhood A 8" 1.0 100 125 96 96 Outlet-02 PRACTICE Flowhood A 8" 1.0 100 128 95 95 Outlet-03 CORRIDOR Flowhood A 101, 1.0 200 156 194 97 (1) Outlet-04 CORRIDOR Flowhood A 10" 1.0 200 173 191 96 Totals: - - 600 1 582 1 576 1 96 FCU-01 Return Inlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Readin Final % Remarks Inlet-01 PRACTICE Flowhood RG 12x24 1.0 155 193 143 92 (1) Inlet-02 PRACTICE Flowhood RG 12x24 1.0 155 160 150 97 Totals: - - 310 353 293 95 - Neudorfer Engineers, Inc. Page 36 of 93 Fan Coil PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: FCU-02 AREA: CUSTODIAL/MUSIC OFFICE Unit Data Unit Manufacturer NAILOR Unit Model Number D35FHE Unit Serial Number 589771-2.01 Unit Location Mezzanine Drive Type Direct Drive Fan Speed 54% Test Data Total Design Flow 1050 CFM Total Actual Flow 1095 CFM RA Design Flow 550 CFM OA Design Flow 500 CFM Log: DATE: 10/25/2018 CONTACT: AUTHOR: Tested By: Dwight Hammack Date: 10/24/2018 Motor Data Motor HP Motor Rated Volts Motor Phase Motor Hertz Motor FL Amps 112 208 1 60 4.9 Test Pressures Design External SP 0.50 " W.C. Filter Data Filter Manufacturer Filter Type Filter Qty - S1 Filter Size - S1 Koch Pleated 1 16x35x2 FCU-02 10/24/2018 Dwight Hammack (1) The volume damper is full open. FCU-02 10/24/2018 Dwight Hammack Need an RFI to clarify the outside air total. Return outlet totals equals the sum of the supply outlets. The schedule calls for 500 CFM of OSA. FCU-02 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 PRACTICE Flowhood A 12" 1.0 350 401 350 100 Outlet-02 CUSTODIAL OFFICE Flowhood A 12" 1.0 500 465 535 107 (1) Outlet-03 CORRIDOR Flowhood A 10" 1.0 200 298 210 105 Totals: - - 1050 1 1164 1 1095 1 104 FCU-02 Return Inlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readin Final Reading Final % Remarks Inlet-01 PRACTICE Flowhood E 24X12 1.0 350 Inlet-02 CORRIDOR Flowhood E 24X12 1.0 200 Inlet-03 CUSTODIAL OFFICE Flowhood E 18X12 1.0 500 Totals: - - - - - 1050 0 1 0 1 0 - Neudorfer Engineers, Inc. Page 37 of 93 Fan Coil PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: FCU-03 AREA: GYM OFFICE Unit Data Unit Manufacturer NAILOR Unit Model Number D35FHE Fan Speed 1220 Test Data Total Design Flow 400 CFM FCU-03 Supply Outlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor HP 1/4 Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.35 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 GYM OFFICE Flowhood A 8" 1.0 200 Outlet-02 GYM OFFICE Flowhood A 8" 1.0 200 Totals: - - - 400 0 0 0 FCU-03 Return Inlet Summary System/Unit Type of Reading Outlet Type Size LxW / D AK Design Design Value Prelim Reading Final Readin Final % Remarks Inlet-01 Flowhood E 24X12 —Velocity 1.0 200 Inlet-02 Flowhood E 24X12 1.0 200 - - - - 400 0 0 0 - SYSTEM/UNIT: SAC-01 AREA: MDF 137 Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKA-A24KA6 Test Data Total Design Flow 425 CFM SAC-01 Supply Outlet Summary Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 MDF 137 Flowhood 1.0 425 Totals: - - - I- - 425 0 0 0 Neudorfer Engineers, Inc. Page 38 of 93 Fan Coil PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: SAC-02A AREA: IDF 303A Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-02A Supply Outlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 IDF 303A Flowhood 1.0 425 Totals: - 425 0 0 0 SYSTEM/UNIT: SAC-02B AREA: ELEC 303 Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-02B Supply Outlet Summary Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 ELEC 303 Flowhood 1.0 425 Totals: - 425 0 0 0 Neudorfer Engineers, Inc. Page 39 of 93 Fan Coil PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: SAC-03A AREA: IDF 503A Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-03A Supply Outlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 IDF 503A Flowhood 1.0 425 Totals: - 425 0 0 0 SYSTEM/UNIT: SAC-03B AREA: ELEC 503 Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-03B Supply Outlet Summary Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 IDF 503A Flowhood 1.0 425 Totals: - 425 0 0 0 Neudorfer Engineers, Inc. Page 40 of 93 Fan Coil PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: SAC-04A AREA: IDF 205A Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-04A Supply Outlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 IDF 205A Flowhood 1.0 425 Totals: - 425 0 0 0 SYSTEM/UNIT: SAC-04B AREA: ELEC 205 Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-04B Supply Outlet Summary Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 ELEC 205 Flowhood 1.0 425 Totals: - 425 0 0 0 Neudorfer Engineers, Inc. Page 41 of 93 Fan Coil PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: SAC-05A AREA: IDF 405A Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-05A Supply Outlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 IDF 405A Flowhood 1.0 425 Totals: - 425 0 0 0 SYSTEM/UNIT: SAC-05B AREA: ELEC 405 Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-05B Supply Outlet Summary Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 ELEC 405 Flowhood 1.0 425 Totals: - 425 0 0 0 Neudorfer Engineers, Inc. Page 42 of 93 Fan Coil PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: SAC-06A AREA: IDF 605A Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-06A Supply Outlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 IDF 605A Flowhood 1.0 425 Totals: - 425 0 0 0 SYSTEM/UNIT: SAC-06B AREA: ELEC 605 Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKFY-P18NHMU-E2 Test Data Total Design Flow 425 CFM SAC-06B Supply Outlet Summary Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 ELEC 605 Flowhood 1.0 425 Totals: - 425 0 0 0 Neudorfer Engineers, Inc. Page 43 of 93 Fan Coil PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 SYSTEM/UNIT: SAC-07 AREA: IDF 101 F Unit Data Unit Manufacturer MITSUBISHI Unit Model Number PKA-A18HA6 Test Data Total Design Flow 425 CFM SAC-07 Supply Outlet Summary DATE: 10/25/2018 CONTACT: AUTHOR: Tested By: Xuan Nguyen Date: 10/12/2018 Motor Data Motor Phase 1 Motor Hertz 60 Test Pressures Design External SP 0.25 " W.C. System/Unit Area Served Type of ReadingT Outlet e Size LxW / D AK Design Velocit Design Value Prelim Readin Final Readin Final % Remarks Outlet-01 IDF 101F Flowhood 1.0 425 Totals: 425 0 1 0 0 Neudorfer Engineers, Inc. Page 44 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-01(info) AREA: CLASSROOMS/READING Unit Data Unit Manufacturer D-AirTech Unit Model Number D-AHU-6 Unit Serial Number D-17-072 HRU-01(info)/EF Filter Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 24x24x2 Filter Quantity - Size 3 3 Filter Dimensions - Size 3 12x24x4 Filter Quantity - Size 4 3 Filter Dimensions - Size 4 12x24x2 HRU-01(info)/SF Filter Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 24x24x2 Test Data SF Total Design Flow 5750 CFM SF OA Design Flow 3440 CFM EF Total Design Flow 5750 CFM Tested By: Dwight Hammack Date: 9/25/2018 Motor Data HRU-01(info)/Exhaust Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP 7 HP Motor RPM 2682 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 6.9 Amps HRU-01(info)/Supply Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP (2)4.4 HP Motor RPM 2419 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps (2)4.4 Amps Test Pressures SF Design ESP 2.30 in. w.c. EF Actual ESP 1.70 in. w.c. Log: HRU-01(info) 10/16/2018 Dwight Hammack Motorized damper not installed on outlet that serves mechanical room. HRU-01(info) Exhaust Inlet Summary System/Unit Type of Readinq Outlet Tvpe Size LxW / D AK Design Velocity Design Value Prelim ReadingReadin Final Final % Remarks Inlet-01 Flowhood E 24X24 1.0 1085 Inlet-02 Flowhood E 24X24 1.0 1085 Inlet-03 Flowhood E 12X12 1.0 150 Inlet-04 Flowhood E 24X12 1.0 50 Inlet-05 Flowhood E 24X12 1.0 140 Inlet-06 Flowhood E 24X12 1.0 200 Inlet-07 Flowhood E 24X24 1.0 1200 Inlet-08 Flowhood E 24X12 1.0 240 Inlet-09 Flowhood E 24X12 1.0 100 Inlet-10 Flowhood E 24X24 1.0 950 Inlet-11 Flowhood E 24X24 1.0 205 Inlet-12 Flowhood E 24X12 1.0 130 Inlet-13 Flowhood R 12X12 1.0 150 Inlet-14 I Flowhood E 12X12 1 1.0 150 Inlet-15 Flowhood E 24X12 1.0 115 5950 0 0 0 Neudorfer Engineers, Inc. Page 45 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-01(info)/VAV-101 AREA: PARENT ROOM 132 Unit Data Manufacturer NAILOR Cooling Inlet Size 9 inches HRU-01 (info)/VAV-1 01 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 505 CFM Clg Min Des. Primary Flow 350 CFM System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 PARENT Flowhood B 36X48 1.0 505 ROOM Totals: - 505 0 0 0 SYSTEM/UNIT: HRU-01(info)/VAV-102 AREA: MIT OFFICE 132B Unit Data Manufacturer NAILOR Cooling Inlet Size 5 inches HRU-01(info)/VAV-102 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 130 CFM Clg Min Des. Primary Flow 80 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 MT OFFICE Flowhood B 23X23 1.0 130 Totals: - - - 4-130 0 0 0 SYSTEM/UNIT: HRU-01(info)/VAV-103 AREA: LG (DHH) 134 Unit Data Manufacturer NAILOR Cooling Inlet Size 12 inches HRU-01 (info)/VAV-1 03 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 950 CFM Clg Min Des. Primary Flow 570 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readinq Final Readin Final % Remarks Outlet-01 LC (DHH) Flowhood B 72X52 1.0 950 Totals: - 950 1 0 0 0 1 - Neudorfer Engineers, Inc. Page 46 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-01(info)/VAV-104 AREA: SMALL GROUP 134A Unit Data Manufacturer NAILOR Cooling Inlet Size 4 inches HRU-01(info)/VAV-104 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 100 CFM Clg Min Des. Primary Flow 60 CFM System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 SMALL Flowhood B 23X23 1.0 100 GROUP Totals: - - - - - 100 0 0 0 - SYSTEM/UNIT: HRU-01(info)/VAV-105 AREA: SCI PREP 136A Unit Data Manufacturer NAILOR Cooling Inlet Size 6 inches HRU-01(info)/VAV-105 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 240 CFM Clg Min Des. Primary Flow 145 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 SCI PREP Flowhood B 23X23 1.0 120 Outlet-02 SCI PREP Flowhood B 23X23 1.0 120 Totals: - - - - - 240 0 0 0 - SYSTEM/UNIT: HRU-01(info)/VAV-106 AREA: LC (M SCI) 136 Unit Data Manufacturer NAILOR Cooling Inlet Size 14 inches HRU-01(info)/VAV-106 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 1200 CFM Clg Min Des. Primary Flow 720 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (M SCI) Flowhood B 8OX24 1.0 400 Outlet-02 LC (M SCI) Flowhood B 56X52 1.0 800 Totals: - - - - - 1200 0 0 0 - Neudorfer Engineers, Inc. Page 47 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-01(info)/VAV-107 AREA: GREEN ROOM 135 Unit Data Manufacturer NAILOR Cooling Inlet Size 7 inches HRU-01 (info)/VAV-1 07 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 340 CFM Clg Min Des. Primary Flow 150 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 GREEN ROOM Flowhood A 101, 1.0 200 Outlet-02 GREEN ROOM Flowhood B 23X23 1.0 140 Totals: - - - - 340 0 0 0 SYSTEM/UNIT: HRU-01(info)/VAV-108 AREA: LIBRARY 131 Unit Data Manufacturer NAILOR HRU-01 (info)/VAV-1 08 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 2170 CFM Clg Min Des. Primary Flow 1300 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LIBRARY Flowhood B 80X52 1.0 1085 Outlet-02 LIBRARY Flowhood B 80X52 1.0 1085 Totals: - 2170 0 0 0 SYSTEM/UNIT: HRU-01(info)/VAV-109 AREA: SMALL GROUP 131A Unit Data Manufacturer NAILOR Cooling Inlet Size 5 inches HRU-01 (info)NAV-1 09 Supply Outlet Summary Air Test Data Clg Max Des. Primary Flow 115 CFM Clg Min Des. Primary Flow 65 CFM System/Unit Area Served Type of Outlet Size AK Design Design Prelim Final Final Remarks Reading Type LxW / D Velocity Value Reading Reading % Outlet-01 SMALL Flowhood B 23X23 1.0 115 GROUP Totals: - 115 0 0 0 Neudorfer Engineers, Inc. Page 48 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-02 AREA: CLASSROOMS Unit Data Unit Manufacturer D-AirTech Unit Model Number D-AHU-4 Unit Serial Number D-17-078 Unit Type Air to Air EF Fan Rotation Counterclockwise SF Fan Rotation Counterclockwise HRU-02/EF Filter Filter Manufacturer Flanders Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 12x24x2 HRU-02/SF Filter Filter Manufacturer Flanders Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 24x24x4 Test Data SF Total Design Flow 4420 CFM SF Total Actual Flow 4534 CFM EF Total Design Flow 4420 CFM EF Total Actual Flow 4390 CFM HRU-02/Exhaust Fan Motor Volts T1-T2 206 Volts Motor Volts T2-T3 206 Volts Motor Volts T1-T3 207 Volts Motor Amps T1 1.5 Amps Motor Amps T2 1.6 Amps Motor Amps T3 1.6 Amps HRU-02/Supply Fan Motor Volts T1-T2 206 Volts Motor Volts T2-T3 206 Volts Motor Volts T1-T3 207 Volts Motor Amps T1 4.3 Amps Motor Amps T2 4.5 Amps Motor Amps T3 4.4 Amps Log: Tested By: Dwight Hammack Date: 10/23/2018 Motor Data HRU-02/Exhaust Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP 2-1.53 HP Motor RPM 2005 RPM Motor Rated Volts 208-230 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 10.6 Amps HRU-02/Supply Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP 2-1.99 HP Motor RPM 3182 RPM Motor Rated Volts 208-230 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 2x9.42 Amps Test Pressures SF Design ESP 2.30 in. w.c. SF Pre -Filter SP In -0.53 in. we SF Pre -Filter SP Out -0.58 in. we SF Fan SP In -1.65 in. we SF Fan SP Out 1.76 in. we SF HC SP In -1.46 in. we SF HC SP Out -1.65 in. we EF Actual ESP 1.70 in. w.c. EF Pre -Filter SP In -0.29 in. we EF Pre -Filter SP Out -0.39 in. we EF Fan SP In -0.71 in. we EF Fan SP Out 0.18 in. we EF HEX SP In -0.39 in. we EF HEX SP Out -0.71 in. we HRU-02 10/23/2018 Dwight Hammack (2) The volume damper is full closed. HRU-02 10/23/2018 Dwight Hammack (1) The volume damper is full open. HRU-02 10/23/2018 Dwight Hammack Building static pressure is +0.03 and the design is +0.04. HRU-02 10/16/2018 Dwight Hammack Motorized damper not installed on outlet that serves mechanical room. Neudorfer Engineers, Inc. Page 49 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: HRU-02 Exhaust Inlet Summary System/Unit Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim ReadingReadin Final Final % Remarks Inlet-01 Flowhood R 30C12 1.0 1105 515 1090 99 (1) Inlet-02 Flowhood R 30C12 1.0 1105 525 1090 99 Inlet-03 Flowhood R 30X12 1.0 905 535 920 102 Inlet-04 Flowhood R 30X12 1.0 905 500 915 101 Inlet-05 Flowhood E 12X12 1.0 150 180 140 93 Inlet-06 Flowhood E 12X12 1.0 100 85 95 95 (2) Inlet-07 Flowhood E 12X12 1.0 150 125 140 93 - - - - - 4420 2465 4390 99 - SYSTEM/UNIT: HRU-02/VAV-110 AREA: LC (L) 305A Unit Data Manufacturer Price Model Number SDV5 VAV Address 6 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2200.00 Tested By: Dwight Hammack Date: 10/16/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1141 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-02NAV-110 10/16/2018 Dwight Hammack (1) The volume damper is full open. HRU-02/VAV-110 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (L) Flowhood B 30X44 1.0 500 464 502 100 (1) Outlet-02 LC (L) Flowhood B 4X44 1.0 605 674 639 106 Totals: - - - - - 1105 1138 1141 103 - Neudorfer Engineers, Inc. Page 50 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-02/VAV-111 AREA: LC (L) 305B Unit Data Manufacturer Price Model Number SDV5 VAV Address 7 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2199.00 Tested By: Dwight Hammack Date: 10/16/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1135 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-02NAV-111 10/16/2018 Dwight Hammack (1) The volume damper is full open. HRU-02/VAV-111 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (L) Flowhood B 36X44 1.0 500 484 497 99 (1) Outlet-02 LC (L) Flowhood B 44X44 1.0 605 700 635 105 Totals: - - - - 1105 1184 1132 102 SYSTEM/UNIT: HRU-02/VAV-112 AREA: LC (P) 301A Unit Data Manufacturer Price Model Number SDV5 VAV Address 8 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2219.00 Tested By: Dwight Hammack Date: 10/16/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1132 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-02NAV-112 10/16/2018 Dwight Hammack (1) The volume damper is full open. HRU-02/VAV-112 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (P) Flowhood B 26X44 1.0 500 364 493 99 (1) Outlet-02 LC (P) Flowhood B 44X44 1.0 605 496 639 106 Totals: - - 1105 860 1132 102 - Neudorfer Engineers, Inc. Page 51 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-02/VAV-113 AREA: LC (P) 301 B Unit Data Manufacturer Price Model Number SDV5 VAV Address 9 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2073.00 Tested By: Dwight Hammack Date: 10/16/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1126 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-02NAV-113 10/16/2018 Dwight Hammack (1) The volume damper is full open. HRU-02/VAV-113 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (P) Flowhood B 36X44 1.0 500 332 522 104 (1) Outlet-02 LC (P) Flowhood B 44X44 1.0 605 468 604 100 Totals: - - - - - 1105 800 1126 102 - Neudorfer Engineers, Inc. Page 52 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-03 AREA: CLASSROOMS Unit Data Unit Manufacturer D-AirTech Unit Model Number D-AHU-4 Unit Serial Number D-17-074 Unit Type Air to Air EF Fan Rotation Counterclockwise SF Fan Rotation Counterclockwise HRU-03/EF Filter Filter Manufacturer Flanders Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 12x24x2 HRU-03/SF Filter Filter Manufacturer Flanders Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 24x24x4 Test Data SF Total Design Flow 4420 CFM SF Total Actual Flow 4424 CFM EF Total Design Flow 4420 CFM EF Total Actual Flow 4330 CFM Log: Tested By: Dwight Hammack Date: 10/23/2018 Motor Data HRU-03/Exhaust Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP 4.88 HP Motor RPM 2005 RPM Motor Rated Volts 208-230 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 10.6 Amps HRU-03/Supply Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP 2x4.14 HP Motor RPM 3182 RPM Motor Rated Volts 208-230 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 2x9.42 Amps Test Pressures SF Design ESP 2.30 in. w.c. EF Actual ESP 1.70 in. w.c. HRU-03 10/16/2018 Dwight Hammack (2) The volume damper is full closed. HRU-03 10/16/2018 Dwight Hammack (1) The volume damper is full open. HRU-03 10/16/2018 Dwight Hammack Motorized damper not installed on outlet that serves mechanical room. HRU-03 Exhaust Inlet Summary System/Unit Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim ReadingReadin Final Final % Remarks Inlet-01 Flowhood R 30X12 1.0 1105 715 1080 98 (1) Inlet-02 Flowhood R 30X12 1.0 1105 770 1075 97 Inlet-03 Flowhood R 30X12 1.0 905 735 900 99 Inlet-04 Flowhood R 30X12 1.0 905 690 890 98 Inlet-05 Flowhood E 12X12 1.0 150 150 145 97 Inlet-06 Flowhood E 12X12 1.0 100 65 95 95 Inlet-07 Flowhood E 12X12 1.0 150 85 145 97 - - - - - 4420 3210 4330 98 - Neudorfer Engineers, Inc. Page 53 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-03/VAV-114 AREA: LC (L) 505A Unit Data Manufacturer Price Model Number SDV5 VAV Address 15 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2147.00 Tested By: Dwight Hammack Date: 10/16/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1130 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-03NAV-114 10/16/2018 Dwight Hammack (1) The volume damper is full open. HRU-03/VAV-114 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (L) Flowhood B 36X44 1.0 500 410 502 100 (1) Outlet-02 LC (L) Flowhood B 44X44 1.0 605 633 628 104 Totals: - - - - 1105 1043 1130 102 SYSTEM/UNIT: HRU-03/VAV-115 AREA: LC (L) 505B Unit Data Manufacturer Price Model Number SDV5 VAV Address 16 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2307.00 Tested By: Dwight Hammack Date: 10/16/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1126 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-03NAV-115 10/16/2018 Dwight Hammack (1) The volume damper is full open. HRU-03/VAV-115 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (L) Flowhood B 36X44 1.0 500 439 509 102 (1) Outlet-02 LC (L) Flowhood B 44X44 1.0 605 638 617 102 Totals: - - 1105 1077 1126 102 - Neudorfer Engineers, Inc. Page 54 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-03/VAV-116 AREA: LC (P) 501A Unit Data Manufacturer Price Model Number SDV5 VAV Address 17 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2140.00 Tested By: Dwight Hammack Date: 10/16/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1062 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-03NAV-116 10/15/2018 Dwight Hammack (1) The volume damper is full open. HRU-03/VAV-116 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (P) Flowhood B 36X44 1.0 500 323 487 97 (1) Outlet-02 LC (P) Flowhood B 44X44 1.0 605 435 575 95 Totals: - - - - 1105 758 1062 96 SYSTEM/UNIT: HRU-03/VAV-117 AREA: LC (P) 501 B Unit Data Manufacturer Price Model Number SDV5 VAV Address 18 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2038.00 Tested By: Dwight Hammack Date: 10/16/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1106 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-03NAV-117 10/16/2018 Dwight Hammack (1) The volume damper is full open. HRU-03/VAV-117 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (P) Flowhood B 36X44 1.0 500 541 489 98 (1) Outlet-02 LC (P) Flowhood B 44X44 1.0 605 480 617 102 Totals: - - 1105 1021 1106 100 - Neudorfer Engineers, Inc. Page 55 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-04 AREA: CLASSROOMS Unit Data Unit Manufacturer D-AirTech Unit Model Number D-AHU-6 Unit Serial Number D-17-076 Unit Type Air to Air EF Fan Rotation Counterclockwise SF Fan Rotation Counterclockwise HRU-04/EF Filter Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 12x24x2 HRU-04/SF Filter Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x4 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 24x24x2 Filter Quantity - Size 3 3 Filter Dimensions - Size 3 12x24x4 Filter Quantity - Size 4 3 Filter Dimensions - Size 4 12x24x2 Test Data SF Total Design Flow 6640 CFM SF Total Actual Flow 6573 CFM EF Total Design Flow 6640 CFM EF Total Actual Flow 6470 CFM Log: Tested By: Dwight Hammack Date: 10/24/2018 Motor Data HRU-04/Exhaust Fan Drive Type Direct Drive Motor HP (2)4 HP Motor RPM 2270 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps (2)3.66 Amps HRU-04/Supply Fan Drive Type Direct Drive Motor HP (2)4 HP Motor RPM 2494 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps (2)3.66 Amps Test Pressures SF Design ESP 2.30 in. w.c. EF Actual ESP 1.70 in. w.c. HRU-04 10/23/2018 Dwight Hammack (1) The volume damper is full open. HRU-04 10/16/2018 Dwight Hammack Motorized damper not installed on outlet that serves mechanical room. Neudorfer Engineers, Inc. Page 56 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: HRU-04 Exhaust Inlet Summary System/Unit Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim ReadingReadin Final Final % Remarks Inlet-01 Flowhood E 24X12 1.0 105 170 100 95 Inlet-02 Flowhood E 24X12 1.0 105 270 100 95 Inlet-03 Flowhood R 30X12 1.0 1005 960 1000 100 Inlet-04 Flowhood R 30X12 1.0 755 840 735 97 Inlet-05 Flowhood E 12XX12 1.0 100 120 100 100 Inlet-06 Flowhood E 12X12 1.0 150 110 145 97 Inlet-07 Flowhood E 24X12 1.0 105 130 100 95 Inlet-08 Flowhood E 24X12 1.0 105 155 100 95 Inlet-09 Flowhood R 30X12 1.0 1000 920 1000 100 (1) Inlet-10 Flowhood R 30X12 1.0 925 1 930 925 100 Inlet-11 Flowhood E 12X12 1.0 150 190 145 1 97 Inlet-12* Flowhood E 12X12 1.0 100 70 90 90 (1) Inlet-13 Flowhood E 12X12 1.0 100 80 95 95 Inlet-14 Flowhood E 12X12 1.0 150 120 140 93 Inlet-15 Flowhood R 30X12 1.0 800 675 755 94 (1) Inlet-16 Flowhood R 30X12 1.0 800 1 670 1 740 93 Inlet-17 Flowhood E 24X2 1.0 105 110 100 1 95 Inlet-18 Flowhood E 24X12 1.0 105 90 100 95 - - 6665 1 6610 6470 97 - Log: HRU-04/Inlet-12 10/16/2018 Andrey Polishchuk (1) The volume damper is full open. SYSTEM/UNIT: HRU-04/VAV-118 AREA: LC (M) 201 Unit Data Manufacturer Price Model Number SDV5 VAV Address 6 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 1359.00 HRU-04/VAV-118 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/15/2018 Air Test Data Clg Max Des. Primary Flow 1005 CFM Clg Min Des. Primary Flow 605 CFM Clg Max Act. Primary Flow 984 CFM Clg Min Act. Primary Flow 605 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC (M) Flowhood B 72X44 1.0 1005 629 984 98 1 Totals: - - - 4-1005 629 984 98 1 - Neudorfer Engineers, Inc. Page 57 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-04/VAV-119 AREA: LC (MO 201 Unit Data Manufacturer Price Model Number SDV5 VAV Address 7 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 1353.00 HRU-04/VAV-119 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/15/2018 Air Test Data Clg Max Des. Primary Flow 1005 CFM Clg Min Des. Primary Flow 605 CFM Clg Max Act. Primary Flow 974 CFM Clg Min Act. Primary Flow 605 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC (M) Flowhood B 72X44 1.0 1005 607 974 97 1 Totals: - - - 4-1005 607 974 97 1 - SYSTEM/UNIT: HRU-04/VAV-120 AREA: LC SMALL 201A Unit Data Manufacturer Price Model Number SDV5 VAV Address 8 Application # 2061 Cooling Inlet Size 4 inches Cooling K Factor 334.00 HRU-04/VAV-120 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/15/2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 106 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 23X23 1.0 105 138 106 101 1 Totals: - 105 138 106 101 Neudorfer Engineers, Inc. Page 58 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-04/VAV-121 AREA: LC SMALL 201 B Unit Data Manufacturer Price Model Number SDV5 VAV Address 9 Application # 2061 Cooling Inlet Size 4 inches Cooling K Factor 320.00 HRU-04/VAV-121 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/15/2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 107 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 23X23 1.0 105 132 107 102 1 Totals: - - - 4-105 132 107 102 1 - SYSTEM/UNIT: HRU-04/VAV-122 AREA: LC (DHH PK/K) 204 Unit Data Manufacturer Price Model Number SDV5 VAV Address 10 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 1434.00 Tested By: Dwight Hammack Date: 10/15/2018 Air Test Data Clg Max Des. Primary Flow 1000 CFM Clg Min Des. Primary Flow 600 CFM Clg Max Act. Primary Flow 1020 CFM Clg Min Act. Primary Flow 600 CFM Log: I HRU-04NAV-122 10/15/2018 Dwight Hammack (1) The volume damper is full open. HRU-04/VAV-122 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (DHH PK/K) Flowhood B 36X44 1.0 500 273 510 102 (1) Outlet-02 LC (DHH PK/K) Flowhood B 44X44 1.0 500 435 510 102 Totals: - 1000 708 1020 102 - Neudorfer Engineers, Inc. Page 59 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-04/VAV-123 AREA: LC (K) 203 Unit Data Manufacturer Price Model Number SDV5 VAV Address 11 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 1457.00 Tested By: Dwight Hammack Date: 10/15/2018 Air Test Data Clg Max Des. Primary Flow 1000 CFM Clg Min Des. Primary Flow 600 CFM Clg Max Act. Primary Flow 983 CFM Clg Min Act. Primary Flow 600 CFM Log: I HRU-04NAV-123 10/15/2018 Dwight Hammack (1) The volume damper is full open. HRU-04/VAV-123 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (K) Flowhood B 36X44 1.0 500 261 497 99 (1) Outlet-02 LC (K) Flowhood B 44X44 1.0 500 423 486 97 Totals: - - - - 1000 684 983 98 SYSTEM/UNIT: HRU-04/VAV-124 AREA: LC SMALL 203A Unit Data Manufacturer Price Model Number SDV5 VAV Address 12 Application # 2061 Cooling Inlet Size 4 inches Cooling K Factor 313.00 HRU-04/VAV-124 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/15/2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 105 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 23X23 1.0 105 264 105 100 1 Totals: - 4-105 264 105 100 Neudorfer Engineers, Inc. Page 60 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-04/VAV-125 AREA: LC SMALL 203B Unit Data Manufacturer Price Model Number SDV5 VAV Address 13 Application # 2061 Cooling Inlet Size 4 inches Cooling K Factor 319.00 HRU-04/VAV-125 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/15/2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 107 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 23X23 1.0 105 234 107 102 1 Totals: - - - 4-105 234 107 102 1 - SYSTEM/UNIT: HRU-04/VAV-126 AREA: LC (K) 207A Unit Data Manufacturer Price Model Number SDV5 VAV Address 14 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 1460.00 Tested By: Dwight Hammack Date: 10/12/2018 Air Test Data Clg Max Des. Primary Flow 1000 CFM Clg Min Des. Primary Flow 600 CFM Clg Max Act. Primary Flow 990 CFM Clg Min Act. Primary Flow 600 CFM Log: 1 HRU-041VAV-126 10/12/2018 Dwight Hammack (1) The volume damper is full open. HRU-04/VAV-126 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (K) Flowhood B 44X45 1.0 500 288 485 97 (1) Outlet-02 LC (K) Flowhood B 44X44 1.0 500 408 505 101 Totals: - 1000 696 990 99 - Neudorfer Engineers, Inc. Page 61 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-04/VAV-127 AREA: LC (K) 207B Unit Data Manufacturer Price Model Number SDV5 VAV Address 15 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 1437.00 Tested By: Dwight Hammack Date: 10/12/2018 Air Test Data Clg Max Des. Primary Flow 1000 CFM Clg Min Des. Primary Flow 600 CFM Clg Max Act. Primary Flow 988 CFM Clg Min Act. Primary Flow 600 CFM Log: I HRU-04NAV-127 10/12/2018 Dwight Hammack (1) The volume damper is full open. HRU-04/VAV-127 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (K) Flowhood B 44X45 1.0 500 346 496 99 (1) Outlet-02 LC (K) Flowhood B 43X44 1.0 500 632 492 98 Totals: - - - - 1000 978 988 99 SYSTEM/UNIT: HRU-04/VAV-128 AREA: LC SMALL 207A Unit Data Manufacturer Price Model Number SDV5 VAV Address 16 Application # 2061 Cooling Inlet Size 4 inches Cooling K Factor 410.00 HRU-04/VAV-128 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/12/2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 105 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 24X12 1.0 105 301 105 100 1 Totals: - 4-105 301 105 100 1 - Neudorfer Engineers, Inc. Page 62 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-04/VAV-129 AREA: LC SMALL 207B Unit Data Manufacturer Price Model Number SDV5 VAV Address 17 Application # 2061 Cooling Inlet Size 4 inches Cooling K Factor 328.00 HRU-04/VAV-129 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/12/2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 104 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 23X23 1.0 105 306 104 99 1 Totals: - - - 4-105 306 104 99 1 - Neudorfer Engineers, Inc. Page 63 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-05 AREA: CLASSROOMS Unit Data Unit Manufacturer D-AirTech Unit Model Number D-AHU-6 Unit Serial Number D-17-076 Unit Type Air to Air EF Fan Rotation Counterclockwise SF Fan Rotation Counterclockwise HRU-05/EF Filter Filter Manufacturer Flanders Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 12x24x2 HRU-05/SF Filter Filter Manufacturer Flanders Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 12x24x2 Filter Quantity - Size 3 3 Filter Dimensions - Size 3 24x24x4 Filter Quantity - Size 4 3 Filter Dimensions - Size 4 12x24x4 Test Data SF Total Design Flow 6640 CFM SF Total Actual Flow 6552 CFM EF Total Design Flow 6640 CFM EF Total Actual Flow 6227 CFM Log: Tested By: Dwight Hammack Date: 10/24/2018 Motor Data HRU-05/Exhaust Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP 4x2 HP Motor RPM 2270 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 8.65x2 Amps HRU-05/Supply Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP 4x2 HP Motor RPM 2494 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 8.65x2 Amps Test Pressures SF Design ESP 2.30 in. w.c. EF Actual ESP 1.70 in. w.c. HRU-05 10/12/2018 Dwight Hammack (2) The volume damper is full closed. HRU-05 10/12/2018 Dwight Hammack (1) The volume damper is full open. HRU-05 8/9/2018 Dwight Hammack Motorized damper not installed on outlet that serves mechanical room. Neudorfer Engineers, Inc. Page 64 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: HRU-05 Exhaust Inlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim ReadingReadin Final Final % Remarks Inlet-01 SMALL GROUP Flowhood E 24X12 1.0 105 62 97 92 Inlet-02 SMALL GROUP Flowhood E 24X12 1.0 105 66 103 98 Inlet-03 OPEN AREA Flowhood R 30X12 1.0 1005 1 751 916 91 1 (1) Inlet-04 OPEN AREA Flowhood R 30X12 1.0 755 812 679 90 Inlet-05 BATHROOM Flowhood E 24XS12 1.0 100 90 95 95 Inlet-06 BATHROOM Flowhood E 24X12 1.0 150 130 136 91 Inlet-07 OPEN AREA Flowhood R 30X12 1.0 1105 1070 1043 94 Inlet-08 OPEN AREA Flowhood R 30X12 1.0 1105 1175 993 90 Inlet-09 BATHROOM Flowhood E 12X12 1.0 150 354 159 106 Inlet-10 BATHROOM Flowhood E 12X12 1.0 100 159 170 170 1 (2) Inlet-11 BATHROOM Flowhood E 12X12 1.0 150 219 150 100 (2) Inlet-12 OPEN AREA Flowhood R 30X12 1.0 905 1244 837 92 Inlet-13 OPEN AREA Flowhood R 30XX12 1.0 905 856 849 94 Totals: - - - 1 6640 6988 6227 94 SYSTEM/UNIT: HRU-05/VAV-130 AREA: LC (DHH)401 Unit Data Manufacturer Price Model Number SDV5 VAV Address 23 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 1318.00 HRU-05/VAV-130 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 1005 CFM Clg Min Des. Primary Flow 605 CFM Clg Max Act. Primary Flow 1040 CFM Clg Min Act. Primary Flow 605 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC (DHH) Flowhood B 72X44 1.0 1005 630 1040 103 1 Totals: - 4-1005 630 1040 103 1 - Neudorfer Engineers, Inc. Page 65 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-05/VAV-131 AREA: LC (DHH) 402 Unit Data Manufacturer Price Model Number SDV5 VAV Address 24 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 1370.00 HRU-05/VAV-131 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 1005 CFM Clg Min Des. Primary Flow 605 CFM Clg Max Act. Primary Flow 1005 CFM Clg Min Act. Primary Flow 605 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC (DHH) Flowhood B 72X44 1.0 1005 610 1050 104 1 Totals: - - - 4-1005 610 1050 104 1 - SYSTEM/UNIT: HRU-05/VAV-132 AREA: LC SMALL 401A Unit Data Manufacturer Price Model Number SDV5 VAV Address 25 Application # 2061 Cooling Inlet Size 4 inches Cooling K Factor 282.00 HRU-05NAV-132 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 105 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 23X23 1.0 105 280 105 100 1 Totals: - - - - 105 280 105 100 Neudorfer Engineers, Inc. Page 66 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-05/VAV-133 AREA: LC SMALL 401 B Unit Data Manufacturer Price Model Number SDV5 VAV Address 26 Application # 2061 Cooling Inlet Size 4 inches Cooling K Factor 740.00 HRU-05/VAV-133 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/24/2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 107 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 23X23 1.0 105 295 107 102 1 Totals: - - - 4-105 295 107 102 1 - SYSTEM/UNIT: HRU-05/VAV-134 AREA: LC (P) 403A Unit Data Manufacturer Price Model Number SDV5 VAV Address 27 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 2141.00 Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1050 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-05/VAV-134 10/11/2018 Dwight Hammack (1) The volume damper is full open. HRU-05/VAV-134 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (P) Flowhood B 44X46 1.0 500 295 470 94 (1) Outlet-02 LC (P) Flowhood B 43X44 1.0 605 500 580 96 Totals: - 1105 795 1050 95 - Neudorfer Engineers, Inc. Page 67 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-05/VAV-135 AREA: LC (P) 403B Unit Data Manufacturer Price Model Number SDV5 VAV Address 28 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 2082.00 Tested By: Dwight Hammack Date: 10/11/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1095 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-05NAV-135 10/11/2018 Dwight Hammack (1) The volume damper is full open. HRU-05/VAV-135 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (P) Flowhood B 44X46 1.0 500 315 480 96 (1) Outlet-02 LC (P) Flowhood B 43X44 1.0 605 405 615 102 Totals: - - - - 1105 720 1095 99 SYSTEM/UNIT: HRU-05/VAV-136 AREA: LC (LO) 407A Unit Data Manufacturer Price Model Number SDV5 VAV Address 29 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 2226.00 Tested By: Dwight Hammack Date: 10/11/2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1065 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-05NAV-136 10/11/2018 Dwight Hammack (1) The volume damper is full open. HRU-05/VAV-136 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (L) Flowhood B 44X46 1.0 500 335 475 95 (1) Outlet-02 LC (L) Flowhood B 43X44 1.0 605 465 590 98 Totals: - 1105 800 1065 96 - Neudorfer Engineers, Inc. Page 68 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-05/VAV-137 AREA: LC (L) 407B Unit Data Manufacturer Price Model Number SDV5 VAV Address 30 Application # 2061 Cooling Inlet Size 12 inches Cooling K Factor 2185.00 Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1085 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-05NAV-137 10/11/2018 Dwight Hammack (1) The volume damper is full open. HRU-05/VAV-137 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (L) Flowhood B 44X46 1.0 500 270 495 99 (1) Outlet-02 LC (L) Flowhood B 43X44 1.0 605 470 590 98 Totals: - - - - - 1105 740 1085 98 - Neudorfer Engineers, Inc. Page 69 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-06 AREA: CLASSROOMS Unit Data Unit Manufacturer D-AirTech Unit Model Number D-AHU-6 Unit Serial Number D-17-077 Unit Type Air to Air EF Fan Rotation Counterclockwise SF Fan Rotation Counterclockwise HRU-06/EF Filter Filter Manufacturer Flanders Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 12x24x2 HRU-06/SF Filter Filter Manufacturer Flanders Filter Type Pleated Filter Quantity - Size 1 3 Filter Dimensions - Size 1 24x24x2 Filter Quantity - Size 2 3 Filter Dimensions - Size 2 12x24x2 Filter Quantity - Size 3 3 Filter Dimensions - Size 3 24x24x4 Filter Quantity - Size 4 3 Filter Dimensions - Size 4 12x24x4 Test Data SF Total Design Flow 6640 CFM SF Total Actual Flow 6565 CFM EF Total Design Flow 6640 CFM EF Total Actual Flow 6475 CFM Log: Tested By: Dwight Hammack Date: 10/23/2018 Motor Data HRU-06/Exhaust Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP 4x2 HP Motor RPM 2270 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 8.65x2 Amps HRU-06/Supply Fan Drive Type Direct Drive Motor Manufacturer Ziehl-Abegg Motor HP 4x2 HP Motor RPM 2494 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 8.65x2 Amps Test Pressures SF Design ESP 2.30 in. w.c. EF Actual ESP 1.70 in. w.c. HRU-06 10/12/2018 Dwight Hammack (2) The volume damper is full closed. HRU-06 10/12/2018 Dwight Hammack (1) The volume damper is full open. HRU-06 8/10/2018 Dwight Hammack Motorized damper not installed on outlet that serves mechanical room. Neudorfer Engineers, Inc. Page 70 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: HRU-06 Exhaust Inlet Summary System/Unit Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim ReadingReadin Final Final % Remarks Inlet-01 Flowhood E 24X12 1.0 105 70 100 95 Inlet-02 Flowhood E 24X12 1.0 105 85 100 95 Inlet-03 Flowhood R 30X12 1.0 755 630 740 98 Inlet-04 Flowhood R 30X12 1.0 1005 590 980 98 (1) Inlet-05 Flowhood E 12X12 1.0 150 135 145 97 Inlet-06 Flowhood E 12X12 1.0 100 140 95 95 Inlet-07 Flowhood R 30X12 1.0 1105 1075 1000 90 Inlet-08 Flowhood R 30X12 1.0 1105 980 1080 98 Inlet-09 Flowhood E 12X12 1.0 150 97 195 130 (2) Inlet-10 Flowhood E 12X12 1.0 100 1 108 145 145 (2) Inlet-11 Flowhood E 12X12 1.0 150 180 140 93 (2) Inlet-12 Flowhood R 30X12 1.0 905 180 880 97 Inlet-13 Flowhood R 30X12 1.0 905 1820 875 97 - - I - - 6640 6090 1 6475 98 - SYSTEM/UNIT: HRU-06/VAV-138 AREA: LC (M) 601 Unit Data Manufacturer Price Model Number SDV5 VAV Address 24 Application # 2051 Cooling Inlet Size 10 inches Cooling K Factor 1347.00 HRU-06/VAV-138 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/23/2018 Air Test Data Clg Max Des. Primary Flow 1005 CFM Clg Min Des. Primary Flow 605 CFM Clg Max Act. Primary Flow 990 CFM Clg Min Act. Primary Flow 605 CFM Htg Max Des. Primary Flow 605 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC (M) Flowhood B 73x44 1 1005 802 990 99 1 Totals: I- - 1 1005 802 990 99 1 - Neudorfer Engineers, Inc. Page 71 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-06/VAV-139 AREA: LC (M) 602 Unit Data Manufacturer Price Model Number SDV5 VAV Address 25 Application # 2051 Cooling Inlet Size 10 inches Cooling K Factor 1359.00 HRU-06/VAV-139 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 1005 CFM Clg Min Des. Primary Flow 605 CFM Clg Max Act. Primary Flow 990 CFM Clg Min Act. Primary Flow 605 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC (M) Flowhood B 73x44 1 1005 1 892 990 99 Totals: - - - - - 1005 1 892 990 99 1 - SYSTEM/UNIT: HRU-06/VAV-140 AREA: LC SMALL 601A Unit Data Manufacturer Price Model Number SDV5 VAV Address 26 Application # 2051 Cooling Inlet Size 4 inches Cooling K Factor 364.00 HRU-06NAV-140 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 105 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 23X23 1.0 105 210 105 100 Totals: - - - 105 210 105 100 - Neudorfer Engineers, Inc. Page 72 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-06/VAV-141 AREA: LC SMALL 601 B Unit Data Manufacturer Price Model Number SDV5 VAV Address 27 Application # 2051 Cooling Inlet Size 4 inches Cooling K Factor 422.00 HRU-06/VAV-141 Supply Outlet Summary Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 105 CFM Clg Min Des. Primary Flow 65 CFM Clg Max Act. Primary Flow 100 CFM Clg Min Act. Primary Flow 65 CFM System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Readina Final Readin Final % Remarks Outlet-01 LC SMALL Flowhood B 23X23 1.0 105 45 100 95 1 Totals: I- - 105 45 100 95 1 - SYSTEM/UNIT: HRU-06/VAV-142 AREA: LC (P) 603A Unit Data Manufacturer Price Model Number SDV5 VAV Address 28 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2118.00 Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1105 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-06NAV-142 10/10/2018 Dwight Hammack (1) The volume damper is full open. HRU-06/VAV-142 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (P) Flowhood B 44X46 1 500 485 495 99 Outlet-02 LC (P) Flowhood B 43X44 1 605 502 610 101 (1) Totals: - 1105 987 1105 100 - Neudorfer Engineers, Inc. Page 73 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-06/VAV-143 AREA: LC (P) 603B Unit Data Manufacturer NAILOR Model Number SDV5 VAV Address 29 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2203.00 Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1075 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-06NAV-143 10/10/2018 Dwight Hammack (1) The volume damper is full open. HRU-06/VAV-143 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (P) Flowhood B 44X46 1 500 447 495 99 (1) Outlet-02 LC (P) Flowhood B 43X44 1 605 539 580 96 Totals: - - - - 1105 986 1075 97 SYSTEM/UNIT: HRU-06/VAV-144 AREA: LC (L) 607A Unit Data Manufacturer Price Model Number SDV5 VAV Address 30 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2146.00 Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1090 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-06NAV-144 10/10/2018 Dwight Hammack (1) The volume damper is full open. HRU-06/VAV-144 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (L) Flowhood B 44X46 1.0 500 450 510 102 (1) Outlet-02 LC (L) Flowhood B 43X44 1.0 605 650 580 96 Totals: - - 1105 1100 1090 99 - Neudorfer Engineers, Inc. Page 74 of 93 Energy Recovery Unit PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: HRU-06/VAV-145 AREA: LC (L) 607B Unit Data Manufacturer Price Model Number SDV5 VAV Address 31 Application # 2051 Cooling Inlet Size 12 inches Cooling K Factor 2191.00 Tested By: Dwight Hammack Date: 10/11 /2018 Air Test Data Clg Max Des. Primary Flow 1105 CFM Clg Min Des. Primary Flow 665 CFM Clg Max Act. Primary Flow 1110 CFM Clg Min Act. Primary Flow 665 CFM Log: I HRU-06NAV-145 10/10/2018 Dwight Hammack (1) The volume damper is full open. HRU-06/VAV-145 Supply Outlet Summary System/Unit Area Served Type of Reading Outlet Type Size LxW / D AK Design Velocity Design Value Prelim Reading Final Reading Final % Remarks Outlet-01 LC (L) Flowhood B 44x46 1 500 458 500 100 (1) Outlet-02 LC (L) Flowhood B 43X44 1 605 650 610 101 Totals: - - - - - 1105 1108 1110 100 - Neudorfer Engineers, Inc. Page 75 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-01 Cooling Mode Final Test Data Final Disch Press. 49 PSI Final Suction Press. 26 PSI Final Press. Diff. Actual 23 PSI VFD Hertz 38.5 Hz Motor Volts T1-T2 229 Volts Motor Volts T2-T3 228 Volts Motor Volts T1-T3 229 Volts Motor Amps T1 12.8 Amps Motor Amps T2 12.8 Amps Motor Amps T3 12.7 Amps PU-01 Cooling Mode Autoflow Valve Summary Tested By: Alex Lebedev Date: 10/24/2018 System/Unit Manufacturer Model Number Valve Size Design Flow Actual Flow Design D.P. Actual D.P. AHU-01 Flow Design AC-100 1" 6.9 2-32 9 AHU-02 Flow Design AC-100 1" 6.9 2-32 12 AHU-03 Flow Design AC-125 1 1/4" 11.8 2-32 7 AHU-04 Flow Design AC-125 1 1/4" 7.8 2-32 9 AHU-05 Flow Design AC-200 2" 20 2-32 2 AHU-06 Flow Design AC-125 1 1/4" 8.0 2-32 8 AHU-07 Flow Design WS-250 2 1/2" 59.9 2-32 6 HRU-01" Flow Design AC-150 1 1/2" 17.9 2-32 12 HRU-02" Flow Design AC-150 1 1/2" 13.6 2-32 3 HRU-03" Flow Design AC-150 1 1/2" 13.6 2-32 9 HRU-04" Flow Design AC-200 2" 20 2-32 12 HRU-05" Flow Design AC-200 2" 20 2-32 11 HRU-06" Flow Design AC-200 2" 20 2-32 11 Totals: - - I - 1 0 226.4 - - Log: ng PU-01 Cooling Mode/HRU-02 PU-01 Cooling Mode/HRU-03 PU-01 Cooling Mode/HRU-04 PU-01 Cooling Mode/HRU-05 PU-01 Cooling Mode/HRU-06 Armflo. Set to 1.3ftWC each 10/24/2018 Alex Lebedev Coil has 2 sections with 2 Armstrong CBV 3/4 inch Armflo. Set to 3 ftWC each 10/24/2018 Alex Lebedev Coil has 2 sections with 2 Armstrong CBV 3/4 inch Armflo. Set to 3.3 ftWC each 10/24/2018 Alex Lebedev Coil has 2 sections with 2 Armstrong CBV 1 inch Armflo. Set to 1.5 ftWC each 10/24/2018 Alex Lebedev Coil has 2 sections with 2 Armstrong CBV 1 inch Armflo. Set to 1.6ftWC each 10/24/2018 Alex Lebedev Coil has 2 sections with 2 Armstrong CBV 1 inch Armflo. Set to 1.7 ftWC each Neudorfer Engineers, Inc. Page 76 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-01 Heating mode AREA: HYDRONIC WATER Unit Data Pump Manufacturer Armstrong Pump Model Number 4x3x11.5 Pump Serial Number 843868 Pump Flowrate 390 GPM TDH/FT 130 Final Test Data Final Disch Press. 56 PSI Final Suction Press. 22 PSI Final Press. Diff. Actual 34 PSI Final Design Flow 400 GPM Final Actual Flow 440 GPM VFD Hertz 50.1 Hz Motor Volts T1-T2 350 Volts Motor Volts T2-T3 350 Volts Motor Volts T1-T3 350 Volts Motor Amps T1 19.4 Amps Motor Amps T2 19.5 Amps Motor Amps T3 19.4 Amps Log: Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor Manufacturer Brook Crompton Motor Frame 284T Motor HP 25 HP Motor RPM 1770 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor F.L. Amps 27.9 Amps Motor S.F. 1.25 Motor Nominal Efficiency 93.6 Motor Power Factor 0.89 Pump Impeller Diam. 11.5 Measured Data Pump Off Pressure 25 PSI Valve Shut DP 72 PSI Valve Shut SP 26 PSI Valve Shut Diff. 46 PSI Valve Open DP 74 PSI Valve Open SP 22 PSI Valve Open Diff. 52.0 PSI Valve Open Flow 480 GPM PU-01 Heating mode 10/23/2018 Alex Lebedev Actual final water flow was calculated using approved pump curve provided by the manufacturer. PU-01 Heating mode 10/23/2018 Alex Lebedev System operating pressure setpoint is 20.5PS1. PU-01 Heating mode 10/17/2018 Alex Lebedev The operating Amps and Volts were recorded from the VFD. PU-01 Heating mode Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer AHU-01(info) ORCHESTRA 123 AC-100 1" 17 5.8 6.9 6.9 Flow Design AHU-02(info) BAND 121 AC-100 1" 20 5.8 6.9 6.9 Flow Design AHU-03(info) KITCHEN 117 AC-125 1 1/4" 12 10.2 11.8 11.8 Flow Design AHU-04(info) MUSIC 122 AC-125 1 1/4" 15 6.9 7.6 7.6 Flow Design AHU-05 COMMONS 115/SERVERY 115A AC-200 2" 3 28.5 32.2 32.2 Flow Design AHU-06(info) HALLWAY COMMONS 100C AC-125 1 1/4" 16 7.3 8 8 Flow Design AHU-07 GYMNASIUM 107 WS-250 2 1/2" 9 55.3 59.9 59.9 Flow Design AHU-08(info) ADMIN WING AC-150 1 1/2" 17 15.4 18 18 Flow Design HRU-01(info) CLASSROOM/ READING AC-150 1 1/2" 16 16.1 17.9 17.9 Flow Design HRU-02 CLASSROOM AC-150 1 1/2" 3 12.4 13.6 Flow Design HRU-03 CLASSROOM AC-150 1 1/2" 3 12.4 13.6 Flow Design HRU-04 CLASSROOM AC-200 2" 6 18.6 20.0 Flow Design HRU-05 CLASSROOM AC-200 2" 5 18.6 18.6 18.6 Flow Design HRU-06 CLASSROOM AC-200 2" 4 18.6 18.6 18.6 Flow Design Neudorfer Engineers, Inc. Page 77 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer PU-01 Info / VAV-129 ACM 075 3/4" 5 0.2 0.2 Flow Design RF-101 PARENT ROOM 132 AC-100 1" 18 0.9 0.9 0.9 Flow Design RF-102 MITOFF ICE 132E AC-100 1" 7 0.5 0.5 0.5 Flow Design RF-103 LC9 DHH) 134 AC-100 1" 18 2.0 2.0 2.0 Flow Design RF-104 SMALL GROUP 134A AC-100 1" 7 0.5 0.5 0.5 Flow Design RF-105 SCIPR EP 136A AC-100 1" 20 0.4 0.4 0.4 Flow Design RF-106 LC9 M SCI) 136 AC-100 1" 18 2.3 1 2.3 2.3 Flow Design RF-107 GREEN ROOM 135 AC-100 1" 7 0.4 0.4 0.4 Flow Design RF-108A/108B' LIBRARY 131 AC-100 1" 2.2 Flow Design RF-109 SMALL GROUP 131A AC-100 1" 14 0.2 0.2 0.2 Flow Design RF-110 LC (L) 305A AC-100 1" 7 2.6 2.6 Flow Design RF-111 LC (L) 305B AC-100 1" 7 2.5 2.5 Flow Design RF-112 LC (P) 301A AC-100 1" 9 2.5 2.5 Flow Design RF-113 LC (P) 301 B AC-100 1" 8 2.5 2.5 Flow Design RF-114 LC (L) 505A AC-100 1" 6 2.5 2.5 Flow Design RF-115 LC (L) 505B AC-100 1" 5 2.5 2.5 Flow Design RF-116 LC (P) 501A AC-100 1" 5 2.5 2.5 Flow Design RF-117 LC (P) 501 B AC-100 1" 5 2.5 2.5 Flow Design RF-118 LC (M) 201 AC-100 1" 5 2.3 1 2.3 2.3 Flow Design RF-119 LC (M) 202 AC-100 1" 5 2.3 2.3 2.3 Flow Design RF-120 LC SMALL 201 A AC-100 1" 5 0.4 0.4 0.4 Flow Design RF-121 LC SMALL 201 B AC-100 1" 5 0.2 0.2 0.2 Flow Design RF-122' LC (DHH/PK/K) 204 AC-100 1" 1 2.1 Flow Design RF-123 LC (K) 203 AC-100 1" 4 2.1 2.5 Flow Design RF-124 SMALL GROUP 203A AC-100 1" 8 0.2 0.2 Flow Design RF-125 SMALL GROUP 203E AC-100 1" 3 0.2 0.2 0.2 Flow Design RF-126 LC (K) 207 AC-100 1" 10 2.3 2.5 Flow Design RF-127' LC (L) 208 AC-100 1" 2.3 Flow Design RF-128' SMALL GROUP 207A AC-100 1" 0.2 Flow Design RF-129" SMALL GROUP 207B AC-100 1" 1.0 0.3 Flow Design RF-130 LC (DHH) 401 AC-100 1/2" 8 2.3 2.3 2.3 Flow Design RF-131 LC9 DHH) 402 AC-100 3/4" 3 2.3 2.3 2.3 Flow Design RF-132 LC SMALL 401A AC-100 1/2" 7 0.4 0.4 0.4 Flow Design RF-133 LC SMALL 401B AC-100 1/2" 4 0.2 0.2 0.2 Flow Design RF-134 LC (P) 403A AC-100 3/4" 5 2.5 2.5 2.5 Flow Design RF-135 LC (P) 403B AC-100 3/4" 4 2.5 2.5 2.5 Flow Design RF-136 LC (L) 407A AC-100 3/4" 7 2.5 2.5 2.5 Flow Design RF-137 LC (L) 407B AC-100 3/4" 8 2.5 2.5 2.5 Flow Design RF-138 LC (M) 601 AC-100 3/4" 6 2.3 2.3 2.3 Flow Design RF-139 LC (M) 602 AC-100 3/4" 5 2.3 2.3 2.3 Flow Design RF-140 LC SMALL 601 A AC-100 1/2" 5 0.4 0.4 0.4 Flow Design RF-141 LC SMALL 601 B AC-100 1/2" i i 4 0.2 0.2 0.2 Flow Design Neudorfer Engineers, Inc. Page 78 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer RF-142 LC (P) 603A AC-100 3/4" 4 2.5 2.5 2.5 Flow Design RF-143 AC-100 3/4" 5 2.5 2.5 2.5 Flow Design RF-144 LC (L) 607A AC-100 3/4" 4 2.5 2.5 2.5 Flow Design RF-145 LC (L) 607B AC-100 3/4" 4 2.5 2.5 2.5 Flow Design VAV-101 PARENT ROOM 132 ACM-075 3/4" 20 0.9 0.9 0.9 Flow Design VAV-102" MIT OFFICE 132B ACM-075 3/4" 0.3 Flow Design VAV-103 LG (DHH) 134 ACM-075 1/2" 22 1.6 1.6 1.6 Flow Design VAV-104 SMALL GROUP 134A ACM-075 3/4" 20 0.2 0.2 0.2 Flow Design VAV-105` SCI PREP 136A ACM-075 3/4" 0.4 Flow Design VAV-106 LC (M SCI) 136 ACM-075 3/4" 21 2.0 2.0 2.0 Flow Design VAV-107 GREEN ROOM 135 ACM-075 3/4" 20 0.6 0.6 0.6 Flow Design VAV-108 LIBRARY 131 AC-100 3/4" 20 3.7 3.7 3.7 Flow Design VAV-109 SMALL GROUP 131A ACM-075 3/4" 5 0.2 0.2 0.2 Flow Design VAV-110 LC (L) 305A ACM 075 3/4" 3 1.9 1.9 Flow Design VAV-111 LC (L) 305B ACM 075 3/4" 9 1.9 1.9 Flow Design VAV-112 LC (P) 301A ACM 075 3/4" 5 1.9 1.9 Flow Design VAV-113 LC (P) 301 B ACM 075 3/4" 3 1.9 1.9 Flow Design VAV-114 LC (L) 505A ACM 075 3/4" 3 1.9 1.9 Flow Design VAV-115 LC (L) 505B ACM 075 3/4" 4 1.9 1 1.9 Flow Design VAV-116 LC (P) 501A ACM 075 3/4" 4 1.9 1.9 Flow Design VAV-117 LC (P) 501 B ACM 075 3/4" 4 1.9 1.9 Flow Design VAV-118 LC (M) 201 ACM 075 3/4" 3 1.7 1.7 1.7 Flow Design VAV-119 LC (MO 201 ACM 075 3/4" 6 1.7 1.7 1.7 Flow Design VAV-120 LC SMALL 201 A ACM 075 3/4" 5 0.2 0.2 0.2 Flow Design VAV-121 LC SMALL 201 B ACM 075 3/4" 3 0.2 0.2 0.2 Flow Design VAV-122* LC (DHH PK/K) 204 ACM 075 3/4" 4 1.7 1.7 1.7 Flow Design VAV-123 LC (K) 203 ACM 075 3/4" 7 1.7 1.7 Flow Design VAV-124 LC SMALL 203A ACM 075 3/4" 7 0.2 0.2 0.2 Flow Design VAV-125 LC SMALL 203B ACM 075 3/4" 5 0.2 0.2 0.2 Flow Design VAV-126 LC (K) 207A ACM 075 3/4" 8 1.7 1.7 1.7 Flow Design VAV-127 LC (K) 207B ACM 075 3/4" 8 1.7 1.7 Flow Design VAV-128 LC SMALL 207A ACM-075 1/2" 5 0.2 0.2 0.2 Flow Design VAV-129 LC SMALL 207B ACM-075 1/2" 5 0.2 0.2 0.2 Flow Design VAV-130 LC (DHH)401 ACM-075 3/4" 41 3 1.7 1.7 1.7 Flow Design VAV-131 LC (DHH) 402 ACM-075 1/2" 4 1.7 1.7 1.7 Flow Design VAV-132 LC SMALL 401A ACM-075 1/2" 2 0.2 0.2 0.2 Flow Design VAV-133 LC SMALL 401E ACM-075 1/2" 8 0.2 0.2 0.2 Flow Design VAV-134 LC (P) 403A ACM-075 1/2" 5 1.9 1.9 1.9 Flow Design VAV-135 LC (P) 403B ACM-075 1/2" 7 1.9 1.9 1.9 Flow Design VAV-136 LC (LO) 407A ACM-075 1/2" 4 1.9 1.9 1.9 Flow Design VAV-137 LC (L) 407B ACM-075 1/2" 4 1.9 1.9 1.9 Flow Design VAV-138 LC (M) 601 ACM-075 1/2" 5 1.7 1.7 1.7 Flow Design VAV-139 LC (M) 602 ACM-075 1/2" 5 1.7 1.7 1.7 Flow Design Neudorfer Engineers, Inc. Page 79 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: System/Unit Area Served Model Number Valve Size Valve DP Actual Design Prelim. Actual Manufacturer Position Flow Flow Flow VAV-140 LC SMALL ACM-075 1/2" 7 0.2 0.2 0.2 Flow Design 601 A VAV-141 LC SMALL ACM-075 1/2" 5 0.2 0.2 0.2 Flow Design 601 B VAV-142 LC (P) 603A ACM-075 1/2" 4 1.9 1 1.9 1.9 Flow Design VAV-143 LC (P) 603B ACM-075 1/2" 5 1.9 1.9 1.9 Flow Design VAV-144 LC (L) 607A ACM-075 1/2" 6 1.9 1.9 1.9 Flow Design VAV-145 LC (L) 607B ACM-075 1/2" 4 1.9 1.9 1.9 Flow Design VAV-146 DEN 104 AC-100 1" 17 3.5 3.5 3.5 Flow Design VAV-147 COUNSELOR ACM-075 3/4" 3 0.4 0.4 0.4 Flow Design 103 VAV-148 SMALL GROUP ACM-075 3/4" 3 0.5 0.5 0.5 Flow Design 102A VAV-149 SMALL GROUP ACM-075 3/4" 7 0.9 0.9 0.9 Flow Design 102B VAV-150 LEARENING AC-100 1" 18 3.9 3.9 3.9 Flow Design SUPPORT 102 VAV-151wood LOBBY 100A 1.3 ceiling* VAV-152 RECEPTION AC-100 3/4" 20 3.5 3.5 3.5 Flow Design OFFICE 101 VAV-153 CONFERENCE ACM-075 3/4" 22 1.0 1.0 1.0 Flow Design 101A VAV-154 HEALTH ACM-075 3/4" 7 0.8 0.8 0.8 Flow Design CLINIC 101B VAV-155 COT ROOM ACM-075 3/4" 5 1.1 1.1 1.1 Flow Design 101 D VAV-156 OFFICE MGR ACM-075 3/4" 18 0.9 0.9 0.9 Flow Design 101C VAV-157 DEAN/RECOR ACM-075 3/4" 5 2.0 2.0 2.0 Flow Design D STG 101 E/101 K VAV-158 DHH OFFICES ACM-075 3/4" 17 1.3 1.3 1.3 Flow Design 101 N/101 L VAV-159 AP ACM-075 3/4" 17 1.9 1.9 1.9 Flow Design OFFICE/DHH RECEPT 101 R/101 Q VAV-160 P OFFICE ACM-075 3/4" 18 1.0 1.0 1.0 Flow Design 101S VAV-161 WORKROOM ACM-075 3/4" 16 0.8 0.8 0.8 Flow Design 101 M VAV-162 STAFF OFFICE ACM-075 3/4" 17 1.8 1.9 1.9 Flow Design 101P VAV-163 PROF ACM-075 3/4" 17 2.0 2.0 2.0 Flow Design DEVELOPEME NT 101T VAV-164 SLP 108 ACM-075 3/4" 8 0.4 1 0.4 0.4 Flow Design VAV-165 DHH ACM-075 3/4" 11 0.4 0.4 0.4 Flow Design PYCH/COUNS 109 VAV-166` AUDIO/DHH ACM-075 3/4" 0.4 Flow Design SLP 110 VAV-167 OT/PT 122 ACM-075 3/4" 21 1.2 1.2 1.2 Flow Design Totals: - - - 397.199999 318.8 410.099999 - 999999 999999 Neudorfer Engineers, Inc. Page 80 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT LOCATION: EDMONDS, WA PROJECT #: 2017-557 Log: I PU-01 Heating mode/RF-129 10/18/2018 PU-01 Heating mode/RF-108A/108B 10/23/2018 Alex Lebedev PU-01 Heating mode/RF-122 10/18/2018 Alex Lebedev PU-01 Heating mode/RF-127 10/18/2018 Alex Lebedev PU-01 Heating mode/RF-128 10/18/2018 Alex Lebedev PU-01 Heating mode/RF-129 10/18/2018 Alex Lebedev PU-01 Heating mode/VAV-102 10/22/2018 Alex Lebedev PU-01 Heating mode/VAV-105 PU-01 Heating mode/VAV-122 PU-01 Heating mode/VAV-1 51 wood ceiling PU-01 Heating mode/VAV-166 SYSTEM/UNIT: PU-02 Cooling mode 10/22/2018 Alex Lebedev 10/22/2018 Alex Lebedev 10/23/2018 Alex Lebedev 10/22/2018 Alex Lebedev Final Test Data Final Disch Press. 48 PSI Final Suction Press. 26 PSI Final Press. Diff. Design 22 PSI VFD Hertz 38.5 Hz Motor Volts T1-T2 230 Volts Motor Volts T2-T3 229 Volts Motor Volts T1-T3 230 Volts Motor Amps T1 13.2 Amps Motor Amps T2 13.2 Amps Motor Amps T3 13.3 Amps DATE: 10/25/2018 CONTACT: AUTHOR: DP across the RF is 10PS1 DP across the auto flow valve is approximately 1 PSI. Return pipe is warm. Control and autoflow valve are installed backwards. Auto flow valve is installed upstream from the control valve No DP was measured across the valve No DP was measured across the valve No DP was measured across the valve No DP was measured across the valve Auto flow valve is installed in the HHW supply pipe. Should be in the return line after CTV. DP across auto flow valve is 1 PSI DP across control valve 23 PSI DP across the coil 2 PSI Control valve should be checked out Was Pulsing at 52HZ Access Coil piped backwards. Enterina P=30 leavina P=53 Tested By: Alex Lebedev Date: 10/24/2018 Neudorfer Engineers, Inc. Page 81 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-02 Heating mode AREA: HYDRONIC WASTER Unit Data Pump Manufacturer Armstrong Pump Model Number 4030 4X3x11.5 BF STD Pump Serial Number 843869 Pump Flowrate 390 GPM TDH/FT 130 Final Test Data Final Disch Press. 56 PSI Final Suction Press. 23 PSI Final Press. Diff. Design 33 PSI Final Press. Diff. Actual 33 PSI Final Design Flow 400 GPM Final Actual Flow 450 GPM VFD Hertz 50.1 Hz Motor Volts T1-T2 350 Volts Motor Volts T2-T3 350 Volts Motor Volts T1-T3 350 Volts Motor Amps T1 19.7 Amps Motor Amps T2 19.7 Amps Motor Amps T3 19.8 Amps Log: Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor Manufacturer Brook Crompton Motor Frame 284T Motor HP 25 HP Motor RPM 1770 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor F.L. Amps 27.9 Amps Motor S.F. 1.25 Motor Nominal Efficiency 93.6 Motor Power Factor 0.89 Pump Impeller Diam. 11.5 Measured Data Pump Off Pressure 25 PSI Valve Shut DP 72 PSI Valve Shut SP 27 PSI Valve Shut Diff. 45 PSI Valve Open DP 73 PSI Valve Open SP 23 PSI Valve Open Diff. 50.0 PSI Valve Open Flow 500 GPM PU-02 Heating mode 10/23/2018 Alex Lebedev System operating pressure setpoint is 20.5PS1. PU-02 Heating mode 10/23/2018 Alex Lebedev Actual final water flow was calculated using approved pump curve provided by the manufacturer. PU-02 Heating mode 10/17/2018 Alex Lebedev The operating Amps and Volts were recorded from the VFD. PU-02 Heating mode Balance Valve Summary System/Unit Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 - - - - 0 0 0 - Neudorfer Engineers, Inc. Page 82 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-03 Info AREA: DOMESTIC WATER BOOSTER Unit Data Pump Manufacturer Armstrong Pump Model Number VMS-1503B Pump Serial Number 555499-02 Pump Flowrate 70 GPM TDH/FT 162 PU-03 Info Balance Valve Summary Tested By: Vinh Nguyen Date: 7/6/2018 Motor Data Motor Manufacturer Armstrong Motor Frame 184TC Motor HP 5 HP Motor RPM 3515 RPM Motor Rated Volts 208-230/416-460/480 Volts Motor Phase 3 Motor Hertz 60 Hz Motor F.L. Amps 13-11.6/6.5-5.8/5.6 Amps Motor S.F. 1.25 Motor Nominal Efficiency 88.5 Motor Power Factor 0.90 System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 DOMESTIC CBV 2" 70 Armstrong BOOSTER PUMP Totals: - - - 70 0 0 - SYSTEM/UNIT: PU-04 Info AREA: DOMISTIC WATER BOOSTER Unit Data Pump Manufacturer B & G Pump Model Number FLOWTHERM /70 VS Pump Serial Number 555499-01 Pump Flowrate 70 GPM TDH/FT 162 PU-04 Info Balance Valve Summary Tested By: Vinh Nguyen Date: 7/6/2018 Motor Data Motor Manufacturer Armstrong Motor Frame 184TC Motor HP 5 HP Motor RPM 3515 RPM Motor Rated Volts 208-230/416-460/480 Volts Motor Phase 3 Motor Hertz 60 Hz Motor F.L. Amps 13-11.6/6.5-5.8/5.6 Amps Motor S.F. 1.25 Motor Nominal Efficiency 88.5 Motor Power Factor 0.90 System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 DOMESTICV CBV 2" 70 Armstrong BOOSTER PUMP Totals: - 70 0 0 Neudorfer Engineers, Inc. Page 83 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-05 AREA: BOILER CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number 3X3X6 4380 Pump Serial Number 842226 Pump Flowrate 180 GPM TDH/FT 20 Final Test Data Final Disch Press. 33.6 PSI Final Suction Press. 25.4 PSI Final Press. Diff. Actual 8.2 PSI Final Design Flow 180 GPM Final Actual Flow 180 GPM Motor Volts T1-T2 483 Volts Motor Volts T2-T3 482 Volts Motor Volts T1-T3 482 Volts Motor Amps T1 2.2 Amps Motor Amps T2 2.3 Amps Motor Amps T3 2.2 Amps PU-05 Balance Valve Summary Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor Manufacturer WEG Motor Frame 143 Motor HP 2 HP Motor RPM 1750 RPM Motor Rated Volts 230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor F.L. Amps 5.52/2.76 Amps Motor S.F. 1.25 Motor Nominal Efficiency 86.5 Measured Data Pump Off Pressure 28 PSI Valve Shut DP 42 PSI Valve Shut SP 27.8 PSI Valve Shut Diff. 14.2 PSI System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 BOILER CIRC CBV 4" 4.75 7.0 180 235 180 TA Totals: - - - 180 235 180 Neudorfer Engineers, Inc. Page 84 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-06 AREA: BOILER CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number 3X3X6 4380 Pump Serial Number 842227 Pump Flowrate 180 GPM TDH/FT 20 Final Test Data Final Disch Press. 36.9 PSI Final Suction Press. 24.9 PSI Final Press. Diff. Actual 8.0 PSI Final Design Flow 180 GPM Final Actual Flow 185 GPM Motor Volts T1-T2 482 Volts Motor Volts T2-T3 483 Volts Motor Volts T1-T3 482 Volts Motor Amps T1 2.3 Amps Motor Amps T2 2.3 Amps Motor Amps T3 2.4 Amps PU-06 Balance Valve Summary Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor Manufacturer WEG Motor Frame 143 Motor HP 2 HP Motor RPM 1750 RPM Motor Rated Volts 230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor F.L. Amps 5.52/2.76 Amps Motor S.F. 1.25 Motor Nominal Efficiency 86.5 Measured Data Pump Off Pressure 28 PSI Valve Shut DP 42.9 PSI Valve Shut SP 28.5 PSI Valve Shut Diff. 14.3 PSI System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 BOILER CIRC CBV 4" 4.75 7.2 180 240 185 TA Totals: - - - 180 1 240 185 Neudorfer Engineers, Inc. Page 85 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-07 AREA: DOMESTIC HW CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number ASTRO 280ss Pump Serial Number 110233-321 Pump Flowrate 12 GPM TDH/FT 10 Final Test Data Final Design Flow 12 GPM Final Actual Flow 12.2 GPM Motor Volts T1-T2 118 Volts Motor Amps T1 1.3 Amps Log: Tested By: Dwight Hammack Date: 10/17/2018 Motor Data Motor HP 1/6 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor F.L. Amps 1.3 Amps PU-07 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and discharge side of the pump water flow was measured using CBV installed on the discharge side of the pump. PU-07 10/17/2018 Dwight Hammack Pump is on low speed. PU-07 Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve DP Actual Design Prelim. Actual Manufacturer Position Flow Flow Flow Valve-01 DOMESTIC Arm FLo 1" 4 Turns 1.8 12 18.26 12.2 Armstrong HW CIRC Totals: - 12 18.26 12.2 Neudorfer Engineers, Inc. Page 86 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-08 AREA: DOMESTIC HW CIRC Unit Data Pump Manufacturer B & G Pump Model Number SERIES PL-36B Pump Serial Number 110233-321 Pump Flowrate 12 GPM TDH/FT 10 Final Test Data Final Design Flow 12 GPM Final Actual Flow 12.2 GPM Motor Volts T1-T2 118 Volts Motor Amps T1 0.9 Amps Log: Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor HP 1/6 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor F.L. Amps 1.3 Amps PU-08 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and discharge side of the pump water flow was measured using CBV installed on the discharge side of the pump. PU-08 10/24/2018 Alex Lebedev Pump is not making any water flow. The water line is cold. PU-08 Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve DP Actual Design Prelim. Actual Manufacturer Position Flow Flow Flow Valve-01 KITCHEN HW Arm FLo 3/4" 6 Turns 12 Armstrong CIRC Totals: - - - 12 0 0 - Neudorfer Engineers, Inc. Page 87 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-09 AREA: AWHP CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number 2X2X6 4380 Pump Serial Number 843614 Pump Flowrate 92 GPM TDH/FT 30 Final Test Data Final Disch Press. 32 PSI Final Suction Press. 26 PSI Final Press. Diff. Actual 6 PSI Final Design Flow 92 GPM Final Actual Flow 92 GPM VFD Hertz 45 Hz Motor Volts T1-T2 293 Volts Motor Volts T2-T3 292 Volts Motor Volts T1-T3 293 Volts Motor Amps T1 1.74 Amps Motor Amps T2 1.75 Amps Motor Amps T3 1.74 Amps Log: Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor Manufacturer Brook Crompton Motor Frame 145JM Motor HP 2 HP Motor RPM 1710 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor F.L. Amps 2.9 Amps Motor S.F. 1.25 Motor Nominal Efficiency 86.5 Motor Power Factor 0.74 Measured Data Pump Off Pressure 23 PSI Valve Shut DP 40 PSI Valve Shut SP 23 PSI Valve Shut Diff. 17 PSI Valve Open Flow 100 GPM PU-09 10/24/2018 Alex Lebedev Final water flow was measured at the balancing valve installed on the discharge side of the pump. PU-09 10/24/2018 Alex Lebedev System operating pressure setpoint is 2.8 PSI. PU-09 10/24/2018 Alex Lebedev The operating Amps and Volts were recorded from the VFD. PU-09 Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 WHP CIRC CBV 3" 6.5 1.8 92 95 95 TA Totals: - - - 92 1 95 95 Neudorfer Engineers, Inc. Page 88 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-10 AREA: DOMESTIC HW CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number Astro 28OSS Pump Flowrate 12 GPM TDH/FT 10 Final Test Data Final Design Flow 12 GPM Final Actual Flow 4.2 GPM Motor Volts T1-T2 119 Volts Motor Amps T1 1.3 Amps Log: Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor HP 1/6 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor F.L. Amps 1.9 Amps PU-10 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and discharge side of the pump water flow was measured using CBV installed on the discharge side of the pump. PU-10 10/17/2018 Alex Lebedev Pump is operating in high speed. PU-10 10/24/2018 Alex Lebedev Flow is 35% of design Water is hot in 30 seconds PU-10 Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 DOMESTIC H Arm FLo 3/4" 6 1.5 12 4.2 4.2 Armstrong CIRC (MECH 206 Totals: - - - 12 4.2 4.2 Neudorfer Engineers, Inc. Page 89 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-11 AREA: DOMESTIC HW CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number Astro 28OSS Pump Flowrate 12 GPM TDH/FT 10 Log: Tested By: Alex Lebedev Date: 10/17/2018 Motor Data Motor HP 1/6 HP Motor Phase 1 Motor Hertz 60 Hz Motor F.L. Amps 1.9 Amps PU-11 10/17/2018 Alex Lebedev Testing ports are not installed on the suction and discharge side of the pump. PU-11 10/17/2018 Alex Lebedev Pump is not operating. Motor is making humming noise but not rotating. Motor is hot PU-11 Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 DOMESTIC Arm FLo 3/4" 6 12 Armstrong HW CIRC MECH 504 Totals: - - 12 0 0 - SYSTEM/UNIT: PU-12 AREA: DOMESTIC HW CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number Astro 280SS Pump Flowrate 12 GPM TDH/FT 10 Log: Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor HP 1/6 HP Motor Phase 1 Motor Hertz 60 Hz PU-12 10/17/2018 Alex Lebedev Testing ports are not installed on the suction and discharge side of the pump. PU-12 10/24/2018 Alex Lebedev Pump is not operating. Motor is making humming noise but not motor is hot PU-12 Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 DOMESTIC Arm FLo 3/4" 12 Armstrong HW CIRC MECH 304 Totals: - - - 12 0 0 - Neudorfer Engineers, Inc. Page 90 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-13 AREA: DOMESTIC HW CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number Astro 28OSS Pump Flowrate 12 GPM TDH/FT 10 Final Test Data Final Design Flow 12 GPM Final Actual Flow 6.3 GPM Motor Volts T1-T2 120 Volts Motor Amps T1 1.4 Amps Log: Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor HP 1/6 HP Motor Phase 1 Motor Hertz 60 Hz Motor F.L. Amps 1.9 Amps PU-13 10/24/2018 Alex Lebedev Pump is operating in high speed. PU-13 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and discharge side of the pump water flow was measured using CBV installed on the discharge side of the pump. PU-13 10/24/2018 Alex Lebedev Flow is 53% of design Water is hot in the toilet sink in 30 seconds PU-13 Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 DOMESTIC Arm FLo 3/4" 6 3.1 12 6.3 6.3 Armstrong HW CIRC MECH 406 Totals: - - - 12 6.3 6.3 Neudorfer Engineers, Inc. Page 91 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-14 AREA: DOMESTIC HW CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number Astro 28OSS Pump Flowrate 12 GPM TDH/FT 10 Final Test Data Final Design Flow 12 GPM Final Actual Flow 6.6 GPM Motor Volts T1-T2 120 Volts Motor Amps T1 1.8 Amps Log: Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor HP 1/6 HP Motor Phase 1 Motor Hertz 60 Hz Motor F.L. Amps 1.9 Amps PU-14 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and discharge side of the pump water flow was measured using CBV installed on the discharge side of the pump. PU-14 10/24/2018 Alex Lebedev Pump is operating in high speed. PU-14 10/24/2018 Alex Lebedev Flow is 55% of design Water is hot in the toilet sink in 1 minute PU-14 Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 DOMESTIC Arm FLo 3/4" 6 3.4 12 6.6 6.6 Armstrong HW CIRC MECH 606 Totals: - - - 12 6.6 6.6 Neudorfer Engineers, Inc. Page 92 of 93 Hydronic Pump PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018 LOCATION: EDMONDS, WA CONTACT: PROJECT #: 2017-557 AUTHOR: SYSTEM/UNIT: PU-15 AREA: SCIENCE HW CIRC Unit Data Pump Manufacturer Armstrong Pump Model Number Astro 280SS Pump Flowrate 12 GPM TDH/FT 10 Final Test Data Final Design Flow 12 GPM Final Actual Flow 4.3 GPM Motor Volts T1-T2 117 Volts Motor Amps T1 1.3 Amps Log: Tested By: Alex Lebedev Date: 10/24/2018 Motor Data Motor HP 1/6 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor F.L. Amps 1.9 Amps PU-15 10/24/2018 Alex Lebedev Pump is operating in high speed. PU-15 10/17/2018 Alex Lebedev Testing ports are not installed on the suction and discharge side of the pump water flow was measured using CBV installed on the discharge side of the pump. PU-15 10/24/2018 Alex Lebedev Flow is 36% of design Water is hot in 30 seconds PU-15 Balance Valve Summary System/Unit Area Served Model Number Valve Size Valve Position DP Actual Design Flow Prelim. Flow Actual Flow Manufacturer Valve-01 SCIENCE HW Armflo 3/4" 6 1.4 12 4.3 4.3 Armstrong CIRC (SCI PREP 136A Totals: 12 4.3 4.3 Neudorfer Engineers, Inc. Page 93 of 93