Preliminary TAB_10.25.18Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-01(info)
AREA: ORCHESTRA 123
Unit Data
Unit Manufacturer
D-AIRTECH
Unit Model Number
D-AHU 2
Unit Serial Number
D-18-002
AHU-01(info)/SF Filter Bank
Filter Type
Pleated
Filter Quantity - Size 1
1
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
1
Filter Dimensions - Size 2
12x24x4
Filter Quantity - Size 3
1
Filter Dimensions - Size 3
12x24x2
Filter Quantity - Size 4
1
Filter Dimensions - Size 4
24x24x2
Test Data
Total Design Flow 1500 CFM
CA Design Flow 900 CFM
AHU-01(info) Supply Outlet Summary
Tested By: Dwight Hammack
Date: 9/24/2018
Motor Data
AHU-01(info)/Supply Fan
Motor HP
1-1.08 HP
Motor Phase
3
Motor Hertz
60 Hz
Test Pressures
SF Design External SP
1.6 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
ORCHESTRA
Flowhood
C
101,
1.0
225
123
Outlet-02
ORCHESTRA
Flowhood
C
12"
1.0
225
123
Outlet-03
ORCHESTRA
Flowhood
C
101,
1.0
175
123
Outlet-04
ORCHESTRA
Flowhood
C
101,
1.0
175
123
Outlet-05
ORCHESTRA
Flowhood
C
101,
1.0
175
123
Outlet-06
ORCHESTRA
Flowhood
C
101,
1.0
175
123
Outlet-07
ORCHESTRA
Flowhood
C
101,
1.0
175
123
Outlet-08
ORCHESTRA
Flowhood
C
10"
1.0
175
123
Totals:
-
1500
0
0
0
Neudorfer Engineers, Inc. Page 1 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-02(info)
AREA: BAND 121
Unit Data
Unit Manufacturer
D-AIRTECH
Unit Model Number
D-AHU 2
Unit Serial Number
D-18-003
AHU-02(info)/SF Filter Bank
Filter Type
Pleated
Filter Quantity - Size 1
1
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
1
Filter Dimensions - Size 2
12x24x4
Filter Quantity - Size 3
1
Filter Dimensions - Size 3
12x24x2
Filter Quantity - Size 4
1
Filter Dimensions - Size 4
24x24x2
Test Data
Total Design Flow 1500 CFM
OA Design Flow 900 CFM
AHU-02(info) Supply Outlet Summary
Tested By: Dwight Hammack
Date: 9/24/2018
Motor Data
AHU-02(info)/Supply Fan
Motor HP
1-1.08 HP
Motor Phase
3
Motor Hertz
60 Hz
Test Pressures
SF Design External SP
1.6 in. we
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
BAND 121
Flowhood
C
101,
1.0
225
Outlet-02
BAND 121
Flowhood
C
101,
1.0
225
Outlet-03
BAND 121
Flowhood
C
101,
1.0
175
Outlet-04
BAND 121
Flowhood
C
101,
1.0
175
Outlet-05
BAND 121
Flowhood
C
101,
1.0
175
Outlet-06
BAND 121
Flowhood
C
101,
1.0
175
Outlet-07
BAND 121
Flowhood
C
101,
1.0
175
Outlet-08
BAND 121
Flowhood
C
101,
1.0
175
Totals:
-
-
-
-
-
1500
0
0
0
-
Neudorfer Engineers, Inc. Page 2 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-03(info)
AREA: KITCHEN 117
Unit Data
Unit Manufacturer
D-AIRTECH
Unit Model Number
D-AHU 2
Unit Serial Number
D-18-004
Unit Discharge
Top Horizontal
AHU-03(info)/SF Filter Bank
Filter Type
Pleated
Filter Quantity - Size 1
1
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
1
Filter Dimensions - Size 2
12x24x4
Filter Quantity - Size 3
1
Filter Dimensions - Size 3
24x24x2
Filter Quantity - Size 4
1
Filter Dimensions - Size 4
12x24x2
Test Data
Total Design Flow
1500 CFM
Total Actual Flow
1565 CFM
OA Design Flow
780 CFM
RA Design Flow
1500 CFM
EA Design Flow
1500 CFM
EA Actual Flow
1493 CFM
AHU-03(info) Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/24/2018
Motor Data
AHU-03(info)/Return/Relief fan
Motor HP
1-0.665 HP
Motor Phase
3
Motor Hertz
60 Hz
AHU-03(info)/Supoly Fan
Motor HP
1.1.08 HP
Motor Phase
3
Motor Hertz
60 Hz
Test Pressures
SF Design External SP 1.6 in. we
RF Design External SP 1.5 in. we
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
KITCHEN 117
Flowhood
A
101,
1.0
300
269
312
104
(1)
Outlet-02
KITCHEN 117
Flowhood
A
101,
1.0
300
263
305
102
Outlet-03
KITCHEN 117
Flowhood
A
101,
1.0
300
278
324
108
Outlet-04
KITCHEN 117
Flowhood
A
101,
1.0
300
271
314
105
Outlet-05
KITCHEN 117
Flowhood
A
10"
1.0
300
267
310
103
Totals:
-
-
-
-
I -
1 1500
1348
1565
104
-
AHU-03(info) Return Inlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size LxW /
D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Inlet-01
KITCHEN
Flowhood
RG
24x24
1.0
1500
1387
1493
100
Totals:
-
-
1500
1387
1493
100
Neudorfer Engineers, Inc. Page 3 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-04(info)
AREA: MUSIC 122
Unit Data
Unit Manufacturer
D-AIRTECH
Unit Model Number
D-AHU 2
Unit Serial Number
D-18-005
AHU-04(info)/SF Filter Bank
Filter Type
Pleated
Filter Quantity - Size 1
1
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
1
Filter Dimensions - Size 2
12x24x4
Filter Quantity - Size 3
1
Filter Dimensions - Size 3
12x24x2
Filter Quantity - Size 4
1
Filter Dimensions - Size 4
24x24x2
Test Data
Total Design Flow 1800 CFM
OA Design Flow 1080 CFM
AHU-04(info) Supply Outlet Summary
Tested By: Dwight Hammack
Date: 9/24/2018
Motor Data
AHU-04(info)/Supply Fan
Motor HP
1-1.22 HP
Motor Phase
3
Motor Hertz
60 Hz
Test Pressures
SF Design External SP
1.6 in. we
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
MUSIC 122
Flowhood
C
12"
1.0
360
Outlet-02
MUSIC 122
Flowhood
C
12"
1.0
360
Outlet-03
MUSIC 122
Flowhood
C
12"
1.0
360
Outlet-04
MUSIC 122
Flowhood
C
12"
1.0
360
Outlet-05
MUSIC 122
Flowhood
C
12"
1.0
360
Totals:
-
-
-
I -
1 1800
0
0
1 0
AHU-04(info) Return Inlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size LxW /
D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Inlet-01
MUSIC
Flowhood
1.0
Totals:
-
-
0
0
1 0
1 0
Neudorfer Engineers, Inc. Page 4 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-05(info)
AREA: COMMONS 115/SERVERY 115A
Unit Data
Unit Manufacturer
D-AIRTECH
Unit Model Number
D-AHU 6
Unit Serial Number
D-18-006
Fan Rotation
Counterclockwise
AHU-05(info)/SF Filter Bank
Filter Type
Pleated
Filter Quantity - Size 1
4
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
4
Filter Dimensions - Size 2
24x24x2
Filter Quantity - Size 3
2
Filter Dimensions - Size 3
12x24x2
Filter Quantity - Size 4
2
Filter Dimensions - Size 4
12x24x4
Test Data
Total Design Flow 5800 CFM
CA Design Flow 3480 CFM
Tested By: Dwight Hammack
Date: 9/24/2018
Motor Data
AHU-05(info)/Supply Fan
Drive Type
Direct Drive
Motor Manufacturer
Rosenberg
Motor HP
(2)4.42 HP
Motor RPM
2636 RPM
Motor Rated Volts
480 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
(2)4.4 Amps
Test Pressures
SF Design External SP 1.8 in. we
Neudorfer Engineers, Inc. Page 5 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
AHU-05(info) Supply Outlet Summary
System/Unit
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
Flowhood
C
101,
1.0
210
Outlet-02
Flowhood
C
101,
1.0
210
Outlet-03
Flowhood
C
101,
1.0
210
Outlet-04
Flowhood
C
101,
1.0
210
Outlet-05
Flowhood
C
101,
1.0
210
Outlet-06
Flowhood
C
101,
1.0
210
Outlet-07
Flowhood
C
101,
1.0
210
Outlet-08
Flowhood
K
101,
1.0
180
Outlet-09
Flowhood
K
101,
1.0
180
Outlet-10
Flowhood
K
101,
1.0
180
Outlet-11
Flowhood
K
101,
1.0
180
Outlet-12
Flowhood
K
101,
1.0
180
Outlet-13
Flowhood
K
101,
1.0
180
Outlet-14
Flowhood
K
101,
1.0
180
Outlet-15
Flowhood
K
101,
1.0
180
Outlet-16
Flowhood
K
101,
1.0
180
Outlet-17
Flowhood
K
101,
1.0
180
Outlet-18
Flowhood
K
101,
1.0
180
Outlet-19
Flowhood
K
101,
1.0
180
Outlet-20
Flowhood
K
101,
1.0
185
Outlet-21
Flowhood
K
101,
1.0
185
Outlet-22
Flowhood
K
101,
1.0
180
Outlet-23
Flowhood
K
101,
1.0
180
Outlet-24
Flowhood
K
101,
1.0
180
Outlet-25
Flowhood
K
101,
1.0
180
Outlet-26
Flowhood
K
101,
1.0
180
Outlet-27
Flowhood
K
101,
1.0
180
Outlet-28
Flowhood
K
10"
1.0
180
Outlet-29
Flowhood
K
101,
1.0
180
Outlet-30
Flowhood
K
101,
1.0
180
Outlet-31
Flowhood
K
101,
1.0
180
-
-
5800
0
0
0
-
Neudorfer Engineers, Inc. Page 6 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-06(info)
AREA: HALLWAY COMMONS 100C
Unit Data
Unit Manufacturer
D-AIRTECH
Unit Model Number
D-AHU 2
Unit Serial Number
D-18-007
Fan Rotation
Counterclockwise
AHU-06(info)/SF Filter Bank
Filter Type
Pleated
Filter Quantity - Size 1
1
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
1
Filter Dimensions - Size 2
12x24x4
Filter Quantity - Size 3
1
Filter Dimensions - Size 3
12x24x2
Filter Quantity - Size 4
1
Filter Dimensions - Size 4
24x24x2
Test Data
Total Design Flow 1900 CFM
CA Design Flow 1140 CFM
Tested By: Dwight Hammack
Date: 9/24/2018
Motor Data
AHU-06(info)/Supply Fan
Drive Type
Direct Drive
Motor Manufacturer
Rosenberg
Motor HP
2.3 HP
Motor RPM
2202 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
2.3 Amps
Test Pressures
SF Design External SP 1.8 in. we
Neudorfer Engineers, Inc. Page 7 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
AHU-06(info) Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
HALLWAY
Flowhood
K
10"
1.0
190
COMMONS
100C
Outlet-02
HALLWAY
Flowhood
K
10"
1.0
190
COMMONS
100C
Outlet-03
HALLWAY
Flowhood
K
10"
1.0
190
COMMONS
100C
Outlet-04
HALLWAY
Flowhood
K
101,
1.0
190
COMMONS
100C
Outlet-05
HALLWAY
Flowhood
K
101,
1.0
190
COMMONS
100C
Outlet-06
HALLWAY
Flowhood
K
101,
1.0
190
COMMONS
100C
Outlet-07
HALLWAY
Flowhood
K
101,
1.0
190
COMMONS
100C
Outlet-08
HALLWAY
Flowhood
K
101,
1.0
190
COMMONS
100C
Outlet-09
HALLWAY
Flowhood
K
101,
1.0
190
COMMONS
100C
Outlet-10
HALLWAY
Flowhood
K
101,
1.0
190
COMMONS
100C
Totals:
-
-
-
-
1900
0
1 0
0
AHU-06(info) Return Inlet Summary
System/Unit
Type of
Reading
Outlet
Type
Size LxW /
D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Readin
Final
%
Remarks
Inlet-01
Flowhood
E
24X24
1.0
950
Inlet-02
Flowhood
E
24X24
1.0
950
-
-
-
1900
0
0
0
Neudorfer Engineers, Inc. Page 8 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-07(info)
AREA: GYMNASIUM 107
Unit Data
Unit Manufacturer
D-AIRTECH
Unit Model Number
D-AHU 12
Unit Serial Number
D-18-008
AHU-07(info)/SF Filter Bank
Filter Type
Pleated
Filter Quantity - Size 1
6
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
6
Filter Dimensions - Size 2
24x24x2
Filter Quantity - Size 3
3
Filter Dimensions - Size 3
12x24x2
Filter Quantity - Size 4
3
Filter Dimensions - Size 4
12x24x4
Test Data
Total Design Flow 11400 CFM
OA Design Flow 6840 CFM
AHU-07(info) Supply Outlet Summary
Tested By: Dwight Hammack
Date: 9/24/2018
Motor Data
AHU-07(info)/Supply Fan
Motor HP
(4)4.42 HP
Motor RPM
2671 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
(4)4.4 Amps
Test Pressures
SF Design External SP 2.1 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
GYMNASIM
C
32"
1.0
5700
107
(DUCT
Outlet-02
GYMNASIM
C
32"
1.0
5700
107
(DUCT
Totals:
-
-
-
-
-
11400
1 0
0
0
-
Neudorfer Engineers, Inc. Page 9 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)
AREA: ADMIN WING
Unit Data
Unit Manufacturer
D-AIRTECH
Unit Model Number
D-AHU-12
Unit Serial Number
D-18-009
Unit Discharge
Top Vertical
Fan Rotation
Counterclockwise
AHU-08(info)/SF Filter Bank
Filter Manufacturer
Flanders
Filter Type
Pleated
Filter Quantity - Size 1
6
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
12x24x2
Filter Quantity - Size 3
6
Filter Dimensions - Size 3
24x24x4
Filter Quantity - Size 4
3
Filter Dimensions - Size 4
12x24x4
Test Data
Total Design Flow 11095 CFM
CA Design Flow 6660 CFM
RA Design Flow 11095 CFM
Tested By: Dwight Hammack
Date: 8/9/2018
Motor Data
AHU-08(info)/RA/EF
Drive Type
Direct Drive
Motor Manufacturer
Rosenberg
Motor HP
4.83x2 HP
Motor RPM
1600 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
4.6x2 Amps
AHU-08(info)/Supoly Fan
Drive Type
Direct Drive
Motor Manufacturer
Rosenberg
Motor HP
4.42x4 HP
Motor RPM
2789 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
4.4x4 Amps
Test Pressures
SF Design External SP 2.5 in. we
RF Design External SP 1.8 in. we
Neudorfer Engineers, Inc. Page 10 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
AHU-08(info) Return Inlet Summary
System/Unit
Type of
Reading
Outlet
Type
Size LxW /
D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Readin
Final
%
Remarks
Inlet-01
Flowhood
E
24X12
1.0
360
Inlet-02
Flowhood
E
24X24
1.0
930
Inlet-03
Flowhood
E
24X24
1.0
730
Inlet-04
Flowhood
E
24X12
1.0
355
Inlet-05
Flowhood
E
24X24
1.0
500
Inlet-06
Flowhood
E
24X12
1.0
295
Inlet-07
Flowhood
1.0
210
Inlet-08
Flowhood
E
24X12
1.0
210
Inlet-09
Flowhood
E
24X12
1.0
325
Inlet-10
Flowhood
E
24X12
1.0
325
Inlet-11
Flowhood
E
24X12
1.0
50
Inlet-12
Flowhood
E
24X12
1.0
285
Inlet-13
Flowhood
E
24X12
1.0
110
Inlet-14
Flowhood
E
24X12
1.0
260
Inlet-15
Flowhood
E
24X12
1.0
330
Inlet-16
Flowhood
E
24X12
1.0
165
Inlet-17
Flowhood
E
24X24
1.0
1110
Inlet-18
Flowhood
E
24X12
1.0
155
Inlet-19
Flowhood
E
24X24
1.0
700
Inlet-20
Flowhood
E
24X24
1.0
700
Inlet-21
Flowhood
E
24X24
1.0
450
Inlet-22
Flowhood
E
24X12
1.0
150
Inlet-23
Flowhood
E
24X12
1.0
150
Inlet-24
Flowhood
E
24X12
1.0
135
Inlet-25
Flowhood
E
24X12
1.0
420
-
-
9410
0
0
0
SYSTEM/UNIT: AHU-08(info)/VAV-146
AREA: DEN 104
Unit Data
Manufacturer Price
Model Number SDV5
Cooling Inlet Size 14 inches
AHU-08(info)/VAV-146 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 9/27/2018
Air Test Data
Clg Max Des. Primary Flow 1260 CFM
Clg Min Des. Primary Flow 380 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
DEN
Flowhood
A
12"
1.0
315
Outlet-02
DEN
Flowhood
A
12"
1.0
315
Outlet-03
DEN
Flowhood
A
12"
1.0
315
Outlet-04
DEN
Flowhood
A
12"
1.0
315
Totals:
I -
-
I -
-
1260
0
1 0
0
Neudorfer Engineers, Inc. Page 11 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-147
AREA: COUNSELOR 103
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
22
Application #
2021
Cooling Inlet Size
5 inches
Cooling K Factor
351.00
Tested By: Dwight Hammack
Date: 9/27/2018
Air Test Data
Clg Max Des. Primary Flow
155 CFM
Clg Min Des. Primary Flow
45 CFM
Clg Max Act. Primary Flow
160 CFM
Clg Min Act. Primary Flow
45 CFM
Log: I
AHU-08(info)NAV-147 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-147 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
COUNSELOR
Flowhood
A
8"
1.0
155
205
160
103
1
1 (1)
Totals:
-
-
-
155
205
160
103
1 -
SYSTEM/UNIT: AHU-08(info)/VAV-148
AREA: SMALL GROUP 102A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
20
Application #
2021
Cooling Inlet Size
5 inches
Cooling K Factor
324.00
Tested By: Dwight Hammack
Date: 9/26/2018
Air Test Data
Clg Max Des. Primary Flow
165 CFM
Clg Min Des. Primary Flow
50 CFM
Clg Max Act. Primary Flow
170 CFM
Clg Min Act. Primary Flow
50 CFM
Log: I
AHU-08(info)NAV-148 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-148 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
SMALL
Flowhood
A
8"
1.0
165
205
170
103
(1)
GROUP
Totals:
-
-
-
165
205
170
103
Neudorfer Engineers, Inc. Page 12 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-149
AREA: SMALL GROUP 102B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
19
Application #
2021
Cooling Inlet Size
7 inches
Cooling K Factor
478.00
Tested By: Dwight Hammack
Date: 9/27/2018
Air Test Data
Clg Max Des. Primary Flow
330 CFM
Clg Min Des. Primary Flow
100 CFM
Clg Max Act. Primary Flow
340 CFM
Clg Min Act. Primary Flow
100 CFM
Log: I
AHU-08(info)NAV-149 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-149 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
SMALL
Flowhood
A
12"
1.0
330
205
340
103
(1)
GROUP
Totals:
-
-
-
330
205
340
103
-
SYSTEM/UNIT: AHU-08(info)/VAV-150
AREA: LEARENING SUPPORT 102
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
18
Application #
2021
Cooling Inlet Size
14 inches
Cooling K Factor
2050.00
Tested By: Dwight Hammack
Date: 9/26/2018
Air Test Data
Clg Max Des. Primary Flow
1400 CFM
Clg Min Des. Primary Flow
420 CFM
Clg Max Act. Primary Flow
1415 CFM
Clg Min Act. Primary Flow
420 CFM
Log: I
AHU-08(info)NAV-150 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-150 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
LEARNING
Flowhood
A
12"
1.0
350
305
350
100
SUPPORT
Outlet-02
LEARNING
Flowhood
A
12"
1.0
350
280
345
99
SUPPORT
Outlet-03
LEARNING
Flowhood
A
12"
1.0
350
290
360
103
SUPPORT
Outlet-04
LEARNING
Flowhood
A
12"
1.0
350
210
360
103
(1)
SUPPORT
Totals:
-
1400
1085
1415
101
-
Neudorfer Engineers, Inc. Page 13 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-151
AREA: LOBBY 100A
Unit Data
Manufacturer NAILOR
Cooling Inlet Size 9 inches
AHU-08(info)/VAV-151 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 450 CFM
Clg Min Des. Primary Flow 135 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LOBBY
Flowhood
K
10"
1.0
225
Outlet-02
LOBBY
Flowhood
K
112"
1.0
225
Totals:
-
-
-
-
450
0
0
0
SYSTEM/UNIT: AHU-08(info)/VAV-152
AREA: RECEPTION OFFICE 101
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
15
Application #
2021
Cooling Inlet Size
14 inches
Cooling K Factor
2241.00
Tested By: Dwight Hammack
Date: 9/26/2018
Air Test Data
Clg Max Des. Primary Flow
1230 CFM
Clg Min Des. Primary Flow
370 CFM
Clg Max Act. Primary Flow
1215 CFM
Clg Min Act. Primary Flow
370 CFM
Log: I
AHU-08(info)NAV-152 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-152 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
RECEPTION
Flowhood
A
10"
1.0
305
210
310
102
(1)
OFFICE
Outlet-02
RECEPTION
Flowhood
A
101,
1.0
310
240
305
98
OFFICE
Outlet-03
RECEPTION
Flowhood
A
101,
1.0
305
210
300
98
OFFICE
Outlet-04
RECEPTION
Flowhood
A
10"
1.0
310
235
300
97
OFFICE
Totals:
-
-
-
-
-
1230
895
1215
99
-
Neudorfer Engineers, Inc. Page 14 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-153
AREA: CONFERENCE 101A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
16
Application #
2021
Cooling Inlet Size
8 inches
Cooling K Factor
451.00
Tested By: Dwight Hammack
Date: 9/27/2018
Air Test Data
Clg Max Des. Primary Flow
360 CFM
Clg Min Des. Primary Flow
110 CFM
Clg Max Act. Primary Flow
345 CFM
Clg Min Act. Primary Flow
110 CFM
Log: I
AHU-08(info)NAV-153 9/26/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-153 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
CONFERFENC
Flowhood
A
12"
1.0
360
265
345
96
(1)
E
Totals:
-
-
-
360
265
345
96
-
SYSTEM/UNIT: AHU-08(info)/VAV-154
AREA: HEALTH CLINIC 101B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
14
Application #
2021
Cooling Inlet Size
7 inches
Cooling K Factor
438.00
Tested By: Dwight Hammack
Date: 9/26/2018
Air Test Data
Clg Max Des. Primary Flow
300 CFM
Clg Min Des. Primary Flow
90 CFM
Clg Max Act. Primary Flow
310 CFM
Clg Min Act. Primary Flow
90 CFM
Log: I
AHU-08(info)NAV-154 9/26/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-154 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
HEALTH
Flowhood
A
10"
1.0
300
260
310
103
(1)
CLINIC
Totals:
-
-
-
300
260
310
103
-
Neudorfer Engineers, Inc. Page 15 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-155
AREA: COT ROOM 101 D
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
13
Application #
2021
Cooling Inlet Size
8 inches
Cooling K Factor
650.00
Tested By: Dwight Hammack
Date: 10/1 /2018
Air Test Data
Clg Max Des. Primary Flow
400 CFM
Clg Min Des. Primary Flow
350 CFM
Clg Max Act. Primary Flow
400 CFM
Clg Min Act. Primary Flow
350 CFM
Log: I
AHU-08(info)NAV-155 10/1/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-155 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Readin
Final
Remarks
Outlet-01
COT ROOM
Flowhood
A
12"
1.0
400
260
1 400
100
(1)
Totals:
-
-
-
-
400
260
1 400
100
SYSTEM/UNIT: AHU-08(info)/VAV-156
AREA: OFFICE MGR 101C
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
12
Application #
2021
Cooling Inlet Size
7 inches
Cooling K Factor
468.00
Tested By: Dwight Hammack
Date: 9/27/2018
Air Test Data
Clg Max Des. Primary Flow
310 CFM
Clg Min Des. Primary Flow
95 CFM
Clg Max Act. Primary Flow
310 CFM
Clg Min Act. Primary Flow
95 CFM
Log: I
AHU-08(info)NAV-156 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-156 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
I
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
OFFICE MGR
Flowhood
A
10"
1 1.0
310
195
310
100
(1)
Totals:
-
-
-
I -
-
310
195
310
100
-
Neudorfer Engineers, Inc. Page 16 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-157
AREA: DEAN/RECORD STG 101 E/101 K
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
11
Application #
2021
Cooling Inlet Size
10 inches
Cooling K Factor
1048.00
Tested By: Dwight Hammack
Date: 9/27/2018
Air Test Data
Clg Max Des. Primary Flow
670 CFM
Clg Min Des. Primary Flow
210 CFM
Clg Max Act. Primary Flow
680 CFM
Clg Min Act. Primary Flow
210 CFM
Log: I
AHU-08(info)NAV-157 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-157 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
DEN/RECORD
Flowhood
A
12"
1.0
350
275
360
103
(1)
STG
Outlet-02
DEN/RECORD
Flowhood
A
12"
1.0
320
250
320
100
STG
Totals:
-
-
-
670
1 525
1 680
1 101
SYSTEM/UNIT: AHU-08(info)/VAV-158
AREA: DHH OFFICES 101 N/101 L
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
10
Application #
2021
Cooling Inlet Size
9 inches
Cooling K Factor
674.00
Tested By: Dwight Hammack
Date: 9/27/2018
Air Test Data
Clg Max Des. Primary Flow
470 CFM
Clg Min Des. Primary Flow
140 CFM
Clg Max Act. Primary Flow
460 CFM
Clg Min Act. Primary Flow
140 CFM
Log: I
AHU-08(info)NAV-158 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-158 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
DHH OFFICE
Flowhood
A
12"
1.0
235
145
230
98
Outlet-02
DHH OFFICE
Flowhood
A
12"
1.0
235
120
230
98
(1)
Totals:
-
-
470
265
460
98
-
Neudorfer Engineers, Inc. Page 17 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-159
AREA: AP OFFICE/DHH RECEPT 101R/101Q
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
9
Application #
2021
Cooling Inlet Size
10 inches
Cooling K Factor
1179.00
Tested By: Dwight Hammack
Date: 9/27/2018
Air Test Data
Clg Max Des. Primary Flow
675 CFM
Clg Min Des. Primary Flow
300 CFM
Clg Max Act. Primary Flow
645 CFM
Clg Min Act. Primary Flow
300 CFM
Log: I
AHU-08(info)NAV-159 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-159 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
AP
Flowhood
A
12"
1.0
355
330
330
93
OFFICE/DHH
RECPT
Outlet-02
AP
Flowhood
A
10"
1.0
320
225
315
98
(1)
OFFICE/DHH
RECPT
Totals:
-
-
-
-
-
675
1 555
1 645
1 96
SYSTEM/UNIT: AHU-08(info)/VAV-160
AREA: P OFFICE 101S
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
8
Application #
2021
Cooling Inlet Size
8 inches
Cooling K Factor
467.00
Tested By: Dwight Hammack
Date: 9/27/2018
Air Test Data
Clg Max Des. Primary Flow
360 CFM
Clg Min Des. Primary Flow
110 CFM
Clg Max Act. Primary Flow
365 CFM
Clg Min Act. Primary Flow
110 CFM
Log: I
AHU-08(info)NAV-160 9/27/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-160 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readinq
Final
Readin
Final
%
Remarks
Outlet-01
P OFFICE
Flowhood
A
12"
1.0
360
170
365
101
(1)
Totals:
-
-
360
170
365
101
-
Neudorfer Engineers, Inc. Page 18 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-161
AREA: WORK ROOM 101 M
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
5
Application #
2021
Cooling Inlet Size
7 inches
Cooling K Factor
479.00
Tested By: Dwight Hammack
Date: 10/1/2018
Air Test Data
Clg Max Des. Primary Flow
300 CFM
Clg Min Des. Primary Flow
90 CFM
Clg Max Act. Primary Flow
305 CFM
Clg Min Act. Primary Flow
90 CFM
Log: I
AHU-08(info)NAV-161 10/1/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-161 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Readin
Final
Remarks
Outlet-01
WORKROOM
Flowhood
A
10"
1.0
300
200
305
102
(1)
Totals:
-
-
-
-
300
200
305
102
SYSTEM/UNIT: AHU-08(info)/VAV-162
AREA: STAFF OFFICE 101 P
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
7
Application #
2021
Cooling Inlet Size
10 inches
Cooling K Factor
1116.00
Tested By: Dwight Hammack
Date: 10/1/2018
Air Test Data
Clg Max Des. Primary Flow
650 CFM
Clg Min Des. Primary Flow
400 CFM
Clg Max Act. Primary Flow
655 CFM
Clg Min Act. Primary Flow
400 CFM
Log: I
AHU-08(info)NAV-162 10/1/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-162 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
STAFF
Flowhood
A
12"
1.0
325
250
335
103
LOUNGE
Outlet-02
STAFF
Flowhood
A
12"
1.0
325
240
320
98
(1)
LOUNGE
Totals:
-
650
1 490
1 655
1 101
1 -
Neudorfer Engineers, Inc. Page 19 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-163
AREA: PROF DEVELOPEMENT 101T
Unit Data
Manufacturer
Price
Model Number
SDV5
Cooling Inlet Size
12 inches
AHU-08(info)/VAV-163 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/1 /2018
Air Test Data
Clg Max Des. Primary Flow 730 CFM
Clg Min Des. Primary Flow 220 CFM
Clg Min Act. Primary Flow 220 CFM
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
PROF
Flowhood
A
12"
1.0
365
DEVELOPMEN
T
Outlet-02
PROF
Flowhood
A
12"
1.0
365
DEVELOPMEN
T
Totals:
-
-
-
-
-
730
0
1 0
0
SYSTEM/UNIT: AHU-08(info)/VAV-164
AREA: SLP 108
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
23
Application #
2021
Cooling Inlet Size
5 inches
Cooling K Factor
390.00
Tested By: Dwight Hammack
Date: 10/1 /2018
Air Test Data
Clg Max Des. Primary Flow
150 CFM
Clg Min Des. Primary Flow
45 CFM
Clg Max Act. Primary Flow
145 CFM
Clg Min Act. Primary Flow
45 CFM
Log: I
AHU-08(info)/VAV-164 10/1/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-164 Supply Outlet Summary
System/Unit
Area Served
Type of
Readin
Outlet
T e
Size
LxW / D
AK
Design
Velocit
Design
Value
Prelim
Readin
Final
Final
Final
Remarks
Outlet-01
SLP
Flowhood
A
8"
1.0
150
185
145
97
(1)
Totals:
-
-
150
185
145
97
Neudorfer Engineers, Inc. Page 20 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-165
AREA: DHH PYCH/COUNS 109
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
24
Application #
2021
Cooling Inlet Size
5 inches
Cooling K Factor
343.00
Tested By: Dwight Hammack
Date: 10/1/2018
Air Test Data
Clg Max Des. Primary Flow
145 CFM
Clg Min Des. Primary Flow
45 CFM
Clg Max Act. Primary Flow
155 CFM
Clg Min Act. Primary Flow
45 CFM
Log: I
AHU-08(info)NAV-165 10/1/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-165 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
DHH
Flowhood
A
8"
1.0
145
205
155
107
(1)
PYSCH/COUN
S
Totals:
-
-
-
-
-
145
205
155
107
-
SYSTEM/UNIT: AHU-08(info)/VAV-166
AREA: AUDIO/DHH SLP 110
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
25
Application #
2021
Cooling Inlet Size
5 inches
Cooling K Factor
329.00
Tested By: Dwight Hammack
Date: 10/1/2018
Air Test Data
Clg Max Des. Primary Flow
135 CFM
Clg Min Des. Primary Flow
40 CFM
Clg Max Act. Primary Flow
140 CFM
Clg Min Act. Primary Flow
40 CFM
Log: I
AHU-08(info)NAV-166 10/1/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-166 Supply Outlet Summary
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
AUDIO/DHH
Flowhood
A
8"
1.0
135
150
140
104
(1)
SLP
Totals:
-
-
-
-
-
135
150
140
104
-
Neudorfer Engineers, Inc. Page 21 of 93
Air Handling Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: AHU-08(info)/VAV-167
AREA: OT/PT 122
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
26
Application #
2021
Cooling Inlet Size
8 inches
Cooling K Factor
650.00
Tested By: Dwight Hammack
Date: 10/1 /2018
Air Test Data
Clg Max Des. Primary Flow
420 CFM
Clg Min Des. Primary Flow
125 CFM
Clg Max Act. Primary Flow
445 CFM
Clg Min Act. Primary Flow
125 CFM
Log: I
AHU-08(info)NAV-167 10/1/2018 Dwight Hammack (1) The volume damper is full open.
AHU-08(info)/VAV-167 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
OT/PT
Flowhood
A
8"
1.0
210
130
225
107
(1)
Outlet-02
OT/PT
Flowhood
A
8"
1.0
210
155
220
105
Totals:
-
-
-
-
-
420
285
445
106
-
Neudorfer Engineers, Inc. Page 22 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: EF-01
AREA: TYPE II KITCHEN HOOD
Unit Data
Fan Manufacturer
Cook
Fan Model Number
150 ACRUH
Fan Serial Number
033SH28555
Fan Rotation
Counterclockwise
Fan Discharge
Vertical
Drive Type
DIRECT
Fan Speed
48%
Test Data
Total Design Flow
788 CFM
Total Actual Flow
835 CFM
Fan RPM Design
1593 RPM
Fan RPM Actual
957 RPM
Motor Volts T1-T2
120 Volts
Motor Amps T1
1.00 Amps
EF-01 Exhaust Inlet Summary
Tested By: Dwight Hammack
Date: 10/5/2018
Motor Data
Motor Manufacturer
US Motors
Motor HP
1/2 HP
Motor RPM
300-1800 RPM
Motor Rated Volts
120/208-240 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor Full Load Amps
6.2/3.8-3.5 Amps
Test Pressures
Fan Suction SP
-0.05 in. we
Fan Discharge SP
0.00 in. we
Design Total SP
1.30 in. we
Actual Total SP
0.05 in. we
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
ReadingReadin
Final
Final %
Remarks
Inlet-01
KITCHEN
Flowhood
KITCHE
14" Rd
1.0
788
1590
835
106
N
HOOD
Totals:
-
-
-
788
1590
835
106
Neudorfer Engineers, Inc. Page 23 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: EF-02
AREA: DISHWASSHER
Unit Data
Fan Manufacturer
Cook
Fan Model Number
101 ACRU
Fan Serial Number
033SH28555
Fan Rotation
Counterclockwise
Fan Discharge
Vertical
Drive Type
DIRECT
Fan Speed
Medium
Test Data
Total Design Flow
525 CFM
Total Actual Flow
550 CFM
Fan RPM Design
1419 RPM
Fan RPM Actual
1031 RPM
Motor Volts T1-T2
120 Volts
Motor Amps T1
0.50 Amps
EF-02 Exhaust Inlet Summary
Tested By: Dwight Hammack
Date: 10/5/2018
Motor Data
Motor Manufacturer
Cook
Motor HP
1/4 HP
Motor RPM
350-1725 RPM
Motor Rated Volts
120 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor Full Load Amps
3.40 Amps
Test Pressures
Fan Suction SP
-0.21 in. we
Fan Discharge SP
0.00 in. we
Design Total SP
0.75 in. we
Actual Total SP
0.21 in. we
System/Unit
Area Served
Type of
Readin
Outlet
T e
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final %
Remarks
Inlet-01
DISHWASHER
Flowhood
Duct
10" Rd
1.0
525
895
550
105
Totals:
-
-
525
1 895
550
105
SYSTEM/UNIT: EF-03
AREA: CUST/RECEIVING 126
Unit Data
Fan Manufacturer
GREENHECK
Fan Model Number
SQ-95-VG
Drive Type
DIRECT
Test Data
Total Design Flow
500 CFM
Fan RPM Design
1594 RPM
EF-03 Exhaust Inlet Summary
Motor Data
Motor HP
1/6 HP
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Design Total SP
0.50 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
Readin
Readin
Inlet-01
CUST/RECEIVI
Flowhood
1.0
500
NG
Totals:
-
-
-
500
0
0
0
Neudorfer Engineers, Inc. Page 24 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: EF-04
AREA: ACTIVITIES TOILET 116
Unit Data
Fan Manufacturer
Cook
Fan Model Number
135 SQN
Fan Serial Number
033SH28555
Fan Rotation
Counterclockwise
Fan Discharge
Vertical
Drive Type
DIRECT
Fan Speed
67%
Test Data
Total Design Flow
1550 CFM
Total Actual Flow
1675 CFM
Fan RPM Design
1577 RPM
Fan RPM Actual
1208 RPM
Motor Volts T1-T2
120 Volts
Motor Amps T1
3.30 Amps
Log:
Tested By: Dwight Hammack
Date: 10/24/2018
Motor Data
Motor Manufacturer
US Motors
Motor HP
3/4 HP
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Design Total SP
1.00 in. we
EF-04
10/5/2018
Dwight Hammack
(2) The volume damper is full closed.
EF-04
10/5/2018
Dwight Hammack
(1) The volume damper is full open.
EF-04
10/5/2018
Dwight Hammack
Statics
Neudorfer Engineers, Inc. Page 25 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
EF-04 Exhaust Inlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
ReadingReadin
Inlet-01`
ACTIVITIES
Flowhood
E
12X12
1.0
150
60
157
105
(1)
TOILET
Inlet-02
ACTIVITIES
Flowhood
E
12X12
1.0
150
65
162
108
TOILET
Inlet-03
ACTIVITIES
Flowhood
E
12X12
1.0
100
95
95
95
TOILET
Inlet-04
ACTIVITIES
Flowhood
E
12X12
1.0
75
110
71
95
TOILET
Inlet-05"
ACTIVITIES
Flowhood
E
12X12
1.0
75
115
81
108
(2)
TOILET
Inlet-06
ACTIVITIES
Flowhood
E
12X12
1.0
75
145
70
93
TOILET
Inlet-07
ACTIVITIES
Flowhood
E
12X12
1.0
75
220
82
109
(2)
TOILET
Inlet-08
ACTIVITIES
Flowhood
E
12X12
1.0
75
105
71
95
TOILET
Inlet-09
ACTIVITIES
Flowhood
E
12X12
1.0
75
130
81
108
(2)
TOILET
Inlet-10
ACTIVITIES
Flowhood
E
12X12
1.0
75
160
107
143
(2)
TOILET
Inlet-11
ACTIVITIES
Flowhood
E
12X12
1.0
75
160
75
100
(2)
TOILET
Inlet-12
ACTIVITIES
Flowhood
E
12X12
1.0
75
130
78
104
TOILET
Inlet-13
ACTIVITIES
Flowhood
E
12X12
1.0
75
135
83
111
(2)
TOILET
Inlet-14
ACTIVITIES
Flowhood
E
12X12
1.0
75
180
117
156
(2)
TOILET
Inlet-15
ACTIVITIES
Flowhood
E
12X12
1.0
75
145
71
95
TOILET
Inlet-16
ACTIVITIES
Flowhood
E
12X12
1.0
75
120
81
108
TOILET
Inlet-17
ACTIVITIES
Flowhood
E
12X12
1.0
75
120
71
95
(2)
TOILET
Inlet-18
ACTIVITIES
Flowhood
E
12X12
1.0
100
115
95
95
TOILET
Totals:
-
-
1550
2310
1648
106
-
Log:
EF-04/Inlet-01 10/2/2018 Xuan Nguyen (1) The volume damper with Young's regulator is full
open.
EF-04/Inlet-05 10/3/2018 Xuan Nguyen (2) The volume damper with Young's regulator is full
closed (Typical).
Neudorfer Engineers, Inc. Page 26 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: EF-05
AREA: LC (M SCI) 136
Unit Data
Fan Manufacturer
Cook
Fan Model Number
135 ACRU
Fan Serial Number
033SH28555
Fan Rotation
Counterclockwise
Fan Discharge
Vertical
Drive Type
DIRECT
Fan Speed
61 %
Test Data
Total Design Flow
1200 CFM
Total Actual Flow
1210 CFM
Fan RPM Design
1191 RPM
Fan RPM Actual
786 RPM
Motor Volts T1-T2
120 Volts
Motor Amps T1
1.10 Amps
EF-05 Exhaust Inlet Summary
Tested By: Dwight Hammack
Date: 10/5/2018
Motor Data
Motor Manufacturer
US Motors
Motor HP
1/2 HP
Motor RPM
300-1800 RPM
Motor Rated Volts
120-208/240 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor Full Load Amps
6.2/3.8-3.5 Amps
Test Pressures
Fan Suction SP
-0.17 in. we
Fan Discharge SP
0.00 in. we
Design Total SP
0.60 in. we
Actual Total SP
0.17 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
ReadingReadin
Inlet-01
LC (M SCI)
Velgrid
E
24X24
2.8
1200
1855
1210
101
136
Totals:
-
1200
1855
1210
101
Neudorfer Engineers, Inc. Page 27 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: EF-06(info)
AREA: FUME HOOD EXH
Unit Data
Fan Manufacturer
Cook
Fan Model Number
150 ACRUH
Fan Serial Number
033SH28555
Fan Rotation
Counterclockwise
Fan Discharge
Vertical
Drive Type
DIRECT
Fan Speed
46%
Test Data
Total Design Flow 580 CFM
Fan RPM Design 1389 RPM
Fan RPM Actual 882 RPM
EF-06(info) Exhaust Inlet Summary
Tested By: Xuan Nguyen
Date: 10/3/2018
Motor Data
Motor Manufacturer
US Motors
Motor HP
1/2 HP
Motor RPM
300-1800 RPM
Motor Rated Volts
120-208/240 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor Full Load Amps
6.2/3.8-3.5 Amps
Test Pressures
Design Total SP 1.20 in. we
System/Unit
Area Served
Type of
Readin
Outlet
Type
Size
LxW / D
AK
Design
VelocityValue
Design
Prelim
Readin
Final
Readin
Final %
Remarks
Inlet-01
FUME HOOD
Pitot Tube
HOOD
38x19.5
5.15
1
580
1340
Totals:
-
1
580
1340
1 0
1 0
1 -
SYSTEM/UNIT: EF-07
AREA: BOILER/MECH 125
Unit Data
Fan Manufacturer
Cook
Fan Model Number
120-SQM-120-VG
Fan Serial Number
033SH28555-8601
Fan Rotation
Clockwise
Drive Type
DIRECT
Fan Speed
55
Test Data
Total Design Flow
1000 CFM
Total Actual Flow
1005 CFM
Fan RPM Actual
1034 RPM
Motor Amps T1
1.10 Amps
EF-07 Exhaust Inlet Summary
Tested By: Alex Lebedev
Date: 10/22/2018
Motor Data
Motor Manufacturer
Cook
Motor HP
1/2 HP
Motor RPM
1418 RPM
Motor Rated Volts
115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Fan Suction SP -0.07 in. we
Fan Discharge SP 0.09 in. we
Design Total SP 0.60 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
Readin
Readin
Inlet-01
BOILER/MECH
Velgrid
EG
14x14
1.36
1000
1679
1005
101
125
Totals:
-
-
1000
1679
1005
101
Neudorfer Engineers, Inc. Page 28 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: EF-08(info)
AREA: ELECTRICAL 126
Unit Data
Fan Manufacturer
Cook
Fan Model Number
120 ACE
Fan Serial Number
033SH44823
Fan Rotation
Counterclockwise
Fan Discharge
Vertical
Drive Type
DIRECT
Test Data
Total Design Flow 800 CFM
Fan RPM Design 1500 RPM
EF-08(info) Exhaust Inlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Tested By: Dwight Hammack
Date: 9/24/2018
Motor Data
Motor Manufacturer
US Motors
Motor HP
1/2 HP
Motor RPM
300-1800 RPM
Motor Rated Volts
120-208/240 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor Full Load Amps
6.2/3.8-3.5 Amps
Test Pressures
Design Total SP 0.60 in. we
System/Unit
Area Served
Type of
Readin
Outlet
T e
Size
LxW / D
AK
Design
Velocit
Design
Value
Prelim
Readin
Final
Readin
Final %
Remarks
Inlet-01
ELEC 128
Flowhood
1.0
800
Totals:
800
1 0
1 0
1 0
1 -
SYSTEM/UNIT: EF-09
AREA: KILN
Unit Data
Fan Manufacturer ENVIROVENT 2
Fan Model Number ENVIROVENT 2
Drive Type DIRECT
Test Data
Total Design Flow 140 CFM
EF-09 Exhaust Inlet Summary
Motor Data
Motor HP 14 AMPS HP
Motor Phase 1
Motor Hertz 60 Hz
System/Unit
Area Served
Type of
Readin
Outlet
T e
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final %
Remarks
Inlet-01
KILN
Flowhood
1.0
140
Totals:
-
-
140
1 0
0
0
Neudorfer Engineers, Inc. Page 29 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: EF-10
AREA: TOILET 113A
Unit Data
Fan Manufacturer
GREENHECK
Fan Model Number
SQ-97-VG
Drive Type
DIRECT
Test Data
Total Design Flow
150 CFM
Fan RPM Design
1501 RPM
EF-10 Exhaust Inlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor HP
1/4 HP
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Design Total SP
0.60 in. we
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final %
Remarks
Inlet-01
TOILET 113A
Flowhood
E
12X12
1.0
150
Totals:
-
150
0
0
0
Neudorfer Engineers, Inc. Page 30 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: EF-11
AREA: NORTH ADMIN TLTS/HEALTH ROOM
Unit Data
Fan Manufacturer
Cook
Fan Model Number
150 ACE
Fan Serial Number
033SH28555 00/0011601
Fan Rotation
Counterclockwise
Fan Discharge
Vertical
Drive Type
DIRECT
Fan Speed
57%
Test Data
Total Design Flow
1550 CFM
Total Actual Flow
1525 CFM
Fan RPM Design
1242 RPM
Fan RPM Actual
1148 RPM
Motor Volts T1-T2
120 Volts
Motor Amps T1
1.10 Amps
EF-11 Exhaust Inlet Summary
Tested By: Dwight Hammack
Date: 10/24/2018
Motor Data
Motor Manufacturer
US Motors
Motor HP
1 HP
Motor RPM
300-1800 RPM
Motor Rated Volts
120-208/240 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor Full Load Amps
12.4/8.1-7.2 Amps
Test Pressures
Fan Suction SP
-0.17 in. we
Fan Discharge SP
0.00 in. we
Design Total SP
1.00 in. we
Actual Total SP
0.17 in. we
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readin
Final
Readin
Final %
Remarks
Inlet-01
NORTH ADMIN
TLTS
Flowhood
E
24X12
1.0
400
280
385
96
Inlet-02
Flowhood
E
24X12
1.0
100
90
100
100
Inlet-03
Flowhood
E
12X12
1.0
150
110
155
103
Inlet-04"
Flowhood
E
12X12
1.0
150
40
150
100
(1)
Inlet-05
Velgrid
R
18X12
1.05
200
525
190
95
Inlet-06
Flowhood
E
24X12
1.0
200
360
210
105
Inlet-07
Flowhood
E
12X12
1.0
150
120
140
93
Inlet-08
Flowhood
E
24X12
1.0
200
210
195
98
Totals:
I -
I -
I -
I -
I -
1550
1735
1 1525
98
-
Log: I EF-11 /Inlet-04 10/3/2018 Xuan Nguyen (1) The volume damper with Young's regulator is full
open.
Neudorfer Engineers, Inc. Page 31 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: EF-12
AREA: SOUTH ADMIN
Unit Data
Fan Manufacturer
GREENHECK
Fan Model Number
G-098-VG
Drive Type
DIRECT
Test Data
Total Design Flow
450 CFM
Fan RPM Design
1383 RPM
EF-12 Exhaust Inlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor HP
1/4 HP
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Design Total SP
0.60 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
Readin
Readin
Inlet-01`
SOUTH ADMIN
Flowhood
E
12X12
1.0
150
TLTS
Inlet-02"
SOUTH ADMIN
Flowhood
E
12X12
1.0
150
TLTS
Inlet-03
SOUTH ADMIN
Flowhood
E
12X12
1.0
150
TLTS
Totals:
-
-
450
1 0
0
0
-
Log:
EF-12/Inlet-01 10/3/2018 Xuan Nguyen The grille/register/diffuser is not installed.
EF-12/Inlet-02 10/3/2018 Xuan Nguyen The grille/register/diffuser is not installed.
SYSTEM/UNIT: EF-13
AREA: MECH 304 CUST CLOSET
Unit Data
Fan Manufacturer
GREENHECK
Fan Model Number
G-097-VG
Drive Type
DIRECT
Test Data
Total Design Flow
150 CFM
Fan RPM Design
1324 RPM
EF-13 Exhaust Inlet Summary
Motor Data
Motor HP
1/4 HP
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Design Total SP
0.60 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
ReadingReadin
Inlet-01
304 CUST
Flowhood
E
24x12
1.0
150
CLOSET
Totals:
-
-
-
150
0
0
0
Neudorfer Engineers, Inc. Page 32 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: EF-14
AREA: MECH 504 CUST CLOSET
Unit Data
Fan Manufacturer
GREENHECK
Fan Model Number
G-097-VG
Drive Type
DIRECT
Test Data
Total Design Flow
150 CFM
Fan RPM Design
1324 RPM
EF-14 Exhaust Inlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor HP
1/4 HP
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Design Total SP
0.60 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
ReadingReadin
Inlet-01
MECH 504
Flowhood
E
24x12
1.0
150
CUST CLOSET
Totals:
-
-
-
-
-
150
0
0
0
SYSTEM/UNIT: EF-15
AREA: MECH 206 CUST CLOSET
Unit Data
Fan Manufacturer
GREENHECK
Fan Model Number
G-097-VG
Drive Type
DIRECT
Test Data
Total Design Flow
150 CFM
Fan RPM Design
1324 RPM
EF-15 Exhaust Inlet Summary
Motor Data
Motor HP
1/4 HP
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Design Total SP
0.60 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
ReadingReadin
Inlet-01
MECH 206
Flowhood
E
24X12
1.0
150
CUST CLOSET
Totals:
-
150
0
0
0
Neudorfer Engineers, Inc. Page 33 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: EF-16
AREA: MECH 406 CUST CLOSET
Unit Data
Fan Manufacturer
GREENHECK
Fan Model Number
G-097-VG
Drive Type
DIRECT
Test Data
Total Design Flow
150 CFM
Fan RPM Design
1324 RPM
EF-16 Exhaust Inlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor HP
1/4 HP
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Design Total SP
0.60 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
ReadingReadin
Inlet-01
MECH 406
Flowhood
E
24X12
1.0
150
CUST CLOSET
Totals:
-
-
-
-
-
150
0
0
0
SYSTEM/UNIT: EF-17
AREA: MECH 605 CUST CLOSET
Unit Data
Fan Manufacturer
GREENHECK
Fan Model Number
G-097-VG
Drive Type
DIRECT
Test Data
Total Design Flow
150 CFM
Fan RPM Design
1324 RPM
EF-17 Exhaust Inlet Summary
Motor Data
Motor HP
1/4 HP
Motor Phase
1
Motor Hertz
60 Hz
Test Pressures
Design Total SP
0.60 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
ReadingReadin
Inlet-01
MECH 605
Flowhood
E
24X12
1.0
150
CUST CLOSET
Totals:
-
150
0
0
0
Neudorfer Engineers, Inc. Page 34 of 93
Fan Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: EF-18 Info
AREA: STAFF LOUNGE 101 P HOOD
Unit Data
Fan Manufacturer
Cook
Fan Model Number
101 ACE
Fan Serial Number
033SH28555 00/0014201
Fan Rotation
Counterclockwise
Fan Discharge
Vertical
Drive Type
DIRECT
Test Data
Total Design Flow 400 CFM
Fan RPM Design 1437 RPM
EF-18 Info Exhaust Inlet Summary
Tested By: Xuan Nguyen
Date: 10/3/2018
Motor Data
Motor Manufacturer
Cook
Motor HP
1/4 HP
Motor RPM
300-1725 RPM
Motor Rated Volts
120 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor Full Load Amps
3.40 Amps
Test Pressures
Design Total SP 0.60 in. we
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final %
Remarks
Reading
Type
LxW / D
Velocity
Value
ReadingReadin
Inlet-01"
MECH 406
Flowhood
HOOD
1.0
400
CUST CLOSET
Totals:
-
400
0
0
0
Log: EF-18 Info/Inlet-01 10/3/2018 Xuan Nguyen The ductwork is incomplete due to range hood is not
installed.
Neudorfer Engineers, Inc. Page 35 of 93
Fan Coil
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: FCU-01
AREA: PRACTICE
Unit Data
Unit Manufacturer
NAILOR
Unit Model Number
D35FHE
Unit Serial Number
589771-1.01
Drive Type
Direct Drive
Fan Speed
50%
Test Data
Total Design Flow
600 CFM
Total Actual Flow
576 CFM
RA Design Flow
310 CFM
RA Actual Flow
293 CFM
OA Design Flow
290 CFM
OA Actual Flow
283 CFM
RA Damper Position
67
OA Damper Position
33
Motor Volts T1-T2
207 Volts
Motor Amps T1
0.90 Amps
Log:
DATE: 10/25/2018
CONTACT:
AUTHOR:
Tested By: Dwight Hammack
Date: 10/24/2018
Motor Data
Motor HP
1/4
Motor Rated Volts
208
Motor Phase
1
Motor Hertz
60
Motor FL Amps
2.2
Test Pressures
Fan Suction SP
-0.10 " W.C.
Fan Discharge SP
0.05 " W.C.
Design External SP
0.35 " W.C.
Actual External SP
0.15 " W.C.
Filter Data
Filter Type
Pleated
Filter Qty - S1
1
Filter Size - S1
16x20x2
FCU-01 10/24/2018 Dwight Hammack OSA was set by subtracting return air from the supply
air.
FCU-01 10/24/2018 Dwight Hammack (1) The volume damper is full open.
FCU-01 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
PRACTICE
Flowhood
A
8"
1.0
100
125
96
96
Outlet-02
PRACTICE
Flowhood
A
8"
1.0
100
128
95
95
Outlet-03
CORRIDOR
Flowhood
A
101,
1.0
200
156
194
97
(1)
Outlet-04
CORRIDOR
Flowhood
A
10"
1.0
200
173
191
96
Totals:
-
-
600
1 582
1 576
1 96
FCU-01 Return Inlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size LxW /
D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Readin
Final
%
Remarks
Inlet-01
PRACTICE
Flowhood
RG
12x24
1.0
155
193
143
92
(1)
Inlet-02
PRACTICE
Flowhood
RG
12x24
1.0
155
160
150
97
Totals:
-
-
310
353
293
95
-
Neudorfer Engineers, Inc. Page 36 of 93
Fan Coil
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: FCU-02
AREA: CUSTODIAL/MUSIC OFFICE
Unit Data
Unit Manufacturer
NAILOR
Unit Model Number
D35FHE
Unit Serial Number
589771-2.01
Unit Location
Mezzanine
Drive Type
Direct Drive
Fan Speed
54%
Test Data
Total Design Flow
1050 CFM
Total Actual Flow
1095 CFM
RA Design Flow
550 CFM
OA Design Flow
500 CFM
Log:
DATE: 10/25/2018
CONTACT:
AUTHOR:
Tested By: Dwight Hammack
Date: 10/24/2018
Motor Data
Motor HP
Motor Rated Volts
Motor Phase
Motor Hertz
Motor FL Amps
112
208
1
60
4.9
Test Pressures
Design External SP
0.50 " W.C.
Filter Data
Filter Manufacturer
Filter Type
Filter Qty - S1
Filter Size - S1
Koch
Pleated
1
16x35x2
FCU-02 10/24/2018 Dwight Hammack (1) The volume damper is full open.
FCU-02 10/24/2018 Dwight Hammack Need an RFI to clarify the outside air total. Return
outlet totals equals the sum of the supply outlets. The
schedule calls for 500 CFM of OSA.
FCU-02 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
PRACTICE
Flowhood
A
12"
1.0
350
401
350
100
Outlet-02
CUSTODIAL
OFFICE
Flowhood
A
12"
1.0
500
465
535
107
(1)
Outlet-03
CORRIDOR
Flowhood
A
10"
1.0
200
298
210
105
Totals:
-
-
1050
1 1164
1 1095
1 104
FCU-02 Return Inlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size LxW /
D
AK
Design
Velocity
Design
Value
Prelim
Readin
Final
Reading
Final
%
Remarks
Inlet-01
PRACTICE
Flowhood
E
24X12
1.0
350
Inlet-02
CORRIDOR
Flowhood
E
24X12
1.0
200
Inlet-03
CUSTODIAL
OFFICE
Flowhood
E
18X12
1.0
500
Totals:
-
-
-
-
-
1050
0
1 0
1 0
-
Neudorfer Engineers, Inc. Page 37 of 93
Fan Coil
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: FCU-03
AREA: GYM OFFICE
Unit Data
Unit Manufacturer NAILOR
Unit Model Number D35FHE
Fan Speed 1220
Test Data
Total Design Flow 400 CFM
FCU-03 Supply Outlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor HP 1/4
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.35 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
GYM OFFICE
Flowhood
A
8"
1.0
200
Outlet-02
GYM OFFICE
Flowhood
A
8"
1.0
200
Totals:
-
-
-
400
0
0
0
FCU-03 Return Inlet Summary
System/Unit
Type of
Reading
Outlet
Type
Size LxW /
D
AK
Design
Design
Value
Prelim
Reading
Final
Readin
Final
%
Remarks
Inlet-01
Flowhood
E
24X12
—Velocity
1.0
200
Inlet-02
Flowhood
E
24X12
1.0
200
-
-
-
-
400
0
0
0
-
SYSTEM/UNIT: SAC-01
AREA: MDF 137
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKA-A24KA6
Test Data
Total Design Flow 425 CFM
SAC-01 Supply Outlet Summary
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
MDF 137
Flowhood
1.0
425
Totals:
-
-
-
I-
-
425
0
0
0
Neudorfer Engineers, Inc. Page 38 of 93
Fan Coil
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: SAC-02A
AREA: IDF 303A
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-02A Supply Outlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
IDF 303A
Flowhood
1.0
425
Totals:
-
425
0
0
0
SYSTEM/UNIT: SAC-02B
AREA: ELEC 303
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-02B Supply Outlet Summary
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
ELEC 303
Flowhood
1.0
425
Totals:
-
425
0
0
0
Neudorfer Engineers, Inc. Page 39 of 93
Fan Coil
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: SAC-03A
AREA: IDF 503A
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-03A Supply Outlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
IDF 503A
Flowhood
1.0
425
Totals:
-
425
0
0
0
SYSTEM/UNIT: SAC-03B
AREA: ELEC 503
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-03B Supply Outlet Summary
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
IDF 503A
Flowhood
1.0
425
Totals:
-
425
0
0
0
Neudorfer Engineers, Inc. Page 40 of 93
Fan Coil
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: SAC-04A
AREA: IDF 205A
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-04A Supply Outlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
IDF 205A
Flowhood
1.0
425
Totals:
-
425
0
0
0
SYSTEM/UNIT: SAC-04B
AREA: ELEC 205
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-04B Supply Outlet Summary
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
ELEC 205
Flowhood
1.0
425
Totals:
-
425
0
0
0
Neudorfer Engineers, Inc. Page 41 of 93
Fan Coil
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: SAC-05A
AREA: IDF 405A
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-05A Supply Outlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
IDF 405A
Flowhood
1.0
425
Totals:
-
425
0
0
0
SYSTEM/UNIT: SAC-05B
AREA: ELEC 405
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-05B Supply Outlet Summary
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
ELEC 405
Flowhood
1.0
425
Totals:
-
425
0
0
0
Neudorfer Engineers, Inc. Page 42 of 93
Fan Coil
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: SAC-06A
AREA: IDF 605A
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-06A Supply Outlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
IDF 605A
Flowhood
1.0
425
Totals:
-
425
0
0
0
SYSTEM/UNIT: SAC-06B
AREA: ELEC 605
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKFY-P18NHMU-E2
Test Data
Total Design Flow 425 CFM
SAC-06B Supply Outlet Summary
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
ELEC 605
Flowhood
1.0
425
Totals:
-
425
0
0
0
Neudorfer Engineers, Inc. Page 43 of 93
Fan Coil
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
SYSTEM/UNIT: SAC-07
AREA: IDF 101 F
Unit Data
Unit Manufacturer MITSUBISHI
Unit Model Number PKA-A18HA6
Test Data
Total Design Flow 425 CFM
SAC-07 Supply Outlet Summary
DATE: 10/25/2018
CONTACT:
AUTHOR:
Tested By: Xuan Nguyen
Date: 10/12/2018
Motor Data
Motor Phase 1
Motor Hertz 60
Test Pressures
Design External SP 0.25 " W.C.
System/Unit
Area Served
Type of
ReadingT
Outlet
e
Size
LxW / D
AK
Design
Velocit
Design
Value
Prelim
Readin
Final
Readin
Final
%
Remarks
Outlet-01
IDF 101F
Flowhood
1.0
425
Totals:
425
0
1 0
0
Neudorfer Engineers, Inc. Page 44 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-01(info)
AREA: CLASSROOMS/READING
Unit Data
Unit Manufacturer
D-AirTech
Unit Model Number
D-AHU-6
Unit Serial Number
D-17-072
HRU-01(info)/EF Filter
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
24x24x2
Filter Quantity - Size 3
3
Filter Dimensions - Size 3
12x24x4
Filter Quantity - Size 4
3
Filter Dimensions - Size 4
12x24x2
HRU-01(info)/SF Filter
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
24x24x2
Test Data
SF Total Design Flow
5750 CFM
SF OA Design Flow
3440 CFM
EF Total Design Flow
5750 CFM
Tested By: Dwight Hammack
Date: 9/25/2018
Motor Data
HRU-01(info)/Exhaust Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
7 HP
Motor RPM
2682 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
6.9 Amps
HRU-01(info)/Supply Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
(2)4.4 HP
Motor RPM
2419 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
(2)4.4 Amps
Test Pressures
SF Design ESP 2.30 in. w.c.
EF Actual ESP 1.70 in. w.c.
Log: HRU-01(info) 10/16/2018 Dwight Hammack Motorized damper not installed on outlet that serves
mechanical room.
HRU-01(info) Exhaust Inlet Summary
System/Unit
Type of
Readinq
Outlet
Tvpe
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
ReadingReadin
Final
Final %
Remarks
Inlet-01
Flowhood
E
24X24
1.0
1085
Inlet-02
Flowhood
E
24X24
1.0
1085
Inlet-03
Flowhood
E
12X12
1.0
150
Inlet-04
Flowhood
E
24X12
1.0
50
Inlet-05
Flowhood
E
24X12
1.0
140
Inlet-06
Flowhood
E
24X12
1.0
200
Inlet-07
Flowhood
E
24X24
1.0
1200
Inlet-08
Flowhood
E
24X12
1.0
240
Inlet-09
Flowhood
E
24X12
1.0
100
Inlet-10
Flowhood
E
24X24
1.0
950
Inlet-11
Flowhood
E
24X24
1.0
205
Inlet-12
Flowhood
E
24X12
1.0
130
Inlet-13
Flowhood
R
12X12
1.0
150
Inlet-14
I Flowhood
E
12X12
1 1.0
150
Inlet-15
Flowhood
E
24X12
1.0
115
5950
0
0
0
Neudorfer Engineers, Inc. Page 45 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-01(info)/VAV-101
AREA: PARENT ROOM 132
Unit Data
Manufacturer NAILOR
Cooling Inlet Size 9 inches
HRU-01 (info)/VAV-1 01 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 505 CFM
Clg Min Des. Primary Flow 350 CFM
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
PARENT
Flowhood
B
36X48
1.0
505
ROOM
Totals:
-
505
0
0
0
SYSTEM/UNIT: HRU-01(info)/VAV-102
AREA: MIT OFFICE 132B
Unit Data
Manufacturer NAILOR
Cooling Inlet Size 5 inches
HRU-01(info)/VAV-102 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 130 CFM
Clg Min Des. Primary Flow 80 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
MT OFFICE
Flowhood
B
23X23
1.0
130
Totals:
-
-
- 4-130
0
0
0
SYSTEM/UNIT: HRU-01(info)/VAV-103
AREA: LG (DHH) 134
Unit Data
Manufacturer NAILOR
Cooling Inlet Size 12 inches
HRU-01 (info)/VAV-1 03 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 950 CFM
Clg Min Des. Primary Flow 570 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readinq
Final
Readin
Final
%
Remarks
Outlet-01
LC (DHH)
Flowhood
B
72X52
1.0
950
Totals:
-
950
1 0
0
0
1 -
Neudorfer Engineers, Inc. Page 46 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-01(info)/VAV-104
AREA: SMALL GROUP 134A
Unit Data
Manufacturer NAILOR
Cooling Inlet Size 4 inches
HRU-01(info)/VAV-104 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 100 CFM
Clg Min Des. Primary Flow 60 CFM
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
SMALL
Flowhood
B
23X23
1.0
100
GROUP
Totals:
-
-
-
-
-
100
0
0
0
-
SYSTEM/UNIT: HRU-01(info)/VAV-105
AREA: SCI PREP 136A
Unit Data
Manufacturer NAILOR
Cooling Inlet Size 6 inches
HRU-01(info)/VAV-105 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 240 CFM
Clg Min Des. Primary Flow 145 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
SCI PREP
Flowhood
B
23X23
1.0
120
Outlet-02
SCI PREP
Flowhood
B
23X23
1.0
120
Totals:
-
-
-
-
-
240
0
0
0
-
SYSTEM/UNIT: HRU-01(info)/VAV-106
AREA: LC (M SCI) 136
Unit Data
Manufacturer NAILOR
Cooling Inlet Size 14 inches
HRU-01(info)/VAV-106 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 1200 CFM
Clg Min Des. Primary Flow 720 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (M SCI)
Flowhood
B
8OX24
1.0
400
Outlet-02
LC (M SCI)
Flowhood
B
56X52
1.0
800
Totals:
-
-
-
-
-
1200
0
0
0
-
Neudorfer Engineers, Inc. Page 47 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-01(info)/VAV-107
AREA: GREEN ROOM 135
Unit Data
Manufacturer NAILOR
Cooling Inlet Size 7 inches
HRU-01 (info)/VAV-1 07 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 340 CFM
Clg Min Des. Primary Flow 150 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
GREEN ROOM
Flowhood
A
101,
1.0
200
Outlet-02
GREEN ROOM
Flowhood
B
23X23
1.0
140
Totals:
-
-
-
-
340
0
0
0
SYSTEM/UNIT: HRU-01(info)/VAV-108
AREA: LIBRARY 131
Unit Data
Manufacturer NAILOR
HRU-01 (info)/VAV-1 08 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 2170 CFM
Clg Min Des. Primary Flow 1300 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LIBRARY
Flowhood
B
80X52
1.0
1085
Outlet-02
LIBRARY
Flowhood
B
80X52
1.0
1085
Totals:
-
2170
0
0
0
SYSTEM/UNIT: HRU-01(info)/VAV-109
AREA: SMALL GROUP 131A
Unit Data
Manufacturer NAILOR
Cooling Inlet Size 5 inches
HRU-01 (info)NAV-1 09 Supply Outlet Summary
Air Test Data
Clg Max Des. Primary Flow 115 CFM
Clg Min Des. Primary Flow 65 CFM
System/Unit
Area Served
Type of
Outlet
Size
AK
Design
Design
Prelim
Final
Final
Remarks
Reading
Type
LxW / D
Velocity
Value
Reading
Reading
%
Outlet-01
SMALL
Flowhood
B
23X23
1.0
115
GROUP
Totals:
-
115
0
0
0
Neudorfer Engineers, Inc. Page 48 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-02
AREA: CLASSROOMS
Unit Data
Unit Manufacturer
D-AirTech
Unit Model Number
D-AHU-4
Unit Serial Number
D-17-078
Unit Type
Air to Air
EF Fan Rotation
Counterclockwise
SF Fan Rotation
Counterclockwise
HRU-02/EF Filter
Filter Manufacturer
Flanders
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
12x24x2
HRU-02/SF Filter
Filter Manufacturer
Flanders
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
24x24x4
Test Data
SF Total Design Flow
4420 CFM
SF Total Actual Flow
4534 CFM
EF Total Design Flow
4420 CFM
EF Total Actual Flow
4390 CFM
HRU-02/Exhaust Fan
Motor Volts T1-T2
206 Volts
Motor Volts T2-T3
206 Volts
Motor Volts T1-T3
207 Volts
Motor Amps T1
1.5 Amps
Motor Amps T2
1.6 Amps
Motor Amps T3
1.6 Amps
HRU-02/Supply Fan
Motor Volts T1-T2
206 Volts
Motor Volts T2-T3
206 Volts
Motor Volts T1-T3
207 Volts
Motor Amps T1
4.3 Amps
Motor Amps T2
4.5 Amps
Motor Amps T3
4.4 Amps
Log:
Tested By: Dwight Hammack
Date: 10/23/2018
Motor Data
HRU-02/Exhaust Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
2-1.53 HP
Motor RPM
2005 RPM
Motor Rated Volts
208-230 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
10.6 Amps
HRU-02/Supply Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
2-1.99 HP
Motor RPM
3182 RPM
Motor Rated Volts
208-230 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
2x9.42 Amps
Test Pressures
SF Design ESP
2.30 in. w.c.
SF Pre -Filter SP In
-0.53 in. we
SF Pre -Filter SP Out
-0.58 in. we
SF Fan SP In
-1.65 in. we
SF Fan SP Out
1.76 in. we
SF HC SP In
-1.46 in. we
SF HC SP Out
-1.65 in. we
EF Actual ESP
1.70 in. w.c.
EF Pre -Filter SP In
-0.29 in. we
EF Pre -Filter SP Out
-0.39 in. we
EF Fan SP In
-0.71 in. we
EF Fan SP Out
0.18 in. we
EF HEX SP In
-0.39 in. we
EF HEX SP Out
-0.71 in. we
HRU-02
10/23/2018
Dwight Hammack
(2) The volume damper is full closed.
HRU-02
10/23/2018
Dwight Hammack
(1) The volume damper is full open.
HRU-02
10/23/2018
Dwight Hammack
Building static pressure is +0.03 and the design is
+0.04.
HRU-02
10/16/2018
Dwight Hammack
Motorized damper not installed on outlet that serves
mechanical room.
Neudorfer Engineers, Inc. Page 49 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
HRU-02 Exhaust Inlet Summary
System/Unit
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
ReadingReadin
Final
Final %
Remarks
Inlet-01
Flowhood
R
30C12
1.0
1105
515
1090
99
(1)
Inlet-02
Flowhood
R
30C12
1.0
1105
525
1090
99
Inlet-03
Flowhood
R
30X12
1.0
905
535
920
102
Inlet-04
Flowhood
R
30X12
1.0
905
500
915
101
Inlet-05
Flowhood
E
12X12
1.0
150
180
140
93
Inlet-06
Flowhood
E
12X12
1.0
100
85
95
95
(2)
Inlet-07
Flowhood
E
12X12
1.0
150
125
140
93
-
-
-
-
-
4420
2465
4390
99
-
SYSTEM/UNIT: HRU-02/VAV-110
AREA: LC (L) 305A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
6
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2200.00
Tested By: Dwight Hammack
Date: 10/16/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1141 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-02NAV-110 10/16/2018 Dwight Hammack (1) The volume damper is full open.
HRU-02/VAV-110 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (L)
Flowhood
B
30X44
1.0
500
464
502
100
(1)
Outlet-02
LC (L)
Flowhood
B
4X44
1.0
605
674
639
106
Totals:
-
-
-
-
-
1105
1138
1141
103
-
Neudorfer Engineers, Inc. Page 50 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-02/VAV-111
AREA: LC (L) 305B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
7
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2199.00
Tested By: Dwight Hammack
Date: 10/16/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1135 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-02NAV-111 10/16/2018 Dwight Hammack (1) The volume damper is full open.
HRU-02/VAV-111 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (L)
Flowhood
B
36X44
1.0
500
484
497
99
(1)
Outlet-02
LC (L)
Flowhood
B
44X44
1.0
605
700
635
105
Totals:
-
-
-
-
1105
1184
1132
102
SYSTEM/UNIT: HRU-02/VAV-112
AREA: LC (P) 301A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
8
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2219.00
Tested By: Dwight Hammack
Date: 10/16/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1132 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-02NAV-112 10/16/2018 Dwight Hammack (1) The volume damper is full open.
HRU-02/VAV-112 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (P)
Flowhood
B
26X44
1.0
500
364
493
99
(1)
Outlet-02
LC (P)
Flowhood
B
44X44
1.0
605
496
639
106
Totals:
-
-
1105
860
1132
102
-
Neudorfer Engineers, Inc. Page 51 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-02/VAV-113
AREA: LC (P) 301 B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
9
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2073.00
Tested By: Dwight Hammack
Date: 10/16/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1126 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-02NAV-113 10/16/2018 Dwight Hammack (1) The volume damper is full open.
HRU-02/VAV-113 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (P)
Flowhood
B
36X44
1.0
500
332
522
104
(1)
Outlet-02
LC (P)
Flowhood
B
44X44
1.0
605
468
604
100
Totals:
-
-
-
-
-
1105
800
1126
102
-
Neudorfer Engineers, Inc. Page 52 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-03
AREA: CLASSROOMS
Unit Data
Unit Manufacturer
D-AirTech
Unit Model Number
D-AHU-4
Unit Serial Number
D-17-074
Unit Type
Air to Air
EF Fan Rotation
Counterclockwise
SF Fan Rotation
Counterclockwise
HRU-03/EF Filter
Filter Manufacturer
Flanders
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
12x24x2
HRU-03/SF Filter
Filter Manufacturer
Flanders
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
24x24x4
Test Data
SF Total Design Flow
4420 CFM
SF Total Actual Flow
4424 CFM
EF Total Design Flow
4420 CFM
EF Total Actual Flow
4330 CFM
Log:
Tested By: Dwight Hammack
Date: 10/23/2018
Motor Data
HRU-03/Exhaust Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
4.88 HP
Motor RPM
2005 RPM
Motor Rated Volts
208-230 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
10.6 Amps
HRU-03/Supply Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
2x4.14 HP
Motor RPM
3182 RPM
Motor Rated Volts
208-230 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
2x9.42 Amps
Test Pressures
SF Design ESP 2.30 in. w.c.
EF Actual ESP 1.70 in. w.c.
HRU-03 10/16/2018 Dwight Hammack
(2) The volume damper is full closed.
HRU-03 10/16/2018 Dwight Hammack
(1) The volume damper is full open.
HRU-03 10/16/2018 Dwight Hammack
Motorized damper not installed on outlet that serves
mechanical room.
HRU-03 Exhaust Inlet Summary
System/Unit
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
ReadingReadin
Final
Final %
Remarks
Inlet-01
Flowhood
R
30X12
1.0
1105
715
1080
98
(1)
Inlet-02
Flowhood
R
30X12
1.0
1105
770
1075
97
Inlet-03
Flowhood
R
30X12
1.0
905
735
900
99
Inlet-04
Flowhood
R
30X12
1.0
905
690
890
98
Inlet-05
Flowhood
E
12X12
1.0
150
150
145
97
Inlet-06
Flowhood
E
12X12
1.0
100
65
95
95
Inlet-07
Flowhood
E
12X12
1.0
150
85
145
97
-
-
-
-
-
4420
3210
4330
98
-
Neudorfer Engineers, Inc. Page 53 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-03/VAV-114
AREA: LC (L) 505A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
15
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2147.00
Tested By: Dwight Hammack
Date: 10/16/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1130 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-03NAV-114 10/16/2018 Dwight Hammack (1) The volume damper is full open.
HRU-03/VAV-114 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (L)
Flowhood
B
36X44
1.0
500
410
502
100
(1)
Outlet-02
LC (L)
Flowhood
B
44X44
1.0
605
633
628
104
Totals:
-
-
-
-
1105
1043
1130
102
SYSTEM/UNIT: HRU-03/VAV-115
AREA: LC (L) 505B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
16
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2307.00
Tested By: Dwight Hammack
Date: 10/16/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1126 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-03NAV-115 10/16/2018 Dwight Hammack (1) The volume damper is full open.
HRU-03/VAV-115 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (L)
Flowhood
B
36X44
1.0
500
439
509
102
(1)
Outlet-02
LC (L)
Flowhood
B
44X44
1.0
605
638
617
102
Totals:
-
-
1105
1077
1126
102
-
Neudorfer Engineers, Inc. Page 54 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-03/VAV-116
AREA: LC (P) 501A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
17
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2140.00
Tested By: Dwight Hammack
Date: 10/16/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1062 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-03NAV-116 10/15/2018 Dwight Hammack (1) The volume damper is full open.
HRU-03/VAV-116 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (P)
Flowhood
B
36X44
1.0
500
323
487
97
(1)
Outlet-02
LC (P)
Flowhood
B
44X44
1.0
605
435
575
95
Totals:
-
-
-
-
1105
758
1062
96
SYSTEM/UNIT: HRU-03/VAV-117
AREA: LC (P) 501 B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
18
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2038.00
Tested By: Dwight Hammack
Date: 10/16/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1106 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-03NAV-117 10/16/2018 Dwight Hammack (1) The volume damper is full open.
HRU-03/VAV-117 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (P)
Flowhood
B
36X44
1.0
500
541
489
98
(1)
Outlet-02
LC (P)
Flowhood
B
44X44
1.0
605
480
617
102
Totals:
-
-
1105
1021
1106
100
-
Neudorfer Engineers, Inc. Page 55 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-04
AREA: CLASSROOMS
Unit Data
Unit Manufacturer
D-AirTech
Unit Model Number
D-AHU-6
Unit Serial Number
D-17-076
Unit Type
Air to Air
EF Fan Rotation
Counterclockwise
SF Fan Rotation
Counterclockwise
HRU-04/EF Filter
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
12x24x2
HRU-04/SF Filter
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x4
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
24x24x2
Filter Quantity - Size 3
3
Filter Dimensions - Size 3
12x24x4
Filter Quantity - Size 4
3
Filter Dimensions - Size 4
12x24x2
Test Data
SF Total Design Flow
6640 CFM
SF Total Actual Flow
6573 CFM
EF Total Design Flow
6640 CFM
EF Total Actual Flow
6470 CFM
Log:
Tested By: Dwight Hammack
Date: 10/24/2018
Motor Data
HRU-04/Exhaust Fan
Drive Type
Direct Drive
Motor HP
(2)4 HP
Motor RPM
2270 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
(2)3.66 Amps
HRU-04/Supply Fan
Drive Type
Direct Drive
Motor HP
(2)4 HP
Motor RPM
2494 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
(2)3.66 Amps
Test Pressures
SF Design ESP 2.30 in. w.c.
EF Actual ESP 1.70 in. w.c.
HRU-04 10/23/2018 Dwight Hammack (1) The volume damper is full open.
HRU-04 10/16/2018 Dwight Hammack Motorized damper not installed on outlet that serves
mechanical room.
Neudorfer Engineers, Inc. Page 56 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
HRU-04 Exhaust Inlet Summary
System/Unit
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
ReadingReadin
Final
Final %
Remarks
Inlet-01
Flowhood
E
24X12
1.0
105
170
100
95
Inlet-02
Flowhood
E
24X12
1.0
105
270
100
95
Inlet-03
Flowhood
R
30X12
1.0
1005
960
1000
100
Inlet-04
Flowhood
R
30X12
1.0
755
840
735
97
Inlet-05
Flowhood
E
12XX12
1.0
100
120
100
100
Inlet-06
Flowhood
E
12X12
1.0
150
110
145
97
Inlet-07
Flowhood
E
24X12
1.0
105
130
100
95
Inlet-08
Flowhood
E
24X12
1.0
105
155
100
95
Inlet-09
Flowhood
R
30X12
1.0
1000
920
1000
100
(1)
Inlet-10
Flowhood
R
30X12
1.0
925
1 930
925
100
Inlet-11
Flowhood
E
12X12
1.0
150
190
145
1 97
Inlet-12*
Flowhood
E
12X12
1.0
100
70
90
90
(1)
Inlet-13
Flowhood
E
12X12
1.0
100
80
95
95
Inlet-14
Flowhood
E
12X12
1.0
150
120
140
93
Inlet-15
Flowhood
R
30X12
1.0
800
675
755
94
(1)
Inlet-16
Flowhood
R
30X12
1.0
800
1 670
1 740
93
Inlet-17
Flowhood
E
24X2
1.0
105
110
100
1 95
Inlet-18
Flowhood
E
24X12
1.0
105
90
100
95
-
-
6665
1 6610
6470
97
-
Log: HRU-04/Inlet-12 10/16/2018 Andrey Polishchuk (1) The volume damper is full open.
SYSTEM/UNIT: HRU-04/VAV-118
AREA: LC (M) 201
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
6
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
1359.00
HRU-04/VAV-118 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/15/2018
Air Test Data
Clg Max Des. Primary Flow
1005 CFM
Clg Min Des. Primary Flow
605 CFM
Clg Max Act. Primary Flow
984 CFM
Clg Min Act. Primary Flow
605 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC (M)
Flowhood
B
72X44
1.0
1005
629
984
98
1
Totals:
-
-
- 4-1005
629
984
98
1 -
Neudorfer Engineers, Inc. Page 57 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-04/VAV-119
AREA: LC (MO 201
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
7
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
1353.00
HRU-04/VAV-119 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/15/2018
Air Test Data
Clg Max Des. Primary Flow
1005 CFM
Clg Min Des. Primary Flow
605 CFM
Clg Max Act. Primary Flow
974 CFM
Clg Min Act. Primary Flow
605 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC (M)
Flowhood
B
72X44
1.0
1005
607
974
97
1
Totals:
-
-
- 4-1005
607
974
97
1 -
SYSTEM/UNIT: HRU-04/VAV-120
AREA: LC SMALL 201A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
8
Application #
2061
Cooling Inlet Size
4 inches
Cooling K Factor
334.00
HRU-04/VAV-120 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/15/2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
106 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
23X23
1.0
105
138
106
101
1
Totals:
-
105
138
106
101
Neudorfer Engineers, Inc. Page 58 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-04/VAV-121
AREA: LC SMALL 201 B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
9
Application #
2061
Cooling Inlet Size
4 inches
Cooling K Factor
320.00
HRU-04/VAV-121 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/15/2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
107 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
23X23
1.0
105
132
107
102
1
Totals:
-
-
- 4-105
132
107
102
1 -
SYSTEM/UNIT: HRU-04/VAV-122
AREA: LC (DHH PK/K) 204
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
10
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
1434.00
Tested By: Dwight Hammack
Date: 10/15/2018
Air Test Data
Clg Max Des. Primary Flow
1000 CFM
Clg Min Des. Primary Flow
600 CFM
Clg Max Act. Primary Flow
1020 CFM
Clg Min Act. Primary Flow
600 CFM
Log: I
HRU-04NAV-122 10/15/2018 Dwight Hammack (1) The volume damper is full open.
HRU-04/VAV-122 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (DHH PK/K)
Flowhood
B
36X44
1.0
500
273
510
102
(1)
Outlet-02
LC (DHH PK/K)
Flowhood
B
44X44
1.0
500
435
510
102
Totals:
-
1000
708
1020
102
-
Neudorfer Engineers, Inc. Page 59 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-04/VAV-123
AREA: LC (K) 203
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
11
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
1457.00
Tested By: Dwight Hammack
Date: 10/15/2018
Air Test Data
Clg Max Des. Primary Flow
1000 CFM
Clg Min Des. Primary Flow
600 CFM
Clg Max Act. Primary Flow
983 CFM
Clg Min Act. Primary Flow
600 CFM
Log: I
HRU-04NAV-123 10/15/2018 Dwight Hammack (1) The volume damper is full open.
HRU-04/VAV-123 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (K)
Flowhood
B
36X44
1.0
500
261
497
99
(1)
Outlet-02
LC (K)
Flowhood
B
44X44
1.0
500
423
486
97
Totals:
-
-
-
-
1000
684
983
98
SYSTEM/UNIT: HRU-04/VAV-124
AREA: LC SMALL 203A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
12
Application #
2061
Cooling Inlet Size
4 inches
Cooling K Factor
313.00
HRU-04/VAV-124 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/15/2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
105 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
23X23
1.0
105
264
105
100
1
Totals:
-
4-105
264
105
100
Neudorfer Engineers, Inc. Page 60 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-04/VAV-125
AREA: LC SMALL 203B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
13
Application #
2061
Cooling Inlet Size
4 inches
Cooling K Factor
319.00
HRU-04/VAV-125 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/15/2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
107 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
23X23
1.0
105
234
107
102
1
Totals:
-
-
- 4-105
234
107
102
1 -
SYSTEM/UNIT: HRU-04/VAV-126
AREA: LC (K) 207A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
14
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
1460.00
Tested By: Dwight Hammack
Date: 10/12/2018
Air Test Data
Clg Max Des. Primary Flow
1000 CFM
Clg Min Des. Primary Flow
600 CFM
Clg Max Act. Primary Flow
990 CFM
Clg Min Act. Primary Flow
600 CFM
Log: 1
HRU-041VAV-126 10/12/2018 Dwight Hammack (1) The volume damper is full open.
HRU-04/VAV-126 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (K)
Flowhood
B
44X45
1.0
500
288
485
97
(1)
Outlet-02
LC (K)
Flowhood
B
44X44
1.0
500
408
505
101
Totals:
-
1000
696
990
99
-
Neudorfer Engineers, Inc. Page 61 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-04/VAV-127
AREA: LC (K) 207B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
15
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
1437.00
Tested By: Dwight Hammack
Date: 10/12/2018
Air Test Data
Clg Max Des. Primary Flow
1000 CFM
Clg Min Des. Primary Flow
600 CFM
Clg Max Act. Primary Flow
988 CFM
Clg Min Act. Primary Flow
600 CFM
Log: I
HRU-04NAV-127 10/12/2018 Dwight Hammack (1) The volume damper is full open.
HRU-04/VAV-127 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (K)
Flowhood
B
44X45
1.0
500
346
496
99
(1)
Outlet-02
LC (K)
Flowhood
B
43X44
1.0
500
632
492
98
Totals:
-
-
-
-
1000
978
988
99
SYSTEM/UNIT: HRU-04/VAV-128
AREA: LC SMALL 207A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
16
Application #
2061
Cooling Inlet Size
4 inches
Cooling K Factor
410.00
HRU-04/VAV-128 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/12/2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
105 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
24X12
1.0
105
301
105
100
1
Totals:
-
4-105
301
105
100
1 -
Neudorfer Engineers, Inc. Page 62 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-04/VAV-129
AREA: LC SMALL 207B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
17
Application #
2061
Cooling Inlet Size
4 inches
Cooling K Factor
328.00
HRU-04/VAV-129 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/12/2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
104 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
23X23
1.0
105
306
104
99
1
Totals:
-
-
- 4-105
306
104
99
1 -
Neudorfer Engineers, Inc. Page 63 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-05
AREA: CLASSROOMS
Unit Data
Unit Manufacturer
D-AirTech
Unit Model Number
D-AHU-6
Unit Serial Number
D-17-076
Unit Type
Air to Air
EF Fan Rotation
Counterclockwise
SF Fan Rotation
Counterclockwise
HRU-05/EF Filter
Filter Manufacturer
Flanders
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
12x24x2
HRU-05/SF Filter
Filter Manufacturer
Flanders
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
12x24x2
Filter Quantity - Size 3
3
Filter Dimensions - Size 3
24x24x4
Filter Quantity - Size 4
3
Filter Dimensions - Size 4
12x24x4
Test Data
SF Total Design Flow
6640 CFM
SF Total Actual Flow
6552 CFM
EF Total Design Flow
6640 CFM
EF Total Actual Flow
6227 CFM
Log:
Tested By: Dwight Hammack
Date: 10/24/2018
Motor Data
HRU-05/Exhaust Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
4x2 HP
Motor RPM
2270 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
8.65x2 Amps
HRU-05/Supply Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
4x2 HP
Motor RPM
2494 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
8.65x2 Amps
Test Pressures
SF Design ESP 2.30 in. w.c.
EF Actual ESP 1.70 in. w.c.
HRU-05 10/12/2018 Dwight Hammack
(2) The volume damper is full closed.
HRU-05 10/12/2018 Dwight Hammack
(1) The volume damper is full open.
HRU-05 8/9/2018 Dwight Hammack
Motorized damper not installed on outlet that serves
mechanical room.
Neudorfer Engineers, Inc. Page 64 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
HRU-05 Exhaust Inlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
ReadingReadin
Final
Final %
Remarks
Inlet-01
SMALL
GROUP
Flowhood
E
24X12
1.0
105
62
97
92
Inlet-02
SMALL
GROUP
Flowhood
E
24X12
1.0
105
66
103
98
Inlet-03
OPEN AREA
Flowhood
R
30X12
1.0
1005
1 751
916
91
1 (1)
Inlet-04
OPEN AREA
Flowhood
R
30X12
1.0
755
812
679
90
Inlet-05
BATHROOM
Flowhood
E
24XS12
1.0
100
90
95
95
Inlet-06
BATHROOM
Flowhood
E
24X12
1.0
150
130
136
91
Inlet-07
OPEN AREA
Flowhood
R
30X12
1.0
1105
1070
1043
94
Inlet-08
OPEN AREA
Flowhood
R
30X12
1.0
1105
1175
993
90
Inlet-09
BATHROOM
Flowhood
E
12X12
1.0
150
354
159
106
Inlet-10
BATHROOM
Flowhood
E
12X12
1.0
100
159
170
170
1 (2)
Inlet-11
BATHROOM
Flowhood
E
12X12
1.0
150
219
150
100
(2)
Inlet-12
OPEN AREA
Flowhood
R
30X12
1.0
905
1244
837
92
Inlet-13
OPEN AREA
Flowhood
R
30XX12
1.0
905
856
849
94
Totals:
-
-
-
1 6640
6988
6227
94
SYSTEM/UNIT: HRU-05/VAV-130
AREA: LC (DHH)401
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
23
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
1318.00
HRU-05/VAV-130 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
1005 CFM
Clg Min Des. Primary Flow
605 CFM
Clg Max Act. Primary Flow
1040 CFM
Clg Min Act. Primary Flow
605 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC (DHH)
Flowhood
B
72X44
1.0
1005
630
1040
103
1
Totals:
-
4-1005
630
1040
103
1 -
Neudorfer Engineers, Inc. Page 65 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-05/VAV-131
AREA: LC (DHH) 402
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
24
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
1370.00
HRU-05/VAV-131 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
1005 CFM
Clg Min Des. Primary Flow
605 CFM
Clg Max Act. Primary Flow
1005 CFM
Clg Min Act. Primary Flow
605 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC (DHH)
Flowhood
B
72X44
1.0
1005
610
1050
104
1
Totals:
-
-
- 4-1005
610
1050
104
1 -
SYSTEM/UNIT: HRU-05/VAV-132
AREA: LC SMALL 401A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
25
Application #
2061
Cooling Inlet Size
4 inches
Cooling K Factor
282.00
HRU-05NAV-132 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
105 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
23X23
1.0
105
280
105
100
1
Totals:
-
-
-
-
105
280
105
100
Neudorfer Engineers, Inc. Page 66 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-05/VAV-133
AREA: LC SMALL 401 B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
26
Application #
2061
Cooling Inlet Size
4 inches
Cooling K Factor
740.00
HRU-05/VAV-133 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/24/2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
107 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
23X23
1.0
105
295
107
102
1
Totals:
-
-
- 4-105
295
107
102
1 -
SYSTEM/UNIT: HRU-05/VAV-134
AREA: LC (P) 403A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
27
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
2141.00
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1050 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-05/VAV-134 10/11/2018 Dwight Hammack (1) The volume damper is full open.
HRU-05/VAV-134 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (P)
Flowhood
B
44X46
1.0
500
295
470
94
(1)
Outlet-02
LC (P)
Flowhood
B
43X44
1.0
605
500
580
96
Totals:
-
1105
795
1050
95
-
Neudorfer Engineers, Inc. Page 67 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-05/VAV-135
AREA: LC (P) 403B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
28
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
2082.00
Tested By: Dwight Hammack
Date: 10/11/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1095 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-05NAV-135 10/11/2018 Dwight Hammack (1) The volume damper is full open.
HRU-05/VAV-135 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (P)
Flowhood
B
44X46
1.0
500
315
480
96
(1)
Outlet-02
LC (P)
Flowhood
B
43X44
1.0
605
405
615
102
Totals:
-
-
-
-
1105
720
1095
99
SYSTEM/UNIT: HRU-05/VAV-136
AREA: LC (LO) 407A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
29
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
2226.00
Tested By: Dwight Hammack
Date: 10/11/2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1065 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-05NAV-136 10/11/2018 Dwight Hammack (1) The volume damper is full open.
HRU-05/VAV-136 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (L)
Flowhood
B
44X46
1.0
500
335
475
95
(1)
Outlet-02
LC (L)
Flowhood
B
43X44
1.0
605
465
590
98
Totals:
-
1105
800
1065
96
-
Neudorfer Engineers, Inc. Page 68 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-05/VAV-137
AREA: LC (L) 407B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
30
Application #
2061
Cooling Inlet Size
12 inches
Cooling K Factor
2185.00
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1085 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-05NAV-137 10/11/2018 Dwight Hammack (1) The volume damper is full open.
HRU-05/VAV-137 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (L)
Flowhood
B
44X46
1.0
500
270
495
99
(1)
Outlet-02
LC (L)
Flowhood
B
43X44
1.0
605
470
590
98
Totals:
-
-
-
-
-
1105
740
1085
98
-
Neudorfer Engineers, Inc. Page 69 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-06
AREA: CLASSROOMS
Unit Data
Unit Manufacturer
D-AirTech
Unit Model Number
D-AHU-6
Unit Serial Number
D-17-077
Unit Type
Air to Air
EF Fan Rotation
Counterclockwise
SF Fan Rotation
Counterclockwise
HRU-06/EF Filter
Filter Manufacturer
Flanders
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
12x24x2
HRU-06/SF Filter
Filter Manufacturer
Flanders
Filter Type
Pleated
Filter Quantity - Size 1
3
Filter Dimensions - Size 1
24x24x2
Filter Quantity - Size 2
3
Filter Dimensions - Size 2
12x24x2
Filter Quantity - Size 3
3
Filter Dimensions - Size 3
24x24x4
Filter Quantity - Size 4
3
Filter Dimensions - Size 4
12x24x4
Test Data
SF Total Design Flow
6640 CFM
SF Total Actual Flow
6565 CFM
EF Total Design Flow
6640 CFM
EF Total Actual Flow
6475 CFM
Log:
Tested By: Dwight Hammack
Date: 10/23/2018
Motor Data
HRU-06/Exhaust Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
4x2 HP
Motor RPM
2270 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
8.65x2 Amps
HRU-06/Supply Fan
Drive Type
Direct Drive
Motor Manufacturer
Ziehl-Abegg
Motor HP
4x2 HP
Motor RPM
2494 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
8.65x2 Amps
Test Pressures
SF Design ESP 2.30 in. w.c.
EF Actual ESP 1.70 in. w.c.
HRU-06 10/12/2018 Dwight Hammack
(2) The volume damper is full closed.
HRU-06 10/12/2018 Dwight Hammack
(1) The volume damper is full open.
HRU-06 8/10/2018 Dwight Hammack
Motorized damper not installed on outlet that serves
mechanical room.
Neudorfer Engineers, Inc. Page 70 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
HRU-06 Exhaust Inlet Summary
System/Unit
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
ReadingReadin
Final
Final %
Remarks
Inlet-01
Flowhood
E
24X12
1.0
105
70
100
95
Inlet-02
Flowhood
E
24X12
1.0
105
85
100
95
Inlet-03
Flowhood
R
30X12
1.0
755
630
740
98
Inlet-04
Flowhood
R
30X12
1.0
1005
590
980
98
(1)
Inlet-05
Flowhood
E
12X12
1.0
150
135
145
97
Inlet-06
Flowhood
E
12X12
1.0
100
140
95
95
Inlet-07
Flowhood
R
30X12
1.0
1105
1075
1000
90
Inlet-08
Flowhood
R
30X12
1.0
1105
980
1080
98
Inlet-09
Flowhood
E
12X12
1.0
150
97
195
130
(2)
Inlet-10
Flowhood
E
12X12
1.0
100
1 108
145
145
(2)
Inlet-11
Flowhood
E
12X12
1.0
150
180
140
93
(2)
Inlet-12
Flowhood
R
30X12
1.0
905
180
880
97
Inlet-13
Flowhood
R
30X12
1.0
905
1820
875
97
-
-
I -
-
6640
6090
1 6475
98
-
SYSTEM/UNIT: HRU-06/VAV-138
AREA: LC (M) 601
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
24
Application #
2051
Cooling Inlet Size
10 inches
Cooling K Factor
1347.00
HRU-06/VAV-138 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/23/2018
Air Test Data
Clg Max Des. Primary Flow
1005 CFM
Clg Min Des. Primary Flow
605 CFM
Clg Max Act. Primary Flow
990 CFM
Clg Min Act. Primary Flow
605 CFM
Htg Max Des. Primary Flow
605 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC (M)
Flowhood
B
73x44
1
1005
802
990
99
1
Totals:
I-
-
1 1005
802
990
99
1 -
Neudorfer Engineers, Inc. Page 71 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-06/VAV-139
AREA: LC (M) 602
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
25
Application #
2051
Cooling Inlet Size
10 inches
Cooling K Factor
1359.00
HRU-06/VAV-139 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
1005 CFM
Clg Min Des. Primary Flow
605 CFM
Clg Max Act. Primary Flow
990 CFM
Clg Min Act. Primary Flow
605 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC (M)
Flowhood
B
73x44
1
1005
1 892
990
99
Totals:
-
-
-
-
-
1005
1 892
990
99
1 -
SYSTEM/UNIT: HRU-06/VAV-140
AREA: LC SMALL 601A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
26
Application #
2051
Cooling Inlet Size
4 inches
Cooling K Factor
364.00
HRU-06NAV-140 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
105 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
23X23
1.0
105
210
105
100
Totals:
-
-
-
105
210
105
100
-
Neudorfer Engineers, Inc. Page 72 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-06/VAV-141
AREA: LC SMALL 601 B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
27
Application #
2051
Cooling Inlet Size
4 inches
Cooling K Factor
422.00
HRU-06/VAV-141 Supply Outlet Summary
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
105 CFM
Clg Min Des. Primary Flow
65 CFM
Clg Max Act. Primary Flow
100 CFM
Clg Min Act. Primary Flow
65 CFM
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Readina
Final
Readin
Final
%
Remarks
Outlet-01
LC SMALL
Flowhood
B
23X23
1.0
105
45
100
95
1
Totals:
I-
-
105
45
100
95
1 -
SYSTEM/UNIT: HRU-06/VAV-142
AREA: LC (P) 603A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
28
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2118.00
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1105 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-06NAV-142 10/10/2018 Dwight Hammack (1) The volume damper is full open.
HRU-06/VAV-142 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (P)
Flowhood
B
44X46
1
500
485
495
99
Outlet-02
LC (P)
Flowhood
B
43X44
1
605
502
610
101
(1)
Totals:
-
1105
987
1105
100
-
Neudorfer Engineers, Inc. Page 73 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-06/VAV-143
AREA: LC (P) 603B
Unit Data
Manufacturer
NAILOR
Model Number
SDV5
VAV Address
29
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2203.00
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1075 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-06NAV-143 10/10/2018 Dwight Hammack (1) The volume damper is full open.
HRU-06/VAV-143 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (P)
Flowhood
B
44X46
1
500
447
495
99
(1)
Outlet-02
LC (P)
Flowhood
B
43X44
1
605
539
580
96
Totals:
-
-
-
-
1105
986
1075
97
SYSTEM/UNIT: HRU-06/VAV-144
AREA: LC (L) 607A
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
30
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2146.00
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1090 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-06NAV-144 10/10/2018 Dwight Hammack (1) The volume damper is full open.
HRU-06/VAV-144 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (L)
Flowhood
B
44X46
1.0
500
450
510
102
(1)
Outlet-02
LC (L)
Flowhood
B
43X44
1.0
605
650
580
96
Totals:
-
-
1105
1100
1090
99
-
Neudorfer Engineers, Inc. Page 74 of 93
Energy Recovery Unit
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: HRU-06/VAV-145
AREA: LC (L) 607B
Unit Data
Manufacturer
Price
Model Number
SDV5
VAV Address
31
Application #
2051
Cooling Inlet Size
12 inches
Cooling K Factor
2191.00
Tested By: Dwight Hammack
Date: 10/11 /2018
Air Test Data
Clg Max Des. Primary Flow
1105 CFM
Clg Min Des. Primary Flow
665 CFM
Clg Max Act. Primary Flow
1110 CFM
Clg Min Act. Primary Flow
665 CFM
Log: I
HRU-06NAV-145 10/10/2018 Dwight Hammack (1) The volume damper is full open.
HRU-06/VAV-145 Supply Outlet Summary
System/Unit
Area Served
Type of
Reading
Outlet
Type
Size
LxW / D
AK
Design
Velocity
Design
Value
Prelim
Reading
Final
Reading
Final
%
Remarks
Outlet-01
LC (L)
Flowhood
B
44x46
1
500
458
500
100
(1)
Outlet-02
LC (L)
Flowhood
B
43X44
1
605
650
610
101
Totals:
-
-
-
-
-
1105
1108
1110
100
-
Neudorfer Engineers, Inc. Page 75 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-01 Cooling Mode
Final Test Data
Final Disch Press.
49 PSI
Final Suction Press.
26 PSI
Final Press. Diff. Actual
23 PSI
VFD Hertz
38.5 Hz
Motor Volts T1-T2
229 Volts
Motor Volts T2-T3
228 Volts
Motor Volts T1-T3
229 Volts
Motor Amps T1
12.8 Amps
Motor Amps T2
12.8 Amps
Motor Amps T3
12.7 Amps
PU-01 Cooling Mode Autoflow Valve Summary
Tested By: Alex Lebedev
Date: 10/24/2018
System/Unit
Manufacturer
Model
Number
Valve Size
Design
Flow
Actual
Flow
Design
D.P.
Actual
D.P.
AHU-01
Flow Design
AC-100
1"
6.9
2-32
9
AHU-02
Flow Design
AC-100
1"
6.9
2-32
12
AHU-03
Flow Design
AC-125
1 1/4"
11.8
2-32
7
AHU-04
Flow Design
AC-125
1 1/4"
7.8
2-32
9
AHU-05
Flow Design
AC-200
2"
20
2-32
2
AHU-06
Flow Design
AC-125
1 1/4"
8.0
2-32
8
AHU-07
Flow Design
WS-250
2 1/2"
59.9
2-32
6
HRU-01"
Flow Design
AC-150
1 1/2"
17.9
2-32
12
HRU-02"
Flow Design
AC-150
1 1/2"
13.6
2-32
3
HRU-03"
Flow Design
AC-150
1 1/2"
13.6
2-32
9
HRU-04"
Flow Design
AC-200
2"
20
2-32
12
HRU-05"
Flow Design
AC-200
2"
20
2-32
11
HRU-06"
Flow Design
AC-200
2"
20
2-32
11
Totals:
-
-
I -
1 0
226.4
-
-
Log:
ng
PU-01 Cooling Mode/HRU-02
PU-01 Cooling Mode/HRU-03
PU-01 Cooling Mode/HRU-04
PU-01 Cooling Mode/HRU-05
PU-01 Cooling Mode/HRU-06
Armflo. Set to 1.3ftWC each
10/24/2018
Alex Lebedev
Coil has 2 sections with 2 Armstrong CBV 3/4 inch
Armflo. Set to 3 ftWC each
10/24/2018
Alex Lebedev
Coil has 2 sections with 2 Armstrong CBV 3/4 inch
Armflo. Set to 3.3 ftWC each
10/24/2018
Alex Lebedev
Coil has 2 sections with 2 Armstrong CBV 1 inch
Armflo. Set to 1.5 ftWC each
10/24/2018
Alex Lebedev
Coil has 2 sections with 2 Armstrong CBV 1 inch
Armflo. Set to 1.6ftWC each
10/24/2018
Alex Lebedev
Coil has 2 sections with 2 Armstrong CBV 1 inch
Armflo. Set to 1.7 ftWC each
Neudorfer Engineers, Inc. Page 76 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-01 Heating mode
AREA: HYDRONIC WATER
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
4x3x11.5
Pump Serial Number
843868
Pump Flowrate
390 GPM
TDH/FT
130
Final Test Data
Final Disch Press.
56 PSI
Final Suction Press.
22 PSI
Final Press. Diff. Actual
34 PSI
Final Design Flow
400 GPM
Final Actual Flow
440 GPM
VFD Hertz
50.1 Hz
Motor Volts T1-T2
350 Volts
Motor Volts T2-T3
350 Volts
Motor Volts T1-T3
350 Volts
Motor Amps T1
19.4 Amps
Motor Amps T2
19.5 Amps
Motor Amps T3
19.4 Amps
Log:
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor Manufacturer
Brook Crompton
Motor Frame
284T
Motor HP
25 HP
Motor RPM
1770 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor F.L. Amps
27.9 Amps
Motor S.F.
1.25
Motor Nominal Efficiency
93.6
Motor Power Factor
0.89
Pump Impeller Diam.
11.5
Measured Data
Pump Off Pressure
25 PSI
Valve Shut DP
72 PSI
Valve Shut SP
26 PSI
Valve Shut Diff.
46 PSI
Valve Open DP
74 PSI
Valve Open SP
22 PSI
Valve Open Diff.
52.0 PSI
Valve Open Flow
480 GPM
PU-01 Heating mode 10/23/2018 Alex Lebedev Actual final water flow was calculated using approved
pump curve provided by the manufacturer.
PU-01 Heating mode 10/23/2018 Alex Lebedev System operating pressure setpoint is 20.5PS1.
PU-01 Heating mode 10/17/2018 Alex Lebedev The operating Amps and Volts were recorded from
the VFD.
PU-01 Heating mode Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
AHU-01(info)
ORCHESTRA
123
AC-100
1"
17
5.8
6.9
6.9
Flow Design
AHU-02(info)
BAND 121
AC-100
1"
20
5.8
6.9
6.9
Flow Design
AHU-03(info)
KITCHEN 117
AC-125
1 1/4"
12
10.2
11.8
11.8
Flow Design
AHU-04(info)
MUSIC 122
AC-125
1 1/4"
15
6.9
7.6
7.6
Flow Design
AHU-05
COMMONS
115/SERVERY
115A
AC-200
2"
3
28.5
32.2
32.2
Flow Design
AHU-06(info)
HALLWAY
COMMONS
100C
AC-125
1 1/4"
16
7.3
8
8
Flow Design
AHU-07
GYMNASIUM
107
WS-250
2 1/2"
9
55.3
59.9
59.9
Flow Design
AHU-08(info)
ADMIN WING
AC-150
1 1/2"
17
15.4
18
18
Flow Design
HRU-01(info)
CLASSROOM/
READING
AC-150
1 1/2"
16
16.1
17.9
17.9
Flow Design
HRU-02
CLASSROOM
AC-150
1 1/2"
3
12.4
13.6
Flow Design
HRU-03
CLASSROOM
AC-150
1 1/2"
3
12.4
13.6
Flow Design
HRU-04
CLASSROOM
AC-200
2"
6
18.6
20.0
Flow Design
HRU-05
CLASSROOM
AC-200
2"
5
18.6
18.6
18.6
Flow Design
HRU-06
CLASSROOM
AC-200
2"
4
18.6
18.6
18.6
Flow Design
Neudorfer Engineers, Inc. Page 77 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
PU-01 Info /
VAV-129
ACM 075
3/4"
5
0.2
0.2
Flow Design
RF-101
PARENT
ROOM 132
AC-100
1"
18
0.9
0.9
0.9
Flow Design
RF-102
MITOFF ICE
132E
AC-100
1"
7
0.5
0.5
0.5
Flow Design
RF-103
LC9 DHH) 134
AC-100
1"
18
2.0
2.0
2.0
Flow Design
RF-104
SMALL GROUP
134A
AC-100
1"
7
0.5
0.5
0.5
Flow Design
RF-105
SCIPR EP
136A
AC-100
1"
20
0.4
0.4
0.4
Flow Design
RF-106
LC9 M SCI) 136
AC-100
1"
18
2.3
1 2.3
2.3
Flow Design
RF-107
GREEN ROOM
135
AC-100
1"
7
0.4
0.4
0.4
Flow Design
RF-108A/108B'
LIBRARY 131
AC-100
1"
2.2
Flow Design
RF-109
SMALL GROUP
131A
AC-100
1"
14
0.2
0.2
0.2
Flow Design
RF-110
LC (L) 305A
AC-100
1"
7
2.6
2.6
Flow Design
RF-111
LC (L) 305B
AC-100
1"
7
2.5
2.5
Flow Design
RF-112
LC (P) 301A
AC-100
1"
9
2.5
2.5
Flow Design
RF-113
LC (P) 301 B
AC-100
1"
8
2.5
2.5
Flow Design
RF-114
LC (L) 505A
AC-100
1"
6
2.5
2.5
Flow Design
RF-115
LC (L) 505B
AC-100
1"
5
2.5
2.5
Flow Design
RF-116
LC (P) 501A
AC-100
1"
5
2.5
2.5
Flow Design
RF-117
LC (P) 501 B
AC-100
1"
5
2.5
2.5
Flow Design
RF-118
LC (M) 201
AC-100
1"
5
2.3
1 2.3
2.3
Flow Design
RF-119
LC (M) 202
AC-100
1"
5
2.3
2.3
2.3
Flow Design
RF-120
LC SMALL
201 A
AC-100
1"
5
0.4
0.4
0.4
Flow Design
RF-121
LC SMALL
201 B
AC-100
1"
5
0.2
0.2
0.2
Flow Design
RF-122'
LC (DHH/PK/K)
204
AC-100
1"
1
2.1
Flow Design
RF-123
LC (K) 203
AC-100
1"
4
2.1
2.5
Flow Design
RF-124
SMALL GROUP
203A
AC-100
1"
8
0.2
0.2
Flow Design
RF-125
SMALL GROUP
203E
AC-100
1"
3
0.2
0.2
0.2
Flow Design
RF-126
LC (K) 207
AC-100
1"
10
2.3
2.5
Flow Design
RF-127'
LC (L) 208
AC-100
1"
2.3
Flow Design
RF-128'
SMALL GROUP
207A
AC-100
1"
0.2
Flow Design
RF-129"
SMALL GROUP
207B
AC-100
1"
1.0
0.3
Flow Design
RF-130
LC (DHH) 401
AC-100
1/2"
8
2.3
2.3
2.3
Flow Design
RF-131
LC9 DHH) 402
AC-100
3/4"
3
2.3
2.3
2.3
Flow Design
RF-132
LC SMALL
401A
AC-100
1/2"
7
0.4
0.4
0.4
Flow Design
RF-133
LC SMALL
401B
AC-100
1/2"
4
0.2
0.2
0.2
Flow Design
RF-134
LC (P) 403A
AC-100
3/4"
5
2.5
2.5
2.5
Flow Design
RF-135
LC (P) 403B
AC-100
3/4"
4
2.5
2.5
2.5
Flow Design
RF-136
LC (L) 407A
AC-100
3/4"
7
2.5
2.5
2.5
Flow Design
RF-137
LC (L) 407B
AC-100
3/4"
8
2.5
2.5
2.5
Flow Design
RF-138
LC (M) 601
AC-100
3/4"
6
2.3
2.3
2.3
Flow Design
RF-139
LC (M) 602
AC-100
3/4"
5
2.3
2.3
2.3
Flow Design
RF-140
LC SMALL
601 A
AC-100
1/2"
5
0.4
0.4
0.4
Flow Design
RF-141
LC SMALL
601 B
AC-100
1/2"
i
i
4
0.2
0.2
0.2
Flow Design
Neudorfer Engineers, Inc. Page 78 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
RF-142
LC (P) 603A
AC-100
3/4"
4
2.5
2.5
2.5
Flow Design
RF-143
AC-100
3/4"
5
2.5
2.5
2.5
Flow Design
RF-144
LC (L) 607A
AC-100
3/4"
4
2.5
2.5
2.5
Flow Design
RF-145
LC (L) 607B
AC-100
3/4"
4
2.5
2.5
2.5
Flow Design
VAV-101
PARENT
ROOM 132
ACM-075
3/4"
20
0.9
0.9
0.9
Flow Design
VAV-102"
MIT OFFICE
132B
ACM-075
3/4"
0.3
Flow Design
VAV-103
LG (DHH) 134
ACM-075
1/2"
22
1.6
1.6
1.6
Flow Design
VAV-104
SMALL GROUP
134A
ACM-075
3/4"
20
0.2
0.2
0.2
Flow Design
VAV-105`
SCI PREP
136A
ACM-075
3/4"
0.4
Flow Design
VAV-106
LC (M SCI) 136
ACM-075
3/4"
21
2.0
2.0
2.0
Flow Design
VAV-107
GREEN ROOM
135
ACM-075
3/4"
20
0.6
0.6
0.6
Flow Design
VAV-108
LIBRARY 131
AC-100
3/4"
20
3.7
3.7
3.7
Flow Design
VAV-109
SMALL GROUP
131A
ACM-075
3/4"
5
0.2
0.2
0.2
Flow Design
VAV-110
LC (L) 305A
ACM 075
3/4"
3
1.9
1.9
Flow Design
VAV-111
LC (L) 305B
ACM 075
3/4"
9
1.9
1.9
Flow Design
VAV-112
LC (P) 301A
ACM 075
3/4"
5
1.9
1.9
Flow Design
VAV-113
LC (P) 301 B
ACM 075
3/4"
3
1.9
1.9
Flow Design
VAV-114
LC (L) 505A
ACM 075
3/4"
3
1.9
1.9
Flow Design
VAV-115
LC (L) 505B
ACM 075
3/4"
4
1.9
1
1.9
Flow Design
VAV-116
LC (P) 501A
ACM 075
3/4"
4
1.9
1.9
Flow Design
VAV-117
LC (P) 501 B
ACM 075
3/4"
4
1.9
1.9
Flow Design
VAV-118
LC (M) 201
ACM 075
3/4"
3
1.7
1.7
1.7
Flow Design
VAV-119
LC (MO 201
ACM 075
3/4"
6
1.7
1.7
1.7
Flow Design
VAV-120
LC SMALL
201 A
ACM 075
3/4"
5
0.2
0.2
0.2
Flow Design
VAV-121
LC SMALL
201 B
ACM 075
3/4"
3
0.2
0.2
0.2
Flow Design
VAV-122*
LC (DHH PK/K)
204
ACM 075
3/4"
4
1.7
1.7
1.7
Flow Design
VAV-123
LC (K) 203
ACM 075
3/4"
7
1.7
1.7
Flow Design
VAV-124
LC SMALL
203A
ACM 075
3/4"
7
0.2
0.2
0.2
Flow Design
VAV-125
LC SMALL
203B
ACM 075
3/4"
5
0.2
0.2
0.2
Flow Design
VAV-126
LC (K) 207A
ACM 075
3/4"
8
1.7
1.7
1.7
Flow Design
VAV-127
LC (K) 207B
ACM 075
3/4"
8
1.7
1.7
Flow Design
VAV-128
LC SMALL
207A
ACM-075
1/2"
5
0.2
0.2
0.2
Flow Design
VAV-129
LC SMALL
207B
ACM-075
1/2"
5
0.2
0.2
0.2
Flow Design
VAV-130
LC (DHH)401
ACM-075
3/4"
41
3
1.7
1.7
1.7
Flow Design
VAV-131
LC (DHH) 402
ACM-075
1/2"
4
1.7
1.7
1.7
Flow Design
VAV-132
LC SMALL
401A
ACM-075
1/2"
2
0.2
0.2
0.2
Flow Design
VAV-133
LC SMALL
401E
ACM-075
1/2"
8
0.2
0.2
0.2
Flow Design
VAV-134
LC (P) 403A
ACM-075
1/2"
5
1.9
1.9
1.9
Flow Design
VAV-135
LC (P) 403B
ACM-075
1/2"
7
1.9
1.9
1.9
Flow Design
VAV-136
LC (LO) 407A
ACM-075
1/2"
4
1.9
1.9
1.9
Flow Design
VAV-137
LC (L) 407B
ACM-075
1/2"
4
1.9
1.9
1.9
Flow Design
VAV-138
LC (M) 601
ACM-075
1/2"
5
1.7
1.7
1.7
Flow Design
VAV-139
LC (M) 602
ACM-075
1/2"
5
1.7
1.7
1.7
Flow Design
Neudorfer Engineers, Inc. Page 79 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
System/Unit
Area Served
Model Number
Valve Size
Valve
DP Actual
Design
Prelim.
Actual
Manufacturer
Position
Flow
Flow
Flow
VAV-140
LC SMALL
ACM-075
1/2"
7
0.2
0.2
0.2
Flow Design
601 A
VAV-141
LC SMALL
ACM-075
1/2"
5
0.2
0.2
0.2
Flow Design
601 B
VAV-142
LC (P) 603A
ACM-075
1/2"
4
1.9
1 1.9
1.9
Flow Design
VAV-143
LC (P) 603B
ACM-075
1/2"
5
1.9
1.9
1.9
Flow Design
VAV-144
LC (L) 607A
ACM-075
1/2"
6
1.9
1.9
1.9
Flow Design
VAV-145
LC (L) 607B
ACM-075
1/2"
4
1.9
1.9
1.9
Flow Design
VAV-146
DEN 104
AC-100
1"
17
3.5
3.5
3.5
Flow Design
VAV-147
COUNSELOR
ACM-075
3/4"
3
0.4
0.4
0.4
Flow Design
103
VAV-148
SMALL GROUP
ACM-075
3/4"
3
0.5
0.5
0.5
Flow Design
102A
VAV-149
SMALL GROUP
ACM-075
3/4"
7
0.9
0.9
0.9
Flow Design
102B
VAV-150
LEARENING
AC-100
1"
18
3.9
3.9
3.9
Flow Design
SUPPORT 102
VAV-151wood
LOBBY 100A
1.3
ceiling*
VAV-152
RECEPTION
AC-100
3/4"
20
3.5
3.5
3.5
Flow Design
OFFICE 101
VAV-153
CONFERENCE
ACM-075
3/4"
22
1.0
1.0
1.0
Flow Design
101A
VAV-154
HEALTH
ACM-075
3/4"
7
0.8
0.8
0.8
Flow Design
CLINIC 101B
VAV-155
COT ROOM
ACM-075
3/4"
5
1.1
1.1
1.1
Flow Design
101 D
VAV-156
OFFICE MGR
ACM-075
3/4"
18
0.9
0.9
0.9
Flow Design
101C
VAV-157
DEAN/RECOR
ACM-075
3/4"
5
2.0
2.0
2.0
Flow Design
D STG
101 E/101 K
VAV-158
DHH OFFICES
ACM-075
3/4"
17
1.3
1.3
1.3
Flow Design
101 N/101 L
VAV-159
AP
ACM-075
3/4"
17
1.9
1.9
1.9
Flow Design
OFFICE/DHH
RECEPT
101 R/101 Q
VAV-160
P OFFICE
ACM-075
3/4"
18
1.0
1.0
1.0
Flow Design
101S
VAV-161
WORKROOM
ACM-075
3/4"
16
0.8
0.8
0.8
Flow Design
101 M
VAV-162
STAFF OFFICE
ACM-075
3/4"
17
1.8
1.9
1.9
Flow Design
101P
VAV-163
PROF
ACM-075
3/4"
17
2.0
2.0
2.0
Flow Design
DEVELOPEME
NT 101T
VAV-164
SLP 108
ACM-075
3/4"
8
0.4
1 0.4
0.4
Flow Design
VAV-165
DHH
ACM-075
3/4"
11
0.4
0.4
0.4
Flow Design
PYCH/COUNS
109
VAV-166`
AUDIO/DHH
ACM-075
3/4"
0.4
Flow Design
SLP 110
VAV-167
OT/PT 122
ACM-075
3/4"
21
1.2
1.2
1.2
Flow Design
Totals:
-
-
-
397.199999
318.8
410.099999
-
999999
999999
Neudorfer Engineers, Inc. Page 80 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT
LOCATION: EDMONDS, WA
PROJECT #: 2017-557
Log: I PU-01 Heating mode/RF-129 10/18/2018
PU-01 Heating mode/RF-108A/108B 10/23/2018 Alex Lebedev
PU-01
Heating
mode/RF-122
10/18/2018
Alex Lebedev
PU-01
Heating
mode/RF-127
10/18/2018
Alex Lebedev
PU-01
Heating
mode/RF-128
10/18/2018
Alex Lebedev
PU-01
Heating
mode/RF-129
10/18/2018
Alex Lebedev
PU-01
Heating
mode/VAV-102
10/22/2018
Alex Lebedev
PU-01 Heating mode/VAV-105
PU-01 Heating mode/VAV-122
PU-01 Heating mode/VAV-1 51 wood
ceiling
PU-01 Heating mode/VAV-166
SYSTEM/UNIT: PU-02 Cooling mode
10/22/2018 Alex Lebedev
10/22/2018 Alex Lebedev
10/23/2018 Alex Lebedev
10/22/2018 Alex Lebedev
Final Test Data
Final Disch Press.
48 PSI
Final Suction Press.
26 PSI
Final Press. Diff. Design
22 PSI
VFD Hertz
38.5 Hz
Motor Volts T1-T2
230 Volts
Motor Volts T2-T3
229 Volts
Motor Volts T1-T3
230 Volts
Motor Amps T1
13.2 Amps
Motor Amps T2
13.2 Amps
Motor Amps T3
13.3 Amps
DATE: 10/25/2018
CONTACT:
AUTHOR:
DP across the RF is 10PS1 DP across the auto flow
valve is approximately 1 PSI. Return pipe is warm.
Control and autoflow valve are installed backwards.
Auto flow valve is installed upstream from the control
valve
No DP was measured across the valve
No DP was measured across the valve
No DP was measured across the valve
No DP was measured across the valve
Auto flow valve is installed in the HHW supply pipe.
Should be in the return line after CTV.
DP across auto flow valve is 1 PSI
DP across control valve 23 PSI
DP across the coil 2 PSI
Control valve should be checked out
Was Pulsing at 52HZ
Access
Coil piped backwards.
Enterina P=30 leavina P=53
Tested By: Alex Lebedev
Date: 10/24/2018
Neudorfer Engineers, Inc. Page 81 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-02 Heating mode
AREA: HYDRONIC WASTER
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
4030 4X3x11.5 BF STD
Pump Serial Number
843869
Pump Flowrate
390 GPM
TDH/FT
130
Final Test Data
Final Disch Press.
56 PSI
Final Suction Press.
23 PSI
Final Press. Diff. Design
33 PSI
Final Press. Diff. Actual
33 PSI
Final Design Flow
400 GPM
Final Actual Flow
450 GPM
VFD Hertz
50.1 Hz
Motor Volts T1-T2
350 Volts
Motor Volts T2-T3
350 Volts
Motor Volts T1-T3
350 Volts
Motor Amps T1
19.7 Amps
Motor Amps T2
19.7 Amps
Motor Amps T3
19.8 Amps
Log:
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor Manufacturer
Brook Crompton
Motor Frame
284T
Motor HP
25 HP
Motor RPM
1770 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor F.L. Amps
27.9 Amps
Motor S.F.
1.25
Motor Nominal Efficiency
93.6
Motor Power Factor
0.89
Pump Impeller Diam.
11.5
Measured Data
Pump Off Pressure
25 PSI
Valve Shut DP
72 PSI
Valve Shut SP
27 PSI
Valve Shut Diff.
45 PSI
Valve Open DP
73 PSI
Valve Open SP
23 PSI
Valve Open Diff.
50.0 PSI
Valve Open Flow
500 GPM
PU-02 Heating mode 10/23/2018 Alex Lebedev System operating pressure setpoint is 20.5PS1.
PU-02 Heating mode 10/23/2018 Alex Lebedev Actual final water flow was calculated using approved
pump curve provided by the manufacturer.
PU-02 Heating mode 10/17/2018 Alex Lebedev The operating Amps and Volts were recorded from
the VFD.
PU-02 Heating mode Balance Valve Summary
System/Unit
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
-
-
-
-
0
0
0
-
Neudorfer Engineers, Inc. Page 82 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-03 Info
AREA: DOMESTIC WATER BOOSTER
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
VMS-1503B
Pump Serial Number
555499-02
Pump Flowrate
70 GPM
TDH/FT
162
PU-03 Info Balance Valve Summary
Tested By: Vinh Nguyen
Date: 7/6/2018
Motor Data
Motor Manufacturer
Armstrong
Motor Frame
184TC
Motor HP
5 HP
Motor RPM
3515 RPM
Motor Rated Volts
208-230/416-460/480 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor F.L. Amps
13-11.6/6.5-5.8/5.6 Amps
Motor S.F.
1.25
Motor Nominal Efficiency
88.5
Motor Power Factor
0.90
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
DOMESTIC
CBV
2"
70
Armstrong
BOOSTER
PUMP
Totals:
-
-
-
70
0
0
-
SYSTEM/UNIT: PU-04 Info
AREA: DOMISTIC WATER BOOSTER
Unit Data
Pump Manufacturer
B & G
Pump Model Number
FLOWTHERM /70 VS
Pump Serial Number
555499-01
Pump Flowrate
70 GPM
TDH/FT
162
PU-04 Info Balance Valve Summary
Tested By: Vinh Nguyen
Date: 7/6/2018
Motor Data
Motor Manufacturer
Armstrong
Motor Frame
184TC
Motor HP
5 HP
Motor RPM
3515 RPM
Motor Rated Volts
208-230/416-460/480 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor F.L. Amps
13-11.6/6.5-5.8/5.6 Amps
Motor S.F.
1.25
Motor Nominal Efficiency
88.5
Motor Power Factor
0.90
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
DOMESTICV
CBV
2"
70
Armstrong
BOOSTER
PUMP
Totals:
-
70
0
0
Neudorfer Engineers, Inc. Page 83 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-05
AREA: BOILER CIRC
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
3X3X6 4380
Pump Serial Number
842226
Pump Flowrate
180 GPM
TDH/FT
20
Final Test Data
Final Disch Press.
33.6 PSI
Final Suction Press.
25.4 PSI
Final Press. Diff. Actual
8.2 PSI
Final Design Flow
180 GPM
Final Actual Flow
180 GPM
Motor Volts T1-T2
483 Volts
Motor Volts T2-T3
482 Volts
Motor Volts T1-T3
482 Volts
Motor Amps T1
2.2 Amps
Motor Amps T2
2.3 Amps
Motor Amps T3
2.2 Amps
PU-05 Balance Valve Summary
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor Manufacturer
WEG
Motor Frame
143
Motor HP
2 HP
Motor RPM
1750 RPM
Motor Rated Volts
230/460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor F.L. Amps
5.52/2.76 Amps
Motor S.F.
1.25
Motor Nominal Efficiency
86.5
Measured Data
Pump Off Pressure
28 PSI
Valve Shut DP
42 PSI
Valve Shut SP
27.8 PSI
Valve Shut Diff.
14.2 PSI
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
BOILER CIRC
CBV
4"
4.75
7.0
180
235
180
TA
Totals:
-
-
-
180
235
180
Neudorfer Engineers, Inc. Page 84 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-06
AREA: BOILER CIRC
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
3X3X6 4380
Pump Serial Number
842227
Pump Flowrate
180 GPM
TDH/FT
20
Final Test Data
Final Disch Press.
36.9 PSI
Final Suction Press.
24.9 PSI
Final Press. Diff. Actual
8.0 PSI
Final Design Flow
180 GPM
Final Actual Flow
185 GPM
Motor Volts T1-T2
482 Volts
Motor Volts T2-T3
483 Volts
Motor Volts T1-T3
482 Volts
Motor Amps T1
2.3 Amps
Motor Amps T2
2.3 Amps
Motor Amps T3
2.4 Amps
PU-06 Balance Valve Summary
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor Manufacturer
WEG
Motor Frame
143
Motor HP
2 HP
Motor RPM
1750 RPM
Motor Rated Volts
230/460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor F.L. Amps
5.52/2.76 Amps
Motor S.F.
1.25
Motor Nominal Efficiency
86.5
Measured Data
Pump Off Pressure
28 PSI
Valve Shut DP
42.9 PSI
Valve Shut SP
28.5 PSI
Valve Shut Diff.
14.3 PSI
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
BOILER CIRC
CBV
4"
4.75
7.2
180
240
185
TA
Totals:
-
-
-
180
1 240
185
Neudorfer Engineers, Inc. Page 85 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-07
AREA: DOMESTIC HW CIRC
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
ASTRO 280ss
Pump Serial Number
110233-321
Pump Flowrate
12 GPM
TDH/FT
10
Final Test Data
Final Design Flow
12 GPM
Final Actual Flow
12.2 GPM
Motor Volts T1-T2
118 Volts
Motor Amps T1
1.3 Amps
Log:
Tested By: Dwight Hammack
Date: 10/17/2018
Motor Data
Motor HP
1/6 HP
Motor Rated Volts
115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor F.L. Amps
1.3 Amps
PU-07 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and
discharge side of the pump water flow was measured
using CBV installed on the discharge side of the
pump.
PU-07 10/17/2018 Dwight Hammack Pump is on low speed.
PU-07 Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
DP Actual
Design
Prelim.
Actual
Manufacturer
Position
Flow
Flow
Flow
Valve-01
DOMESTIC
Arm FLo
1"
4 Turns
1.8
12
18.26
12.2
Armstrong
HW CIRC
Totals:
-
12
18.26
12.2
Neudorfer Engineers, Inc. Page 86 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-08
AREA: DOMESTIC HW CIRC
Unit Data
Pump Manufacturer
B & G
Pump Model Number
SERIES PL-36B
Pump Serial Number
110233-321
Pump Flowrate
12 GPM
TDH/FT
10
Final Test Data
Final Design Flow
12 GPM
Final Actual Flow
12.2 GPM
Motor Volts T1-T2
118 Volts
Motor Amps T1
0.9 Amps
Log:
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor HP
1/6 HP
Motor Rated Volts
115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor F.L. Amps
1.3 Amps
PU-08 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and
discharge side of the pump water flow was measured
using CBV installed on the discharge side of the
pump.
PU-08 10/24/2018 Alex Lebedev Pump is not making any water flow.
The water line is cold.
PU-08 Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
DP Actual
Design
Prelim.
Actual
Manufacturer
Position
Flow
Flow
Flow
Valve-01
KITCHEN HW
Arm FLo
3/4"
6 Turns
12
Armstrong
CIRC
Totals:
-
-
-
12
0
0
-
Neudorfer Engineers, Inc. Page 87 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-09
AREA: AWHP CIRC
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
2X2X6 4380
Pump Serial Number
843614
Pump Flowrate
92 GPM
TDH/FT
30
Final Test Data
Final Disch Press.
32 PSI
Final Suction Press.
26 PSI
Final Press. Diff. Actual
6 PSI
Final Design Flow
92 GPM
Final Actual Flow
92 GPM
VFD Hertz
45 Hz
Motor Volts T1-T2
293 Volts
Motor Volts T2-T3
292 Volts
Motor Volts T1-T3
293 Volts
Motor Amps T1
1.74 Amps
Motor Amps T2
1.75 Amps
Motor Amps T3
1.74 Amps
Log:
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor Manufacturer
Brook Crompton
Motor Frame
145JM
Motor HP
2 HP
Motor RPM
1710 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor F.L. Amps
2.9 Amps
Motor S.F.
1.25
Motor Nominal Efficiency
86.5
Motor Power Factor
0.74
Measured Data
Pump Off Pressure
23 PSI
Valve Shut DP
40 PSI
Valve Shut SP
23 PSI
Valve Shut Diff.
17 PSI
Valve Open Flow
100 GPM
PU-09 10/24/2018 Alex Lebedev Final water flow was measured at the balancing valve
installed on the discharge side of the pump.
PU-09 10/24/2018 Alex Lebedev System operating pressure setpoint is 2.8 PSI.
PU-09 10/24/2018 Alex Lebedev The operating Amps and Volts were recorded from
the VFD.
PU-09 Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
WHP CIRC
CBV
3"
6.5
1.8
92
95
95
TA
Totals:
-
-
-
92
1 95
95
Neudorfer Engineers, Inc. Page 88 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-10
AREA: DOMESTIC HW CIRC
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
Astro 28OSS
Pump Flowrate
12 GPM
TDH/FT
10
Final Test Data
Final Design Flow
12 GPM
Final Actual Flow
4.2 GPM
Motor Volts T1-T2
119 Volts
Motor Amps T1
1.3 Amps
Log:
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor HP
1/6 HP
Motor Rated Volts
115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor F.L. Amps
1.9 Amps
PU-10 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and
discharge side of the pump water flow was measured
using CBV installed on the discharge side of the
pump.
PU-10 10/17/2018 Alex Lebedev Pump is operating in high speed.
PU-10 10/24/2018 Alex Lebedev Flow is 35% of design
Water is hot in 30 seconds
PU-10 Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
DOMESTIC H
Arm FLo
3/4"
6
1.5
12
4.2
4.2
Armstrong
CIRC (MECH
206
Totals:
-
-
-
12
4.2
4.2
Neudorfer Engineers, Inc. Page 89 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-11
AREA: DOMESTIC HW CIRC
Unit Data
Pump Manufacturer Armstrong
Pump Model Number Astro 28OSS
Pump Flowrate 12 GPM
TDH/FT 10
Log:
Tested By: Alex Lebedev
Date: 10/17/2018
Motor Data
Motor HP
1/6 HP
Motor Phase
1
Motor Hertz
60 Hz
Motor F.L. Amps
1.9 Amps
PU-11 10/17/2018 Alex Lebedev Testing ports are not installed on the suction and
discharge side of the pump.
PU-11 10/17/2018 Alex Lebedev Pump is not operating. Motor is making humming
noise but not rotating. Motor is hot
PU-11 Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
DOMESTIC
Arm FLo
3/4"
6
12
Armstrong
HW CIRC
MECH 504
Totals:
-
-
12
0
0
-
SYSTEM/UNIT: PU-12
AREA: DOMESTIC HW CIRC
Unit Data
Pump Manufacturer Armstrong
Pump Model Number Astro 280SS
Pump Flowrate 12 GPM
TDH/FT 10
Log:
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor HP 1/6 HP
Motor Phase 1
Motor Hertz 60 Hz
PU-12 10/17/2018 Alex Lebedev Testing ports are not installed on the suction and
discharge side of the pump.
PU-12 10/24/2018 Alex Lebedev Pump is not operating. Motor is making humming
noise but not motor is hot
PU-12 Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
DOMESTIC
Arm FLo
3/4"
12
Armstrong
HW CIRC
MECH 304
Totals:
-
-
-
12
0
0
-
Neudorfer Engineers, Inc. Page 90 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-13
AREA: DOMESTIC HW CIRC
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
Astro 28OSS
Pump Flowrate
12 GPM
TDH/FT
10
Final Test Data
Final Design Flow
12 GPM
Final Actual Flow
6.3 GPM
Motor Volts T1-T2
120 Volts
Motor Amps T1
1.4 Amps
Log:
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor HP
1/6 HP
Motor Phase
1
Motor Hertz
60 Hz
Motor F.L. Amps
1.9 Amps
PU-13 10/24/2018 Alex Lebedev Pump is operating in high speed.
PU-13 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and
discharge side of the pump water flow was measured
using CBV installed on the discharge side of the
pump.
PU-13 10/24/2018 Alex Lebedev Flow is 53% of design
Water is hot in the toilet sink in 30 seconds
PU-13 Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
DOMESTIC
Arm FLo
3/4"
6
3.1
12
6.3
6.3
Armstrong
HW CIRC
MECH 406
Totals:
-
-
-
12
6.3
6.3
Neudorfer Engineers, Inc. Page 91 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-14
AREA: DOMESTIC HW CIRC
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
Astro 28OSS
Pump Flowrate
12 GPM
TDH/FT
10
Final Test Data
Final Design Flow
12 GPM
Final Actual Flow
6.6 GPM
Motor Volts T1-T2
120 Volts
Motor Amps T1
1.8 Amps
Log:
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor HP
1/6 HP
Motor Phase
1
Motor Hertz
60 Hz
Motor F.L. Amps
1.9 Amps
PU-14 10/24/2018 Alex Lebedev Testing ports are not installed on the suction and
discharge side of the pump water flow was measured
using CBV installed on the discharge side of the
pump.
PU-14 10/24/2018 Alex Lebedev Pump is operating in high speed.
PU-14 10/24/2018 Alex Lebedev Flow is 55% of design
Water is hot in the toilet sink in 1 minute
PU-14 Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
DOMESTIC
Arm FLo
3/4"
6
3.4
12
6.6
6.6
Armstrong
HW CIRC
MECH 606
Totals:
-
-
-
12
6.6
6.6
Neudorfer Engineers, Inc. Page 92 of 93
Hydronic Pump
PROJECT: MADRONA K-8 SCHOOL REPLACEMENT DATE: 10/25/2018
LOCATION: EDMONDS, WA CONTACT:
PROJECT #: 2017-557 AUTHOR:
SYSTEM/UNIT: PU-15
AREA: SCIENCE HW CIRC
Unit Data
Pump Manufacturer
Armstrong
Pump Model Number
Astro 280SS
Pump Flowrate
12 GPM
TDH/FT
10
Final Test Data
Final Design Flow
12 GPM
Final Actual Flow
4.3 GPM
Motor Volts T1-T2
117 Volts
Motor Amps T1
1.3 Amps
Log:
Tested By: Alex Lebedev
Date: 10/24/2018
Motor Data
Motor HP
1/6 HP
Motor Rated Volts
115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor F.L. Amps
1.9 Amps
PU-15 10/24/2018 Alex Lebedev Pump is operating in high speed.
PU-15 10/17/2018 Alex Lebedev Testing ports are not installed on the suction and
discharge side of the pump water flow was measured
using CBV installed on the discharge side of the
pump.
PU-15 10/24/2018 Alex Lebedev Flow is 36% of design
Water is hot in 30 seconds
PU-15 Balance Valve Summary
System/Unit
Area Served
Model Number
Valve Size
Valve
Position
DP Actual
Design
Flow
Prelim.
Flow
Actual
Flow
Manufacturer
Valve-01
SCIENCE HW
Armflo
3/4"
6
1.4
12
4.3
4.3
Armstrong
CIRC (SCI
PREP 136A
Totals:
12
4.3
4.3
Neudorfer Engineers, Inc. Page 93 of 93