2020-12-01 Edmonds Waterfront Center ABT ReportDuildirg Cnwlnp. Cnginnwring BEE Consulting LLC 170 West Dayton St., Suite 206 Edmonds, WA 98020 EDMONDS WATERFRONT CENTER WHOLE BUILDING AIR LEAKAGE TESTING REPORT Project Name: Edmonds Waterfront Report Date: 12/7/2020 Center Project #: 2012-1001 Air Barrier Testing E779 Project 220 Railroad Ave Field Rep: Chris Shafer, Test Specialist Address: Edmonds, WA 98020 Test Date: 12/01/2020 Client: W.G. Clark Weather: Overcast, -50 °F Present at Site: (BEE) - Chris S. (BEE) - Torin G. (BEE) - Robert S. BEE was retained by W.G. Clark for the purpose of providing whole building air barrier testing in accordance with ASTM E779 as required by the 2015 Washington State Energy Code. The Edmonds Waterfront Center project is a 2 story building. This report contains the data for the whole building and completes the building air barrier test requirements in total. Testing was completed on 12/01/2020. BEE performed the building air barrier test procedure with positive pressure. The whole building air testing was completed using a total of 3 mechanical blower door fans. The fans were placed in the entryway on the Eastern elevation of level 1. Flow rates of each fan were recorded at different building pressures ranging between 25 (pa) to 80 (pa). Data was taken over 12 separate points. Final Results for Edmonds Waterfront Center: 0.136 CFM/SQFT at 75 Pa Pressurization Test, Passed Final pressurization results of the building performance was an air leakage rate of 0.136 CFM/ SQFT of envelope at 75 Pa at the upper 95% confidence interval with the code maximum allowable defined as 0.40 CFM/ SQFT of envelope at 75 Pa. Below are the results with diagrams attached. P: 425 672 3900 F: 425 712 8608 Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 1 of 8 9uildirg Cnwlop� Crgi�rirrg Prepared by: X Chris Shafer Testing Specialist Reviewed and Approved by: X i1i S Chad S�MK, P.E. Principal Engineer DISCLAIMER Please note that there is no guarantee expressed, written or implied by this report. The data complied herein is subject to change in case of new or additional data discovery. The information contained in this report is based on information available at the time that this report was prepared. Concerns do not represent a total listing of all locations with issues nor do they BEE Consulting LLC imply all similar locations to have issues. If additional information is discovered, it should be forwarded to our office for 170 West Dayton further review and comment. We reserve the right to amend and/or modify this report if new and/or significant data Suite 206 Edmonds, WA becomes available that impacts the situation and parameters of this investigation. Our services were performed using the Ed 98020 degree of skill normally exercised by practicing investigation individuals in this area and similar locales. No other warranty is either expressed or implied. P: 425 672 3900 F: 425 712 8608 Edmonds Waterfront Center / 2012-1001 12/3/2020 Page 2 of 8 Edmonds Waterfront Center Air Barrier Test Report In accordance with ASTM E779 WSEC 2015 Air Leakage Protocol Performed by: 4i�. BEE Consulting, LLC , 170 W Dayton St, Ste. 206 Edmonds, WA 98020 Building Envelope Engineering 425.672.3900 FanTestic version: 5.11.79 licensed to: BEE Consulting, LLC Building Address: 220 Railroad Ave Edmonds, WA 98020 Performed for: W.G. Clark Performed by: Chris Shafer, Testing Specialist Test Date: 2020-12-01 Associated Test File: Edmonds waterfront center USACE 2020-12-01 1159 Project Number: 2012-1001 Testing Location: Edmonds Waterfront Center Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 3 of 8 Ftuildirg Cnr.lop� Cnginnwring Summary Building and Test Information Test file name: Edmonds waterfront center USACE 2020- 12-01 1159 Building Height from ground to top) [ft]: 28 Envelope Area [ft2]: 41404 Building Elevation (of ground, above sea level) [ft]: 20 Results Average air flowsTP at 75 Pa [CFM] 5565.5 Average equivalent leakage area at 75 Pa [sq in] 597.0 Mean 95% Confidence Interval Lower Upper Average CFM / sq ft of envelope at 75 Pa 0.134 0.133 0.136 Building Information Building Measurements Building elevation above sea level [ft] 20 Building Envelope Area [ft] 41,404 Building Height [ft] 28 Isolation / Heating / Ventilation System All external HVAC and exhaust fan systems were properly set or isolated. All isolations were performed from the exterior with the exceptions for any unique interior conditioned spaces containing intentional penetrations through the building envelope. Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 4 of 8 Duildi�g L�wbp� Ggurri.q Discussion of Results Combined Test Data (Tested in one direction only) Combined Test Data (Tested in one direction only) Average air flowsTP at +75 Pa [CFM] 5565.5 Average equivalent leakage area at 75 Pa [sq in] 597.0 Mean 95% Confidence Interval Lower Upper Average CFM / sq ft of envelope at 75 Pa 0.134 0.133 0.136 Building Air Leakage Test Photo Documentation Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 5 of 8 9uildirg Cnwlop� Crginwrirrg Air Leakage Test Data Appendix - Pressurize Data Set Test Dataset Date and Time: 2020-12-01-11:51:15 Finish Time: 11:53:28 Environmental Conditions Operator Location: Inside the building Greatest Initial Baseline Pressure 0.873 Pa Initial Bias Pressure: -0.21 Pa Final Bias Pressure: 0.11 Pa Initial Temperature: indoors: 68 outdoors: 50. Final Temperature: indoors: 68 outdoors: 50. Test Analysis Squared correlation coefficient r2 0.99907 Exponent, n: 0.664 Air leakage coefficient, C [CFM/Pan]: 316.18 CFM referenced to STP at 75 Pa 5565.5 Equivalent leakage area at 75 Pa [sq in] 598.0 Mean 95% confidence limits Lower Upper CFM/sq ft of envelope at 75 0.137 0.1330 0.1359 Induced Pressure Pa 26.5 30.7 35.1 40.7 44.0 49.9 54.3 61.2 65.2 71.4 74.7 80.3 Total Flow [CFM] 2780.54 3015.60 3317.67 3687.67 3801.64 4115.55 4406.84 4740.97 5082.69 5360.45 5480.50 5725.40 Total Corrected flow [CFM] 2824.1 3062.9 3369.7 3745.5 3861.2 4180.1 4475.9 4815.3 5162.4 5444.5 5566.4 5815.1 Error [%] 1.2% -0.4% 0.1 % 0.8% -1.3% -1.6% -0.4% -1.1 % 1.7% 1.1 % 0.2% -0.2% 12 induced pressures each taken for 10 of the required 10 seconds. 12 baseline pressures each taken for 10 of required 10 seconds. Greatest Initial Baseline Pressure: 0.873 Pa Static Pressure Averages: initial [Pa] AP01 -0.21 4P01- -0.31 AP01+ 0.87 final Pa AP02 0.11 OP02- -0.22 OP02+ 0.17 Baseline, initial Pa 0.87 -0.51 -0.31 -0.46 -0.58 -0.23 -0.27 -0.29 -0.05 -0.45 -0.19 -0.04 Baseline, final [Pa] -0.05 0.58 0.04 0.08 0.21 0.27 0.10 0.22 -0.39 0.10 0.07 0.04 Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 6 of 8 Duildi.g L.wbp� C.gurri.q W 2 C a 10000- 1000- Induced Pressure vs. Flow (Pressurize Set) Pressurize r2 = U.9981 1� 100 10 10D (Lag) Pressure (Pa) Building Gauge Pressure (Pressurize Set) 100 90 so 70 60 50 40 30 20 10 0 -10 -20 0 200 400 600 800 T-me Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 7 of 8 100 10 10D (Lag) Pressure (Pa) Building Gauge Pressure (Pressurize Set) 100 90 so 70 60 50 40 30 20 10 0 -10 -20 0 200 400 600 800 T-me Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 7 of 8 Duildi�g L�wbp� Ggurrilq Test Equipment The following test equipment was used in the performance of the building air leakage test. Fan Model Fan Serial Fan Location Gauge Gauge Serial #1 Retrotec 3000SR PH001510 Top DM32 407027 #2 Retrotec 3000SR PH001507 Mid DM32 400832 #3 Retrotec 3000SR PH002041 Low DM32 400796 Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 8 of 8 Certificate of Gauge Calibration Issued by: Retrotec Calibration Date: 2016-09-08 retroL"� 1060 E Pole Rd. Everson, WA, USA 98247 T: +1 (360) 738-9835 E: calibration@retrotec.com W: www.retrotec.com Instrument: Description: Pressure and Flow Gauge Manufacturer: Retrotec Model Number: DM32 10A Serial Number: 400796 Environmental conditions: Temperature: 200C ±2°C Relative Humidity: 50% ±10% Mains Voltage: 120V ±10V Mains Frequency: 60Hz ±1Hz Certificate Number: 215213 084058 Results: As Found AC-1943 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025. Comments: Results recorded as received. No adjustment performed. Calibration Information: Calibrated by: Mike Shtunyuk JJAv".fit, P4,-, Signature The Device was calibrated against laboratory standards whose values are traceable to recognized national standards. The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95% confidence level. In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account. The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full, without written approval from Retrotec. Certificate of Gauge Calibration Issued by: Retrotec Calibration Date: 2016-09-08 Calibration Results Channel A Applied Value (Pa) Reading (Pa) Error (%) -749.97 -753.88 0.52 -600.01 -603.22 0.53 -300.03 -301.55 0.51 -150.05 -150.70 0.43 -74.99 -75.28 0.39 -49.99 -50.17 0.36 -25.00 -25.10 0.40 -15.00 -15.02 0.13 0.00 -0.02 N/A 14.99 15.10 0.73 25.01 25.12 0.44 49.99 50.28 0.58 75.00 75.41 0.55 150.00 150.68 0.45 300.02 301.30 0.43 599.98 602.55 0.43 749.99 752.96 0.40 Instrument display resolution is 0.1 Pa. Certificate Number: 215213 084058 Results: As Found Channel B Applied Value (Pa) Reading (Pa) Error (%) -749.97 -754.82 0.65 -600.01 -603.94 0.65 -300.03 -301.75 0.57 -150.05 -150.87 0.55 -74.99 -75.33 0.45 -49.99 -50.21 0.44 -25.00 -25.07 0.28 -15.00 -15.00 0.00 0.00 -0.03 N/A 14.99 15.12 0.87 25.01 25.22 0.84 49.99 50.37 0.76 75.00 75.47 0.63 150.00 150.87 0.58 300.02 301.50 0.49 599.98 602.70 0.45 749.99 753.11 0.42 Uncertainties Calibration and measurement capability (Expanded Uncertainty) is .01 Pa + 0.3% of reading (Range 0 - 20 000 Pa) based on a 95% confidence interval, using coverage of K=2. IN S inmai The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from) the following standards or guidelines: NFPA 2001 EN13829 ATTMA: TS1 ASTM E779-10 CGSB GAP50-784 ±1 Pa ±2 Pa ±2 Pa ±5% or 0.25 Pa ±1 Pa ±1% or 1 Pa ±(10 to 50) Pa (up to ±60 Pa) (up to ±100 Pa) whichever is greater (up to ±50 Pa) whichever is greater ISO14520 EN15004 USACE TITLE 24 RESNET ±1 Pa ±1 Pa ±1% or 0.25 Pa ±1% or 0.2 Pa ±1% or 0.5 Pa (up to ±60 Pa) (up to ±100 Pa) ±(25 to 250) Pa whichever is greater whichever is greater Certificate of Gauge Calibration Issued by: Retrotec Calibration Date: 2016-06-14 retroL"� 1060 E Pole Rd. Everson, WA, USA 98247 T: +1 (360) 738-9835 E: calibration@retrotec.com W: www.retrotec.com Instrument: Description: Pressure and Flow Gauge Manufacturer: Retrotec Model Number: DM32 10A Serial Number: 400832 Environmental conditions: Temperature: 200C ±2°C Relative Humidity: 50% ±10% Mains Voltage: 120V ±10V Mains Frequency: 60Hz ±1Hz Certificate Number: 217465 121501 Results: As Found AC-1943 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025. Comments: Results recorded as received. No adjustment performed. Calibration Information: Calibrated by: Mike Shtunyuk JJAv".fit, P4,-, Signature The Device was calibrated against laboratory standards whose values are traceable to recognized national standards. The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95% confidence level. In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account. The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full, without written approval from Retrotec. Certificate of Gauge Calibration Issued by: Retrotec Calibration Date: 2016-06-14 Calibration Results Channel A Applied Value (Pa) Reading (Pa) Error (%) -750.00 -751.40 0.19 -600.01 -601.25 0.21 -300.00 -300.38 0.13 -150.02 -150.09 0.05 -75.01 -75.10 0.12 -50.01 -50.03 0.04 -25.01 -24.98 0.12 -15.01 -14.98 0.20 0.00 -0.01 N/A 15.00 15.03 0.20 25.02 25.05 0.12 49.99 50.08 0.18 74.99 75.14 0.20 150.00 150.18 0.12 299.98 300.22 0.08 600.01 600.00 0.00 750.00 749.81 0.03 Instrument display resolution is 0.1 Pa. Certificate Number: 217465 121501 Results: As Found Channel B Applied Value (Pa) Reading (Pa) Error (%) -750.00 -751.24 0.17 -600.01 -601.10 0.18 -300.00 -300.31 0.10 -150.02 -150.10 0.05 -75.01 -75.00 0.01 -50.01 -50.04 0.06 -25.01 -24.98 0.12 -15.01 -14.98 0.20 0.00 -0.04 N/A 15.00 15.04 0.27 25.02 25.03 0.04 49.99 50.07 0.16 74.99 75.09 0.13 150.00 150.15 0.10 299.98 300.18 0.07 600.01 599.98 0.00 750.00 749.91 0.01 Uncertainties Calibration and measurement capability (Expanded Uncertainty) is .01 Pa + 0.3% of reading (Range 0 - 20 000 Pa) based on a 95% confidence interval, using coverage of K=2. IN S inmai The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from) the following standards or guidelines: NFPA 2001 EN13829 ATTMA: TS1 ASTM E779-10 CGSB GAP50-784 ±1 Pa ±2 Pa ±2 Pa ±5% or 0.25 Pa ±1 Pa ±1% or 1 Pa ±(10 to 50) Pa (up to ±60 Pa) (up to ±100 Pa) whichever is greater (up to ±50 Pa) whichever is greater ISO14520 EN15004 USACE TITLE 24 RESNET ±1 Pa ±1 Pa ±1% or 0.25 Pa ±1% or 0.2 Pa ±1% or 0.5 Pa (up to ±60 Pa) (up to ±100 Pa) ±(25 to 250) Pa whichever is greater whichever is greater Certificate of Gauge Calibration Issued by: Retrotec Calibration Date: 2017-07-06 retroL"� 1060 E Pole Rd. Everson, WA, USA 98247 T: +1 (360) 738-9835 E: calibration@retrotec.com W: www.retrotec.com Instrument: Description: Pressure and Flow Gauge Manufacturer: Retrotec Model Number: DM32 10A Serial Number: 407027 Environmental conditions: Temperature: 200C ±2°C Relative Humidity: 50% ±10% Mains Voltage: 120V ±10V Mains Frequency: 60Hz ±1Hz Certificate Number: 215214 090025 Results: As Found AC-1943 This calibration laboratory has been assessed by the ANSI- ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025. Comments: Results recorded as received. No adjustment performed. Calibration Information: Calibrated by: Mike Shtunyuk JJAv".fit, P4,-, Signature The Device was calibrated against laboratory standards whose values are traceable to recognized national standards. The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95% confidence level. In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account. The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: CP-35-01 This Calibration Certificate shall not be reproduced except in full, without written approval from Retrotec. Certificate of Gauge Calibration Issued by: Retrotec Calibration Date: 2017-07-06 Calibration Results Channel A Applied Value (Pa) Reading (Pa) Error (%) -749.97 -755.31 0.71 -600.01 -604.40 0.73 -300.03 -301.96 0.64 -150.00 -150.86 0.57 -74.99 -75.41 0.56 -50.00 -50.21 0.42 -25.00 -25.11 0.44 -15.01 -15.06 0.33 0.00 -0.02 N/A 15.00 15.12 0.80 25.00 25.11 0.44 50.00 50.31 0.62 75.00 75.43 0.57 150.03 150.80 0.51 299.99 301.48 0.50 599.96 602.27 0.39 749.94 752.72 0.37 Instrument display resolution is 0.1 Pa. Certificate Number: 215214 090025 Results: As Found Channel B Applied Value (Pa) Reading (Pa) Error (%) -749.97 -754.33 0.58 -600.01 -603.68 0.61 -300.03 -301.73 0.57 -150.00 -150.80 0.53 -74.99 -75.40 0.55 -50.00 -50.20 0.40 -25.00 -25.17 0.68 -15.01 -15.02 0.07 0.00 0.04 N/A 15.00 15.10 0.67 25.00 25.15 0.60 50.00 50.25 0.50 75.00 75.34 0.45 150.03 150.76 0.49 299.99 301.36 0.46 599.96 602.31 0.39 749.94 753.02 0.41 Uncertainties Calibration and measurement capability (Expanded Uncertainty) is .01 Pa + 0.3% of reading (Range 0 - 20 000 Pa) based on a 95% confidence interval, using coverage of K=2. e I inmai The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from) the following standards or guidelines: NFPA 2001 EN13829 ATTMA: TS1 ASTM E779-10 CGSB GAP50-784 ±1 Pa ±2 Pa ±2 Pa ±5% or 0.25 Pa ±1 Pa ±1% or 1 Pa ±(10 to 50) Pa (up to ±60 Pa) (up to ±100 Pa) whichever is greater (up to ±50 Pa) whichever is greater ISO14520 EN15004 USACE TITLE 24 RESNET ±1 Pa ±1 Pa ±1% or 0.25 Pa ±1% or 0.2 Pa ±1% or 0.5 Pa (up to ±60 Pa) (up to ±100 Pa) ±(25 to 250) Pa whichever is greater whichever is greater retraL"� Fan Calibration Verification Report Calibrated Equipment Calibration Facility Fan Shell Serial Number PH001507 Company Retrotec Fantop Serial Number 1AC000217(SD) Address 1060 E Pole Rd Fan Model 3350 Location Everson, WA USA Manufacturer Retrotec Phone (360) 738-9835 Calibration Date 2016-07-28 Technician OA Tester Flow calibration verification data The accuracy of this system was checked against an orifice plate mounted in a chamber which was verified with fans calibrated to ASTM E-1258. Pressure gauge 400830 used for calibration was checked against one of two NIST tracable Furness 550 pressure calibrators: 0704353, 0907002 Total Leakage Test Background Leakage Test Number of Range Chamber Fan Fan Leakage System samples Ring /Plate pressure pressure speed area (in) flow PrA (Pa) PrB (Pa) M (CFM) 114 A -50.0 65.6 22 340.0 2234 114 L1 -60.4 176.2 32 1.9 14 Measured Orifice Flow (CFM) Actual Orifice Flow (CFM) Error 2220 91d7 Measured flow calculation (using flow equations) System flow = [65.6 - (-50.0 *-0.075)]^0.503 * [264.9959 + 65.6 * 0] = 2234 CFM System flow = [176.2 - (-60.4 * 0.1)]^0.4925 * [1.1614 + 176.2 * 0] = 14 CFM System flow equations Depressurization with operator indoors ( air flow away from operator): System flow (cfm) = (PrB - PrA*K1)N * (K + PrB*K3) Pressurization with operator indoors (air flow towards the operator): System flow (cfm) = [(PrB - PrA) - PrA*K1]N * [K + (PrB - PrA)*K3] Range Ring / Plate N System flow equation constants K K1 K2* K3 Min Fan Pressure* (Pa) Open 0.5214 519.6 -0.070 0.8 -0.1150 8.6 A 0.5030 265.0 -0.075 1.0 0.0000 12 B 0.5000 174.9 0.000 0.3 0.0000 10 C8 0.5000 78.50 -0.020 0.5 0.0160 10 C6 0.5050 61.30 0.054 0.5 0.0040 10 C4 0.5077 42.00 0.009 0.5 0.0005 10 C2 0.5200 22.00 0.110 0.5 -0.0010 10 C1 0.5410 11.92 0.1300 0.4 0.0014 10 L4 0.4800 4.099 0.003 1.0 0.0004 10 L2 0.5020 2.068 0.000 0.5 0.0001 10 L1 0.4925 1.161 0.100 0.5 0.0001 10 * Fan Pressure "PrB" must be greater than "Min Fan Pressure" and greater than (PrA*K2) Door fan systems should be checked for calibration every 5 years Calibration for the Door Fan should be checked before:2021-07-28 The flow accuracy requirements of the following Standards are: ATTMA: TS1 EN13829 ISO 9972 ASTM E779 CGSB EN15004 IS014520 7% 7% 7% 5% 5% 5% 5% Title 24 5% retraL"� Fan Calibration Verification Report Calibrated Equipment Calibration Facility Fan Shell Serial Number PH001510 Company Retrotec Fantop Serial Number 1AC000217(SD) Address 1060 E Pole Rd Fan Model 3350 Location Everson, WA USA Manufacturer Retrotec Phone (360) 738-9835 Calibration Date 2017-07-17 Technician OA Tester Flow calibration verification data The accuracy of this system was checked against an orifice plate mounted in a chamber which was verified with fans calibrated to ASTM E-1258. Pressure gauge 406268 used for calibration was checked against one of two NIST tracable Furness 550 pressure calibrators: 0704353, 0907002 Total Leakage Test Background Leakage Test Number of Range Chamber Fan Fan Leakage System samples Ring /Plate pressure pressure speed area (in) flow PrA (Pa) PrB (Pa) M (CFM) 114 A -50.5 66.7 21 341.0 2253 114 L1 -54.1 114.9 15 1.7 12 Measured Orifice Flow (CFM) Actual Orifice Flow (CFM) Error 2241 91rIR 1). V /o Measured flow calculation (using flow equations) System flow = [66.7 - (-50.5 *-0.075)]^0.503 * [264.9959 + 66.7 * 0] = 2253 CFM System flow = [114.9 - (-54.1 * 0.1)]^0.4925 * [1.1614 + 114.9 * 0] = 12 CFM System flow equations Depressurization with operator indoors ( air flow away from operator): System flow (cfm) = (PrB - PrA*K1)N * (K + PrB*K3) Pressurization with operator indoors (air flow towards the operator): System flow (cfm) = [(PrB - PrA) - PrA*K1]N * [K + (PrB - PrA)*K3] Range Ring / Plate N System flow equation constants K K1 K2* K3 Min Fan Pressure* (Pa) Open 0.5214 519.6 -0.070 0.8 -0.1150 8.6 A 0.5030 265.0 -0.075 1.0 0.0000 12 B 0.5000 174.9 0.000 0.3 0.0000 10 C8 0.5000 78.50 -0.020 0.5 0.0160 10 C6 0.5050 61.30 0.054 0.5 0.0040 10 C4 0.5077 42.00 0.009 0.5 0.0005 10 C2 0.5200 22.00 0.110 0.5 -0.0010 10 C1 0.5410 11.92 0.1300 0.4 0.0014 10 L4 0.4800 4.099 0.003 1.0 0.0004 10 L2 0.5020 2.068 0.000 0.5 0.0001 10 L1 0.4925 1.161 0.100 0.5 0.0001 10 * Fan Pressure "PrB" must be greater than "Min Fan Pressure" and greater than (PrA*K2) Door fan systems should be checked for calibration every 5 years Calibration for the Door Fan should be checked before:2022-07-17 The flow accuracy requirements of the following Standards are: ATTMA: TS1 EN13829 ISO 9972 ASTM E779 CGSB EN15004 IS014520 7% 7% 7% 5% 5% 5% 5% Title 24 5% Certificate of Calibration ■ QC Issued by: Retrotec Calibration Date: 2019-02-07 Calibration laboratory Retrotec 1060 East Pole Road Everson, WA, US 98274 +1 (360) 738-9835 calibration@retrotec.com http://www.retrotec.com Tested in accordance to ISO 9972, CGSB 2002, ATTMA-TS1, ASTM-E779, RESNET: Pass Certificate Number: 201902071309-PH002041 Results: As Left A14 0 A C C R C D I T C D CALIR:IATION LA130RATORY AG-1943 This calibration laboratory has been assessed by the ANSI-ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025. All pressure and flow devices used in this calibration are traceable to the National Institute of Standards and Technology. Device being calibrated: Description: Test Fan Manufacturer: Retrotec Model Number: Model 3000SR Shell Serial Number: PH002041 Main Voltage: 110 V - 240 V Main Frequency: 50 Hz / 60 Hz Reference Flow: Nozzle 2010 Chamber, in accordance with ANSI/AMCA 210-07: Device Under Test Gauge: DM-32 Gauge Serial number 408019 Reference Gauge: DM-32 Gauge Serial number 407350 Calibrated by: Mike Cline Signature Calibration Information: The Device was calibrated against laboratory standards whose values are traceable to recognized national standards. The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a 95% confidence level. In tolerance conditions are based on test results falling within specified limits without taking uncertainty into account. The uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements. Calibration Procedure: Procedure ID No.CP-CHB-01 This Calibration Certificate shall not be reproduced except in full, without written approval from Retrotec. Name Calibration Expiration Date Name Calibration Expiration Date IS09972 2024-02-07 CGSB 2002 2024-02-07 ATTMA-TS1 2020-02-07 ASTM-E779 2024-02-07 RESNET 2024-02-07 Page 1 of 3 Calibration Date: 2019-02-07 Certificate of Calibration ■ QC Issued by: Retrotec Calibration Date: 2019-02-07 Tested in accordance to ISO 9972, CGSB 2002, ATTMA-TS1, ASTM-E779, RESNET: Pass Certificate Number: 201902071309-PH002041 Calibration Results: Flow rates are corrected to STIR conditions of 20°C, 101.325 kPa, 50% RH and Air Density: 1.19886 Results: As Left BarometricChamber Humidity % Fan Pressure Reference Fan Flow Range (RH) Temp (C) P esPsau)re Pressure (Pa) (Pa) Flow (m3/h) (m3/h) o Error (/) Open 26.2 21.3 101.200 50.8 14.6 3565.80 3682.75 3.3% Open 26.7 20.9 101.200 51.6 93.1 10094.64 10225.49 1.3% Open 28.7 19.4 101.200 51.1 138.1 12589.77 12706.97 0.9% A 28.5 19.7 101.200 50.9 21.1 2233.50 2211.09 1.0% A 28.4 19.8 101.200 52.2 180.4 6390.78 6409.08 0.3% A 28.6 19.6 101.200 51.3 274.6 7909.95 7893.48 0.2% B 28.9 19.5 101.200 51.4 33.2 1713.78 1704.64 0.5% B 28.8 19.6 101.200 51.1 248.1 4585.19 4575.71 0.2% B 29.1 19.4 101.200 52.3 378.9 5662.33 5633.12 0.5% C8 28.9 19.5 101.200 50.0 90.5 1321.56 1317.37 0.30 C8 28.8 19.6 101.200 51.4 332.9 2547.41 2557.40 0.4% C8 28.6 19.7 101.200 50.6 503.9 3133.23 3158.57 0.8% C6 28.0 20.2 101.200 51.0 35.5 637.72 633.87 0.60 C6 28.0 20.2 101.200 51.5 315.3 1882.22 1887.93 0.3% C6 28.0 20.2 101.200 51.0 509.3 2392.12 2399.24 0.3% C4 27.7 20.3 101.200 50.7 79.7 623.71 624.61 0.10 C4 27.8 20.3 101.200 49.8 323.9 1278.30 1285.43 0.6% C4 27.8 20.4 101.200 50.0 489.9 1578.77 1590.33 0.7% C2 27.6 20.5 101.200 50.7 66.7 292.91 295.43 0.90 C2 27.6 20.5 101.200 51.3 298.4 669.67 667.61 0.3% C2 27.6 20.5 101.200 50.3 457.5 835.66 842.29 0.8% C1 27.4 20.7 101.200 51.2 66.4 162.53 166.71 2.6% C1 27.3 20.8 101.200 51.9 282.5 371.13 370.82 0.1% C1 27.3 20.8 101.200 51.5 434.6 464.75 470.39 1.2% Calibration and measurement capability (Expanded Uncertainty) is 1.58% of reading, based on a 95% confidence interval, using a coverage of K=2 Page 2 of 3 Calibration Date: 2019-02-07 Certificate of Calibration ■ QC Issued by: Retrotec Calibration Date: 2019-02-07 Tested in accordance to ISO 9972, CGSB 2002, ATTMA-TS1, ASTM-E779, RESNET: Pass Published Flow Equation Parameters (Units in m3/h): Certificate Number: 201902071309-PH002041 Results: As Left Range Configuration n K MF (Pa) Open 0.551 842.48 8.6 A 0.496 487.10 12 B 0.491 305.51 10 C8 0.509 132.95 10 C6 0.500 106.52 10 C4 0.514 65.69 10 C2 0.544 30.08 10 C1 0.552 16.45 10 Flow = PA x K Where P = Fan Pressure in Pascals Range Configuration K1 K2 K3 Open 0 0.8 0 A 0 1.0 0 B 0 0.3 0 C8 0 0.5 0 C6 0 0.5 0 C4 0 0.5 0 C2 0 0.5 0 C 1 0 0.4 0 Date Format: This report adheres to ISO 8601: Data elements and interchange formats - Representation of dates and times All dates on this report are in the format: YYYY-MM-DD. Page 3 of 3 Calibration Date: 2019-02-07 I KA 3) (4 5 Al 7 E:3 41�1111ull W General Plan Notes CONC. JOINT, TYP. PER CIVIL WOOD GUARDRAIL N.I.C. 1. DIMENSIONS: GRID LINE DIMENSIONS ARE TO CENTERLINE OF FRAMING UNLESS NOTED OTHERWISE. ALL OTHER DIMENSIONS ARE TO FACE OF FRAMING UNLESS NOTED OTHERWISE. DO NOT SCALE DRAWINGS. ALL EXTERIOR WALL, DOOR, & WINDOW DIMENSIONS ARE TO CENTER OF ROUGH OPENING UNLESS NOTED OTHERWISE. 2. WINDOWS, STOREFRONTS & RELITES: SEE SHEETS A8.3 AND A8.4 FOR TYPES, SIZES AND SCHEDULES. 3. WALL TYPES: SEE SHEET A5.1 AND A5.2 FOR WALL TYPE DESCRIPTIONS. ALL INTERIOR PARTITIONS ARE G/A5.2, UNLESS NOTED OTHERWISE. SEE ENLARGED PLANS, WHERE PROVIDED. 4. DOOR OPENINGS: DOOR OPENINGS ARE LOCATED 4-1/2" FROM FINISH FACE OF WALL TO THE DOOR JAMB, UNLESS OTHERWISE NOTED. SEE SHEET A8.1 FOR TYPES, SIZES, AND SCHEDULES. 5. FIRESTOPPING DETAILS: SEE SHEET A5.4 FOR TYPICAL DETAILS. 6. ACCESS PANELS: ACCESS PANELS IN FIRE RATED ASSEMBLIES SHALL HAVE A FIRE RATING EQUIVALENT TO THE RATED ASSEMBLY IN WHICH THEY ARE INSTALLED. 7. BLOCKING: PROVIDE SAWN DIMENSIONAL LUMBER BLOCKING AT MIRRORS, TOWEL BARS, DOOR HARDWARE, & OTHER WALL -MOUNTED ITEMS. 8. BLOCKING LOADS: SAWN DIMENSIONAL LUMBER BLOCKING FOR GRAB BARS & STAIR HANDRAILS SHALL BE PROVIDED & INSTALLED TO RESIST A SINGLE CONCENTRATED LOAD OF 250 LBS APPLIED IN ANY DIRECTION AT ANY POINT. 9. OCCUPANT LOAD SIGNAGE: ALL ASSEMBLY OCCUPANCY ROOMS OR SPACES SHALL HAVE OCCUPANT LOAD SIGNAGE POSTED NEAR THE MAIN EXIT OR ACCESS DOORWAY FROM THE ROOM OR SPACE. SEE SHEET T1.4 FOR OCCUPANCY GROUPS AND OCCUPANT LOADS. Plan Legend O D.S. DOWNSPOUT +HB HOSE BIB �--- X/A5.1 WALL ASSEMBLY RECESSED FIRE EXTINGUISHER F.E.C. CABINET U WALL-MTD FIRE F.E. EXTINGUISHER FD FLOOR DRAIN SMOKE DETECTOR, SD HARDWIRE W/ BATTERY BACKUP ® 200 CFM RANGE HOOD, VENT TO EXT. �i EXHAUST WALL CAP �-0 STAND PIPE C.G.F_ CORNER GUARD FS FLOOR SINK - - - = TV LOCATION - TV 1 PROVIDE BLOCKING OCCUPANT LOAD SIGN O.L. LOCATION r0mom environmental WORKS Community Design Center 402 15th Avenue East Seattle, Washington 98112 phone: 206.329.8300 fax: 206.329.5494 Edmonds Waterfront Center New Construction 220 RAILROAD AVE. EDMONDS, WA 98020 6443 REGISTERED ARCHI GER - UCKFR First Floor Plan Date 03.15.2019 GMP Pricing Set Revisions 1 08.22.2019 Construction Set ASI 010 11.07.2019 - ASI 010 ASI 007 11.15.2019 - ASI 007 ASI 012 11.15.2019 - ASI 012 Drawn by: FSJ Checked by (P.M.): SK Checked by (Q.C.): RT Project No. 15015A First Floor Plan Scale: 1 /8" = V-0" 0 5 10 15 20 25 FT R Z PLAN All 2 ) ( 3 ) ( 4 ) ( 5 ) ( 6 ) ( 7 ) ( 8 ) ( 9 ) ( 10 ) ( 11 12 General Plan Notes 22'-9" 8'-0" 1 13'-7 1 /4" 1 13'-7 1 /4" 1 13'-7 1 /4" 1 13'-7 1 /4" 1 13'-7 1 /4" 1 8'-0" 1 14'4" 1 14'4' CANOPY BELOW CANOPY BELOW GRID 0 WOOD FRAMING C.L. SEE 6/A8. TO LOCATE HSS COLU 1. DIMENSIONS: GRID LINE DIMENSIONS ARE TO CENTERLINE OF FRAMING UNLESS NOTED OTHERWISE. ALL OTHER DIMENSIONS ARE TO FACE OF FRAMING UNLESS NOTED OTHERWISE. DO NOT SCALE DRAWINGS. ALL EXTERIOR WALL, DOOR, & WINDOW DIMENSIONS ARE TO CENTER OF ROUGH OPENING UNLESS NOTED OTHERWISE. 2. WINDOWS, STOREFRONTS & RELITES: SEE SHEETS A8.3 AND A8.4 FOR TYPES, SIZES AND SCHEDULES. 3. WALL TYPES: SEE SHEET A5.1 AND A5.2 FOR WALL TYPE DESCRIPTIONS. ALL INTERIOR PARTITIONS ARE G/A5.2, UNLESS NOTED OTHERWISE. SEE ENLARGED PLANS, WHERE PROVIDED. 4. DOOR OPENINGS: DOOR OPENINGS ARE LOCATED 4-1/2" FROM FINISH FACE OF WALL TO THE DOOR JAMB, UNLESS OTHERWISE NOTED. SEE SHEET A8.1 FOR TYPES, SIZES, AND SCHEDULES. 5. FIRESTOPPING DETAILS: SEE SHEET A5.4 FOR TYPICAL DETAILS. 6. ACCESS PANELS: ACCESS PANELS IN FIRE RATED ASSEMBLIES SHALL HAVE A FIRE RATING EQUIVALENT TO THE RATED ASSEMBLY IN WHICH THEY ARE INSTALLED. 7. BLOCKING: PROVIDE SAWN DIMENSIONAL LUMBER BLOCKING AT MIRRORS, TOWEL BARS, DOOR HARDWARE, & OTHER WALL -MOUNTED ITEMS. 8. BLOCKING LOADS: SAWN DIMENSIONAL LUMBER BLOCKING FOR GRAB BARS & STAIR HANDRAILS SHALL BE PROVIDED & INSTALLED TO RESIST A SINGLE CONCENTRATED LOAD OF 250 LBS APPLIED IN ANY DIRECTION AT ANY POINT. 9. OCCUPANT LOAD SIGNAGE: ALL ASSEMBLY OCCUPANCY ROOMS OR SPACES SHALL HAVE OCCUPANT LOAD SIGNAGE POSTED NEAR THE MAIN EXIT OR ACCESS DOORWAY FROM THE ROOM OR SPACE. SEE SHEET T1.4 FOR OCCUPANCY GROUPS AND OCCUPANT LOADS. Plan Legend O D.S. DOWNSPOUT +HB HOSE BIB X/A5.1 WALL ASSEMBLY RECESSED FIRE EXTINGUISHER F.E.C. CABINET U WALL-MTD FIRE F.E. EXTINGUISHER FD FLOOR DRAIN SMOKE DETECTOR, SD HARDWIRE W/ BATTERY BACKUP ® 200 CFM RANGE HOOD, VENT TO EXT. �i EXHAUST WALL CAP �-0 STAND PIPE C.G.F_ CORNER GUARD FS FLOOR SINK - - TV LOCATION - TV PROVIDE BLOCKING 1 OCCUPANT LOAD SIGN O.L. LOCATION environmental WORKS Community Design Center 402 15th Avenue East Seattle, Washington 98112 phone: 206.329.8300 fax: 206.329.5494 Edmonds Waterfront Center New Construction 220 RAILROAD AVE. EDMONDS, WA 98020 6443 REGISTERED ARCHI GER E UCKFR Second Floor Plan -------------------- Date 03.15.2019 GMP Pricing Set Revisions 1 08.22.2019 Construction Set 2 08.19.2019 RFI 2 - ASK 1 -------------------- -------------------- Drawn by: FSJ Checked by (P.M.): SK Checked by (Q.C.): RT Project No. 15015A 1 Second Floor Plan Scale: 1 /8" = V-0" 0 5 10 15 20 25 FT R �ZPLAN Al2