2020-12-01 Edmonds Waterfront Center ABT ReportDuildirg Cnwlnp. Cnginnwring
BEE Consulting LLC
170 West Dayton
St., Suite 206
Edmonds, WA
98020
EDMONDS WATERFRONT CENTER
WHOLE BUILDING AIR LEAKAGE TESTING REPORT
Project Name:
Edmonds Waterfront
Report Date:
12/7/2020
Center
Project #:
2012-1001
Air Barrier Testing
E779
Project
220 Railroad Ave
Field Rep:
Chris Shafer, Test Specialist
Address:
Edmonds, WA 98020
Test Date:
12/01/2020
Client:
W.G. Clark
Weather:
Overcast, -50 °F
Present at Site:
(BEE) - Chris S.
(BEE) - Torin G.
(BEE) - Robert S.
BEE was retained by W.G. Clark for the purpose of providing whole building air barrier
testing in accordance with ASTM E779 as required by the 2015 Washington State Energy
Code.
The Edmonds Waterfront Center project is a 2 story building. This report contains the
data for the whole building and completes the building air barrier test requirements in
total. Testing was completed on 12/01/2020.
BEE performed the building air barrier test procedure with positive pressure. The whole
building air testing was completed using a total of 3 mechanical blower door fans. The
fans were placed in the entryway on the Eastern elevation of level 1. Flow rates of each
fan were recorded at different building pressures ranging between 25 (pa) to 80 (pa).
Data was taken over 12 separate points.
Final Results for Edmonds Waterfront Center: 0.136 CFM/SQFT at 75 Pa
Pressurization Test, Passed
Final pressurization results of the building performance was an air leakage rate of 0.136
CFM/ SQFT of envelope at 75 Pa at the upper 95% confidence interval with the code
maximum allowable defined as 0.40 CFM/ SQFT of envelope at 75 Pa. Below are the
results with diagrams attached.
P: 425 672 3900
F: 425 712 8608
Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 1 of 8
9uildirg Cnwlop� Crgi�rirrg
Prepared by:
X
Chris Shafer
Testing Specialist
Reviewed and Approved by:
X
i1i S
Chad S�MK, P.E.
Principal Engineer
DISCLAIMER
Please note that there is no guarantee expressed, written or implied by this report. The data complied herein is subject to
change in case of new or additional data discovery. The information contained in this report is based on information available
at the time that this report was prepared. Concerns do not represent a total listing of all locations with issues nor do they
BEE Consulting LLC imply all similar locations to have issues. If additional information is discovered, it should be forwarded to our office for
170 West Dayton further review and comment. We reserve the right to amend and/or modify this report if new and/or significant data
Suite 206
Edmonds, WA becomes available that impacts the situation and parameters of this investigation. Our services were performed using the
Ed
98020 degree of skill normally exercised by practicing investigation individuals in this area and similar locales. No other warranty is
either expressed or implied.
P: 425 672 3900
F: 425 712 8608
Edmonds Waterfront Center / 2012-1001 12/3/2020 Page 2 of 8
Edmonds Waterfront Center
Air Barrier Test Report
In accordance with ASTM E779 WSEC 2015 Air Leakage Protocol
Performed by: 4i�.
BEE Consulting, LLC ,
170 W Dayton St, Ste. 206
Edmonds, WA 98020
Building Envelope Engineering
425.672.3900
FanTestic
version: 5.11.79
licensed to: BEE Consulting, LLC
Building Address:
220 Railroad Ave
Edmonds, WA 98020
Performed for:
W.G. Clark
Performed by:
Chris Shafer, Testing Specialist
Test Date:
2020-12-01
Associated Test File:
Edmonds waterfront center USACE
2020-12-01 1159
Project Number:
2012-1001
Testing Location:
Edmonds Waterfront Center
Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 3 of 8
Ftuildirg Cnr.lop� Cnginnwring
Summary
Building and Test Information
Test file name:
Edmonds waterfront center USACE 2020-
12-01 1159
Building Height from ground to top) [ft]:
28
Envelope Area [ft2]:
41404
Building Elevation (of ground, above sea
level) [ft]:
20
Results
Average air flowsTP at 75 Pa [CFM]
5565.5
Average equivalent leakage area at 75 Pa
[sq in]
597.0
Mean
95% Confidence Interval
Lower
Upper
Average CFM / sq ft of envelope at 75 Pa
0.134
0.133
0.136
Building Information
Building Measurements
Building elevation above sea level [ft] 20
Building Envelope Area [ft] 41,404
Building Height [ft] 28
Isolation / Heating / Ventilation System
All external HVAC and exhaust fan systems were properly set or isolated. All isolations
were performed from the exterior with the exceptions for any unique interior conditioned
spaces containing intentional penetrations through the building envelope.
Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 4 of 8
Duildi�g L�wbp� Ggurri.q
Discussion of Results
Combined Test Data (Tested in one direction only)
Combined Test Data (Tested in one direction only)
Average air flowsTP at +75 Pa [CFM]
5565.5
Average equivalent leakage area at 75 Pa
[sq in]
597.0
Mean
95% Confidence Interval
Lower
Upper
Average CFM / sq ft of envelope at 75 Pa
0.134
0.133
0.136
Building Air Leakage Test Photo Documentation
Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 5 of 8
9uildirg Cnwlop� Crginwrirrg
Air Leakage Test Data Appendix -
Pressurize Data Set
Test Dataset Date and Time: 2020-12-01-11:51:15
Finish Time: 11:53:28
Environmental Conditions
Operator Location:
Inside the building
Greatest Initial Baseline
Pressure
0.873 Pa
Initial Bias Pressure:
-0.21 Pa
Final Bias Pressure:
0.11 Pa
Initial Temperature:
indoors: 68
outdoors: 50.
Final Temperature:
indoors: 68
outdoors: 50.
Test Analysis
Squared correlation coefficient r2
0.99907
Exponent, n:
0.664
Air leakage coefficient, C
[CFM/Pan]:
316.18
CFM referenced to STP at 75 Pa
5565.5
Equivalent leakage area at 75
Pa [sq in]
598.0
Mean
95% confidence limits
Lower
Upper
CFM/sq ft of envelope at 75
0.137
0.1330
0.1359
Induced
Pressure
Pa
26.5
30.7
35.1
40.7
44.0
49.9
54.3
61.2
65.2
71.4
74.7
80.3
Total Flow
[CFM]
2780.54
3015.60
3317.67
3687.67
3801.64
4115.55
4406.84
4740.97
5082.69
5360.45
5480.50
5725.40
Total
Corrected
flow [CFM]
2824.1
3062.9
3369.7
3745.5
3861.2
4180.1
4475.9
4815.3
5162.4
5444.5
5566.4
5815.1
Error [%]
1.2%
-0.4%
0.1 %
0.8%
-1.3%
-1.6%
-0.4%
-1.1 %
1.7%
1.1 %
0.2%
-0.2%
12 induced pressures each taken for 10 of the required 10 seconds.
12 baseline pressures each taken for 10 of required 10 seconds.
Greatest Initial Baseline Pressure: 0.873 Pa
Static Pressure Averages:
initial [Pa]
AP01 -0.21
4P01- -0.31
AP01+ 0.87
final Pa
AP02 0.11
OP02- -0.22
OP02+ 0.17
Baseline,
initial Pa
0.87
-0.51
-0.31
-0.46
-0.58
-0.23
-0.27
-0.29
-0.05
-0.45
-0.19
-0.04
Baseline,
final [Pa]
-0.05
0.58
0.04
0.08
0.21
0.27
0.10
0.22
-0.39
0.10
0.07
0.04
Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 6 of 8
Duildi.g L.wbp� C.gurri.q
W
2
C
a
10000-
1000-
Induced Pressure vs. Flow (Pressurize Set)
Pressurize r2 = U.9981
1�
100
10 10D
(Lag) Pressure (Pa)
Building Gauge Pressure (Pressurize Set)
100
90
so
70
60
50
40
30
20
10
0
-10
-20
0 200 400 600 800
T-me
Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 7 of 8
100
10 10D
(Lag) Pressure (Pa)
Building Gauge Pressure (Pressurize Set)
100
90
so
70
60
50
40
30
20
10
0
-10
-20
0 200 400 600 800
T-me
Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 7 of 8
Duildi�g L�wbp� Ggurrilq
Test Equipment
The following test equipment was used in the performance of the building air leakage test.
Fan Model
Fan Serial
Fan Location
Gauge
Gauge Serial
#1
Retrotec 3000SR
PH001510
Top
DM32
407027
#2
Retrotec 3000SR
PH001507
Mid
DM32
400832
#3
Retrotec 3000SR
PH002041
Low
DM32
400796
Edmonds Waterfront Center / 2012-1001 12/7/2020 Page 8 of 8
Certificate of Gauge Calibration
Issued by: Retrotec
Calibration Date: 2016-09-08
retroL"�
1060 E Pole Rd.
Everson, WA, USA 98247
T: +1 (360) 738-9835
E: calibration@retrotec.com W: www.retrotec.com
Instrument:
Description:
Pressure and Flow Gauge
Manufacturer:
Retrotec
Model Number:
DM32 10A
Serial Number:
400796
Environmental conditions:
Temperature: 200C ±2°C
Relative Humidity: 50% ±10%
Mains Voltage: 120V ±10V
Mains Frequency: 60Hz ±1Hz
Certificate Number: 215213 084058
Results: As Found
AC-1943
This calibration laboratory has been assessed by the ANSI-
ASQ National Accreditation Board and meets the
requirements of international standard ISO/IEC 17025.
Comments:
Results recorded as received. No adjustment performed.
Calibration Information:
Calibrated by: Mike Shtunyuk
JJAv".fit, P4,-,
Signature
The Device was calibrated against laboratory standards whose values are traceable to
recognized national standards. The uncertainty represents an expanded uncertainty using a
coverage factor of K=2 to approximate a 95% confidence level. In tolerance conditions are based
on test results falling within specified limits without taking uncertainty into account. The
uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements.
Calibration Procedure:
CP-35-01
This Calibration Certificate shall not be reproduced except in full, without written approval from Retrotec.
Certificate of Gauge Calibration
Issued by: Retrotec
Calibration Date: 2016-09-08
Calibration Results
Channel A
Applied Value (Pa)
Reading (Pa)
Error (%)
-749.97
-753.88
0.52
-600.01
-603.22
0.53
-300.03
-301.55
0.51
-150.05
-150.70
0.43
-74.99
-75.28
0.39
-49.99
-50.17
0.36
-25.00
-25.10
0.40
-15.00
-15.02
0.13
0.00
-0.02
N/A
14.99
15.10
0.73
25.01
25.12
0.44
49.99
50.28
0.58
75.00
75.41
0.55
150.00
150.68
0.45
300.02
301.30
0.43
599.98
602.55
0.43
749.99
752.96
0.40
Instrument display resolution is 0.1 Pa.
Certificate Number: 215213 084058
Results: As Found
Channel B
Applied Value (Pa)
Reading (Pa)
Error (%)
-749.97
-754.82
0.65
-600.01
-603.94
0.65
-300.03
-301.75
0.57
-150.05
-150.87
0.55
-74.99
-75.33
0.45
-49.99
-50.21
0.44
-25.00
-25.07
0.28
-15.00
-15.00
0.00
0.00
-0.03
N/A
14.99
15.12
0.87
25.01
25.22
0.84
49.99
50.37
0.76
75.00
75.47
0.63
150.00
150.87
0.58
300.02
301.50
0.49
599.98
602.70
0.45
749.99
753.11
0.42
Uncertainties
Calibration and measurement capability (Expanded Uncertainty) is .01 Pa + 0.3% of reading (Range 0 -
20 000 Pa) based on a 95% confidence interval, using coverage of K=2.
IN S
inmai
The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from) the following standards
or guidelines:
NFPA 2001
EN13829
ATTMA: TS1 ASTM E779-10 CGSB
GAP50-784
±1 Pa
±2 Pa
±2 Pa ±5% or 0.25 Pa ±1 Pa
±1% or 1 Pa
±(10 to 50) Pa
(up to ±60 Pa)
(up to ±100 Pa) whichever is greater (up to ±50 Pa)
whichever is greater
ISO14520
EN15004
USACE TITLE 24
RESNET
±1 Pa
±1 Pa
±1% or 0.25 Pa ±1% or 0.2 Pa
±1% or 0.5 Pa
(up to ±60 Pa)
(up to ±100 Pa)
±(25 to 250) Pa whichever is greater
whichever is greater
Certificate of Gauge Calibration
Issued by: Retrotec
Calibration Date: 2016-06-14
retroL"�
1060 E Pole Rd.
Everson, WA, USA 98247
T: +1 (360) 738-9835
E: calibration@retrotec.com W: www.retrotec.com
Instrument:
Description:
Pressure and Flow Gauge
Manufacturer:
Retrotec
Model Number:
DM32 10A
Serial Number:
400832
Environmental conditions:
Temperature: 200C ±2°C
Relative Humidity: 50% ±10%
Mains Voltage: 120V ±10V
Mains Frequency: 60Hz ±1Hz
Certificate Number: 217465 121501
Results: As Found
AC-1943
This calibration laboratory has been assessed by the ANSI-
ASQ National Accreditation Board and meets the
requirements of international standard ISO/IEC 17025.
Comments:
Results recorded as received. No adjustment performed.
Calibration Information:
Calibrated by: Mike Shtunyuk
JJAv".fit, P4,-,
Signature
The Device was calibrated against laboratory standards whose values are traceable to
recognized national standards. The uncertainty represents an expanded uncertainty using a
coverage factor of K=2 to approximate a 95% confidence level. In tolerance conditions are based
on test results falling within specified limits without taking uncertainty into account. The
uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements.
Calibration Procedure:
CP-35-01
This Calibration Certificate shall not be reproduced except in full, without written approval from Retrotec.
Certificate of Gauge Calibration
Issued by: Retrotec
Calibration Date: 2016-06-14
Calibration Results
Channel A
Applied Value (Pa)
Reading (Pa)
Error (%)
-750.00
-751.40
0.19
-600.01
-601.25
0.21
-300.00
-300.38
0.13
-150.02
-150.09
0.05
-75.01
-75.10
0.12
-50.01
-50.03
0.04
-25.01
-24.98
0.12
-15.01
-14.98
0.20
0.00
-0.01
N/A
15.00
15.03
0.20
25.02
25.05
0.12
49.99
50.08
0.18
74.99
75.14
0.20
150.00
150.18
0.12
299.98
300.22
0.08
600.01
600.00
0.00
750.00
749.81
0.03
Instrument display resolution is 0.1 Pa.
Certificate Number: 217465 121501
Results: As Found
Channel B
Applied Value (Pa)
Reading (Pa)
Error (%)
-750.00
-751.24
0.17
-600.01
-601.10
0.18
-300.00
-300.31
0.10
-150.02
-150.10
0.05
-75.01
-75.00
0.01
-50.01
-50.04
0.06
-25.01
-24.98
0.12
-15.01
-14.98
0.20
0.00
-0.04
N/A
15.00
15.04
0.27
25.02
25.03
0.04
49.99
50.07
0.16
74.99
75.09
0.13
150.00
150.15
0.10
299.98
300.18
0.07
600.01
599.98
0.00
750.00
749.91
0.01
Uncertainties
Calibration and measurement capability (Expanded Uncertainty) is .01 Pa + 0.3% of reading (Range 0 -
20 000 Pa) based on a 95% confidence interval, using coverage of K=2.
IN S
inmai
The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from) the following standards
or guidelines:
NFPA 2001
EN13829
ATTMA: TS1 ASTM E779-10 CGSB
GAP50-784
±1 Pa
±2 Pa
±2 Pa ±5% or 0.25 Pa ±1 Pa
±1% or 1 Pa
±(10 to 50) Pa
(up to ±60 Pa)
(up to ±100 Pa) whichever is greater (up to ±50 Pa)
whichever is greater
ISO14520
EN15004
USACE TITLE 24
RESNET
±1 Pa
±1 Pa
±1% or 0.25 Pa ±1% or 0.2 Pa
±1% or 0.5 Pa
(up to ±60 Pa)
(up to ±100 Pa)
±(25 to 250) Pa whichever is greater
whichever is greater
Certificate of Gauge Calibration
Issued by: Retrotec
Calibration Date: 2017-07-06
retroL"�
1060 E Pole Rd.
Everson, WA, USA 98247
T: +1 (360) 738-9835
E: calibration@retrotec.com W: www.retrotec.com
Instrument:
Description:
Pressure and Flow Gauge
Manufacturer:
Retrotec
Model Number:
DM32 10A
Serial Number:
407027
Environmental conditions:
Temperature: 200C ±2°C
Relative Humidity: 50% ±10%
Mains Voltage: 120V ±10V
Mains Frequency: 60Hz ±1Hz
Certificate Number: 215214 090025
Results: As Found
AC-1943
This calibration laboratory has been assessed by the ANSI-
ASQ National Accreditation Board and meets the
requirements of international standard ISO/IEC 17025.
Comments:
Results recorded as received. No adjustment performed.
Calibration Information:
Calibrated by: Mike Shtunyuk
JJAv".fit, P4,-,
Signature
The Device was calibrated against laboratory standards whose values are traceable to
recognized national standards. The uncertainty represents an expanded uncertainty using a
coverage factor of K=2 to approximate a 95% confidence level. In tolerance conditions are based
on test results falling within specified limits without taking uncertainty into account. The
uncertainty evaluation has been carried out in accordance with ISO/IEC 17025 requirements.
Calibration Procedure:
CP-35-01
This Calibration Certificate shall not be reproduced except in full, without written approval from Retrotec.
Certificate of Gauge Calibration
Issued by: Retrotec
Calibration Date: 2017-07-06
Calibration Results
Channel A
Applied Value (Pa)
Reading (Pa)
Error (%)
-749.97
-755.31
0.71
-600.01
-604.40
0.73
-300.03
-301.96
0.64
-150.00
-150.86
0.57
-74.99
-75.41
0.56
-50.00
-50.21
0.42
-25.00
-25.11
0.44
-15.01
-15.06
0.33
0.00
-0.02
N/A
15.00
15.12
0.80
25.00
25.11
0.44
50.00
50.31
0.62
75.00
75.43
0.57
150.03
150.80
0.51
299.99
301.48
0.50
599.96
602.27
0.39
749.94
752.72
0.37
Instrument display resolution is 0.1 Pa.
Certificate Number: 215214 090025
Results: As Found
Channel B
Applied Value (Pa)
Reading (Pa)
Error (%)
-749.97
-754.33
0.58
-600.01
-603.68
0.61
-300.03
-301.73
0.57
-150.00
-150.80
0.53
-74.99
-75.40
0.55
-50.00
-50.20
0.40
-25.00
-25.17
0.68
-15.01
-15.02
0.07
0.00
0.04
N/A
15.00
15.10
0.67
25.00
25.15
0.60
50.00
50.25
0.50
75.00
75.34
0.45
150.03
150.76
0.49
299.99
301.36
0.46
599.96
602.31
0.39
749.94
753.02
0.41
Uncertainties
Calibration and measurement capability (Expanded Uncertainty) is .01 Pa + 0.3% of reading (Range 0 -
20 000 Pa) based on a 95% confidence interval, using coverage of K=2. e
I
inmai
The Pressure Range uncertainty limits are compliant with (meets or exceeds requirements from) the following standards
or guidelines:
NFPA 2001
EN13829
ATTMA: TS1 ASTM E779-10 CGSB
GAP50-784
±1 Pa
±2 Pa
±2 Pa ±5% or 0.25 Pa ±1 Pa
±1% or 1 Pa
±(10 to 50) Pa
(up to ±60 Pa)
(up to ±100 Pa) whichever is greater (up to ±50 Pa)
whichever is greater
ISO14520
EN15004
USACE TITLE 24
RESNET
±1 Pa
±1 Pa
±1% or 0.25 Pa ±1% or 0.2 Pa
±1% or 0.5 Pa
(up to ±60 Pa)
(up to ±100 Pa)
±(25 to 250) Pa whichever is greater
whichever is greater
retraL"�
Fan Calibration
Verification Report
Calibrated Equipment
Calibration Facility
Fan Shell Serial Number
PH001507
Company Retrotec
Fantop Serial Number
1AC000217(SD)
Address 1060 E Pole Rd
Fan Model
3350
Location Everson, WA USA
Manufacturer
Retrotec
Phone (360) 738-9835
Calibration Date
2016-07-28
Technician OA Tester
Flow calibration verification data
The accuracy of this system was checked against an orifice plate mounted in a chamber which was verified with fans calibrated to
ASTM E-1258. Pressure gauge 400830 used for calibration was checked against one of two NIST tracable Furness 550 pressure
calibrators: 0704353, 0907002
Total Leakage Test
Background Leakage Test
Number of
Range
Chamber
Fan
Fan
Leakage
System
samples
Ring /Plate
pressure
pressure
speed
area (in)
flow
PrA (Pa)
PrB (Pa)
M
(CFM)
114
A
-50.0
65.6
22
340.0
2234
114
L1
-60.4
176.2
32
1.9
14
Measured Orifice Flow (CFM)
Actual Orifice Flow (CFM)
Error
2220
91d7
Measured flow calculation (using flow equations)
System flow = [65.6 - (-50.0 *-0.075)]^0.503 * [264.9959 + 65.6 * 0] = 2234 CFM
System flow = [176.2 - (-60.4 * 0.1)]^0.4925 * [1.1614 + 176.2 * 0] = 14 CFM
System flow equations
Depressurization with operator indoors ( air flow away from operator):
System flow (cfm) = (PrB - PrA*K1)N * (K + PrB*K3)
Pressurization with operator indoors (air flow towards the operator):
System flow (cfm) = [(PrB - PrA) - PrA*K1]N * [K + (PrB - PrA)*K3]
Range
Ring / Plate
N
System flow equation constants
K K1 K2*
K3
Min Fan Pressure*
(Pa)
Open
0.5214
519.6
-0.070
0.8
-0.1150
8.6
A
0.5030
265.0
-0.075
1.0
0.0000
12
B
0.5000
174.9
0.000
0.3
0.0000
10
C8
0.5000
78.50
-0.020
0.5
0.0160
10
C6
0.5050
61.30
0.054
0.5
0.0040
10
C4
0.5077
42.00
0.009
0.5
0.0005
10
C2
0.5200
22.00
0.110
0.5
-0.0010
10
C1
0.5410
11.92
0.1300
0.4
0.0014
10
L4
0.4800
4.099
0.003
1.0
0.0004
10
L2
0.5020
2.068
0.000
0.5
0.0001
10
L1
0.4925
1.161
0.100
0.5
0.0001
10
* Fan Pressure "PrB" must be greater than "Min Fan Pressure" and greater than (PrA*K2)
Door fan systems should be checked for calibration every 5 years
Calibration for the Door Fan should be checked before:2021-07-28
The flow accuracy requirements of the following Standards are:
ATTMA: TS1 EN13829 ISO 9972 ASTM E779 CGSB EN15004 IS014520
7% 7% 7% 5% 5% 5% 5%
Title 24
5%
retraL"�
Fan Calibration
Verification Report
Calibrated Equipment
Calibration Facility
Fan Shell Serial Number
PH001510
Company Retrotec
Fantop Serial Number
1AC000217(SD)
Address 1060 E Pole Rd
Fan Model
3350
Location Everson, WA USA
Manufacturer
Retrotec
Phone (360) 738-9835
Calibration Date
2017-07-17
Technician OA Tester
Flow calibration verification data
The accuracy of this system was checked against an orifice plate mounted in a chamber which was verified with fans calibrated to
ASTM E-1258. Pressure gauge 406268 used for calibration was checked against one of two NIST tracable Furness 550 pressure
calibrators: 0704353, 0907002
Total Leakage Test
Background Leakage Test
Number of
Range
Chamber
Fan
Fan
Leakage
System
samples
Ring /Plate
pressure
pressure
speed
area (in)
flow
PrA (Pa)
PrB (Pa)
M
(CFM)
114
A
-50.5
66.7
21
341.0
2253
114
L1
-54.1
114.9
15
1.7
12
Measured Orifice Flow (CFM)
Actual Orifice Flow (CFM)
Error
2241
91rIR
1). V /o
Measured flow calculation (using flow equations)
System flow = [66.7 - (-50.5 *-0.075)]^0.503 * [264.9959 + 66.7 * 0] = 2253 CFM
System flow = [114.9 - (-54.1 * 0.1)]^0.4925 * [1.1614 + 114.9 * 0] = 12 CFM
System flow equations
Depressurization with operator indoors ( air flow away from operator):
System flow (cfm) = (PrB - PrA*K1)N * (K + PrB*K3)
Pressurization with operator indoors (air flow towards the operator):
System flow (cfm) = [(PrB - PrA) - PrA*K1]N * [K + (PrB - PrA)*K3]
Range
Ring / Plate
N
System flow equation constants
K K1 K2*
K3
Min Fan Pressure*
(Pa)
Open
0.5214
519.6
-0.070
0.8
-0.1150
8.6
A
0.5030
265.0
-0.075
1.0
0.0000
12
B
0.5000
174.9
0.000
0.3
0.0000
10
C8
0.5000
78.50
-0.020
0.5
0.0160
10
C6
0.5050
61.30
0.054
0.5
0.0040
10
C4
0.5077
42.00
0.009
0.5
0.0005
10
C2
0.5200
22.00
0.110
0.5
-0.0010
10
C1
0.5410
11.92
0.1300
0.4
0.0014
10
L4
0.4800
4.099
0.003
1.0
0.0004
10
L2
0.5020
2.068
0.000
0.5
0.0001
10
L1
0.4925
1.161
0.100
0.5
0.0001
10
* Fan Pressure "PrB" must be greater than "Min Fan Pressure" and greater than (PrA*K2)
Door fan systems should be checked for calibration every 5 years
Calibration for the Door Fan should be checked before:2022-07-17
The flow accuracy requirements of the following Standards are:
ATTMA: TS1 EN13829 ISO 9972 ASTM E779 CGSB EN15004 IS014520
7% 7% 7% 5% 5% 5% 5%
Title 24
5%
Certificate of Calibration
■ QC
Issued by: Retrotec
Calibration Date: 2019-02-07
Calibration laboratory
Retrotec
1060 East Pole Road
Everson, WA, US 98274
+1 (360) 738-9835
calibration@retrotec.com
http://www.retrotec.com
Tested in accordance to ISO 9972, CGSB 2002, ATTMA-TS1, ASTM-E779, RESNET: Pass
Certificate Number: 201902071309-PH002041
Results: As Left
A14 0
A C C R C D I T C D
CALIR:IATION LA130RATORY
AG-1943
This calibration laboratory has been assessed by the ANSI-ASQ National Accreditation Board and meets the requirements of international standard ISO/IEC 17025. All
pressure and flow devices used in this calibration are traceable to the National Institute of Standards and Technology.
Device being calibrated:
Description:
Test Fan
Manufacturer:
Retrotec
Model Number:
Model 3000SR
Shell Serial Number:
PH002041
Main Voltage:
110 V - 240 V
Main Frequency:
50 Hz / 60 Hz
Reference Flow:
Nozzle 2010 Chamber, in accordance with ANSI/AMCA 210-07:
Device Under Test Gauge: DM-32 Gauge Serial number 408019
Reference Gauge: DM-32 Gauge Serial number 407350
Calibrated by: Mike Cline
Signature
Calibration Information:
The Device was calibrated against laboratory standards whose values are traceable to recognized national
standards. The uncertainty represents an expanded uncertainty using a coverage factor of K=2 to approximate a
95% confidence level. In tolerance conditions are based on test results falling within specified limits without
taking uncertainty into account. The uncertainty evaluation has been carried out in accordance with ISO/IEC
17025 requirements.
Calibration Procedure: Procedure ID No.CP-CHB-01
This Calibration Certificate shall not be reproduced except in full, without written approval from Retrotec.
Name
Calibration Expiration Date
Name
Calibration Expiration Date
IS09972
2024-02-07
CGSB 2002
2024-02-07
ATTMA-TS1
2020-02-07
ASTM-E779
2024-02-07
RESNET
2024-02-07
Page 1 of 3 Calibration Date: 2019-02-07
Certificate of Calibration
■ QC
Issued by: Retrotec
Calibration Date: 2019-02-07
Tested in accordance to ISO 9972, CGSB 2002, ATTMA-TS1, ASTM-E779, RESNET: Pass
Certificate Number: 201902071309-PH002041
Calibration Results:
Flow rates are corrected to STIR conditions of 20°C, 101.325 kPa, 50% RH and Air Density: 1.19886
Results: As Left
BarometricChamber
Humidity %
Fan Pressure
Reference
Fan Flow
Range
(RH)
Temp (C)
P esPsau)re
Pressure (Pa)
(Pa)
Flow (m3/h)
(m3/h)
o
Error (/)
Open
26.2
21.3
101.200
50.8
14.6
3565.80
3682.75
3.3%
Open
26.7
20.9
101.200
51.6
93.1
10094.64
10225.49
1.3%
Open
28.7
19.4
101.200
51.1
138.1
12589.77
12706.97
0.9%
A
28.5
19.7
101.200
50.9
21.1
2233.50
2211.09
1.0%
A
28.4
19.8
101.200
52.2
180.4
6390.78
6409.08
0.3%
A
28.6
19.6
101.200
51.3
274.6
7909.95
7893.48
0.2%
B
28.9
19.5
101.200
51.4
33.2
1713.78
1704.64
0.5%
B
28.8
19.6
101.200
51.1
248.1
4585.19
4575.71
0.2%
B
29.1
19.4
101.200
52.3
378.9
5662.33
5633.12
0.5%
C8
28.9
19.5
101.200
50.0
90.5
1321.56
1317.37
0.30
C8
28.8
19.6
101.200
51.4
332.9
2547.41
2557.40
0.4%
C8
28.6
19.7
101.200
50.6
503.9
3133.23
3158.57
0.8%
C6
28.0
20.2
101.200
51.0
35.5
637.72
633.87
0.60
C6
28.0
20.2
101.200
51.5
315.3
1882.22
1887.93
0.3%
C6
28.0
20.2
101.200
51.0
509.3
2392.12
2399.24
0.3%
C4
27.7
20.3
101.200
50.7
79.7
623.71
624.61
0.10
C4
27.8
20.3
101.200
49.8
323.9
1278.30
1285.43
0.6%
C4
27.8
20.4
101.200
50.0
489.9
1578.77
1590.33
0.7%
C2
27.6
20.5
101.200
50.7
66.7
292.91
295.43
0.90
C2
27.6
20.5
101.200
51.3
298.4
669.67
667.61
0.3%
C2
27.6
20.5
101.200
50.3
457.5
835.66
842.29
0.8%
C1
27.4
20.7
101.200
51.2
66.4
162.53
166.71
2.6%
C1
27.3
20.8
101.200
51.9
282.5
371.13
370.82
0.1%
C1
27.3
20.8
101.200
51.5
434.6
464.75
470.39
1.2%
Calibration and measurement capability (Expanded Uncertainty) is 1.58% of reading, based on a 95% confidence
interval, using a coverage of K=2
Page 2 of 3 Calibration Date: 2019-02-07
Certificate of Calibration
■ QC
Issued by: Retrotec
Calibration Date: 2019-02-07
Tested in accordance to ISO 9972, CGSB 2002, ATTMA-TS1, ASTM-E779, RESNET: Pass
Published Flow Equation Parameters (Units in m3/h):
Certificate Number: 201902071309-PH002041
Results: As Left
Range Configuration
n
K
MF (Pa)
Open
0.551
842.48
8.6
A
0.496
487.10
12
B
0.491
305.51
10
C8
0.509
132.95
10
C6
0.500
106.52
10
C4
0.514
65.69
10
C2
0.544
30.08
10
C1
0.552
16.45
10
Flow = PA x K
Where P = Fan Pressure in Pascals
Range Configuration
K1
K2
K3
Open
0
0.8
0
A
0
1.0
0
B
0
0.3
0
C8
0
0.5
0
C6
0
0.5
0
C4
0
0.5
0
C2
0
0.5
0
C 1
0
0.4
0
Date Format:
This report adheres to ISO 8601: Data elements and interchange formats - Representation of dates and times
All dates on this report are in the format: YYYY-MM-DD.
Page 3 of 3 Calibration Date: 2019-02-07
I
KA
3) (4
5
Al
7
E:3
41�1111ull
W
General Plan Notes
CONC. JOINT, TYP.
PER CIVIL
WOOD GUARDRAIL N.I.C.
1. DIMENSIONS:
GRID LINE DIMENSIONS ARE TO
CENTERLINE OF FRAMING UNLESS NOTED
OTHERWISE. ALL OTHER DIMENSIONS ARE
TO FACE OF FRAMING UNLESS NOTED
OTHERWISE. DO NOT SCALE DRAWINGS.
ALL EXTERIOR WALL, DOOR, & WINDOW
DIMENSIONS ARE TO CENTER OF ROUGH
OPENING UNLESS NOTED OTHERWISE.
2. WINDOWS, STOREFRONTS & RELITES:
SEE SHEETS A8.3 AND A8.4 FOR TYPES,
SIZES AND SCHEDULES.
3. WALL TYPES:
SEE SHEET A5.1 AND A5.2 FOR WALL TYPE
DESCRIPTIONS.
ALL INTERIOR PARTITIONS ARE G/A5.2,
UNLESS NOTED OTHERWISE. SEE
ENLARGED PLANS, WHERE PROVIDED.
4. DOOR OPENINGS:
DOOR OPENINGS ARE LOCATED 4-1/2"
FROM FINISH FACE OF WALL TO THE
DOOR JAMB, UNLESS OTHERWISE NOTED.
SEE SHEET A8.1 FOR TYPES, SIZES, AND
SCHEDULES.
5. FIRESTOPPING DETAILS:
SEE SHEET A5.4 FOR TYPICAL DETAILS.
6. ACCESS PANELS:
ACCESS PANELS IN FIRE RATED
ASSEMBLIES SHALL HAVE A FIRE RATING
EQUIVALENT TO THE RATED ASSEMBLY IN
WHICH THEY ARE INSTALLED.
7. BLOCKING:
PROVIDE SAWN DIMENSIONAL LUMBER
BLOCKING AT MIRRORS, TOWEL BARS,
DOOR HARDWARE, & OTHER
WALL -MOUNTED ITEMS.
8. BLOCKING LOADS:
SAWN DIMENSIONAL LUMBER BLOCKING
FOR GRAB BARS & STAIR HANDRAILS
SHALL BE PROVIDED & INSTALLED TO
RESIST A SINGLE CONCENTRATED LOAD
OF 250 LBS APPLIED IN ANY DIRECTION AT
ANY POINT.
9. OCCUPANT LOAD SIGNAGE:
ALL ASSEMBLY OCCUPANCY ROOMS OR
SPACES SHALL HAVE OCCUPANT LOAD
SIGNAGE POSTED NEAR THE MAIN EXIT
OR ACCESS DOORWAY FROM THE ROOM
OR SPACE. SEE SHEET T1.4 FOR
OCCUPANCY GROUPS AND OCCUPANT
LOADS.
Plan Legend
O D.S. DOWNSPOUT
+HB HOSE BIB
�--- X/A5.1 WALL ASSEMBLY
RECESSED FIRE
EXTINGUISHER
F.E.C.
CABINET
U
WALL-MTD FIRE
F.E.
EXTINGUISHER
FD
FLOOR DRAIN
SMOKE DETECTOR,
SD
HARDWIRE W/ BATTERY
BACKUP
®
200 CFM RANGE HOOD,
VENT TO EXT.
�i
EXHAUST WALL CAP
�-0
STAND PIPE
C.G.F_
CORNER GUARD
FS
FLOOR SINK
- - - =
TV LOCATION -
TV
1
PROVIDE BLOCKING
OCCUPANT LOAD SIGN
O.L.
LOCATION
r0mom
environmental
WORKS
Community Design Center
402 15th Avenue East
Seattle, Washington 98112
phone: 206.329.8300
fax: 206.329.5494
Edmonds Waterfront
Center
New Construction
220 RAILROAD AVE.
EDMONDS, WA 98020
6443
REGISTERED
ARCHI
GER - UCKFR
First Floor Plan
Date
03.15.2019
GMP Pricing Set
Revisions
1
08.22.2019 Construction Set
ASI 010
11.07.2019 - ASI 010
ASI 007
11.15.2019 - ASI 007
ASI 012
11.15.2019 - ASI 012
Drawn by:
FSJ
Checked by (P.M.):
SK
Checked by (Q.C.):
RT
Project No.
15015A
First Floor Plan
Scale: 1 /8" = V-0"
0 5 10 15 20 25 FT
R
Z PLAN
All
2 ) ( 3 ) ( 4 ) ( 5 ) ( 6 ) ( 7 ) ( 8 ) ( 9 ) ( 10 ) ( 11
12
General Plan Notes
22'-9" 8'-0" 1 13'-7 1 /4" 1 13'-7 1 /4" 1 13'-7 1 /4" 1 13'-7 1 /4" 1 13'-7 1 /4" 1 8'-0" 1 14'4" 1 14'4'
CANOPY BELOW
CANOPY BELOW
GRID 0 WOOD FRAMING C.L.
SEE 6/A8. TO LOCATE HSS
COLU
1. DIMENSIONS:
GRID LINE DIMENSIONS ARE TO
CENTERLINE OF FRAMING UNLESS NOTED
OTHERWISE. ALL OTHER DIMENSIONS ARE
TO FACE OF FRAMING UNLESS NOTED
OTHERWISE. DO NOT SCALE DRAWINGS.
ALL EXTERIOR WALL, DOOR, & WINDOW
DIMENSIONS ARE TO CENTER OF ROUGH
OPENING UNLESS NOTED OTHERWISE.
2. WINDOWS, STOREFRONTS & RELITES:
SEE SHEETS A8.3 AND A8.4 FOR TYPES,
SIZES AND SCHEDULES.
3. WALL TYPES:
SEE SHEET A5.1 AND A5.2 FOR WALL TYPE
DESCRIPTIONS.
ALL INTERIOR PARTITIONS ARE G/A5.2,
UNLESS NOTED OTHERWISE. SEE
ENLARGED PLANS, WHERE PROVIDED.
4. DOOR OPENINGS:
DOOR OPENINGS ARE LOCATED 4-1/2"
FROM FINISH FACE OF WALL TO THE
DOOR JAMB, UNLESS OTHERWISE NOTED.
SEE SHEET A8.1 FOR TYPES, SIZES, AND
SCHEDULES.
5. FIRESTOPPING DETAILS:
SEE SHEET A5.4 FOR TYPICAL DETAILS.
6. ACCESS PANELS:
ACCESS PANELS IN FIRE RATED
ASSEMBLIES SHALL HAVE A FIRE RATING
EQUIVALENT TO THE RATED ASSEMBLY IN
WHICH THEY ARE INSTALLED.
7. BLOCKING:
PROVIDE SAWN DIMENSIONAL LUMBER
BLOCKING AT MIRRORS, TOWEL BARS,
DOOR HARDWARE, & OTHER
WALL -MOUNTED ITEMS.
8. BLOCKING LOADS:
SAWN DIMENSIONAL LUMBER BLOCKING
FOR GRAB BARS & STAIR HANDRAILS
SHALL BE PROVIDED & INSTALLED TO
RESIST A SINGLE CONCENTRATED LOAD
OF 250 LBS APPLIED IN ANY DIRECTION AT
ANY POINT.
9. OCCUPANT LOAD SIGNAGE:
ALL ASSEMBLY OCCUPANCY ROOMS OR
SPACES SHALL HAVE OCCUPANT LOAD
SIGNAGE POSTED NEAR THE MAIN EXIT
OR ACCESS DOORWAY FROM THE ROOM
OR SPACE. SEE SHEET T1.4 FOR
OCCUPANCY GROUPS AND OCCUPANT
LOADS.
Plan Legend
O D.S. DOWNSPOUT
+HB HOSE BIB
X/A5.1 WALL ASSEMBLY
RECESSED FIRE
EXTINGUISHER
F.E.C. CABINET
U WALL-MTD FIRE
F.E. EXTINGUISHER
FD FLOOR DRAIN
SMOKE DETECTOR,
SD HARDWIRE W/ BATTERY
BACKUP
® 200 CFM RANGE HOOD,
VENT TO EXT.
�i EXHAUST WALL CAP
�-0 STAND PIPE
C.G.F_ CORNER GUARD
FS FLOOR SINK
- - TV LOCATION -
TV PROVIDE BLOCKING
1
OCCUPANT LOAD SIGN
O.L. LOCATION
environmental
WORKS
Community Design Center
402 15th Avenue East
Seattle, Washington 98112
phone: 206.329.8300
fax: 206.329.5494
Edmonds Waterfront
Center
New Construction
220 RAILROAD AVE.
EDMONDS, WA 98020
6443
REGISTERED
ARCHI
GER E UCKFR
Second Floor Plan
--------------------
Date
03.15.2019
GMP Pricing Set
Revisions
1 08.22.2019 Construction Set
2 08.19.2019 RFI 2 - ASK 1
--------------------
--------------------
Drawn by:
FSJ
Checked by (P.M.):
SK
Checked by (Q.C.):
RT
Project No.
15015A
1 Second Floor Plan
Scale: 1 /8" = V-0"
0 5 10 15 20 25 FT
R
�ZPLAN
Al2